E E F F 9 9 10 10 K.2 K.2 NEW DUCT PENTRATION, RE: A3/A310 ,F.V. 12'-4" 12'-4" ,F.V. 1 PROJECT NUMBER: 1900 W. 47th Place Suite 300 Westwood, Kansas 66205 p: 913.362.6500 www.pgav.com Structural Engineers 4338 Bellview Avenue Kansas City, MO 64111 BOB D. CAMPBELL & CO, INC. (816) 531-4144 Plumbing and Mechanical Engineers 6 South Old Orchard St Louis, MO 63119 ROSS & BARUZZINI, INC. (314) 918-8383 Electrical Engineers 1600 Genessee St, Suite 260 Kansas City, MO 64102 ANTELLA CONSULTING ENGINEERS, INC. (816) 421-0950 11/19/15 53417 Medical Science Renovate 7th Floor West Laboratories UNIVERSITY OF MISSOURI FOR: The Curators of the University of Missouri - Project No: CP151661 ADDENDUM 01 XA-01 1/8" = 1'-0" A1/A310 ROOF PLAN 1
25
Embed
A1/A310 - Contact Us | Campus Facilities | University of ...operations-webapps.missouri.edu/pdc/adsite/projects/cp151661/... · 1/8" = 1'-0" A1/A310 ... SUBSTITUTION REQUEST (During
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
E
E
F
F
9 9
10 10
K.2 K.2
NEW DUCT PENTRATION,
RE: A3/A310
,F.V.
12'-4"
12'-4" ,F.V.
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP151661
ADDENDUM 01
XA-01
1/8" = 1'-0" A1/A310ROOF PLAN
1
E
E
D
D
1 1
2 2
3 3
16'-4 1/2"
NEW DUCT PENTRATION, RE: A3/A310
PATCH ALL EXISTING PENTRATIONS
ASSOCIATED WITH REMOVED DUCTWORK
25'-7" , F.V.
12'-0" , F.V.
5'-6"
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP151661
ADDENDUM 01
XA-02
1/8" = 1'-0" A1/A310ROOF PLAN
L
L
13 13
14 14
K.1
K.1
J.1
J.1
3'-6" , F.V.
3'-6" , F.V.
NEW DUCT PENTRATION,
RE: A3/A310
6'-1" , F.V.
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP151661
ADDENDUM 01
XA-03
1/8" = 1'-0" A1/A310ROOF PLAN
LEVEL FIVE50' - 7 3/8"
LEVEL SIX61' - 9 3/4"
LEVEL SEVEN73' - 0 1/8"
ROOF84' - 2 1/2"
6 87
T.O. PARAPET89' - 1 5/8"
A
EXISTING
STROBIC FAN, TYP.
PENTHOUSE ROOF97' - 6 1/2"
B
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP151661
ADDENDUM 01
XA-04
1/16" = 1'-0" A3/A400PARTIAL EXISTING WEST ELEVATION
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP151661
ADDENDUM 01
XA-05
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP151661
ADDENDUM 01
XA-06
LEVEL FIVE
50' - 7 3/8"
LEVEL SIX61' - 9 3/4"
LEVEL SEVEN73' - 0 1/8"
ROOF84' - 2 1/2"
6 87
T.O. PARAPET89' - 1 5/8"
A
PENTHOUSE ROOF97' - 6 1/2"
B
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
University of Missouri - Columbia
ADDENDUM 01
XA-07
1/8" = 1'-0" A2/A401PARTIAL EXISTING WEST ELEVATION
11/19/2015
Aluminum Windows
Manko Windows 3300 Series
085113
Medical Science 7th Floor West Lab
6
EFCO 6700
2.1 A
CP151661PGAV Architects
Aluminum Windows
SUBSTITUTION
REQUEST
(During the Bidding Phase)
Project: Medical Science Renovate 7th Floor West Labs
University of Missouri – Columbia
To: Ms. Michelle Gangel
PGAV Architects
Re: Substitution Request
Substitution Request Number:
From: D.L. Neuner Company, Inc.
Date: November 11, 2015
A/E Project Number: CP151661
Contract For:
Specification Title: Door Hardware Description: Surface Closers
Section: 087100 Page: Article/Paragraph: 2.8 Proposed Substitution: Stanley Commercial Door Closers
Manufacturer: Address: Indianapolis, IN Phone: (800) 711-6814
Trade Name: Stanley Security Solutions Model No.: QDC100 Series Attached data includes product description, specifications, drawings, photographs, and performance and test data adequate for evaluation of the request; applicable portions of the data are clearly identified. Attached data also includes a description of changes to the Contract Documents that the proposed substitution will require for its proper installation. The Undersigned certifies:
Proposed substitution has been fully investigated and determined to be equal or superior in all respects to specified product.
Same warranty will be furnished for proposed substitution as for specified product.
Same maintenance service and source of replacement parts, as applicable, is available.
Proposed substitution will have no adverse effect on other trades and will not affect or delay progress schedule.
Proposed substitution does not affect dimensions and functional clearances.
Payment will be made for changes to building design, including A/E design, detailing, and construction costs caused by the substitution. Submitted by: David L. Neuner, Jr., CSI, CDT
Signed by:
Firm: D.L. Neuner Company, Inc.
Address: 3015 S. Brentwood Blvd.
St. Louis, MO 63144
Telephone: (800) 775-9455 A/E’s REVIEW AND ACTION
Substitution approved - Make submittals in accordance with Specification Section 01330. Substitution approved as noted - Make submittals in accordance with Specification Section 01330. Substitution rejected - Use specified materials. Substitution Request received too late - Use specified materials.
Signed by: Date:
Supporting Data Attached: Drawings X Product Data Samples Tests Reports
Manufacturer: Address: Los Angeles, CA Phone: (323) 262-4191
Trade Name: Model No.: Attached data includes product description, specifications, drawings, photographs, and performance and test data adequate for evaluation of the request; applicable portions of the data are clearly identified. Attached data also includes a description of changes to the Contract Documents that the proposed substitution will require for its proper installation. The Undersigned certifies:
Proposed substitution has been fully investigated and determined to be equal or superior in all respects to specified product.
Same warranty will be furnished for proposed substitution as for specified product.
Same maintenance service and source of replacement parts, as applicable, is available.
Proposed substitution will have no adverse effect on other trades and will not affect or delay progress schedule.
Proposed substitution does not affect dimensions and functional clearances.
Payment will be made for changes to building design, including A/E design, detailing, and construction costs caused by the substitution. Submitted by: David L. Neuner, Jr., CSI, CDT
Signed by:
Firm: D.L. Neuner Company, Inc.
Address: 3015 S. Brentwood Blvd.
St. Louis, MO 63144
Telephone: (800) 775-9455 A/E’s REVIEW AND ACTION
Substitution approved - Make submittals in accordance with Specification Section 01330. Substitution approved as noted - Make submittals in accordance with Specification Section 01330. Substitution rejected - Use specified materials. Substitution Request received too late - Use specified materials.
Signed by: Date:
Supporting Data Attached: Drawings X Product Data Samples Tests Reports
99 Canal Center Plaza, Suite 300 Alexandria, VA 22314
Page of September 1996
CSI Form 1.5C
CFH 03 CFH 04
CYLCYL
F G
6
5
7
FEV
7-04B
1
1
S-1
200
FEV
7-04A
16"ø EA
12"ø EA
12"ø EA
12"ø EA 12"ø EA
FD
7-12
FD
7-13
1011
13
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-01
1/8" = 1'-0"M1/M1027TH FL. DUCTWORK NEW WORK
KEYED NOTES:
3 10" DIAMETER EXHAUST DUCT UP & DN IN NEW 2-HOURCHASE.
1
KEYED NOTES:
13 CAP DUCT JUST ABOVE 7TH FLOOR SLAB INSIDE NEWCHASE.
1
E F G
8
9
10
K.2
NEW 20"ø DNTHROUGHNEW OPENINGIN ROOF
20"ø EA
24"ø EA
24"ø EA
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-02
1/8" = 1'-0"M1/M103ROOF NEW WORK PLAN
F G
6
5
7
48"x24" UP
60"x14" EA DN
40"x14" UP &DN
10"x14" UP &DN
16"x10" EA DN
62"x20" SAUP/DN
40"x18" SA UP& DN
OFFICE
743B
SHOWER
703B
BATH
703A
EXAM ROOM
701
OFFICE
700
1
1
1 48"x24" EA DN 1
14
14
14
1
1
1
1
1
1
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/18/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-03
1/8" = 1'-0"M1/MD1027TH FL. DUCTWORK DEMO PLAN
KEYED NOTES:
14 DEMOLISH DUCT FROM PENTHOUSE TO JUST ABOVESEVENTH FLOOR SLAB AND CAP INSIDE NEW CHASE.
1
T
T
T
F G
8
K.2
OFFICE
748
OFFICE
757
1 11 10"ø EA UP
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-04
1/8" = 1'-0"M1/MD1027TH FL. DUCTWORK DEMO PLAN
E F G
8
9
10
K.2
36"ø EA
1
2
1
10"ø EA DN
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-05
1/8" = 1'-0"M1/MD103ROOF DEMOLITION PLAN
T
G
856"x12" SA
2"LPR
3"HWR3"HWS
8"CWS
8"CWR
MECH ROOM
M750
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2 1/2"
146
8
9
VAV 7-28
8"
8"
6"
6"
1
1
1
1
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-06
M2/M2013D VIEW MECH. RM.
8" CWS & CWR 1
1
1/4" = 1'-0"M1/M201ENLARGED MECH RM. PLAN
T T
J K L
6
8
7
K.2
CONT RM
742
OFFICE
741
COPY RM
741D
OFFICE
741C
OFFICE
741B
OFFICE
741A
68"x9" HOT(TOP)
68"x10" COLD(BELOW)
1
11
1
1
1 1
T
B
BB
CC
C
C
11
11
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-07
1/8" = 1'-0"M1/MD1027TH FL. DUCTWORK DEMO. PLAN
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-08
ALTERNATE 4 KEYEDNOTES:
A EXISTING DUAL DUCT VAV BOX TO REMAIN. THISPROJECT SHALL REPLACE EXISTING PNEUMATIC VAVBOX CONTROLS WITH NEW DDC ELECTRIC CONTROLS.REFER TO SHEET M704 FOR THE EXTENT OF WORKREQUIRED. DISCONNECT AND REMOVE PNEUMATICCONTROLS ON EXISTING VAV BOX AND ALL ASSOCIATEDPNEUMATIC CONTROL TUBING FROM BOX TOASSOCIATED WALL MOUNTED THERMOSTAT. EXISTINGPNEUMATIC TUBING LOCATED IN WALL SHALL BEABANDONED IN PLACE. PROVIDE A BRASSCOMPRESSION CAP TYPE FITTING AT ALL UNUSEDTERMINATIONS. DO NOT PINCH-OFF TUBING.
B REMOVE EXISTING WALL MOUNTED THERMOSTAT.ABANDON CONTROL TUBING IN WALL. PROVIDE A BRASSCOMPRESSION CAP TYPE FITTING AT ALL UNUSEDTERMINATIONS. DO NOT PINCH-OFF TUBING. PATCHWALL AS REQUIRED TO MATCH EXISTING CONDITIONS.COVER REMAINING HOLE IN WALL WITH BLANKTHERMOPLASTIC SINGLE COVER PLATE. PROVIDEMANUFACTURER'S STANDARD COLOR THAT MOSTCLOSELY MATCHES EXISTING WALL COLOR.
C REMOVE EXISTING DUAL DUCT VAV BOX. DISCONNECTAND REMOVE PNEUMATIC CONTROLS ON EXISTING VAVBOX AND ALL ASSOCIATED PNEUMATIC CONTROL TUBINGFROM BOX TO ASSOCIATED WALL MOUNTEDTHERMOSTAT. EXISTING PNEUMATIC TUBING LOCATEDIN WALL SHALL BE ABANDONED IN PLACE. PROVIDE ABRASS COMPRESSION CAP TYPE FITTING AT ALL UNUSEDTERMINATIONS. DO NOT PINCH-OFF TUBING.
1
1
T T
J K L
8
K.2
CHASE
M763A
68"x9" HOT(TOP)
68"x10" COLD(BELOW)
EAV
7-38
16"x15"
DD
7-20DD
7-21
DD
7-22
DD
7-23
A
A
A
A
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
ADDENDUM 01
XM-09
1/8" = 1'-0"M1/M1027TH FL. DUCTWORK NEW WORK PLAN
ALTERNATE 4 KEYED NOTES:
A NEW DUAL DUCT VAV TERMINAL UNIT. CONNECT TO EXISTINGHOT AND COLD DUCTS AND EXISTING SUPPLY DUCT. SEALDUCTWORK AND INSULATION AIR TIGHT. CONTRACTOR SHALLFIELD VERIFY EXISTING DUCTWORK SIZES AND PROVIDEREQUIRED DUCT TRANSITIONS FOR INSTALLATION UPSTREAMAND DOWNSTREAM OF NEW VAV BOX.
1
F G
6
8
7NEW 6" HWS & HWRUP AND DN
NEW 8" CWS & CWR UPEXISTING 8" CWS & CWR DN
1
PROJECT NUMBER:
1900 W. 47th Place
Suite 300
Westwood, Kansas
66205p: 913.362.6500www.pgav.com
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(816) 531-4144
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/19/1553417
Medical Science Renovate 7th Floor West Laboratories
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri No.: CP151661
Original Size: 1 1/2" Drawing may have been reduced.
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Mechanical and Plumbing Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(314) 918-8383
(816) 531-4144
(816) 421-0950
NOTE: The architect or engineer sealing this sheettakes responsibility for the drawing that is sealed, andis not responsible for all other sheets in the set.
JEFFREY R. CRAWFORD
MO LICENSE NO. E-27507
11/2
0/20
1 5 9
:15:
20 A
MC
:\Use
rs\s
brue
ning
\Doc
umen
t s\0
1-01
MU
Med
Sci
e nce
_Mec
h_V
15_s
brue
ning
.rvt
M112
11/10/15
53417
SEVENTH FLOORPIPING PLAN
RJD
BID DOCUMENTS
University of Missouri -Columbia
1 Hospital Drive, Columbia, MO65212
RJD JRC
Medical ScienceRenovate 7thFloor West
Laboratories
1/8" = 1'-0"1MECHANICAL SEVENTH FLOOR PIPIING NEW WORK PLAN
NORTH
KEYED NOTES:
2 DIFFERENTIAL PRESSURE TRANSMITTER.
3 10" DIAMETER EXHAUST DUCT UP & DN IN NEW2-HOUR CHASE.
#
0
SCALE:
0
8' - 0"
16' - 0"
24' - 0"1" = 8' - 0"
ALTERNATE 4 KEYEDNOTES:
A A.INSTALL (2) NEW OWNER FURNISHED DDCCONTROLLERS TO EXISTING COOLING AND HEATINGDUAL DUCT VAV BOX. SEE CONTROL DIAGRAMS ONSHEET M704. CALIBRATE AND BALANCE NEWCONTROLLERS TO EXISTING PARAMETERS OF EACHINDIVIDUAL BOX (MAX/MIN CFM BOTH HOT DECK ANDCOLD DECK).
B B.OWNER PROVIDED AND INSTALLED NEW DDCELECTRIC WALL-MOUNTED WIRED THERMOSTAT.EXPOSED CONTROL WIRING IN CONDUIT SHALL BECONCEALED BY WIREMOLD. ALL CONTROL WIRINGTO BE INSTALLED IN FINISHED SPACES SHALL BECONCEALED. WHERE IT IS NOT POSSIBLE TO ROUTEIN EXISTING WALL, PROVIDE WIREMOLD V2000BCTWO-PIECE STEEL SURFACE RACEWAY. WIREMOLDSHALL BE STANDARD PREFINISHED COLOR PICKEDBY ARCHITECT DURING SHOP DRAWING REVIEW.ROUTE WIREMOLD IN A HIGH DISCRETE PATH. PRIORTO INSTALLATION OF WIREMOLD, COORDINATEEXACT ROUTING AND MOUNTING HEIGHT OFWIREMOLD WITH THE OWNER’S REPRESENTATIVE OFA TYPICAL INSTALLATION. DO NOT INSTALLMOUNTED CONDUIT EXPOSED IN FINISHED SPACES.
1
# DATE DESCRIPTION
1 11-19-15 Addendum 1
11/20/15
M
M
M
M
M
T
T
T
GENERATOR
M
M
M
M
M
T
T
T
E F GD
6
5
7
3
M202
16"ø EA
1 1/2"LPR
4"LPS4"LPS3"CWS
3"CWR
48"x11" HOTABOVE
44"x14" RA
EXET
2
24"x
22"
12"x12" OA
24"x22" OA12"x12" OA 14"x10" OA
48"x60" OA
10"x14" OA DN
40"x14" OA DN
1 1/2"LPR
1 1
/2"L
PR
PENTHOUSE
M804
52"x12" EA
26"ø EA
40"x16" OA
80"x
18"
SA
96"x30" SA
EXISTING 12"ø EAUP TO FAN ONPENTHOUSE ROOF
40"x18" OA
48"x12" COLDBELOW
1 1/2"CWR
1 1/2"CWR
1 1
/2"C
WR
12"ø EA DN
12"ø EA
12"ø EA
12"ø
10"x16" EA DN(REMAINS)
EXISTING 10" DIA.GENERATOR EXHAUSTDUCT UP THROUGH ROOF
EXISTING GENERATOROUTSIDE AIR INTAKELOUVER ANDDUCTWORK
EXISTINGGENERATOR
FD
7-13
IN EXISTINGDUCT THROUGHFLOOR
1
1
1
EXISTING AIRHANDLING UNIT
EXISTING AIRHANDLING UNIT
NEW WORK PLAN SHOWINGBASE BID ONLY.
1
E F GD
6
5
7
3
M202
48"x11" DN
48"x12" DN
12"x8" DN 12"x8" DN 10"x14" OA DN
40"x14" OA DN
EXISTING 12"ø EAUP TO FAN ONPENTHOUSEROOF
80"x
18"
SA
40"x16" OA
40"x18" OA
26"ø EA
52"x12" EA
48"x11" HOTABOVE
48"x12" COLDBELOW
EXET
2
44"x14"
44"x14" RA
24"x
22"
OA 12"x12" OA
12"x12" OA
48"x60" OA
24"x22" OA1 1/2"LPR
4"LPS3"CWS
3"CWR
4"LPS
96"x30" SA
1 1/2"CWR
1 1/2"CWR
1 1
/2"C
WR
12"ø
10"x16" EA DN(REMAINS)
DDC PANEL
1
2
3
10" DIA. GENERATOREXHAUST DUCT UPTHROUGH ROOF
GENERATOROUTSIDE AIR INTAKELOUVER ANDDUCTWORK
GENERATOR
4
4
4
EXISTING AIRHANDLING UNIT
EXISTING AIRHANDLING UNIT
1
1
1
ROOF84' - 2 1/2"
F G
T.O. PARAPET89' - 1 5/8"
PENTHOUSE ROOF97' - 6 1/2"
12"ø
80"x18" SA
12"ø EA
10"x16" EA DN(REMAINS)
12"ø
1.
2.
3.
INSULATION IN PIPING AND DUCTWORK MAY CONTAINASBESTOS. SEE ASBESTOS REPORT IN PROJECT MANUAL.CONTRACTOR TO REINSULATE ALL PIPING AND DUCTWORKTHAT SHALL REMAIN TO POINT WHERE INSULATION HASBEEN ABANDONED.
SEE M000 FOR GENERAL NOTES.
CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINESFOR LOCATION OF EQUIPMENT.
Original Size: 1 1/2" Drawing may have been reduced.
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Mechanical and Plumbing Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
Structural Engineers4338 Bellview AvenueKansas City, MO 64111
BOB D. CAMPBELL & CO, INC.
(314) 918-8383
(816) 531-4144
(816) 421-0950
NOTE: The architect or engineer sealing this sheettakes responsibility for the drawing that is sealed, andis not responsible for all other sheets in the set.
JEFFREY R. CRAWFORD
MO LICENSE NO. E-27507
11/2
0/20
1 5 9
:15:
42 A
MC
:\Use
rs\s
brue
ning
\Doc
umen
t s\0
1-01
MU
Med
Sci
e nce
_Mec
h_V
15_s
brue
ning
.rvt
M202
11/10/15
53417
ENLARGEDPENTHOUSE PLANS
RJD
BID DOCUMENTS
University of Missouri -Columbia
1 Hospital Drive, Columbia, MO65212
RJD JRC
Medical ScienceRenovate 7thFloor West
Laboratories
REF: 6 / M201 1/4" = 1'-0"1MECHANICAL PENTHOUSE NEW WORK PLAN
REF: 1 / M202 1/4" = 1'-0"3SECTION THROUGH PENTHOUSE
KEYED NOTES:
1 OWNER WILL DISCONNECT AND REMOVE EXISTINGCONTROL PANEL.
2 BASE BID: ALL EXISTING SYSTEMS IN PENTHOUSE SHALLBE ABANDONED IN PLACE. ALTERNATE 3: HATCHED AREAIS ATTEMPT TO ILLUSTRATE AREA OF WORK ASSOCIATEDWITH ALTERNATE #3. UNLESS OTHERWISE NOTED ALLEXISTING EQUIPMENT ASSOCIATED WITH THE TWO (2)EXISTING AIR HANDLING UNITS SERVING THE 7TH FLOORAND EMERGENCY GENERATOR LOCATED IN THISPENTHOUSE SHALL BE TOTALLY DISCONNECTED, DRAINEDAND REMOVED. DEMOLISH ALL ASSOCIATED DUCTWORK,PIPING, INSULATION, HANGERS, SUPPORTS, LOUVERS, ANDEQUIPMENT CURBS. DO NOT LEAVE ANY THINGABANDONED IN PLACE. CAP ALL EXISTING OPENING INWALLS TO MATCH EXISITNG CONDITIONS. INFILL ALLFLOOR OPENINGS WHERE DUCTS AND/OR PIPING AREREMOVED TO MAINTAIN RATING IN FLOOR. CAP ALLEXISTING PIPES THAT ARE SERVING OTHER EXISTINGSYSTEMS THAT ARE STILL ACTIVE. REPLACE AND/ORREPAIR EXISTING INSULTION.
3 10" DIAMETER EXHAUST DUCT UP & DN IN NEW 2-HOURCHASE.