DETTSON ALIZ INTERFACE (K03081) QUICK SETUP GUIDE
2016-10-07 X40237 rev. E
Simple startup 1. Turn off the breaker of the outdoor unit and
the furnace 2. Connect COND1 and COND2 on the interface board to
N(1) and 2 at the outdoor unit (See complete manuel included with
the unit) 3. Connect the interface board to the furnace:
1. Communicating thermostat: i. Connect the RJ-11 wire (A00443)
between the interface and the furnace control board (See complete
manuel included with the unit)
2. Legacy thermostat: i. Connect all the thermostat control
wires to the interface card and the air
handler control board ii. Make sure to connect the heat output
W1 out and W2 out of the thermostat to the W1 and W2 inputs of the
furnace OR W on W2 on a single stage thermostat
iii. If the thermostat does not have a DH output, a jumper must
be placed between R and DH on the interface board
4. Turn ON the breaker of the outdoor unit 5. Turn ON the
breaker of the furnace Make sure the unit is working properly 1.
The Green LED on the interface board should be blinking once every
two seconds 2. The Orange LED on the interface board should be
blinking once every two seconds 3. The communicating thermostat
will display Heat_Pump_Found 4. Set the thermostat to COOL mode and
adjust the set point to a lower value than the
actual room temperature 5. The furnace and the outdoor unit
should start within 5 minutes
In this configuration, the interface board will gather
information from both the outdoor unit and the furnace in order to
adjust the fan speed to the capacity of the outdoor unit
* Aliz 9/12 kBTU shown. See the Electrical Diagrams section of
the Aliz manual for other models.
INSTALLATION IN VARIOUS MODULATING FURNACES CHINOOK SUPREME
Legacy wiring
-
DETTSON ALIZ INTERFACE (K03081) QUICK SETUP GUIDE
2016-10-07 X40237 rev. E
Balance point adjustment Communicating thermostat: 1. On the
thermostats Home Screen Display, touch the Menu key to display
additional key choices 2. Touch and hold the Installer Config key
for approximately 3 seconds to enter the Thermostat Configuration
Menu 3. Touch and hold the Installer Config key for approximately 3
seconds to enter the Advanced Installer Configuration Menu 4. Using
the up or down arrows, select THERMOSTAT 5. Touch the Installer
Config key 6. Using the up or down arrows, select SETUP 7. Touch
the Installer Config key 8. Using the up or down arrows, select
BALANCE PT 9. Using the right or left arrows, set the desired
balance point 10. Touch the Run Schedule key to return to the Home
Screen
Legacy wiring: 1. On the Interface Board, before powering the
unit, set the balance point using the dipswitches #2, #3 and #4
DIP2 DIP3 DIP4 Balance Point OFF OFF OFF -15C (5F) OFF OFF ON
-13C OFF ON OFF -11C OFF ON ON -9C ON OFF OFF -7C ON OFF ON -5C ON
ON OFF -3C ON ON ON HP heat only
To run the outdoor unit in Air Conditioner mode (no heat), turn
ON the dipswitch #1. ERV/HRV wiring The communicating thermostat
(R02P029) is required
1. Connect the ERV/HRV unit between the R and G terminals on the
Interface Board 2. Connect the RJ-11 wire (A00443) between the
interface and the furnace control board (See complete manuel
included with the unit)
3. Adjust the desired fan demand for ERV/HRV using the
dipswitches #2, #3 and #4 DIP1 DIP2 DIP3 DIP4 Fan Demand
- OFF OFF OFF 20% - OFF OFF ON 25% - OFF ON OFF 30% - OFF ON ON
35% - ON OFF OFF 40% - ON OFF ON 45% - ON ON OFF 50% - ON ON ON
55%
DIP1 Mode OFF AC & HP ON AC Only
-
INTERFACE ALIZ DETTSON (K03081) GUIDE DINSTALLATION RAPIDE
2016-10-07 X40237 rev. E
Ajustement du point de basculement Thermostat communiquant: 1.
Sur lcran daccueil du thermostat, appuyer sur Menu pour afficher
les options additionnelles 2. Appuyer et maintenir la touche
Installer Config environ 3 secondes pour afficher le menu de
configuration du thermostat 3. Appuyer et maintenir la touche
Installer Config environ 3 secondes pour afficher le menu de
configuration installateur
avanc 4. En utilisant les flches haut et bas, slectionner
THERMOSTAT 5. Appuyer sur la touche Installer Config 6. En
utilisant les flches haut et bas, slectionner SETUP 7. Appuyer sur
la touche Installer Config 8. En utilisant les flches haut et bas,
slectionner BALANCE PT 9. En utilisant les flches droite et gauche,
ajuster le point de basculement la valeur dsire 10. Appuyer sur la
touche Run Schedule pour revenir lcran daccueil
Branchement legacy : 1. Sur la carte dinterface, avant
dalimenter lunit, ajuster le point de basculement en utilisant les
dipswitches #2, #3 et #4
DIP2 DIP3 DIP4 Point de basculement OFF OFF OFF -15C (5F) OFF
OFF ON -13C OFF ON OFF -11C OFF ON ON -9C ON OFF OFF -7C ON OFF ON
-5C ON ON OFF -3C ON ON ON Chauffage thermopompe uniquement
Pour mettre lunit extrieure en mode climatiseur seulement (pas
de chauffage), mettre ON la dipswitch #1. Branchement ERV/HRV Le
thermostat communiquant (R02P029) est requis
1. Brancher lunit ERV/HRV entre les bornes R et G de la carte
dinterface 2. Connecter le fil RJ-11 (A00443) entre linterface et
la carte de contrle de la fournaise (Voir le manuel complet fourni
avec lunit intrieure)
3. Ajuster la demande de ventilation continue pour ERV/HRV en
utilisant les dipswitches #2, #3 et #4 DIP1 DIP2 DIP3 DIP4 Demande
de ventilation
- OFF OFF OFF 20% - OFF OFF ON 25% - OFF ON OFF 30% - OFF ON ON
35% - ON OFF OFF 40% - ON OFF ON 45% - ON ON OFF 50% - ON ON ON
55%
DIP1 Mode OFF Climatisation et chauffage ON Climatisation
seulement
-
INTERFACE ALIZ DETTSON (K03081) GUIDE DINSTALLATION RAPIDE
2016-10-07 X40237 rev. E
Dmarrage simple 1. teindre le disjoncteur de lunit extrieure et
de la fournaise 2. Connecter COND1 et COND2 de la carte dinterface
N(1) et 2 de lunit extrieure (Voir le manuel complet fourni avec
lunit) 3. Connecter la carte dinterface la fournaise:
Thermostat communiquant: i. Connecter le fil RJ-11 (A00443)
entre linterface et la carte de contrle de la fournaise (Voir le
manuel complet fourni avec lunit)
Thermostat legacy : i. Connecter tous les fils du thermostat la
carte dinterface et la carte de
contrle de lunit de ventilation ii. Sassurer de connecter les
signaux en chauffage, sorties W1 et W2 connectes aux entres W1 and
W2 de la fournaise OU W sur W2 pour un thermostat 1 stage iii. Si
le thermostat ne comprend pas de sortie DH, un connecteur doit tre
ajout entre les bornes R et DH sur la carte dinterface
4. Mettre le disjonteur de lunit extrieure sur ON 5. Mettre le
disjoncteur de la fournaise sur ON Sassurer que lunit fonctionne
correctement 1. La LED verte de la carte dinterface doit clignoter
toutes les deux secondes 2. La LED orange de la carte dinterface
doit clignoter toutes les deux secondes 3. Le thermostat
communicant doit afficher Heat_Pump_Found ( thermopompe
dtecte ) 4. Rgler le thermostat en mode COOL (climatisation) et
ajuster le point de consigne
une valeur infrieure la temprature actuelle de la pice 5. La
fournaise et lunit extrieure devraient dmarrer en moins de 5
minutes
Dans cette configuration, la carte dinterface va rassembler en
mme temps linformation sur lunit extrieure et sur la fournaise afin
dajuster la vitesse du ventilateur la capacit de lunit
extrieure
* Aliz 9/12 kBTU montre. Voir la section Diagrammes lectrique du
manuel de lAliz pour les autres modles.
INSTALLATION DANS LES DIFFRENTS APPAREILS MODULANTS CHINOOK
SUPREME
Branchement legacy