Approved Document A Structure
Contents
PAGE
Use of guidance 3
Loading and Ground MovementThe Requirements A1/2 5
Guidance 6
Introduction 6
Section 1: Codes, standards andreferences for all building types 7
Introduction 7
References 7
Loading 7
Structural work of timber 7
Structural work of masonry 7
Structural work of reinforced,pre-stressed or plain concrete 7
Structural work of steel 7
Structural work of aluminium 7
Foundations 7
Ground movement (Requirement A2b) 8
Existing buildings 8
Section 2: Sizes of structural elementsfor certain residential buildings and other
small buildings of traditional construction 9General 9
Definitions 9
Section 2A: Basic requirements for stability 10
Section 2B: Sizes of certain timbermembers in floors and roofs for dwellings.Areas at risk from house longhorn beetle 11
Sizing of members 11
House longhorn beetle 11
Section 2C: Thickness of walls in certainsmall buildings 12
Application 12
Wall types 12
The use of this section 12
Conditions relating to the building ofwhich the wall forms part 12
Thickness of walls 13
Conditions relating to the wall 16
PAGE
Construction materials and workmanship 17
Loading on walls 23
End restraint 23
Openings, recesses, overhangs and chases 25
Lateral support by roofs and floors 26
Interruption of lateral support 29
Small single-storey non-residential buildingsand annexes 29
Section 2D: Proportions for masonrychimneys above the roof structure 33
Height to width relationship 33
Section 2E: Foundations of plain concrete 34
Conditions relating to the ground 34
Design provisions 34
Minimum width of strip foundations 34
Minimum depth of strip foundations 35
Section 3: Wall cladding 36
General 36
Technical approach 36
Loading 36
Fixings 36Further guidance 37
Section 4: Roof covering 38
Materials 38
Re-covering of roofs 38
Disproportionate CollapseThe Requirement A3 39
Guidance 40
Performance 40
Introduction 40
Section 5: Reducing the sensitivity of thebuilding to disproportionate collapse inthe event of an accident 41
Alternative approach 42
Standards referred to 44
A
http://www.thenbs.com/http://www.thenbs.com/http://www.thenbs.com/8/10/2019 A - Structure Building Regs
3/462
Structure Approved Document A
PAGE
DIAGRAMS
1. Size and proportion of residentialbuildings of not more than three storeys 13
2. Size and proportion of non-residentialbuildings and annexes 14
3. Determination of wall thickness 15
4. Parapet walls: height 16
5. Maximum floor area enclosed bystructural walls 17
6. Map showing wind speed in m/s formaximum height of buildings 18
7. Maximum height of buildings 19
8. Measuring storey and wall heights 20
9. Declared compressive strength ofmasonry units 22
10. Maximum span of floors 23
11. Differences in ground levels 24
12. Openings in a buttressing wall 25
13. Buttressing 26
14. Sizes of openings and recesses 27
15. Lateral support by floors 28
16. Lateral support at roof level 29
17. Size and location of openings 30
18. Wall thickness 31
19. Lateral restraint at roof level 32
20. Proportions for masonry chimneys 33
21. Elevation of stepped foundation 34
22. Piers and chimneys 34
23. Foundation dimensions 34
24. Area at risk of collapse in the event ofan accident 43
PAGE
TABLES
1. Areas at risk from houselonghorn beetle 11
2. Wall types considered in this section 12
3. Minimum thickness of certainexternal walls, compartment wallsand separating walls 15
4. Imposed loads 17
5. Cavity wall ties 21
6. Declared compressive strength ofmasonry units complying withBS EN 771-1 to -5 21
7. Normalised compressive strength ofmasonry units of clay and calciumsilicate blocks complying withBS EN 771-1 and -2 23
8. Value of Factor X 27
9. Lateral support for walls 27
10. Minimum width of strip footings 35
11. Building classes 41
A CONTENTS
8/10/2019 A - Structure Building Regs
4/463
Approved Document A Structure
THE APPROVED DOCUMENTS
This document is one of a series that has beenapproved by the First Secretary of State for thepurpose of providing practical guidance withrespect to the requirements of Schedule 1 to and
Regulation 7 of the Building Regulations 2000 (SI2000/2531) for England and Wales. SI 2000/2531has been amended by the Building (Amendment)Regulations 2001 (SI 2001/3335), by the Building(Amendment) Regulations 2002 (SI 2002/440), bythe Building (Amendment) (No. 2) Regulations2002 (SI 2001/2871), by the Building (Amendment)Regulations 2003 (SI 2003/2692) and by the Building(Amendment) Regulations 2004 (SI 2004/1465).
At the back of this document is a list of all thedocuments that have been approved and issuedby the Secretary of State for this purpose.
Approved Documents are intended to provideguidance for some of the more commonbuilding situations. However, there may well bealternative ways of achieving compliance withthe requirements. Thus there is no obligation toadopt any particular solution contained in anApproved Document if you prefer to meet therelevant requirement in some other way.
Other requirements
The guidance contained in an ApprovedDocument relates only to the particularrequirements of the Regulations which that
document addresses. The building work willalso have to comply with the requirements ofany other relevant paragraphs in Schedule 1to the Regulations.
There are Approved Documents which giveguidance on each of the parts of Schedule 1and on Regulation 7.
LIMITATION ON REQUIREMENTS
In accordance with regulation 8, the requirementsin Parts A to K and N of Schedule 1 to theBuilding Regulations do not require anything
to be done except for the purpose of securingreasonable standards of health and safety forpersons in or about the buildings.
MATERIALS AND WORKMANSHIP
Any building work which is subject torequirements imposed by Schedule 1 to theBuilding Regulations should, in accordancewith Regulation 7, be carried out with propermaterials and in a workmanlike manner.
You may show that you have complied withregulation 7 in a number of ways. These include
the appropriate use of a product bearing CEmarking in accordance with the ConstructionProducts Directive (89/106/EEC)1 as amendedby the CE Marking Directive (93/68/EEC)2, or a
product complying with an appropriate technicalspecification (as defined in those Directives),a British Standard, or an alternative nationaltechnical specification of any state which is acontracting party to the European Economic Areawhich, in use, is equivalent, or a product coveredby a national or European certificate issued bya European Technical Approval Issuing body,and the conditions of use are in accordance withthe terms of the certificate. You will find furtherguidance in the Approved Document supportingRegulation 7 on materials and workmanship.
Independent certification schemes
There are many UK product certificationschemes. Such schemes certify compliancewith the requirements of a recognised documentwhich is appropriate to the purpose for which thematerial is to be used. Materials which are not socertified may still conform to a relevant standard.
Many certification bodies which approve suchschemes are accredited by UKAS.
Technical specifications
Building Regulations are made for specificpurposes: health and safety, energy conservationand the welfare and convenience of disabledpeople. Standards and technical approvals arerelevant guidance to the extent that they relateto these considerations. However, they may alsoaddress other aspects of performance such as
serviceability, or aspects which although theyrelate to health and safety are not covered bythe Regulations.
When an Approved Document makes referenceto a named standard, the relevant version ofthe standard is the one listed at the end of thepublication. However, if this version has beenrevised or updated by the issuing standardsbody, the new version may be used as a sourceof guidance provided it continues to address therelevant requirements of the Regulations.
The appropriate use of a product which complies
with a European Technical Approval as defined inthe Construction Products Directive will meet therelevant requirements.
The Department intends to issue periodicamendments to its Approved Documents toreflect emerging harmonised European Standards.Where a national standard is to be replaced by aEuropean harmonised Standard, there will be aco-existence period during which either standardmay be referred to. At the end of the co-existenceperiod the national standard will be withdrawn.
Use of guidance A
1 As implemented by the Construction Products Regulations 1991
(SI 1991/1620).
2 As implemented by the Construction Products (Amendment) Regulations
1994 (SI 1994/3051).
8/10/2019 A - Structure Building Regs
5/464
Structure Approved Document A
THE WORKPLACE (HEALTH,
SAFETY AND WELFARE)
REGULATIONS 1992
The Workplace (Health, Safety and Welfare)Regulations 1992 contain some requirementswhich affect building design. The main
requirements are now covered by the BuildingRegulations, but for further information see:Workplace health, safety and welfare, TheWorkplace (Health, Safety and Welfare)Regulations 1992, Approved Code of Practiceand Guidance;The Health and SafetyCommission, L24; Published by HMSO 1992;ISBN 0 11886 333 9.
The Workplace (Health, Safety and Welfare)Regulations 1992 apply to the common partsof flats and similar buildings if people such ascleaners and caretakers are employed to workin these common parts. Where the requirements
of the Building Regulations that are covered bythis Part do not apply to dwellings, the provisionsmay still be required in the situations describedabove in order to satisfy the Workplace Regulations.
OTHER FORMS OF HOUSE
CONSTRUCTION
This Approved Document includes guidance onstructural elements of residential buildings oftraditional masonry construction. It is recognised,however, that there are other suitable forms ofconstruction in use in the housing sector some of
which (e.g. timber framed) have been in commonuse for a number of years and have demonstratedan adequate performance in compliance with theA1 requirement. Such alternative forms includeprefabricated timber, light steel and precastconcrete framed construction.
A number of guidance documents relating tothese alternative forms are presently beingdeveloped by industry. The intention is toreference these in this Approved Documentas soon as they become available and areapproved by the Secretary of State.
EUROCODESThe British Standards Institution will shortlybe publishing a series of Structural Eurocodes,together with their National Annexes. TheseEurocodes are CEN Standards comprising manyParts which, when used in conjunction with theirNational Annexes and when approved by theSecretary of State, are intended to be referencedin this Approved Document as practical guidanceon meeting the Part A Requirements.
A USE OF GUIDANCE
8/10/2019 A - Structure Building Regs
6/465
Approved Document A Structure
The Requirements
This Approved Document deals with the followingRequirements which are contained in the BuildingRegulations 2000 (as amended by SI 2001/3335,SI 2002/440, SI 2002/2871 and SI 2003/2692).
Requirement Limits on application
Loading
A1. (1) The building shall be constructed so that the combined dead,
imposed and wind loads are sustained and transmitted by it to the
ground:
(a) safely; and
(b) without causing such deflection or deformation of any
part of the building, or such movement of the ground, as will impair
the stability of any part of another building.
(2) In assessing whether a building complies with sub paragraph
(1) regard shall be had to the imposed and wind loads to which it is
likely to be subjected in the ordinary course of its use for the purpose
for which it is intended.
Ground movement
A2. The building shall be constructed so that ground movement
caused by:
(a) swelling, shrinkage or freezing of the subsoil; or
(b) land-slip or subsidence (other than subsidence arising from
shrinkage, in so far as the risk can be reasonably foreseen), will not
impair the stability of any part of the building.
LOADING AND GROUND MOVEMENT A1/2
8/10/2019 A - Structure Building Regs
7/466
Structure Approved Document A
Introduction
0.1 In the Secretary of States view therequirements of A1 and A2 will be met byfollowing the recommendations given in thedocuments listed in Section 1 or by adopting
the guidance in Sections 2-4:
a. Section 1is relevant to all building typesand lists Codes, Standards and otherreferences for structural design andconstruction but, where they do not giveprecise guidance, consideration shouldbe given to paragraph 0.2.
b. Section 2give sizes of structural elementsfor certain residential buildings and othersmall buildings of traditional construction.
c. Section 3gives guidance on the supportand fixing of wall cladding.
d. Section 4gives guidance where roofs areto be re-covered as a material alteration asdefined in the Regulations.
0.2 The safety of a structure depends on thesuccessful combination of design and completedconstruction, particularly:
a. The design should be based on identificationof the hazards to which the structure is likelyto be subjected and assessment of the risks.The selection of relevant critical situationsfor design should be made reflecting theconditions that can reasonably be foreseen
during future use.
b. Loading. Dead load, imposed load and windload should be in accordance with the currentCodes of Practice referred to in Section 1 ofthis document.
c. Properties of materials.
d. Detailed design and assembly ofthe structure.
e. Safety factors.
f. Workmanship.
The numeric values of safety factors, whetherexpressed explicitly or implicitly in designequations, or design values, should be derivedfrom considerations of the above aspects ofdesign and construction as a whole. A change inany one of these aspects may disturb the safetyof the structure.
Loads used in calculations should allow forpossible dynamic, concentrated and peak loadeffects that may occur.
0.3 Grandstands and structures erected inplaces of public assembly may need to sustain thesynchronous or rhythmic movement of numbers
of people. It is important to ensure that the designof the structure takes these factors into accountso as to avoid the structure being impaired orcausing alarm to people using the structure.
Interim guidance on the design of grandstandsmay be found in Dynamic performancerequirements for permanent grandstands subjectto crowd action, Interim Guidance on assessmentand design published by the Institution ofStructural Engineers, November 2001.
Supplementary advice on the dynamic testingof grandstands and seating decking has beenpublished in an Advisory Note by the Institutionof Structural Engineers, June 2002.
GuidanceA1/2
8/10/2019 A - Structure Building Regs
8/467
Approved Document A Structure
Introduction
1.1 This section is relevant to all building typesand lists codes, standards and other referencesfor structural design and construction.
References
1.2 Loading:
a. Dead and imposed loads
BS 6399-1:1996 Loading for buildings. Code ofpractice for dead and imposed loads.
b. Wind loads
BS 6399-2:1997 Loading for buildings. Codeof practice for wind loads
BRE digest 436 Parts 1, 2 and 3 (Brief guidancefor using BS 6399-2:1996).
c. Imposed roof loads
BS 6399-3:1998 Loading for buildings. Code ofpractice for imposed roof loads.
1.3 Structural work of timber:
BS 5268-2:2002 Structural use of timber. Code ofpractice for permissible stress design, materialsand workmanship.
BS 5268-3:1998 Structural use of timber. Code ofpractice for trussed rafter roofs.
BS 8103-3:1996 Structural design of low-risebuildings. Code of practice for timber floors androofs for housing.
1.4 Structural work of masonry:
BS 5628-1:1992 Code of practice for use ofmasonry. Structural use of unreinforced masonry.
BS 5628-2:2000 Code of practice for use ofmasonry. Structural use of reinforced andpre-stressed masonry.
BS 5628-3:2001 Code of practice for use of
masonry. Materials and components, designand workmanship.
BS 8103-1:1995 Structural design of low-risebuildings. Code of practice for stability, siteinvestigation, foundations and ground floorslabs for housing.
BS 8103-2:1996 Structural design of low-risebuildings. Code of practice for masonry wallsfor housing.
1.5 Structural work of reinforced,pre-stressed or plain concrete:
BS 8110-1:1997 Structural use of concrete.Code of practice for design and construction.
BS 8110-2:1985 Structural use of concrete.Code of practice for special circumstances.
BS 8110-3:1985 Structural use of concrete.Design charts for singly reinforced beams, doublyreinforced beams and rectangular columns.
BS 8103-4:1995 Structural design of low-risebuildings. Code of practice for suspendedconcrete floors for housing.
1.6 Structural work of steel:
BS 5950-1:2000 Structural use of steelwork inbuilding. Code of practice for design in simpleand continuous construction: hot rolled andwelded sections.
BS 5950-2:2001 Structural use of steelwork inbuilding. Specification for materials, fabricationand erection, hot rolled sections.
BS 5950-3-1:1990 Structural use of steelwork inbuilding. Design in composite construction. Codeof practice for design of simple and continuouscomposite beams.
BS 5950-4:1994 Structural use of steelworkin building. Code of practice for design ofcomposite slabs with profiled steel sheeting.
BS 5950-5:1998 Code of practice for designof cold formed thin gauge sections.
BRE Digest 437 Industrial platform floors:mezzanine and raised storage.
1.7 Structural work of aluminium:BS 8118-1:1991 Structural use of aluminium.Code of practice for design.
BS 8118-2:1991 Structural use of aluminium.Specification for materials, workmanshipand protection.
1.8 Foundations:
BS 8002:1994 Code of practice for earthretaining structures.
BS 8004:1986 Code of practice for foundations.
Section 1: Codes, standards and referencesfor all building types
A1/2
8/10/2019 A - Structure Building Regs
9/468
Structure Approved Document A
Ground movement
(Requirement A2b)
1.9 There may be known or recordedconditions of ground instability, such as thatarising from landslides, disused mines orunstable strata which, if ignored, can have adevastating effect on the safety of a building
and its environs. Such conditions should betaken into account in the design of the buildingand its foundations. Attention is drawn to DOEPlanning Policy Guidance Note 14 Developmenton unstable land (obtainable from The StationeryOffice), which sets out the broad planning andtechnical issues relating to development onunstable land.
The Department has also sponsored a seriesof reviews aimed at determining the scale andnature of problems arising from mining instability,natural underground cavities and adversefoundation conditions. Databases of both
subsidence incidents and subsidence potentialproduced from these reviews are available fromthe following licence holders:
British Geological Survey, Sir Kingsley DunhamCentre, Keyworth, Nottingham NG12 5GG.
Landmark, 7 Abbey Court, Eagle Way, Exeter,Devon EX2 7HY.
Peter Brett Associates, 16 Westcote Road,Reading, Berkshire RG20 2DE.
Catalytic Data Ltd, The Spinney, 19 WoodlandsRoad, Bickley, Kent BRI 2AD.
The reports from these reviews, which include1:250,000 scale maps showing the distributionof the physical constraints, are available from thefollowing organisations:
Arup Geotechnics, 1991. Review of mininginstability in Great Britain.
Obtainable from Arup Geotechnics, Bede House,All Saints, Newcastle-upon-Tyne NE1 2EB.
Applied Geology Ltd, 1994. Review of instabilitydue to natural underground cavities in GreatBritain.
Obtainable from Kennedy & Donkin Ltd,14 Calthorpe Road, Edgbaston, BirminghamB15 1TH.
Wimpey Environmental Ltd, and National HouseBuilding Council, 1995. Foundation conditionsin Great Britain, a guide for planners anddevelopers. Obtainable from ESNR InternationalLtd, 16 Frogmore Road, Hemel Hempstead,Hertfordshire HP3 9RW.
Existing buildings
1.10 Compliance with Part A (Structure) isrequired in certain classes of change of use of abuilding, subject to the control of Regulations 5and 6. Guidance relevant to structural appraisalsrelated to change of use is given in the followingdocuments:
a. BRE Digest 366: Structural Appraisal ofExisting Buildings for Change of Use.
b. The Institution of Structural Engineers ReportAppraisal of Existing Structures, 1996.
Note: With reference to the item design checksin the above mentioned Institution of StructuralEngineers report the choice of various partialfactors should be made to suit the individualcircumstances of each case.
A1/2 CODES, STANDARDS AND REFERENCES FOR ALL BUILDING TYPES
8/10/2019 A - Structure Building Regs
10/469
Approved Document A Structure
Section 2: Sizes of structural elements forcertain residential buildings and other smallbuildings of traditional construction
General
2.1 This section is presented as follows:
Section 2A
Basic requirements for stability.
Section 2B
Sizes of certain timber members in floors androofs for dwellings.
Areas at risk from house longhorn beetle.
Section 2C
Thickness of masonry walls in certain residentialbuildings of not more than three storeys, smallsingle-storey non-residential buildings and annexes.
Section 2D
Proportions for masonry chimneys.
Section 2E
Foundations of plain concrete.
2.2 Section 2A gives general rules which mustbe observed in following Sections 2B and 2C.Sections 2B to 2E may be used independentlyof each other.
Throughout this section the diagrams are onlyillustrative and do not show all the details ofconstruction.
Definitions
2.3 The following meanings apply to termsthroughout this section:
Buttressing wallA wall designed andconstructed to afford lateral support to anotherwall perpendicular to it, support being providedfrom the base to the top of the wall.
Cavity widthThe horizontal distance betweenthe two leaves of a cavity wall.
Compartment wallA wall constructed as acompartment wall to meet the requirements ofregulation B3(2).
Dead loadThe load due to the weight ofall walls, permanent partitions, floors, roofsand finishes including services, and all otherpermanent construction.
Imposed loadThe load assumed to be producedby the intended occupancy or use, includingthe weight of movable partitions, distributed,concentrated, impact, inertia and snow loads,but excluding wind loads.
PierA member which forms an integral part
of a wall, in the form of a thickened section atintervals along the wall, so as to afford lateralsupport to the wall to which it is bonded orsecurely tied.
Separating wallA wall or part of a wall which iscommon to adjoining buildings, and constructedto meet the requirements of regulation B3(2).
SpacingThe distance between the longitudinalcentres of any two adjacent timber members ofthe same type, measured in the plane of floor,ceiling or roof structure.
SpanThe distance measured along the centre
line of a member between the centres of any twoadjacent bearings or supports.
Supported wallA wall to which lateral support isafforded by a combination of buttressing walls,piers or chimneys acting in conjunction withfloor(s) or roof.
Wind loadThe load due to the effect of windpressure or suction.
A1/2
8/10/2019 A - Structure Building Regs
11/4610
Structure Approved Document A
Section 2A: Basic requirements for stability
2A1 This section must be used in conjunctionwith sections 2B and 2C and its principles relateto all forms of low-rise residential buildings.
2A2 Adequate provision shall be made toensure that the building is stable under the likely
imposed and wind loading conditions. This willcommonly necessitate meeting the followingrequirements:
a. That the overall size and proportioningof the building are limited in accordancewith the specific guidance for each form ofconstruction.
b. That a suitable layout of walls (both internaland external) forming a robust 3 dimensionalbox structure in plan is constructed withrestriction on the maximum size of cellsmeasured in accordance with the specificguidance for each form of construction.
c. That the internal and external walls areadequately connected either by masonrybonding or by using mechanical connections.
d. That the intermediate floors and roof are ofsuch construction and interconnection withthe walls that they provide local supportto the walls and also act as horizontaldiaphragms capable of transferring the windforces to buttressing elements of the building.
Note: A traditional cut timber roof (i.e. usingrafters, purlins and ceiling joists) generally hassufficient built in resistance to instability andwind forces (e.g. from hipped ends, tiling battens,rigid sarking or the like). However, the needfor diagonal rafter bracing equivalent to thatrecommended in BS 5268-3:1998 or Annex H ofBS 8103-3:1996 for trussed rafter roofs shouldbe considered especially for single-hipped andnon-hipped roofs of greater than 40 pitch todetached houses.
A1/2
8/10/2019 A - Structure Building Regs
12/4611
Approved Document A Structure
Sizing of members
2B1 Guidance on the sizing of certain membersin floors and roofs is given in Span tables forsolid timber members in floors, ceilings and roofs(excluding trussed rafter roofs) for dwellings,published by TRADA, available from ChilternHouse, Stocking Lane, Hughenden Valley, HighWycombe, Bucks HP14 4ND.
Alternative guidance is available in BS 5268-2:2002Code of practice for permissible stress design,materials and workmanship, BS 5268-3:1998,Code of practice for trussed rafter roofs andBS 8103-3:1996 Structural design of low-rise
buildings, Code of Practice for timber floors androofs for dwellings.
Table 1 Areas at risk from house longhorn beetle
Geographical area
In the Borough of Bracknell Forest the parishes of Sandhurst and Crowthorne.
The Borough of Elmbridge
In the District of Hart, the parishes of Hawley and Yateley
The District of Runnymede
The Borough of Spelthorne
The Borough of Surrey Heath
In the Borough of Rushmoor, the area of the former district of Farnborough
The Borough of Woking
House longhorn beetle
2B2 In the geographical areas specified inTable 1, softwood timber for roof constructionor fixed in the roof space, including ceiling joistswithin the void spaces of the roof, should beadequately treated to prevent infestation by thehouse longhorn beetle (Hylotrupes bajulusL.).
Guidance on suitable preservative treatmentsis given within the British Wood Preserving andDamp-Proofing Associations Manual (2000revision), available from 1 Gleneagles House,Vernongate, South Street, Derby DE1 1UP.
Section 2B: Sizes of certain timber membersin floors and roofs for dwellings. Areas atrisk from house longhorn beetle
A1/2
8/10/2019 A - Structure Building Regs
13/4612
Structure Approved Document A
Section 2C: Thickness of walls in certainsmall buildings
Application
2C1 This section applies to the followingbuilding types:
a. residential buildings of not more thanthree storeys;
b. small single-storey non-residentialbuildings;
c. small buildings forming annexes toresidential buildings (including garagesand outbuildings).
Wall types
2C2 Only the types of wall given in Table 2,which must extend to the full storey height, and
parapet walls are considered in this section.
The use of this section
2C3 When using this section it should benoted that:
a. this section must be used in conjunctionwith Section 2A;
b. if wall thickness is to be determinedaccording to paragraphs 2C5to 2C13, allappropriate design conditions given in thissection must be satisfied;
c. walls should comply with the relevantrequirements of BS 5628: Part 3: 2001, exceptas regards the conditions given in paragraphs2C4and 2C14to 2C38;
d. in formulating the guidance of this section theworst combination of circumstances likely toarise was taken into account. If a requirementof this part is considered too onerous in aparticular case it may be appropriate toconsider a minor departure on the basisof judgement and experience, or to showadequacy by calculation in respect of theaspect of the wall which is subject to thedeparture rather than for the entire wall;
Table 2 Wall types considered in this section
Residential buildings of up to three storeys
External walls
Internal load-bearing walls
Compartment walls
Separating walls
Small single-storey non-residential buildings and annexes
External walls
Internal load-bearing walls
e. the guidance given is based upon thecompressive strengths of bricks and blocksbeing not less than indicated in Tables 6 and 7.
BS 5628-1:1992 gives design strengths for wallswhere the suitability for use of masonry units ofother compressive strengths is being considered.
Conditions relating to the building
of which the wall forms part
2C4 This Section applies only to buildingshaving proportions within the followingparameters (see Diagrams 1 and 2):
a. residential buildings of not more thanthree storeys:
i. the maximum height of the buildingmeasured from the lowest finished groundlevel adjoining the building to the highestpoint of any wall or roof should not begreater than 15m, subject to the limitsof paragraph 2C16;
ii. the height of the building H should notexceed twice the least width of thebuilding W1;
iii. the height of the wing H2 should notexceed twice the least width of the wingW2 where the projection P exceeds twicethe width W2;
b. small single-storey non-residential buildings:height H should not exceed 3m and W (beingthe greatest length or width of the building)should not exceed 9m (see Diagram 2),subject to the limits of paragraph 2C16;
A1/2
8/10/2019 A - Structure Building Regs
14/4613
Approved Document A Structure
c. annexes:height H as variously indicated inDiagram 2 should not exceed 3m, subject tothe limits of paragraph 2C16.
Thickness of walls
2C5 General wall thickness may be determinedaccording to this section provided:
a. conditions relating to the building of whichthe wall forms part (see paragraphs 2C4,2C14to 2C16, 2C38); and
b. conditions relating to the wall (see paragraphs2C17to 2C37) are met. (See Diagram 3.)
2C6 Solid external walls, compartment wallsand separating walls in coursed brickwork orblockwork:Solid walls constructed of coursedbrickwork or blockwork should be at leastas thick as 1/16 of the storey height. Furtherrequirements are given in Table 3.
2C7 Solid external walls, compartmentwalls and separating walls in uncoursed stone,flints, etc.:The thickness of walls constructedin uncoursed stone, flints, clunches, bricks orother burnt or vitrified material should not beless than 1.33 times the thickness determined
by paragraph 2C6.2C8 Cavity walls in coursed brickwork orblockwork:All cavity walls should have leavesat least 90mm thick and cavities at least 50mm
wide. The wall ties should have a horizontalspacing of 900mm and a vertical spacing of450mm, which is equivalent to 2.5 ties per squaremetre. Wall ties should also be provided, spacednot more than 300mm apart vertically, within adistance of 225mm from the vertical edges of allopenings, movement joints and roof verges. Forselection of wall ties for use in a range of cavitywidths refer to Table 5. For specification of cavitywall ties refer to paragraph 2C19.
For external walls, compartment walls andseparating walls in cavity construction, thecombined thickness of the two leaves plus 10mm
should not be less than the thickness determinedby paragraph 2C6 and Table 3 for a solid wall ofthe same height and length.
2C9 Walls providing vertical support toother walls:Irrespective of the material usedin the construction, a wall should not be less inthickness than any part of the wall to which itgives vertical support.
2C10 Internal load-bearing walls in brickworkor blockwork(except compartment walls orseparating walls): All internal load-bearing wallsshould have a thickness not less than:
(specified thickness from Table 3) 5mm2
Continued on page 16
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
Diagram 1 Size and proportion of residential buildings of not more than three storeys
See para 2C4
8/10/2019 A - Structure Building Regs
15/4614
Structure Approved Document A
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 2 Size and proportion of non-residential buildings and annexes
See paras 2C4b and 2C4c
8/10/2019 A - Structure Building Regs
16/4615
Approved Document A Structure
Table 3 Minimum thickness of certain external walls, compartment walls andseparating walls
Height of wall Length of wall Minimum thickness of wall
Not exceeding 3.5m Not exceeding 12m 190mm for whole of its height
Exceeding 3.5m but not exceeding 9m Not exceeding 9m 190mm for whole of its height
Exceeding 9m 290mm from the base for the height ofbut not exceeding 12m one storey and 190mm for the rest of its height
Exceeding 9m but not exceeding 12m Not exceeding 9m 290mm from the base for the height ofone storey and 190mm for the rest of its height
Exceeding 9m 290mm from the base for the height ofbut not exceeding 12m two storeys and 190mm for the rest of its height
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
Diagram 3 Determination of wall thickness
See para 2C5
8/10/2019 A - Structure Building Regs
17/4616
Structure Approved Document A
except for a wall in the lowest storey of a threestorey building, carrying load from both upperstoreys, which should have a thickness asdetermined by the equation or 140mm whicheveris the greatest.
2C11 Parapet walls:The minimum thicknessand maximum height of parapet walls should beas given in Diagram 4.
2C12 Single leaves of certain external walls:The single leaf of external walls of small single-storey non-residential buildings and of annexesneed be only 90mm thick, notwithstandingparagraphs 2C38.
2C13 Modular bricks and blocks:Wherewalls are constructed of bricks or blocks havingmodular dimensions derived from BS 6649:1985,wall thicknesses prescribed in this section whichderive from a dimension of brick or block maybe reduced by an amount not exceeding thedeviation from work size permitted by a British
Standard relating to equivalent sized bricks orblocks made of the same material.
2C14 Maximum floor area:The guidance ofthis section assumes that no floor enclosed bystructural walls on all sides exceeds 70m2, andthat no floor without a structural wall on one sideexceeds 36m2. (See Diagram 5.)
2C15 Imposed loads on roofs, floors andceilings:The design considerations given inthis section are intended to be adequate for the
imposed loads given in Table 4.
2C16 Maximum height of buildings:The design guidance in this section is basedon BS 6399-2:1997. The maximum heights ofbuildings given in Table c of Diagram 7 correlateto various site exposure conditions and windspeeds. A map showing wind speeds is givenin Figure 1 of Diagram 6.
Conditions relating to the wall
2C17 Maximum allowable length and heightof the wall:This section does not deal with walls
longer than 12m, measured from centre to centreof buttressing walls, piers or chimneys providingrestraint, or with walls exceeding 12m in height(see also Table 3).
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 4 Parapet walls: height
See para 2C11
8/10/2019 A - Structure Building Regs
18/4617
Approved Document A Structure
Table 4 Imposed loadsElement Loading
Distributed loadsRoof 1.00kN/m for spans not exceeding 12m
1.5kN/m for spans not exceeding 6m
Floors Distributed load: 2.00kN/m
Ceilings Distributed load: 0.25kN/mtogether with concentrated load: 0.9kN
2C18 Rules of measurement for heights ofwalls and storeys:The height of a wall or a
storey should be measured in accordance withthe rules in Diagram 8.
Construction materials and
workmanship
2C19 Wall ties:Wall ties should either complywith BS 1243, DD 140, or BS EN 845-1 andshould be material references 1 or 3 in BS EN845 Table A 1 austenitic stainless steel. Wall tiesshould be selected in accordance with Table 5 ofthis Approved Document.
2C20 Masonry units:Walls should be properlybonded and solidly put together with mortar andconstructed of masonry units conforming to:
a. clay bricks or blocks to BS 3921:1985 orBS 6649:1985 or BS EN 771-1;
b. calcium silicate bricks to BS 187:1978 orBS 6649:1985 or BS EN 771-2;
c. concrete bricks or blocks to BS 6073-1:1981or BS EN 771-3 or -4;
d. square dressed natural stone to the appropriaterequirements described in BS EN 771-6 orBS 5628-3:2001;
e. manufactured stone to BS 6457:1984 orBS EN 771-5.
2C21 Compressive strength of masonry units:Minimum compressive strength requirementsfor masonry units according to BS EN Standardsare given in Diagram 9, where the masonry unitsindicated for Conditions A, B and C shouldhave declared compressive strengths of notless than the values given in Table 6. Normalisedcompressive strengths for block sized clay andcalcium silicate masonry units not complying withbrick dimensional format are given in Table 7.
Continued on page 24
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
Diagram 5 Maximum floor area enclosed by structural walls
See para 2C14
8/10/2019 A - Structure Building Regs
19/4618
Structure Approved Document A
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 6 Map showing wind speeds in m/s for maximum height of buildings
See para 2C16
8/10/2019 A - Structure Building Regs
20/4619
Approved Document A Structure
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
Diagram 7 Maximum height of buildings
See para 2C16
8/10/2019 A - Structure Building Regs
21/4620
Structure Approved Document A
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 8 Measuring storey and wall heights
See para 2C18
8/10/2019 A - Structure Building Regs
22/4621
Approved Document A Structure
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
Table 5 Cavity wall ties
Nominal cavitywidth mm(Note 1)
50 to 75
76 to 90
91 to 100
101 to 125
126 to 150
151 to 175
176 to 300
Tie length mm(Note 2)
200
225
225
250
275
300
(See Note 2)
Permissible type of tie
Tie shape in accordancewith BS 1243*
Butterfly, double triangle or vertical twist
Double triangle or vertical twist
Double triangle (Note 3) or vertical twist
Vertical twist
Vertical twist
Vertical twist
Vertical twist style
BS EN 845-1 tie(Note 4)
Types 1, 2, 3 or 4 to DD 140-2* andselected on the basis of the design
loading and design cavity width.
*Although BS 1243 and DD 140-2 were due to bewithdrawn on 1 February 2005, the tie user classes(types) given in Tables 1 and 3 of the latterdocument can continue to be used after this date.
Notes:
1. Where face insulated blocks are used the cavity width should be measured from the face of the masonry unit.
2. The embedment depth of the tie should not be less than 50mm in both leaves. For cavities wider than 180mm calculate the length as the structuralcavity width plus 125mm and select the nearest stock length.
3. Double triangle ties of this shape having a strength to satisfy Type 2 of DD 140-2* are manufactured. Specialist tie manufacturers should beconsulted if 225mm long double triangle format ties are needed for 91 to 100mm cavities.
4. Where BS EN 845-1 ties are used reference needs to be made additionally to DD 140-2* for the selection of the type (i.e. type 1, 2, 3 or 4) relevantto the performance levels given in DD 140-2.
Table 6 Declared compressive strength of masonry units complying withBS EN 771-1 to -5 (N/mm2)
Masonry unit Clay masonry units to Calcium silicate masonry Aggregate Autoclaved Manufactured BS EN 771-1 units to BS EN 771-2 concrete aerated conc. stone masonry masonry masonry units to units to units to BS EN 771-3 BS EN 771-4 BS EN 771-5
Condition A (See Diagram 9)Brick Group 1 Group 2 Group 1 Group 2 6.0
6.0 9.0 6.0 9.0
Block See Table 7 See Table 7 See Table 7 See Table 7 2.9* 2.9
Condition B (See Diagram 9)
Brick Group 1 Group 2 Group 1 Group 2 9.0 9.0 13.0 9.0 13.0
Block See Table 7 See Table 7 See Table 7 See Table 7 7.3* 7.3
Condition C (See Diagram 9)
Brick Group 1 Group 2 Group 1 Group 2 18.0 18.0 25.0 18.0 25.0
Block See Table 7 See Table 7 See Table 7 See Table 7 7.3* 7.3
AnyunitcomplyingwithBSEN771-5
will
beacceptableforconditionsA,
BandC
* These values are dry strengths to BS EN 772-1
Notes:
1. This table applies to Group 1 and Group 2 units.
2. For the EN 771 series of standards for masonry units the values of declared compressive strengths (N/mm) given in Table 6 are mean values.
3. Brick: a masonry unit having work sizes not exceeding 337.5mm in length or 112.5mm in height.
4. Block: a masonry unit exceeding either of the limiting work sizes of a brick and with a minimum height of 190mm. For blocks with smaller heights,excluding cuts or make up units, the strength requirements are as for brick except for solid external walls where the blocks should have acompressive strength at least equal to that shown for block for an inner leaf of a cavity wall in the same position.
5. Group 1 masonry units have not more than 25% formed voids (20% for frogged bricks). Group 2 masonry units have formed voids greater than25%, but not more than 55%.
8/10/2019 A - Structure Building Regs
23/4622
Structure Approved Document A
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 9 Declared compressive strength of masonry units
See para 2C21
8/10/2019 A - Structure Building Regs
24/4623
Approved Document A Structure
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
Table 7 Normalised compressive strength of masonry units of clay and calciumsilicate blocks complying with BS EN 771-1 and 2 (N/mm2)
Standard
Clay masonry units to BS EN 771-1Calcium silicate masonry units toBS EN 771-2
Condition (See Diagram 9)
A
B
C
Group 1 masonry units
5.0
7.5
15.0
Group 2 masonry units
8.0
11.0
21.0
Notes:
1. Values in this table are normalised compressive strengths (N/mm). Compressive strengths of masonry units should be derived according to EN 772-1.
2. The table applies to clay and calcium silicate block masonry units where the work size exceeds 337.5mm in length or 112.5mm in height.
3. Group 1 masonry units have not more than 25% formed voids (20% for frogged bricks). Group 2 masonry units have formed voids greater than25%, but not more than 55%.
2C22 Mortar:Mortar should be:
a.
i. Mortar designation (iii) according to
BS BS 5628-3:2001.ii. Strength class M4 according to
BS EN 998-2.
iii. 1:1:5 or 6 CEM 1, lime and fine aggregatemeasured by volume of dry materials, or
b. of equivalent or greater strength anddurability to the specification in a. above.
Loading on walls
2C23 Maximum span of floors:The maximumspan for any floor supported by a wall is 6mwhere the span is measured centre to centre of
bearing (see Diagram 10).
2C24 Other loading conditions:
a. Vertical loading on walls should be distributed.This may be assumed for concrete floorslabs, precast concrete floors, and timberfloors designed in accordance with section2B, and where the bearing length for lintels is150mm or greater. Where a lintel has a clearspan of 1200mm or less the bearing lengthmay be reduced to 100mm.
b. Differences in level of ground or other solidconstruction between one side of the wall
and the other should be less than 4 times thethickness of the wall as shown in Diagram 11.
c. The combined dead and imposed loadshould not exceed 70kN/m at base of wall(see Diagram 11).
d. Walls should not be subjected to lateral loadother than from wind, and that covered byparagraph 2C24(b).
End restraint
2C25 Vertical Lateral Restraint to Walls
The ends of every wall should be bonded or
otherwise securely tied throughout their fullheight to a buttressing wall, pier or chimney.Long walls may be provided with intermediatebuttressing walls, piers or chimneys dividingthe wall into distinct lengths within each storey;each distinct length is a supported wall forthe purposes of this section. The intermediatebuttressing walls, piers or chimneys shouldprovide lateral restraint to the full height of thesupported wall, but they may be staggered ateach storey.
2C26 Buttressing Walls
If the buttressing wall is not itself a supportedwall its thickness T2 should not be less than:
Continued on page 26
Diagram 10 Maximum span of floors
See para 2C23
8/10/2019 A - Structure Building Regs
25/4624
Structure Approved Document A
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 11 Differences in ground levels
See para 2C24b
8/10/2019 A - Structure Building Regs
26/4625
Approved Document A Structure
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
a. half the thickness required by this section foran external or separating wall of similar heightand length less 5mm; or
b. 75mm if the wall forms part of a dwellinghouse and does not exceed 6m in total height
and 10m in length; andc. 90mm in other cases.
The length of the buttressing wall shouldbe at least 1/6 of the overall height of thesupported wall and be bonded or securely tiedto the supporting wall and at the other end to abuttressing wall, pier or chimney.
The size of any opening in the buttressing wallshould be restricted as shown in Diagram 12.
2C27 Design criteria for piers and chimneysproviding restraint:
a. piers should measure at least 3 times thethickness of the supported wall and chimneystwice the thickness, measured at right angles
to the wall. Piers should have a minimumwidth of 190mm (see Diagram 13);
b. the sectional area on plan of chimneys(excluding openings for fireplaces and flues)should be not less than the area required
for a pier in the same wall, and the overallthickness should not be less than twice therequired thickness of the supported wall(see Diagram 13).
Openings, recesses, overhangs
and chases
2C28 General:
The number, size and position of openings andrecesses should not impair the stability of a wallor the lateral restraint afforded by a buttressingwall to a supported wall. Construction over
openings and recesses should be adequatelysupported.
Diagram 12 Openings in a buttressing wall
See para 2C26
8/10/2019 A - Structure Building Regs
27/4626
Structure Approved Document A
2C29 Dimensional criteria for openings andrecesses:
The dimensional criteria are given in Diagram 14and Table 8.
No openings should be provided in walls belowground floor except for small holes for servicesand ventilation, etc. which should be limitedto a maximum area of 0.1m at not less than2m centres.
2C30 Chases:a. vertical chases should not be deeper than 1/3
of the wall thickness or, in cavity walls, 1/3 ofthe thickness of the leaf;
b. horizontal chases should not be deeper than1/6 of the thickness of the leaf of the wall;
c. chases should not be so positioned as toimpair the stability of the wall, particularlywhere hollow blocks are used.
2C31 Overhangs:
The amount of any projection should not impair
the stability of the wall.
Lateral support by roofs and floors
2C32 A wall in each storey of a building shouldextend to the full height of that storey, and havehorizontal lateral supports to restrict movementof the wall at right angles to its plane.
2C33 Floors and roofs should:
a. act to transfer lateral forces from walls tobuttressing walls, piers or chimneys; and
b. be secured to the supported wall byconnections specified in paragraphs 2C34and 2C35.
2C34 The requirements for lateral restraint ofwalls at roof and floor levels are given in Table 9and guidance on satisfying the requirements isgiven in paragraphs 2C35and 2C36.
2C35 Walls should be strapped to floors aboveground level, at intervals not exceeding 2mand as shown in Diagram 15 by tension strapsconforming to BS EN 845-1. For corrosionresistance purposes, the tension straps shouldbe material reference 14 or 16.1 or 16.2
(galvanised steel) or other more resistant
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 13 Buttressing
See para 2C27
8/10/2019 A - Structure Building Regs
28/4627
Approved Document A Structure
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
Diagram 14 Sizes of openings and recesses
See para 2C29
Table 8 Value of Factor X (see Diagram 14)
Span of timber Span of concrete floor into wall floor into wall
Span of floor Minimum is parallel max max max maxNature of Maximum thickness of to wall 4.5m 6.0m 4.5m 6.0mroof span roof span (m) wall inner (mm)
Value of factor X
Roof spans Not 100 6 6 6 6 6parallel to wall applicable
90 6 6 6 6 5
Timber roof 9 100 6 6 5 4 3spans into wall
90 6 4 4 3 3
Table 9 Lateral support for walls
Wall type Wall length Lateral support required
Solid or cavity: external Any length Roof lateral support by every roof forming a junction with thecompartment separating supported wall
Greater than 3m Floor lateral support by every floor forming a junction with the supported wall
Internal load-bearing wall (not being Any length Roof or floor lateral support at the top of each storeya compartment or separating wall)
8/10/2019 A - Structure Building Regs
29/4628
Structure Approved Document A
specifications including material references 1 or3 (austenitic stainless steel). The declared tensilestrength of tension straps should not be lessthan 8kN.
Tension straps need not be provided:
a. in the longitudinal direction of joists in housesof not more than 2 storeys, if the joists areat not more than 1.2m centres and have atleast 90mm bearing on the supported wallsor 75mm bearing on a timber wall-plate ateach end, and
b. in the longitudinal direction of joists in housesof not more than 2 storeys, if the joists arecarried on the supported wall by joist hangersin accordance with BS EN 845-1 of the restrainttype described in BS 5628-1 and shown inDiagram 15(c), and are incorporated at notmore than 2m centres, and
c. when a concrete floor has at least 90mmbearing on the supported wall (see Diagram
15(d)), and
d. where floors are at or about the same levelon each side of a supported wall, andcontact between the floors and wall is eithercontinuous or at intervals not exceeding 2m.Where contact is intermittent, the points ofcontact should be in line or nearly in line onplan (see Diagram 15(e)).
2C36 Gable walls should be strapped to roofs as
shown in Diagram 16(a) and (b) by tension strapsas described in 2C35.
Vertical strapping at least 1m in length should beprovided at eaves level at intervals not exceeding2m as shown in Diagram 16(c) and (d). Verticalstrapping may be omitted if the roof:
a. has a pitch of 15 or more, and
b. is tiled or slated, and
c. is of a type known by local experience to beresistant to wind gusts, and
d. has main timber members spanning onto the
supported wall at not more than 1.2m centres.
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 15 Lateral support by floors
See para 2C35
8/10/2019 A - Structure Building Regs
30/4629
Approved Document A Structure
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
Interruption of lateral support
2C37 Where an opening in a floor or roof for astairway or the like adjoins a supported wall andinterrupts the continuity of lateral support, thefollowing conditions should be satisfied for thepurposes of Section 2C:
a. the maximum permitted length of the opening
is to be 3m, measured parallel to the supportedwall, and
b. where a connection is provided by meansother than by anchor, this should be providedthroughout the length of each portion of thewall situated on each side of the opening, and
c. where a connection is provided by mild steelanchors, these should be spaced closer than2m on each side of the opening to providethe same number of anchors as if there wereno opening, and
d. there should be no other interruption of
lateral support.
Small single-storey non-residential
buildings and annexes
2C38 Size and proportion
i. General
The guidance given applies in the followingcircumstances:
a. The floor area of the building or annexe doesnot exceed 36m.
b. The walls are solidly constructed in brickworkor blockwork using materials which complywith paragraphs 2C19to2C22.
c. Where the floor area of the building or annexeexceeds 10m the walls have a mass of notless than 130kg/m.
Note: There is no surface mass limitationrecommended for floor areas of 10m or less.
d. Access to the roof is only for the purposes of
maintenance and repair.
e. The only lateral loads are wind loads.
Diagram 16 Lateral support at roof level
See para 2C36
8/10/2019 A - Structure Building Regs
31/4630
Structure Approved Document A
f. The maximum length or width of the buildingor annexe does not exceed 9m.
g. The height of the building or annexe does notexceed the lower value derived from Diagram 2.
h. The roof is braced at rafter level, horizontallyat eaves level and at the base of any gable by
roof decking, rigid sarking or diagonal timberbracing, as appropriate, in accordance withBS 5268-3.
i. Walls are tied to the roof structure verticallyand horizontally in accordance with paragraphs2C32to 2C36and with horizontal lateralrestraint at roof level in accordance withparagraph (iv) below.
j. The roof structure of an annexe is securedto the structure of the main building at both
rafter and eaves level.
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 17 Size and location of openings
See para 2C38
8/10/2019 A - Structure Building Regs
32/4631
Approved Document A Structure
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS A1/2
(ii) Size and location of openings
One or two major openings not more than 2.1min height are permitted in one wall of the buildingor annexe only. The width of a single opening or
the combined width of two openings should notexceed 5m.
The only other openings permitted in a buildingor annexe are for windows and a single leaf door.The size and location of these openings shouldbe in accordance with Diagram 17.
(iii) Wall thickness and recommendationsfor piers
The walls should have a minimum thickness of 90mm.
Diagram 18 Wall thickness
See para 2C38
8/10/2019 A - Structure Building Regs
33/4632
Structure Approved Document A
Walls which do not contain a major openingbut exceed 2.5m in length or height should bebonded or tied to piers for their full height at notmore than 3m centres as shown in Diagram 18a.
Walls which contain one or two major openingsshould in addition have piers as shown inDiagrams 18b and 18c. Where ties are usedto connect piers to walls they should be flat,20mm x 3mm in cross section, be in stainlesssteel in accordance with clause 2C19, be placedin pairs and be spaced at not more than 300mmcentre vertically.
(iv) Horizontal lateral restraint at roof level
Walls should be tied horizontally at no more than2m centres to the roof structure at eaves level,base of gables and along roof slopes as shown
in Diagram 19 with straps fixed in accordancewith paragraphs 2C35and 2C36. Wherestraps cannot pass through a wall they shouldbe adequately secured to the masonry usingsuitable fixings. Isolated columns should alsobe tied to the roof structure (see Diagram 19).
A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 19 Lateral restraint at roof level
See para 2C38
8/10/2019 A - Structure Building Regs
34/4633
Approved Document A Structure
A1/2
Section 2D: Proportions for masonrychimneys above the roof surface
Height to width relationship
2D1 Where a chimney is not adequatelysupported by ties or securely restrained in anyway, its height if measured from the highest pointof intersection with the roof surface, gutter, etc.should not exceed 4.5W, provided the density ofthe masonry is greater than 1500kg/m3, where:
Wis the least horizontal dimension of thechimney measured at the same point ofintersection, and
His measured to the top of any chimney pot orother flue terminal (see Diagram 20).
Diagram 20 Proportions for masonrychimneys
See para 2D1
8/10/2019 A - Structure Building Regs
35/4634
Structure Approved Document A
Conditions relating to the ground
2E1 There should not be:
a. non-engineered fill (as described in BREDigest 427) or wide variation in ground
conditions within the loaded area; norb. weaker or more compressible ground at
such a depth below the foundation as couldimpair the stability of the structure.
Design provisions
2E2 The following design provisions relate tofoundations:
a. the foundations should be situated centrallyunder the wall;
b. for foundations in chemically aggressivesoil conditions guidance in BS 8500-1 and
BRE Special Digest 1 should be followed.In non-aggressive soils, concrete shouldbe composed of Portland cement to BS EN197-1 and -2 and fine and coarse aggregateconforming to BS EN 12620 and the mixshould comply with one of the followingrecommendations:
i. in proportion of 50kg of Portland cementto not more than 200kg (0.1m3) of fineaggregate and 400kg (0.2m3) of coarseaggregate; or
ii. grade ST2 or grade GEN I concrete to
BS 8500-2;c. minimum thickness T of concrete foundation
should be 150mm or P, whichever is thegreater where P is derived using Table 10and Diagram 23. Trench fill foundations maybe used as an acceptable alternative to stripfoundations;
d. foundations stepped on elevation shouldoverlap by twice the height of the step, bythe thickness of the foundation, or 300mm,whichever is greater (see Diagram 21).
For trench fill foundations the overlap should
be twice the height of the step or 1m,whichever is greater;
e. steps in foundations should not be of greaterheight than the thickness of the foundation(see Diagram 21);
f. foundations for piers, buttresses and chimneysshould project as indicated in Diagram 22 andthe projection X should never be less than thevalue of P where there is no local thickeningof the wall.
Minimum width of strip
foundations2E3 The recommended minimum widths offoundations given in Table 10 may be used.
Section 2E: Foundations of plain concreteA1/2
Diagram 21 Elevation of steppedfoundation
See paras 2E2d and e
Diagram 22 Piers and chimneys
See para 2E2f
Diagram 23 Foundation dimensions
See para 2E2c
8/10/2019 A - Structure Building Regs
36/46
8/10/2019 A - Structure Building Regs
37/4636
Structure Approved Document A
General
3.1 Wall cladding presents a hazard if itbecomes detached from the building. Thissection provides guidance on the supportand fixing of wall cladding. An acceptable
level of safety can be achieved by differentmeans depending on the type and location ofthe cladding. The guidance given relates toall forms of cladding, including curtain wallingand glass facades. It is not intended to provideguidance concerning the weather resistanceof wall cladding which is included in ApprovedDocument C, Site preparation and resistance tomoisture, or guidance on resistance to spread offire which is included in Approved Document B,Fire safety, or guidance in relation to soundinsulation, which is included in ApprovedDocument E, Resistance to the passage
of sound.
Technical approach
3.2 The cladding will meet the safetyrequirement if:
a. the cladding is capable of safely sustainingand transmitting to the supporting structureof the building all dead, imposed and windloads, and
b. the cladding is securely fixed to andsupported by the structure of the building.This shall comprise both vertical support
and horizontal restraint, andc. provision is made, where necessary, to
accommodate differential movement of thecladding and the supporting structure of thebuilding, and
d. the cladding and its fixings (includingany support components) are of durablematerials; the design life of the fixings beingnot less than that of the cladding. Fixingsshall be corrosion resistant and of a materialtype appropriate for the local environment.
Loading
3.3 Wind loading on the cladding shouldbe derived from BS 6399-2:1997 with dueconsideration given to local increases in windsuction arising from funnelling of the windthrough gaps between buildings. Guidance onfunnelling effects is given in BRE Digest 436Wind loading on buildings Brief guidancefor using BS 6399-2:1997 available from BRE,Bucknalls Lane, Garston, Watford, Herts WD2 7JR.
3.4 Where the cladding is required to supportother fixtures, e.g. handrails, and fittings, e.g.antennae and signboards, account should be
taken of the loads and forces arising from suchfixtures and fittings.
3.5 Where the wall cladding is required tofunction as pedestrian guarding to stairs, ramps,vertical drops of 600mm or greater or as avehicle barrier, then account should be taken ofthe additional imposed loading, as stipulated inApproved Document K, Protection from falling,collision and impact.
3.6 Where the wall cladding is required tosafely withstand lateral pressures from crowds,an appropriate design loading is given in BS6399 Part 1 and the Guide to Safety at SportsGrounds (4th Edition, 1997).
Fixings
3.7 The selection of fixings for supportingcladding should be determined from aconsideration of the proven performance of thefixing and the risks associated with the particular
application. In this regard applications should bedesignated as being either non-redundant (wherethe failure of a single fixing could lead to thedetachment of the cladding) or redundant (wherefailure or excessive movement of one fixingresults in load sharing by adjacent fixings) andthe required reliability of the fixing determinedaccordingly.
Note: Attention is drawn to the availabilityof anchors with an ETA (European TechnicalApproval) gained in accordance with therequirements of ETAG 001 Guideline forEuropean Technical Approval Metal Anchors
for use in ConcreteParts 1-5, which cover bothredundant and non-redundant applications, andPart 6 which covers Anchors for multiple usein non-structural applications and which caneffectively be regarded as covering redundantuse. The UK definition of multiple use iscontained in an annexe to the ETAG Part 6 andis framed in such a way that all applications canbe validated as to whether or not they conform tothis category without calculation. All ETAG partsmay be downloaded in English from www.eota.be.
3.8 The strength of fixings should be derivedfrom tests using materials representative of the
material into which the fixing is to be anchored,taking account of any inherent weaknesses thatmay affect the strength of the fixing, e.g. cracksin concrete due to shrinkage and flexure, or voidsin masonry construction. The design loads willgenerally be available from the manufacturerstest data determined from a European TechnicalApproval (ETA) or an extant British Standard.
Note: ETAS are available which cover use eitherin both cracked and non-cracked concrete or innon-cracked concrete only. Those which coverboth cracked and non-cracked concrete allowhigher loads for use in non-cracked than in
cracked concrete. Guidance on how to determinewhether a particular concrete section may beregarded as cracked or non-cracked withoutreverting to stress calculations is contained
Section 3: Wall claddingA1/2
8/10/2019 A - Structure Building Regs
38/4637
Approved Document A Structure
WALL CLADDING A1/2
in Use of anchors with European TechnicalApprovals. UK Guidance Distinctionbetween cracked and non-cracked concrete.This is available on the BBA websitewww.bbacerts.co.uk click tab ETA.
Further guidance
3.9 The use of large panels of glass incladding of walls and roofs where the claddingis not divided into small areas by load-bearingframing requires special consideration. Guidanceis given in the following documents:
The Institution of Structural Engineers Report onStructural use of glass in buildings dated 1999,available from 11 Upper Belgrave Street, LondonSW1X 8BH.
Nickel sulfide in toughened glass published bythe Centre for Window Cladding and Technologydated 2000.
3.10 Further guidance on cladding is given inthe following documents:
The Institution of Structural Engineers Report onAspects of Cladding dated 1995.
The Institution of Structural Engineers Reporton Guide to the structural use of adhesivesdated 1999.
BS 8297:2000 Code of practice for the designand installation of non-load-bearing pre-castconcrete cladding.
BS 8298:1994 Code of practice for the design andinstallation of natural stone cladding and lining.
3.11 Additional guidance on fixings is given inthe following documents:
ETAG No. 001 1997 Guideline for EuropeanTechnical Approvals of Metal Anchors for use inConcrete, European Organisation for TechnicalApprovals (EOTA), Brussels. All EOTA parts maybe downloaded in English from www.eota.be.
English version published by the British Boardof Agreement, PO Box 195, Bucknalls Lane,Garston, Watford, Hertfordshire WD25 9BA.
Part 1 Anchors in general.
Part 2 Torque controlled anchors.Part 3 Undercut anchors.
Part 4 Deformation controlled anchors.
Part 5 Bonded anchors.
Part 6 Metal anchors for redundant use inconcrete for lightweight systems.
BS 5080-1:1993 Structural fixings in concreteand masonry. Method of test for tensile loading.
CIRIA Report RP 566 Cladding Fixings: Goodpractice guidance, available from 6 StoreysGate, London SWIP 3AU.
CIRIA Reports C579 and C589 Retention ofmasonry facades Best practice guide.
Guidance notes published by the ConstructionFixings Association, c/o Institute of SpringTechnology, Henry Street, Sheffield,South Yorks S3 7EQ.
Guidance Note: Procedure for Site TestingConstruction Fixings (1994).
Guidance Note: European Technical Approvals
for Construction Fixings (1998).Guidance Note: Anchor Selection (1995).
Guidance Note: Fixings and Fire (1998).
Guidance Note: Anchor Installation (1996).
Guidance Note: Bonded Anchors (1999).
Guidance Note: Heavy Duty ExpansionAnchors (1997).
Guidance Note: Fixings for Brickwork andBlockwork (1997).
Guidance Note: Undercut Anchors (1998).
Guidance Note: Fixings and Corrosion (2002).
8/10/2019 A - Structure Building Regs
39/4638
Structure Approved Document A
Materials
4.1 All materials used to cover roofs,including transparent or translucent materials,but excluding windows of glass in residentialbuildings with roof pitches of not less than
15, shall be capable of safely withstandingthe concentrated imposed loads upon roofsspecified in BS 6399: Part 3.
Re-covering of roofs
4.2 The re-covering of roofs is commonlyundertaken to extend the useful life of buildings.Roof structures may be required to carryunderdrawing or insulation provided at a timelater than their initial construction. This sectionprovides guidance on determining whether suchwork to a roof constitutes a material alterationunder the Building Regulations.
4.3 Where the work involves a significantchange in the applied loading the structuralintegrity of the roof structure and the supportingstructure should be checked to ensure thatupon completion of the work the building is notless compliant with Requirement A1 than theoriginal building.
4.4 A significant change in roof loading iswhen the loading upon the roof is increased bymore than 15%.
4.5 Where such checking of the existing roofstructure indicates that the construction is unable
to sustain any proposed increase in loading (e.g.due to overstressed members or unacceptabledeflection leading to ponding), appropriatestrengthening work or replacement of roofingmembers should be undertaken. This is classifiedas a material alteration.
4.6 In carrying out the checks mentioned inparagraph 4.3an increase of stress in a structuralmember arising from increased loading doesnot necessarily indicate that the roof structure isless compliant than the original roof provided anadequate factor of safety is maintained.
4.7 Where work will significantly decreasethe roof dead loading, the roof structure and itsanchorage to the supporting structure shouldbe checked to ensure that an adequate factorof safety is maintained against uplift of the roofunder imposed wind loading.
Section 4: Roof coveringA1/2
8/10/2019 A - Structure Building Regs
40/4639
Approved Document A Structure
DISPROPORTIONATE COLLAPSE A3
This Approved Document deals with the followingRequirements which are contained in the BuildingRegulations 2000 (as amended by SI 2001/3335,SI 2002/440, SI 2002/2871 and SI 2003/2692).
Requirement Limits on application
Disproportionate collapse
A3. The building shall be constructed so that in the event of an accident
the building will not suffer collapse to an extent disproportionate to
the cause.
The Requirement
8/10/2019 A - Structure Building Regs
41/4640
Structure Approved Document A
Performance
In the Secretary of States view the Requirementof A3 will be met by an appropriate choiceof measures to reduce the sensitivity of abuilding to disproportionate collapse should
an accident occur.
Introduction
0.1 The guidance in Section 5 deals with themeans of meeting this performance criterion.
GuidanceA3
8/10/2019 A - Structure Building Regs
42/4641
Approved Document A Structure
A3
Section 5: Reducing the sensitivity of thebuilding to disproportionate collapse in theevent of an accident
5.1 The requirement will be met by
adopting the following approach for ensuringthat the building is sufficiently robust tosustain a limited extent of damage or failure,depending on the class of the building,without collapse.
a. Determine the building class from Table 11.
b. For Class 1 buildings Provided thebuilding has been designed and constructedin accordance with the rules given in thisApproved Document, or other guidancereferenced under Section 1, for meetingcompliance with requirement A1 and A2 innormal use, no additional measures are likelyto be necessary.
Table 11 Building classes
Classes Building type and occupancy
1 Houses not exceeding 4 storeys
Agricultural buildings
Buildings into which people rarely go, provided no part of the building is closer to another building, or area where peopledo go, than a distance of 1.5 times the building height
2A 5 storey single occupancy houses
Hotels not exceeding 4 storeys
Flats, apartments and other residential buildings not exceeding 4 storeys
Offices not exceeding 4 storeys
Industrial buildings not exceeding 3 storeys
Retailing premises not exceeding 3 storeys of less than 2000m floor area in each storey
Single-storey educational buildings
All buildings not exceeding 2 storeys to which members of the public are admitted and which contain floor areas notexceeding 2000m at each storey
2B Hotels, flats, apartments and other residential buildings greater than 4 storeys but not exceeding 15 storeys
Educational buildings greater than 1 storey but not exceeding 15 storeys
Retailing premises greater than 3 storeys but not exceeding 15 storeys
Hospitals not exceeding 3 storeys
Offices greater than 4 storeys but not exceeding 15 storeys
All buildings to which members of the public are admitted which contain floor areas exceeding 2000m but less than5000m at each storey
Car parking not exceeding 6 storeys
3 All buildings defined above as Class 2A and 2B that exceed the limits on area and/or number of storeys
Grandstands accommodating more than 5000 spectators
Buildings containing hazardous substances and/or processes
Notes:
1. For buildings intended for more than one type of use the Class should be that pertaining to the most onerous type.
2. In determining the number of storeys in a building, basement storeys may be excluded provided such basement storeys fulfil the robustnessrequirements of Class 2B buildings.
c. For Class 2A buildings Provide effective
horizontal ties, or effective anchorage ofsuspended floors to walls, as describedin the Codes and Standards listed underparagraph 5.2for framed and load-bearingwall construction (the latter being defined inparagraph 5.3below).
d. For Class 2B buildings Provide effectivehorizontal ties, as described in the Codes andStandards listed under paragraph 5.2for framedand load-bearing wall construction (the latterbeing defined in paragraph 5.3below), togetherwith effective vertical ties, as defined in theCodes and Standards listed under paragraph
5.2, in all supporting columns and walls.
8/10/2019 A - Structure Building Regs
43/4642
Structure Approved Document A
Alternatively, check that upon the notionalremoval of each supporting column and eachbeam supporting one or more columns, or anynominal length of load-bearing wall (one at atime in each storey of the building), the buildingremains stable and that the area of floor at anystorey at risk of collapse does not exceed 15%of the floor area of that storey or 70m2, whichever
is smaller, and does not extend further than theimmediate adjacent storeys (see Diagram 24).
Where the notional removal of such columnsand lengths of walls would result in an extent ofdamage in excess of the above limit, then suchelements should be designed as a key elementas defined in paragraph 5.3 below.
e. For Class 3 buildings A systematicrisk assessment of the building should beundertaken taking into account all the normalhazards that may reasonably be foreseen,together with any abnormal hazards.
Critical situations for design should be selectedthat reflect the conditions that can reasonablybe foreseen as possible during the life of thebuilding. The structural form and concept andany protective measures should then be chosenand the detailed design of the structure andits elements undertaken in accordance withthe recommendations given in the Codes andStandards given in paragraph 5.2.
5.2 Details of the effective horizontal andvertical ties, together with the design approachesfor checking the integrity of the building followingthe notional removal of vertical members and
the design of key elements, are available in thefollowing Codes and Standards:
BS 5628-1:1992 Structural use of unreinforcedmasonry. Code of practice for use of masonry.
BS 5950-1:2000 Structural use of steelworkin building. Code of practice for design. Rolledand welded sections.
BS 8110-1:1997 Structural use of concrete.Code of practice for design and construction.
BS 8110-2:1985 Structural use of concrete. Codeof practice for special circumstances.
5.3 Definitions
Nominal length of load-bearing wall
The nominal length of load-bearing wallconstruction referred to in 5.1dshould be takenas follows:
in the case of a reinforced concrete wall, thedistance between lateral supports subject toa maximum length not exceeding 2.25H.
in the case of an external masonry wall, ortimber or steel stud wall, the length measuredbetween vertical lateral supports.
in the case of an internal masonry wall,or timber or steel stud wall, a length notexceeding 2.25H.
where H is the storey height in metres.
Key elements
A key element, as referred to in paragraph 5.1d,should be capable of sustaining an accidentaldesign loading of 34kN/m2applied in thehorizontal and vertical directions (in one directionat a time) to the member and any attachedcomponents (e.g. cladding etc.) having regardto the ultimate strength of such componentsand their connections. Such accidental designloading should be assumed to act simultaneouslywith 1/3 of all normal characteristic loading (i.e.wind and imposed loading).
Load-bearing construction
For the purposes of this Guidance the termload-bearing wall construction includesmasonry cross-wall construction and wallscomprising close centred timber or lightweightsteel section studs.
Alternative approach
5.4 Alternatively, for any building whichdoes not fall into the classes listed under Table11 or for which the consequences of collapsemay warrant particular examination of the risksinvolved, the performance may be met by therecommendations given in the following Reports:
Guidance on Robustness and Provision againstAccidental Actions dated July,1999.
Calibration of Proposed Revised Guidance onmeeting Compliance with the Requirements ofBuilding Regulation Part A3. Revision of theAllott and Lomax proposals. Project Report
No. 205966.
Both of the above documents are availableon the following ODPM websitehttp://www.odpm.gov.uk
REDUCING THE SENSITIVITY OF THE BUILDING TOA3 DISPROPORTIONATE COLLAPSE IN THE EVENT OF AN ACCIDENT
8/10/2019 A - Structure Building Regs
44/4643
Approved Document A Structure
Diagram 24 Area at risk of collapse in the event of an accident
See para 5.1d
REDUCING THE SENSITIVITY OF THE BUILDING TODISPROPORTIONATE COLLAPSE IN THE EVENT OF AN ACCIDENT A3
8/10/2019 A - Structure Building Regs
45/4644
Structure Approved Document A
A1/2
BS 187:1978Specification for calcium silicate (sandlime andflintlime) bricks. AMD 5427 1987.
BS 1243:1978Specification for metal ties for cavity wallconstruction. AMD 3651 1981, AMD 4024 1982.(Withdrawn and superseded by BS EN 845-1:2003Specification for ancillary components for masonry.Ties, tension straps, hangers and brackets.AMD 14736 2003.)
BS 5080-1:1993Structural fixings in concrete and masonry.Method of test for tensile loading.
BS 5268-2:2002Structural use of timber. Code of practicefor permissible stress design, materials and
workmanship.
BS 5268-3:1998Structural use of timber. Code of practice fortrussed rafter roofs.
BS 5628-1:1992Code of practice for use of masonry. Structuraluse of unreinforced masonry. AMD 7745 1993,AMD 13680 2002.(Withdrawn and superseded by BS 5628-1:2005Code of practice for the use of masonry. Structuraluse of reinforced masonry.)
BS 5628-2:2000
Code of practice for use of masonry. Structuraluse of reinforced and prestressed masonry.(Withdrawn and superseded by BS 5628-2:2005Code of practice for the use of masonry. Structuraluse of reinforced and prestressed masonry.)
BS 5628-3:2001Code of practice for use of masonry. Materialsand components, design and workmanship.(Withdrawn and superseded by BS 5628-3:2005Code of practice for the use of masonry. Materialsand components, design and workmanship.)
BS 5950-1:2000
Structural use of steelwork in building. Code ofpractice for design. Rolled and welded sections.AMD 13199 2001.
BS 5950-2:2001Structural use of steelwork in building.Specification for materials, fabrication anderection. Rolled and welded sections.
BS 5950-3-1:1990Structural use of steelwork in building. Design incomposite construction. Code of practice for designof simple and continuous composite beams.
BS 5950-4:1994
Structural use of steelwork in building. Codeof practice for design of composite slabs withprofiled steel sheeting.
BS 5950-5:1998Structural use of steelwork in building. Codeof practice for design of cold formed thingauge sections.
BS 6399-1:1996
Loading for buildings. Code of practice for deadand imposed loads. AMD 13669 2002.
BS 6399-2:1997Loading for buildings. Code of practice for windloads. AMD 13392 2002, AMD 14009 2002.
BS 6399-3:1998Loading for buildings. Code of practice forimposed roof loads. AMD 6033 1988, AMD 91871996, AMD 9452 1997.
BS 8002:1994Code of practice for earth retaining structures.AMD 8851 1995, AMD 12062 2001,
AMD 13386 2001.BS 8004:1986Code of practice for foundations.
BS 8103-1:1995Structural design of low-rise buildings. Codeof practice for stability, site investigation,foundations and ground floor slabs for housing.AMD 8980 1995.
BS 8103-2:1996Structural design of low-rise buildings. Code ofpractice for masonry walls for housing.(Superseded but remains current by BS 8103-2:2005
Structural design of low rise buildings. Codeof practice for masonry walls for housing, butremains current.)
BS 8103-3:1996Structural design of low-rise buildings. Code ofpractice for timber floors and roofs for housing.
BS 8103-4:1995Structural design of low-rise buildings. Code ofpractice for suspended concrete floors for housing.
BS 8110-1:1997Structural use of concrete. Code of practicefor design and construction. AMD 9882 1998,
AMD 13468 2002.BS 8110-2:1985Structural use of concrete. Code of practicefor special circumstances. AMD 5914 1989,AMD 12061 2001.
BS 8110-3:1995Structural use of concrete. Design charts forsingly reinforced beams, doubly reinforced beamsand rectangular columns. AMD 5918 1989.
BS 8118-1:1991Structural use of aluminium. Code of practicefor design. AMD 10485 1999.
BS 8118-2:1991Structural use of aluminium. Specificationfor materials, workmanship and protection.AMD 10486 1999.
A
Standards referred to
8/10/2019 A - Structure Building Regs
46/46