This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Application Steps .......................................................................................................................... 16Overview............................................................................................................ 16Step 1. Plan The System................................................................................... 16Step 2. Determine Other Bus Devices Required ............................................... 17Step 3. Lay Out Communications and Power Wiring ........................................ 18
Troubleshooting Excel 10 Controllers and Wall Modules ............................. 33Temperature Sensor and Setpoint Potentiometer Resistance Ranges ........ 33Alarms........................................................................................................... 34Broadcasting the Service Message .............................................................. 34W7761A Controller Status LEDs .................................................................. 34T7780 DDWM Bypass Pushbutton ............................................................... 35
([FHO���:����$�5(027(�,1387�287387�'(9,&(
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 2
List of Figures .......................................................................................................................... 2Fig. 1. Typical system overview......................................................................... 4Fig. 2. Typical W7761A control application. ...................................................... 5Fig. 3. Excel 10 W7761A Remote I/O Device. .................................................. 9Fig. 4. W7761A construction. ............................................................................ 10Fig. 5. DIN rail adapters. ................................................................................... 11Fig. 6. T7770A,B,C,D construction (T7770A,C shown). .................................... 14Fig. 7. T7780 construction................................................................................. 15Fig. 8. Connecting the portable operator terminal to the E-Bus. ....................... 17Fig. 9. Bus wiring layout for doubly terminated daisy-chain E-Bus segment..... 18Fig. 10. Bus wiring layout for two singly terminated E-Bus segments. .............. 19Fig. 11. NEMA class 2 transformer voltage output limits................................... 21Fig. 12. Power wiring details for one Excel 10 per transformer. ........................ 21Fig. 13. Power wiring details for two or more Excel 10s per transformer. ......... 21Fig. 14. Transformer power wiring details for one Excel 10 used in UL 1995
equipment (U.S. only). ........................................................................ 22Fig. 15. Attaching two or more wires at terminal blocks. ................................... 23Fig. 16. Typical T7770A and C7770A wiring diagram. ...................................... 25Fig. 17. Typical Humidity and Enthalpy (4 to 20 mA) sensor wiring diagram. ... 25Fig. 18. Typical Window and Occupancy sensor wiring diagram. ..................... 26Fig. 19. Typical PWM Valve Actuator and miscellaneous fan control to
W7761A. ............................................................................................. 26Fig. 20. Typical Pneumatic transducer to (Series 60 - Floating) W7761A......... 27Fig. 21. Typical E-Bus termination module wiring diagrams.............................. 28Fig. 22. E-Bus termination wiring options.......................................................... 29Fig. 23. Temperature sensor resistance plots. .................................................. 33Fig. 24. Location of the Service Pin Button. ...................................................... 34Fig. 25. LED location on W7761A. .................................................................... 35Fig. 26. Bypass pushbutton location on T7780 DDWM..................................... 35
List of Tables .......................................................................................................................... 2Table 1. Agency Listings. .................................................................................. 6Table 2. List Of Available Points ....................................................................... 11Table 3. Application Steps................................................................................. 16Table 4. E-Bus Configuration Rules And Device Node Numbers...................... 17Table 5. VA Ratings For Transformer Sizing..................................................... 20Table 6. Field Wiring Reference Table.............................................................. 23Table 7. W7761A I/O Description...................................................................... 24Table 8. Excel 10 W7761A Device Ordering Information.................................. 30Table 9. Excel 10 Alarms................................................................................... 34Table 10. LED States. ....................................................................................... 3
Appendices .......................................................................................................................... 35Appendix A. Using E-Vision for Commissioning W7761A Controllers. ............. 35
Adding Analog Inputs - Enthalpy (4 to 20 mA)......................................... 36Adding Other Voltage/Current Sensors ................................................... 37Table A-1. Supported Voltage and Current Input Sensors ...................... 37Adding Digital Inputs................................................................................ 37Table A-2. Supported Digital Input Types ................................................ 37Adding Digital Outputs ............................................................................. 37Table A-3. Supported Digital Output Types ............................................. 39
Appendix B. Sequences of Operation. .............................................................. 39Common Operations .................................................................................... 39
Room Temperature Sensor (RmTemp) ................................................... 39Window Sensor (StatusWndw)................................................................ 39Dirty Filter Monitor.................................................................................... 39Series 60 Modulating Control................................................................... 39Pulse Width Modulating (PWM) Control .................................................. 39Indoor Air Quality (IAQ) Override............................................................. 40
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
3 74-2699
Appendix C. Complete List of Excel 10 W7761A Remote I/O Device UserAddresses. ........................................................................................................ 40
Table C0. Engineering Units For Analog Points. .......................................... 40Table C1.Input/Output Points. ...................................................................... 42Table C2. Control Parameters. ..................................................................... 52Table C3. Status Points. ............................................................................... 54Table C4. Configurations Parameters. ......................................................... 60Table C5. Direct Access And Special Points. ............................................... 68
Appendix D. Q7750A Excel 10 Zone Manager Point Estimating Guide. ........... 69Approximate Memory Size Estimating Procedure. ....................................... 69
Fig. D-1 Point capacity estimate for Zone Manager................................. 70Appendix E. Sensor Data for Calibration........................................................... 70
Resistance Sensors...................................................................................... 70C7100A1015, (and C7170A1002), Discharge Air, Outdoor AirTemperature Sensors .............................................................................. 70Table E-1. Sensor Resistance Versus Temperature................................ 70Fig. E-1. Graph of Sensor Resistance Versus Temperature.................... 71C7031B1033, C7031C1031, C7031D1062, C7031F1018, C7031J1050,C7031K1017, Return Air, Discharge Air Temperature Sensors............... 71Table E-2. Sensor Resistance Versus Temperature................................ 71Fig. E-2. Graph of Sensor Resistance Versus Temperature.................... 71T7770A,B,C,D and C7770A Sensors....................................................... 71Table E-3. Sensor Resistance Versus Temperature................................ 71Fig. E-3. Graph of Sensor Resistance Versus Temperature.................... 72
Voltage/Current Sensors. ............................................................................. 72C7600B1000 and C7600C1018 (2 to 10 mV) Humidity Sensors ............. 72Table E-4. Sensor Voltage Versus Humidity............................................ 72Fig. E-4. Graph of Sensor Voltage Versus Humidity................................ 72C7600C1008 (4 to 20 mA) Humidity Sensor............................................ 72Table E-5. Sensor Current Versus Humidity ............................................ 72Fig. E-5. C7600C Output Current Versus Humidity ................................. 73C7400A1004 Enthalpy Sensor................................................................. 73Table E-6. Sensor Current Versus Enthalpy (Volts)................................. 73Fig. E-6. Graph of Sensor Current Versus Enthalpy (Volts)..................... 73Fig. E-7. Partial Pschometric Chart for a C7400A Solid StateEnthalpy Sensor....................................................................................... 74Fig. E-8. C7400A solid State Enthalpy Sensor Output CurrentVersus Relative Humidity......................................................................... 74T7242 (or equivalent) CO2 Sensor .......................................................... 74Table E-7. Sensor Voltage Versus CO2 concentration............................ 75Fig. E-9. Graph of Sensor voltage Versus CO2 Concentration................ 75Monitor (2 to 20V) third Party ................................................................... 75Table E-8. Sensor Voltage Versus Input Voltage to A/D.......................... 75Fig. E-10. Graph of Sensor Voltage Versus Input Voltage to A/D............ 75Voltage/Pressure Sensor (third party)...................................................... 75Table E-9. Sensor voltage (Vdc) Versus Pressure inw (kPa) .................. 76Fig. E-11. Graph of Sensor Voltage (Vdc) Versus Pressure inw (kPa).... 76
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 4
,1752'8&7,21
'HVFULSWLRQ�RI�'HYLFHV
The W7761A, Excel 10 Remote Input/Output (RIO) device,provides auxiliary inputs and outputs for use with an Excel10 Zone Manager and Excel 10 controllers over theEchelon® LonWorks® E-Bus. These I/O points areconfigured with the E-Vision tool. The W7761A deviceuses Echelon® LonWorks® communication technologyand a new free topology twisted pair transceiver (FTT) for
greater network installation flexibility. The Excel 10 RIOdevice can be combined with the Excel 10 Zone Manager(FTT), other Excel 10 Controllers, and the Excel BuildingSupervisor, to provide a complete and low cost controlsolution for small to large commercial buildings.
The Q7750A Excel 10 Zone Manager is a communicationsinterface that allows devices on the E-Bus network tocommunicate with devices on the standard EXCEL 5000®System C-Bus. Fig. 1 shows an overview of a typicalsystem layout. The Q7750A also provides some controland monitoring functions.
PERSONAL COMPUTER TOOLSE-VISIONCARE
Q7752AFTT E-BUSSERIAL ADAPTER
EXCEL 10Q7750AFTT ZONEMANAGER
C-BUS COMMUNICATION NETWORK
EXCEL 500EXCEL BUILDING SUPERVISOR
C-BUS TO E-BUSINTERFACE DEVICE
EXCEL 10 W7751FPANEL PLENUM MOUNT VERSIONVARIABLE AIR VOLUMECONTROLLER
The W7761A, Excel 10 Remote Input/Output device,provides auxiliary inputs and outputs for use with an Excel10 Zone Manager and Excel 10 controllers over theEchelon® LonWorks® E-Bus. The W7761A RemoteInput/Output Device can be connected to outdoor airtemperature and humidity sensors that can be used byother Excel 10 controllers on the E-Bus or Excel 5000controllers on the C-Bus through the Excel 10 ZoneManager. This would allow the controllers to use theirphysical inputs for monitoring other elements such asreturn humidity, IAQ, etc. to achieve better control.
The W7761A can be used to average many spacetemperature sensors that are located in a zone that iscontrolled by the W7750 Constant Volume AHU Controller.The W7761A device has 8 Digital Outputs which may beDiscrete, Modulating or Floating. For example, this allowsthe control of lighting zones, miscellaneous exhaust orventilation fans, miscellaneous pumps, and can enablefreeze protection. See Fig. 2.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
5 74-2699
WINDOW CONTACT
OCCUPANCYSENSOR
OA TEMPERATURE
OA HUMIDITY
MISC.FANS PUMPS
LIGHTING CONTROL
EXCEL 10W7761AREMOTE INPUT/OUTPUT
M12885EXCEL 10 T7770 WALL MODULE
Fig. 2. Typical W7761A control application.
&RQWURO�3URYLGHG
The W7761A was not intended to control staged ormodulating heating/cooling coils, mixed air economizerdampers, or system fan/heat pump units. The W7761Acontains inputs and outputs, but no control software. Allcontrol that would be associated with the inputs andoutputs in the W7761A would be accomplished though theExcel Zone Manager and would not be suitable for VAVcontrol, temperature control, or any control function thatwould require less than a 30 second update rate.
3URGXFWV�&RYHUHG
This System Engineering Guide describes how to applythe W7761A Excel 10 Remote Input/Output Device andrelated accessories to typical applications. The specificdevices covered include:• W7761A Remote I/O device.• T7770 A through D Wall Modules.• Q7750A Excel 10 Zone Manager.• Q7751A Router (FTT to FTT only).• Q7752A Serial Interface Adapter.• Q7740A,B Repeaters (2-way and 4-way).• 209541B FTT Termination Module.
2UJDQL]DWLRQ�RI�0DQXDO
This manual is divided into three basic parts: theIntroduction, the Application Steps, and the Appendicesthat provide supporting information. The Introduction andApplication Steps 1 through 5 provide the informationneeded to make accurate material ordering decisions.Application Step 6 and the Appendices includeconfiguration engineering that can be started using ExcelE-Vision PC Software after the devices and accessoriesare ordered. Application Step 7 is troubleshooting.The organization of the manual assumes a project is beingengineered from start to finish. If an operator is adding to,or is changing an existing system, the Table of Contentscan provide the relevant information.
$SSOLFDEOH�/LWHUDWXUH
The following list of documents contains informationrelated to the Excel 10 W7761 Remote I/O Device and theEXCEL 5000® System in general.
Form No. Title74-2698 Excel 10 W7761A Device Specification
74-2588 Excel E-Vision User’s Guide74-5587 CARE User’s Manual74-5577 CARE Icon Guide74-2039 XBS User’s Manual74-5018 XBS Application Guide
3URGXFW�1DPHV
The W7761A Remote I/O Device is available in one model:• W7761A Remote Input/Output Device.
The T7770 Wall Module is available in five models:• T7770A1xxx Wall Module with temperature sensor only
- not applicable to the RIO device (jumper switches thesensor from 20Kohm NTC to a linearized version of a20 Kohm NTC used with the W7751A,C,E,G).
• T7770A2xxx Wall Module with temperature sensor andE-Bus network connection.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 6
• T7770B Wall Module with temperature sensor—(current feature that can be used with the RIO Device),setpoint, and E-Bus network connection for use with allExcel 5000 controllers (except W7751A,C,E,G).
• T7770C Wall Module with temperature sensor—(current feature that can be used with the RIO Device),setpoint, Bypass button and LED, and E-Bus networkconnection for use with all Excel 5000 controllers(except W7751A,C,E,G).
• T7770D Wall Module with temperature sensor—(current feature that can be used with the RIO Device),Bypass button and LED, and E-Bus network connectionfor use with all Excel 5000 controllers (exceptW7751A,C,E,G).
NOTE: The T7770B,C Models are available with arelative scale plate adjustable in E-Vision °F(± 5°C).
Only one PT3000 sensor is supported with the W7761Adevice.
The T7780 Digital Display Wall Module (DDWM) isavailable in one model:• T7780 DDWM displays and provides space
temperature, setpoint, Occ/Unocc override, ApplicationMode, and Fan mode/speed selection for all Excel 10controllers (except W7751 A,C,E,G).
Other products:• Q7750A Excel 10 Zone Manager.• Q7751A Bus Router.• Q7752A Serial Adapter.• Q7740A,B FTT Repeaters.• 209541B FTT Termination Module.• ML6161 Series 60 Damper Actuator.
• M6410A Series 60 Valve Actuator (use with V5812 orV5813 Valves).
• ML684A Series 60 Versadrive Valve Actuator (use withV5011 and V5013 Valves).
• MMC325-010 Transducer, Series 60 to pneumatic 0 to10 psi.
• MMC325-020 Transducer, Series 60 to pneumatic 0 to20 psi.
• ML6464A Direct Coupled Damper Actuator, 66 lb-in.torque, Series 60.
• ML6474 Direct Coupled Damper Actuator, 132 lb-in.torque, Series 60.
• ML6185A Direct Coupled Damper Actuator, SpringReturn, Series 60.
• ML7984B Direct Coupled Valve Actuator, PWM (usewith V5011 or V5013F,G Valves).
Refer to Table 8 in Application Step 5. Order Equipmentfor a complete listing of all available part numbers.
NOTE: The Q7750A Zone Manager is referred to as(E-Link) in internal software and CARE.
$JHQF\�/LVWLQJV
Table 1 provides information on agency listings for Excel10 products.
Table 1. Agency Listings.
Device Agency Comments
W7761A Input/ UL Tested and listed under UL916 (file number E87741).Output Device cUL Listed (E87741).
CE General Immunity per European Consortium Standards EN50081-1 (CISPR 22,Class B) and EN 50082-1:1992 (based on Residential, Commercial,and Light Industrial).EN 61000-4-2: IEC 1000-4-2 (IEC 801-2) Electromagnetic Discharge.EN 50140, EN 50204: IEC 1000-4-3 (IEC 801-3) Radiated Electromagnetic Field.EN 61000-4-4: IEC 1000-4-4 (IEC 801-4) Electrical Fast Transient (Burst).
Radiated Emissions and Conducted Emissions:EN 55022: 1987 Class B.CISPR-22: 1985.
FCC Complies with requirements in FCC Part 15 rules for a Class B Computing Device.Operation in a residential area can cause interference to radio or TV reception andrequire the operator to take steps necessary to correct the interference.
T7770A through D UL (Not applicable.)Wall Modules CSA (Not applicable.)
FCC (Not applicable.)
T7780 DDWM CE Emissions; EN50081-1, En55022 (CISPR Class B), Immunity 50082-1
UL &cUL Tested and listed under UL916, S8L9 Energy Management Equipment.
FCC Complies with requirements in FCC Part 15 rules for a Class B Computing Device.(continued)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
7 74-2699
Table 1. Agency Listings (continued).
Device Agency Comments
Q7750A Excel 10 UL Tested and listed under UL916, file number S4804 (QVAX, PAZY).Zone Manager CSA Listing pending.
FCC Complies with requirements in FCC Part 15 rules for a Class A Computing Device.Operation in a residential area can cause interference to radio or TV reception andrequire the operator to take steps necessary to correct the interference.
Q7751A,B Router,Q7752A Serial Adapter,Q7740A,B FTT Repeaters
UL UL1784.
CSA Listed.
FCC Complies with requirements in FCC Part 15 rules for a Class B Computing Device.
$EEUHYLDWLRQV�DQG�'HILQLWLRQV
AHU - Air Handling Unit; the central fan system thatincludes the blower, heating equipment, coolingequipment, ventilation air equipment, and otherrelated equipment.
CO - Carbon Monoxide. Occasionally used as ameasure of indoor air quality.
CO2 - Carbon Dioxide. Often used as a measure ofindoor air quality.
CARE - Computer Aided Regulation Engineering; the PCbased tool used to configure C-Bus and E-Busdevices.
C-Bus -Honeywell proprietary Control Bus forcommunications between EXCEL 5000® Systemcontrollers and components.
CPU - Central Processing Unit; an EXCEL 5000®System controller module.
cUL - Underwriters Laboratories Canada.
CVAHU -Constant Volume AHU; refers to a type of airhandler with a single-speed fan that provides aconstant amount of supply air to the space itserves.
DDF - Delta Degrees Fahrenheit.
D/X - Direct Expansion; refers to a type of mechanicalcooling where refrigerant is (expanded) to its coldstate, within a heat-exchanging coil that ismounted in the air stream supplied to theconditioned space.
E-Bus - Honeywell implementation of Echelon®LonWorks® network for communication amongExcel 10 Controllers.
E-Bus Segment - An E-Bus section containing no morethan 60 Excel 10s. Two segments can be joinedtogether using a router.
Echelon® - The company that developed the LON® busand the Neuron® chips used to communicate onthe E-Bus.
Economizer - Refers to the mixed-air dampers thatregulate the quantity of outdoor air that enters the
building. In cool outdoor conditions, fresh air canbe used to supplement the mechanical coolingequipment. Because this action saves energy, thedampers are often referred to as economizerdampers.
EMI - Electromagnetic Interference; electrical noise thatcan cause problems with communicationssignals.
E-Link - Refers to the Q7750A Zone Manager. This nameis used in internal software and in CAREsoftware.
EMS - Energy Management System; refers to thecontrollers and algorithms responsible forcalculating optimum operational parameters formaximum energy savings in the building.
EEPROM - Electrically Erasable Programmable Read OnlyMemory; the variable storage area for saving usersetpoint values and factory calibrationinformation.
EPROM - Erasable Programmable Read Only Memory; thefirmware that contains the control algorithms forthe Excel 10 Controller.
Excel 10 Zone Manager - A controller that is used tointerface between the C-Bus and the E-Bus. TheExcel 10 Zone Manager also has the functionalityof an Excel 100 Controller, but has no physicalI/O points.NOTE: The Q7750A Zone Manager can bereferred to as E-Link in the internal software,CARE.
FCU - Fan Coil Unit.
Firmware - Software stored in a nonvolatile memorymedium such as an EPROM.
Floating Control - Refers to Series 60 Modulating Controlof a valve or damper. Floating Control utilizes onedigital output to pulse the actuator open, andanother digital output to pulse it closed.
FTT - Free Topology Transceiver.
IAQ - Indoor Air Quality. Refers to the quality of the airin the conditioned space, as it relates to occupanthealth and comfort.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 8
I/O - Input/Output; the physical sensors and actuatorsconnected to a controller.
I x R - I times R or current times resistance; refers toOhm’s Law: V = I x R.
K - Degrees Kelvin.
Level IV - Refers to a classification of digitalcommunication wire. Formerly known as UL LevelIV, but not equivalent to Category IV cable. Ifthere is any question about wire compatibility, useHoneywell-approved cables (see Step 5 OrderEquipment section).
NEC - National Electrical Code; the body of standardsfor safe field-wiring practices.
NEMA - National Electrical Manufacturers Association; thestandards developed by an organization ofcompanies for safe field wiring practices.
Node - A Communications Connection on a network; anExcel 10 Controller is one node on the E-Busnetwork.
NV - Network Variable; an Excel 10 parameter that canbe viewed or modified over the E-Bus network.
PC - An IBM compatible Personal Computer with 386or higher processor and capable of runningMicrosoft® Windows™ Version 3.1.
Pot - Potentiometer. A variable resistance electroniccomponent located on the T7770B,C WallModule; used to allow user-adjusted setpoints tobe input into the Excel 10 Controller.
PWM - Pulse Width Modulated output; allows analogmodulating control of equipment using a digitaloutput on the controller.
RTD - Resistance Temperature Detector; refers to atype of temperature sensor whose resistanceoutput changes according to the temperaturechange of the sensing element.
RIO - Remote Input/Output Device. Provides auxiliaryinputs and outputs for use with an Excel 10 ZoneManager and Excel 10 controllers.
Subnet - An E-Bus segment that is separated by a routerfrom its Q7750A Zone Manager.
TOD - Time-Of-Day; the scheduling of Occupied andUnoccupied times of operation.
TPT - Twisted Pair Transceiver.
UV - Unit Ventilator Controller.
VA - Volt Amperes; a measure of electrical poweroutput or consumption as applies to an ac device.
Vac - Voltage alternating current; ac voltage rather thandc voltage.
VAV - Variable Air Volume; Refers to either a type of airdistribution system, or to the W7751 Excel 10VAV Box Controller that controls a single zone ina variable air volume delivery system.
VOC - Volatile Organic Compound; refers to a class ofcommon pollutants sometimes found in buildings.Sources include out-gassing of constructionmaterials, production-line by-products, andgeneral cleaning solvents. A VOC is occasionallyused as a measure of indoor air quality.
W7750 - The model number of the Excel 10 CVAHUControllers (also see CVAHU).
W7751 - The model number of the Excel 10 VAV BoxControllers (also see VAV).
W7752 - The model number of the Excel 10 FCUControllers (also see FCU).
W7753 - The model number of the Excel 10 UV Controllers(also see UV).
W7761 - The model number of the Excel 10 RIO Device(also see RIO).
Wall Module - The Excel 10 Space Temperature Sensorand other optional controller inputs are containedin the T7770 or T7780 Wall Modules. SeeApplication Step 5. Order Equipment for detailson the various models of Wall Modules.
XBS - Excel Building Supervisor; a PC based tool formonitoring and changing parameters in C-Busdevices.
&RQVWUXFWLRQ
&RQWUROOHUV
The Excel 10 W7761A RIO Device is available in onemodel. It contains 4 resistive inputs that can be configuredfor either 20Kohm NTC or PT3000 sensors, 2 voltage orcurrent inputs, 4 digital inputs and 8 Digital Outputs(Triacs) which may be Discrete (maintained ormomentary), Modulating (PWM) or Floating.
The W7761A consists of a single circuit board that ismounted in a sheet metal subbase and protected by afactory snap-on cover. The device mounts with two screws(see Fig. 3 or 4). Using DIN rail adapters (see Fig. 5) theycan also be snapped onto standard EN 50 022 35 mm by7.5 mm (1-3/8 in. by 5/16 in.) DIN rail. DIN rail is availablethrough local suppliers. If using DIN rail also purchasefrom Augat Inc. part number 2TK2D DIN rail (adapter) twoeach for every device (see Fig. 5). Wires are attached tothe screw terminal blocks on both sides of the device.Connection for operator access to the E-Bus is providedby plugging the SLTA connector cable into thecommunications jack.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
9 74-2699
A channel in the cover allows the device status LED to bevisible when the cover is in place. There are no field-serviceable parts on the circuit board and, therefore, it isintended that the cover never be removed.
The W7761A can be mounted in any orientation.Ventilation openings were designed into the cover to allowproper heat dissipation regardless of the mountingorientation. See Fig. 3 and 4.
M15273
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
E GND
NOTUSED
NOTUSED
AI-1OHM
GND AI-2OHM
AI-3 OHM
GND A1-4 OHM 22 VDC
OUT
AI-5 V/mA
AI-6 V/mA
GNDE-BUS E-BUS
JACK
DI-4 GND DI-3 DI-2 GND DI-124
VAC
24 VACCOM
1OUT
2OUT
3OUT
4OUT
5OUT
6OUT
7OUT
8OUT
Fig. 3. Excel 10 W7761A Remote I/O Device.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3
E GND
NOTUSED
NOTUSED
AI-1OHM
AI-2OHM
GND AI-3OHM
GND AI-4OHM
AI-5V/mA
GND AI-6V/mA
22VDCOUT
E-BUS E-BUSJACK
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
DI-4 GND DI-3 DI-2 GND DI-124
VAC
24VACCOM
1OUT
2OUT
3OUT
4OUT
5OUT
6OUT
7OUT
8OUT
5-3/16 (132)
5-5/8(143)
3-1/16(77)
2-1/8(54)
6 (152)
M15274
Fig. 4. W7761A construction in in. (mm).
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
11 74-2699
M6857
1
2
3
Fig. 5. DIN rail adapters.
The input/output points are summarized in Table 2.
Table 2. List Of Available Points.
W7761A
Digital Outputs 8 Triac Outputs
Digital Inputs 4
Analog Inputs 6(4 Resistive and 2 Voltage/CurrentInputs)
DC Power 20 Vdc available to power optionalsensors (50 mA max.)
Floating (Series 60)Control
Heating or Cooling
PWM Control Heating or Cooling
3HUIRUPDQFH 6SHFLILFDWLRQV
Power:24 Vac with a minimum of 20 Vac and a maximum of 30Vac at either 50 or 60 Hz. The W7761A powerconsumption is 6 VA maximum at 50 or 60 Hz. TheW7761A is a NEC Class 2 rated device. This listingimposes limits on the amount of power the product canconsume or directly control to a total of 100 VA (U.S. only).
The individual Triac outputs incorporate an internalcommon connection with the input power transformer. TheTriacs provide a switched path from the hot side (R) of thetransformer through the load to the common of thetransformer. The W7761A Device design must use thesame power transformer for any loads connected to thatdevice; see Fig. 19.
Each individual Triac is rated 500mA at 30 Vac maximum.Under all operating conditions, the maximum load/sourcepower budget for the W7761A Device is 100 VA.
CPU:Motorola or Toshiba 3150 Neuron processor, containingthree eight-bit CPU’s. Each Neuron has a unique 48-bitnetwork identification number.
Memory Capacity:64K ROM/PROM (6K reserved for network operations,
58K usable for control algorithm code).512 bytes EEPROM.2K RAM.
Specified Space Temperature Sensing Range:45 to 99°F (7 to 37°C) with an allowable control setpointrange from 50 to 90°F (10 to 32°C) when initiated from thenetwork and 55 to 85°F (13 to 29°C) when configured andconnected to T7770 Wall Modules or T7780 DDWM.
Communications:The W7761A Device uses a transformer-coupledcommunications port with differential Manchester-encodeddata at 78 kilobits per second (kbs). The transformer-coupled communications interface offers a much higherdegree of common-mode noise rejection while ensuring dcisolation.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 12
Approved cable types for E-Bus communications wiring isLevel IV 22 AWG (0.34 mm2) plenum or non-plenum ratedunshielded, twisted pair, solid conductor wire. For non-plenum areas, use Level IV 22 AWG (0.34 mm2) such asU.S. part AK3781 (one pair) or U.S. part AK3782 (twopair). In plenum areas, use plenum-rated Level IV, 22AWG (0.34 mm2) such as U.S. part AK3791 (one pair) orU.S. part AK3792 (two pair). (See Tables 6 and 8 for partnumbers.) Also use Echelon approved cables.
The Free Topology Transceiver (FTT) supports polarityinsensitive free topology wiring. This frees the systeminstaller from the need to wire using a bus topology. Star,bus, mixed, and loop wiring are all supported by thisarchitecture. The maximum E-Bus length when using acombination of star, loop, and bus wiring (singlyterminated) is 1640 ft (500m) with the maximum node-to-node length of 1312 ft (400m). In the event that the totalwire length is exceeded, then a Q7740A 2-Way Repeateror a Q7740B 4-Way Repeater can be used to allow thenumber of devices to be spread out as well as increasingthe length of wire over which they communicate. Themaximum number of repeaters per segment is one (oneither side of the router). A Q7751A E-Bus Router can alsobe used to effectively double the maximum E-Bus length.The advantage of using the router is that it will segregatetraffic to a segment while when using the repeater, alltraffic is repeated on each segment. When utilizing adoubly terminated E-Bus structure, use a continuousdaisy-chain with no stubs or taps from the main backbone,The maximum E-Bus length is 4593 ft (1400m) with themaximum node-to-node length of 3773 ft (1150m).
FTT networks are very flexible and convenient to installand maintain, but it is imperative to carefully plan thenetwork layout and create and maintain accuratedocumentation. Unknown or inaccurate wire run lengths,node-to-node distances, node counts, total wire length,and misplaced or missing terminators can cause poornetwork performance. Refer to E-Bus Wiring Guidelinesform, 74-2865 for complete description of network topologyrules.
LonMark Functional ProfileW7761A Device supports the LonMark PreliminaryFunctional Profile for a Remote Input/Output Device.
Environmental:Operating Temperature: -40° to 150°F (-40° to 65.5°C).Shipping Temperature: -40° to 150°F (-40° to 65.5°C).Relative Humidity: 5% to 95% noncondensing.
Vibration:Rated V2 level compliant.
Inputs/Outputs:The W7761A Unit supports the following hardwarefeatures:• Four 20KNTC (1000 through 150,000 ohm) or PT3000
(250 through 12,000 ohm) resistive analog inputs.• Two 0.2 to 10 VDC or 2 to 20 mA (user selectable)
analog inputs.• Four dry contact digital inputs.• Eight 24 Vac Triac digital outputs (500 mA MAX).• One 22 Vdc power supply for auxiliary devices with a
Outdoor Air Humidity:Type: Voltage/Current.Supported Sensors: C7600B1000 and C7600B1018
(2 to 10V), C7600C1008 (4 to 20mA).
Return Air Humidity:Type: Voltage/Current.Supported Sensors: C7600B1000 and C7600B1018
(2 to 10V), C7600C1008 (4 to 20mA).
Outdoor Air Enthalpy:Type: Current.Supported Sensors: C7400A1004 (4 to 20mA).
Return Air Enthalpy:Type: Current.Supported Sensors: C7400A1004 (4 to 20mA).
*The PT3000 sensor is not recommended for floating control (real time - discharge or return configured as space sensor).The PT3000 sensor is intended for monitoring or differential (staged) control.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
13 74-2699
Air Filter Differential Pressure:Type: Voltage.Supported Sensors: Third party 2 to 10V, 0 to 5 inw
(0 to 1.25 kPa) differential pressure sensors.
Space CO2 Sensor:Type: Voltage.Supported Sensors: Third party 0 to 10V,
0 to 2000 ppm CO2 sensors.
Outdoor Air CO 2 Sensor:Type: Voltage.Supported Sensors: Third party 0 to 10V,
0 to 2000 ppm CO2 sensors.
Outdoor Air CO Sensor:Type: Current.Supported Sensors: Third party 4 to 20mA,
0 to 300 ppm CO sensor.
Monitor Sensor for network use:Type: Voltage.Supported Sensors: Third party 2 to 10V, 2 to 10 volts
displayed.
Digital Inputs:Dry-contact inputs are sensed using a 9 milliamp at4.8 volts detection circuit. It is very important that thedevice used contains high quality, noncorroding contactswith resistivity that does not degrade; that is, increase overtime. Use noble metal (such as gold or silver) or pimpledor sealed contacts to assure consistent,long-term operation.
Triac Outputs:Triac Outputs on the RIO:— Power ratings: 20 Vac to 30 Vac at 25 mA MIN to 500
mA MAX current for any voltage.
CAUTIONWhen any device is energized by a Triac, thedevice must be able to sink a minimum of 25 mA.
NOTE: Triacs sink current to the 24 Vac common (COMterminal on the W7761A); see Fig. 19 for wiringexample.
IMPORTANTIf non-Honeywell motors, actuators, ortransducers are to be used with Excel 10Controllers, Triac compatibility must be verified(see previous NOTE).
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 14
:DOO�0RGXOHV
The T7770A,B,C,D Wall Module sensor—(current feature thatcan be used with the Excel 10 W7761A RIO Device). See Fig. 6.
STANDARDUTILITYCONDUITBOX (2 X 4)MOUNTINGHOLES
KNOCKOUTS FOR EUROPEANAPPLICATIONS
3-5/32 (80)
2-3/8 (60)
29/32 (23)
5-1/16(128)
2-3/8(60)
T77
70A
1006
M15119
STANDARDUTILITYCONDUITBOX (2 X 4)MOUNTINGHOLES
KNOCKOUTS FOR EUROPEANAPPLICATIONS
3-5/32 (80)
2-3/8 (60)
1-1/4 (32)
5-1/16(128)
2-3/8(60)
T77
70C
7065
60
55 85
80
75
DIP
Sw
itch
S4
Set
tings
:
1,3,
5=on
; 2,4
=off
2,4
=on;
1,3
,5=o
ff
1,2,
3,4=
on; 5
=0ff
W77
53X
L600
-XL2
0W
7752
LED
RE
TU
RN
BY
PAS
S
LED
FAN
SE
TPT
SE
NS
OR
GN
D
LED
SE
TPT
SE
NS
OR
AL
CO
M
LED
SE
TPT
SE
NS
OR
GN
D
BY
PAS
S/F
AN
BY
PAS
S/F
AN
9 8 7 6 5 4 3 2 1
E-B
US
E-B
US
Fig. 6. T7770A,B,C,D (T7770A,C shown) construction in in. (mm), sensor—(current feature that can be usedwith RIO Device).
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
15 74-2699
The T7780 DDWM for the Excel 10 Controllers (seeProduct Names section) is shown in Fig. 7.
M11391
STANDARDUTILITYCONDUITBOX (2 X 4)MOUNTINGHOLES
KNOCKOUTS FOR EUROPEANAPPLICATIONS
3-5/32 (80)
2-3/8 (60)
1 (25)
5-1/16(128)
2-3/8(60)
Fig. 7. T7780 construction, subbase dimension in in. (mm).
&RQILJXUDWLRQV
Each W7761A device can control or monitor a variety ofdifferent types of mechanical equipment. The W7761Awas not intended to control staged or modulatingheating/cooling coils, mixed air economizer dampers, orsystem fan/heat pump units. The W7761A contains inputsand outputs, but no control software. All control that wouldbe associated with the inputs and outputs in the W7761Awould be accomplished though the Excel Zone Managerand would not be suitable for VAV control, temperature
control, or any control function that would require less thana 30 second update rate.
It would be suitable to control miscellaneous exhaust orventilation fans, lighting zones that are spread out througha building which need to be linked to a start/stop timeprogram through the Zone Manager or to enable freezeprotection. The W7761A device can be connected tooutdoor air temperature and humidity sensors that can beused by other Excel 10 controllers on the E-Bus or Excel5000 controllers on the C-Bus through the Excel 10 ZoneManager. The W7761A can be used to monitorOccupancy, Window, Dirty filter, Indoor air quality, andSmoke control sensors. This allows the controllers to usetheir physical inputs for monitoring other elements such asreturn humidity, IAQ, etc. to achieve better control. TheW7761A can be used to average many space temperaturesensors that are located in a zone that is controlled by theW7750 Constant Volume AHU Controller.
0L[HG�2XWSXW�7\SH�&RQWURO
The W7761A Device can control mixed-output-types ofapplications such as PWM and staged control occurringsimultaneously with Series 60 Floating Control.
2FFXSDQF\�6HQVRU
Excel 10 W7761A device can be connected to anoccupancy sensor through a digital input. This is a device,such as a passive infrared motion detector, that contains adry contact (see following NOTE) closure to indicatewhether or not people are present in the space. The Excel10 W7761A Device expects a contact closure to indicatethe space is Occupied. See Fig. 18 in Application Step 4,Prepare Wiring Diagrams, for details on wiringconnections. This occupancy sensor can then be bound toother Excel 10 controllers on the E-Bus or Excel 5000controllers on the C-Bus through the Excel 10 ZoneManager. This would allow the other Excel 10 controllers touse their physical inputs for monitoring other elementssuch as return humidity, IAQ, etc. to achieve better control.
NOTE: The Excel 10 Controllers (W7750 CVAHU andW7761A RIO) have limited power available (only9 mA at 4.8 volts) for checking the digital inputsfor contact closures. It is very important that thedevice used contains high quality, noncorrodingcontacts with resistivity that does not degrade;that is, increase over time. Use noble metal (suchas gold or silver), pimpled or sealed contacts toassure consistent, long-term operation.
The recommended devices for use with the Excel 10W7750 Controller and W7761A Device are theEL7628A1007 Ceiling Mounted Infrared or theEL7680A1008 Wall Mounted Wide View InfraredOccupancy Sensors. If ultrasonic sensors are required, theEL7611A1003 and the EL7612A1001 Occupancy Sensorsare recommended. An EL76XX Power Supply/Control Unitis required for use with these occupancy sensors. TheEL7630A1003 can power up to four sensors, and is multi-tapped for several line voltages. The EL7621A1002 canpower three sensors and it connects to 120 Vac linevoltage. The EL7621A1010 can also power three sensorsbut it connects to 277 Vac line voltage.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 16
:LQGRZ�2SHQ�&ORVHG�'LJLWDO�,QSXW
Excel 10 W7761A device can be connected to a windowsensor to indicate whether a window in the space wasopened. The Excel 10 W7761A device can be connectedto a dry contact (see the NOTE for the Occupancy Sensorand Fig. 18 in Application Step 4. Prepare WiringDiagrams, for details) or a set of contacts wired in series(for monitoring multiple windows) to verify that thewindow(s) are closed. This window(s) sensor can then bebound to other Excel 10 controllers on the E-Bus or Excel5000 controllers on the C-Bus through the Excel 10 ZoneManager. The algorithm in the other Excel 10 controllersexpects a contact closure to indicate the window is closed.If an open window is detected, the algorithm in the otherExcel 10 controllers changes the mode of operation toFREEZE_PROTECT, which shuts down the controlfunctions, and watches for low space temperatureconditions. The freeze protection setpoint is 46.4°F (8°C),and the frost alarm occurs at 42.8°F (6°C).
:DOO�0RGXOH�2SWLRQV
As previously discussed, there are five basic varieties ofthe T7770. There is one variety of the PT3000 sensor andthe T7780 DDWM (see the Product Names and theConstruction sections). The T7770A,B,C,D 20Kohm NTCsensor—(current feature that can be used with the RIODevice) and one PT3000 sensor can be configured on anyof the four resistive inputs. The T7780 is an E-Bus nodeand would not be directly connected to the RIO Device.
'LUW\�)LOWHU�0RQLWRU
The air filter in the air handler can be monitored by theW7761A RIO device and an alarm issued by the ZoneManager when the filter media needs replacement. Thetwo methods of monitoring the filter are:
1. Connecting a differential pressure switch to a digitalinput on the W7761A.
2. Wiring a 2-to-10V differential pressure sensor to avoltage input on the W7761A. If the analog inputsensor is used, its measured value 0 to 5 inw (0 to1.25 kPa) is compared to a user-selectable setpoint.The comparison is done in the Zone Manager —valid range: 0 to 5 inw (0 to 1.25 kPa), and the DirtyFilter alarm is issued when the pressure drop acrossthe filter exceeds the setpoint.
,QGRRU�$LU�4XDOLW\��,$4�
The Excel 10 W7761A device can monitor IAQ using oneof two different methods of detecting poor air quality. Thefirst is with an IAQ switch device connected to a digitalinput on the W7761A, where a contact closure indicatespoor air quality, and an alarm can be issued by the ZoneManager. The device can detect poor air quality using anydesired measure such as CO2, VOC, CO, etc. The secondmethod, is through an analog input that connects to a CO2
sensor (0 to 10V). The measured value of CO2 from thissensor (0 to 2000 ppm) is compared to a user-selectablesetpoint (the comparison is done in the Zone Manager —valid range: 0 to 2000 ppm), and an IAQ alarm can beissued when the CO2 level exceeds the setpoint. The IAQsensor that is connected to the W7750 RIO, can be boundto other W7750 CVAHU Excel 10 controllers on theE-Bus.
$33/,&$7,21�67(36
2YHUYLHZ
The seven application steps shown in Table 3 are planningconsiderations for engineering an Excel 10 W7761Remote Input/Output Device. These steps are guidelinesintended to aid understanding of the product I/O options,bus arrangement choices and the Excel 10 W7761ADevices role in the overall EXCEL 5000® Systemarchitecture.
Table 3 . Application Steps.
Step No. Description
1 Plan The System
2 Determine Other Bus Devices Required
3 Lay Out Communication and Power Wiring
4 Prepare Wiring Diagrams
5 Order Equipment
6 Configure Devices
7 Troubleshooting
6WHS����3ODQ�7KH�6\VWHP
Plan the use of the W7761A Devices according to the jobrequirements. Determine the location, functionality andsensor or actuator usage. Verify the sales estimate of thenumber of W7761A Devices and the number and type ofoutput actuators and other required accessories.
When planning the system layout, consider potentialexpansion possibilities to allow for future growth. Planningis very important to be prepared for adding HVAC systemsand controllers in future projects.
T7770A,B,C,D Wall Modules (sensor—current feature thatcan be used with the RIO Device)can be installed as eitherhardwired I/O-only devices or additional wiring can be runto them (for the E-Bus network ) to allow a CARE/E-Visionoperator terminal to have access to the E-Bus. Theapplication engineer needs to determine how many wallmodules or other input sensors are required. Thisinformation is required during installation to ensure that theproper number and type of wires are pulled to the wallmodules, and the building operators are informed aboutwhere they can plug in to the E-Bus network with aportable operator terminal (see Fig. 8 through 10).
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
17 74-2699
M12891
NOTEBOOK PC
E-BUSPORT
RS-232SERIAL PORT
Q7752ASLTA
CABLEPART NO. 205979
SHIELDED INTERFACE CABLE
EXCEL 10W7761A
REMOTEINPUT/OUTPUT
DEVICE
Fig. 8. Connecting the portable operator terminal to theE-Bus.
The FTT communication loop, (E-Bus) between controllersis a free topology wiring scheme that supports star, loop,and/or bus wiring. Refer to the E-Bus Wiring Guidelinesform, 74-2865 for complete description of network topologyrules. See Application Step 3. Lay Out Communicationsand Power Wiring, for more information on bus wiringlayout, and see Fig. 16 through 19 in Application Step 4.Prepare Wiring Diagrams, for wiring details.
The application engineer must review the Direct DigitalControl (DDC) job requirements. This includes theSequences of Operation for the Excel 10 controllers, andfor the system as a whole. Usually there are variables thatmust be passed between the W7750 (CVAHU), Q7750AZone Manager, W7761 (RIO), and other Excel 10controller(s), or central plant controller(s) that are requiredfor optimum system-wide operation. Typical examples are
the TOD Occ/Unocc signal, the outdoor air temperature,demand limit control signal, and smoke control modesignal.
It is important to understand these interrelationships earlyin the job engineering process to ensure implementingwhen configuring the controllers. (See Application Step 6.Configure Devices, for information on the various Excel 10parameters and on Excel 10 point mapping.)
6WHS���'HWHUPLQH�2WKHU�%XV�'HYLFHV�5HTXLUHG
A maximum of 62 nodes can communicate on a single E-Bus segment. Each W7761A (RIO), W7750 (CVAHU),W7751 (VAV) Controller or T7780 Wall Module constitutesone node. If more nodes are required, a Q7751A Router isnecessary. Using a router allows up to 125 nodes, dividedbetween two E-Bus segments. The router accounts for twoof these nodes (one node on each side of the router); aQ7750A Excel 10 Zone Manager takes one node and twonodes are available for operator terminal nodes, leaving120 nodes available for Excel 10 Controllers and T7780Wall Modules. All 120 controllers and T7780 Wall Modulesare able to talk to each other through the router. A Q7750AExcel 10 Zone Manager is required to connect the E-Busto the standard EXCEL 5000® System C-Bus. Each Excel10 Zone Manager can support no more than 120 Excel 10Controllers and T7780 Wall Modules. This limit is set in theExcel 10 Zone Manager database as an absolutemaximum.Each E-Bus segment is set up with two unused nodes toallow for a CARE/E-Vision or Hand Held Tool (HHT) to beconnected to the E-Bus. Multiple CARE/E-Vision or HHTterminals can be connected to the bus at the same time.Table 4 summarizes the E-Bus segment configurationrules.
Table 4 . E-Bus Configuration Rules And Device Node Numbers.
One E-Bus Segment Example Maximum Number of Nodes Equals 62
One Q7750A Excel 10 Zone Manager 1 node
Port for operator terminal access (CARE/E-Vision or HHT) 1 node
Maximum number of Excel 10s and T7780s 60 nodes(Only T7780 Wall Modules are E-Bus nodes)
Total 62 nodes
Two E-Bus Segments Example Maximum Number of Nodes Equals 125
One Q7750A Excel 10 Zone Manager 1 node
One Q7751A Router 2 nodes (1 in each Bus Segment)
Ports for operator terminal access (two CARE/E-Vision or HHT terminals) 2 nodes (1 in each Bus Segment)
Maximum number of Excel 10s and T7780s in segment number one 60 nodes(Only T7780 Wall Modules are E-Bus nodes)
Maximum number of Excel 10s and T7780s in segment number two 60 nodes(Only T7780 Wall Modules are E-Bus nodes)
Total 125 nodes
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 18
Refer to the E-Bus Wiring Guidelines form, 74-2865 forcomplete description of network topology rules and themaximum wire length limitations. If longer runs arerequired, a Q7740A 2-way or Q7740B 4-way repeater canbe added to extend the length of the E-Bus. A Q7751ARouter can be added to partition the system into twosegments and effectively double the length of the E-Bus.Only one router is allowed with each Excel 10 ZoneManager and each network segment can have a maximumof 1 repeater. In addition, all E-Bus segments require theinstallation of a Bus Termination Module for a singlyterminated E-Bus or two Bus Termination Modules for adoubly terminated E-Bus. For more details on E-Bustermination, refer to the E-Bus Wiring Guidelines form, 74-2865, or see Application Step 3. Lay Out Communicationsand Power Wiring, and the E-Bus Termination Modulesubsection in Application Step 4.
6WHS����/D\�2XW�&RPPXQLFDWLRQV�DQG3RZHU�:LULQJ
(�%XV�/D\RXW
The communications bus, E-Bus, is a 78-kilobit serial linkthat uses transformer isolation and differential Manchesterencoding. Approved cable types for E-Buscommunications wiring is Level IV 22 AWG (0.34 mm2)plenum or non-plenum rated unshielded, twisted pair, solid
conductor wire. For nonplenum areas, use Level IV 22AWG (0.34 mm2), such as U.S. part AK3781 (one pair) orU.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm2) such as U.S. partAK3791 (one pair) or U.S. part AK3792 (two pair). SeeTables 9 and 10 for part numbers. Also use Echelonapproved cables. The FTT communications bus, E-Bus,supports a polarity insensitive, free topology wiringscheme that supports star, loop, and/or bus wiring.
E-Bus networks can be configured in a variety of ways, sorefer to the E-Bus Wiring Guidelines form, 74-2865 for acomplete description of network topology rules andTable 4. Fig. 9 and 10 depict two typical E-Bus networktopologies; one as a singly terminated bus segment thathas 60 nodes or less, and one showing a doublyterminated segment. The bus configuration is set up usingthe Network Manager tool from within CARE (see theCARE User’s Manual form, 74-5587 or Excel E-VisionUser’s Guide form, 74-2588).
NOTE: For wiring details see the E-Bus TerminationModule subsection in Step 4. For wall modulewiring, US part AK3782 (non-plenum) or US partAK3792 (plenum) can be used. These cablescontain two twisted pairs (one for the run down tothe wall module, and one for the run back up tothe controller) for ease of installation.
M12892
EXCEL 10VAV
EXCEL 10VAV
EXCEL 10
RI0
EXCEL 10
RI0
EXCEL 10
RI0
EXCEL 10
UV
EXCEL 10VAV
EXCEL 10VAV
EXCEL 10VAV
EXCEL 10Q7750A FTT ZONE MANAGER
TO C-BUS(SEE FIG. 1)
E-BUS
E-BUS
E-B
US
UP TO 60TOTAL NODES
T7770
T7770T7770T7770
T7770
JACK FOR OPERATOR TERMINAL
(SHARED) T7780
209541BTERMINATION MODULES(AT ENDS OF E-BUS DAISY-CHAIN)
T7770s WITH NO E-BUS ACCESS
E-BUS
I/O CONNECTIONS
EXCEL 10
UV
Fig. 9. Bus wiring layout for doubly terminated daisy-chain E-Bus segment.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
19 74-2699
EXCEL 10VAV
EXCEL 10VAV
EXCEL 10VAV
EXCEL 10Q7750AFTT ZONE MANAGER TO C-BUS
(SEE FIG. 1)
E-BUS SEGMENT NUMBER 2
E-BUS SEGMENT NUMBER 1
E-BUS SEGMENT NUMBER 2
T7770
T7780
E-BUS ACCESS
E-BUS ACCESS
Q7751AFTTE-BUSROUTER
209541BTERMINATION MODULE
209541BTERMINATION MODULE
M12893
EXCEL 10
UV
EXCEL 10
RI0
EXCEL 10
UV
EXCEL 10
RI0
EXCEL 10
UV
Fig. 10. Bus wiring layout for two singly terminated E-Bus segments.
NOTE: See the E-Bus Termination Module section forwiring details.
IMPORTANTNotes on communications wiring:• All field wiring must conform to local codes and
ordinances.• Approved cable types for E-Bus
communications wiring is Level IV 22 AWG(0.34 mm2) plenum or non-plenum ratedunshielded, twisted pair, solid conductor wire.For nonplenum areas, use Level IV 22 AWG(0.34 mm2), such as U.S. part AK3781 (onepair) or U.S. part AK3782 (two pair). In plenumareas, use plenum-rated Level IV, 22 AWG(0.34 mm2) such as U.S. part AK3791 (onepair) or U.S. part AK3792 (two pair). SeeTables 9 and 10 for part numbers. Also useEchelon approved cables.
• Unswitched 24 Vac power wiring can be run inthe same conduit as the E-Bus cable.
• Do not use different wire types or gauges onthe same E-Bus segment. The step change inline impedance characteristics causesunpredictable reflections on the bus. Whenusing different types is unavoidable, use aQ7751A Router at the junction.
• In noisy (high EMI) environments, avoid wireruns parallel to noisy power cables, or linescontaining lighting dimmer switches, and keepat least 3 in. (76 mm) of separation betweennoisy lines and the E-Bus cable.
• Make sure that neither of the E-Bus wires isgrounded.
3RZHU�:LULQJ
A power budget must be calculated for each Excel 10W7761 Device to determine the required transformer sizefor proper operation. A power budget is simply thesumming of the maximum power draw ratings (in VA) of allthe devices to be controlled by an Excel 10 W7761 Device.This includes the device itself, the equipment actuators(ML6161, or other motors) and various contactors andtransducers, as appropriate, for the Excel 10 configuration.
3RZHU %XGJHW &DOFXODWLRQ ([DPSOH
The following is an example power budget calculation for atypical W7761A Excel 10 Device.Device VA Information ObtainedExcel 10 W7761 6.0 VA from the W7761Device Specification Data
ML6161 2.2 VA TRADELINE® CatalogDamper Actuator
R8242A 21.0 VA TRADELINE® CatalogContactor for fan in-rush rating
M6410A Steam 0.7 VA TRADELINE® Catalog,Heating Coil Valve 0.32A at 24 Vac
TOTAL: 29.9 VA
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 20
The Excel 10 System example requires 29.9 VA of peakpower; therefore, a 40 VA AT72D Transformer is able toprovide ample power for this device and its accessories.Alternatively, a 75 VA AT88A Transformer could be usedto power two Excel 10 Systems of this type, or a 100 VAAT92A Transformer could be used to power three of thesecontrollers and meet NEC Class 2 restrictions (no greaterthan 100 VA). See Fig. 12 through 14 for illustrations ofpower wiring details. See Table 5 for VA ratings of variousdevices.
Table 5. VA Ratings For Transformer Sizing.
Device Description VA
W7761A Excel 10 W7761 Device 6.0
ML6161A/B Damper Actuator, 35 lb-in. 2.2
R8242A Contactor 21.0
R6410A Valve Actuator 0.7
MMC325 Pneumatic Transducer 5.0
ML684 Versadrive Valve Actuator 12.0
ML6464 Damper Actuator, 66 lb-in. 3.0
ML6474 Damper Actuator, 132 lb-in. 3.0
ML6185 Damper Actuator SR 50 lb-in. 12.0
For contactors and similar devices, the in-rush powerratings should be used as the worst case values whenperforming power budget calculations. Also, theapplication engineer must consider the possiblecombinations of simultaneously energized outputs andcalculate the VA ratings accordingly. The worst case, thatuses the largest possible VA load, should be determinedwhen sizing the transformer.
/LQH /RVV
Excel 10 Controllers must receive a minimum supplyvoltage of 20 Vac. If long power or output wire runs arerequired, a voltage drop due to Ohms Law (I x R) line lossmust be considered. This line loss can result in asignificant increase in total power required and therebyaffect transformer sizing. The following example is an I x Rline-loss calculation for a 200 ft (61m) run from thetransformer to a W7761 Device drawing 37 VA using 18AWG (1.0 mm2) wire.
The formula is:Loss = [length of round-trip wire run (ft)] x [resistance in
wire (ohms per ft)] x [current in wire (amperes)]
From specification data:18 AWG twisted pair wire has 6.52 ohms per
1000 feet.Loss = [(200 ft) x (2 - round-trip) x (6.52/1000 ohms per
ft)] x [(37 VA)/(24V)] = 4.02 volts
This means that four volts are going to be lost between thetransformer and the device; therefore, to assure the devicereceives at least 20 volts, the transformer must outputmore than 24 volts. Because all transformer output voltagelevels depend on the size of the connected load, a largertransformer outputs a higher voltage than a smaller one fora given load. Fig. 11 shows this voltage load dependence.
In the preceding I x R loss example, even though thedevice load is only 37 VA, a standard 40 VA transformer isnot sufficient due to the line loss. From Fig. 11, a 40 VA
transformer is just under 100 percent loaded (for the 37 VAdevice) and, therefore, has a secondary voltage of 22.9volts. (Use the lower edge of the shaded zone in Fig. 11that represents the worst case conditions.) When theI x R loss of four volts is subtracted, only 18.9 voltsreaches the device, which is not enough voltage for properoperation.
In this situation, the engineer basically has threealternatives:
1. Use a larger transformer; for example, if an 80 VAmodel is used, see Fig. 11, an output of 24.4 voltsminus the four volt line loss supplies 20.4V to thedevice. Although acceptable, the four-volt line-loss inthis example is higher than recommended. See thefollowing IMPORTANT.
2. Use heavier gauge wire for the power run. 14 AWG(2.0 mm2) wire has a resistance of 2.57 ohms per1000 ft which, using the preceding formula, gives aline-loss of only 1.58 volts (compared with 4.02volts). This would allow a 40 VA transformer to beused. 14 AWG (2.0 mm2) wire is the recommendedwire size for 24 Vac wiring.
3. Locate the transformer closer to the device, therebyreducing the length of the wire run, and the line loss.
The issue of line-loss is also important in the case of theoutput wiring connected to the Triac digital outputs. Thesame formula and method are used. The rule to rememberis to keep all power and output wire runs as short aspractical. When necessary, use heavier gauge wire, abigger transformer, or install the transformer closer to thedevice.
IMPORTANTNo installation should be designed where the lineloss is greater than two volts to allow for nominaloperation if the primary voltage drops to 102 Vac(120 Vac minus 15 percent).
To meet the National Electrical Manufacturers Association(NEMA) standards, a transformer must stay within theNEMA limits. The chart in Fig. 11 shows the required limitsat various loads.
With 100 percent load, the transformer secondary mustsupply between 23 and 25 volts to meet the NEMAstandard. When a purchased transformer meets the NEMAstandard DC20-1986, the transformer voltage-regulatingability can be considered reliable. Compliance with theNEMA standard is voluntary.
The following Honeywell transformers meet this NEMAstandard:
Transformer Type VA RatingAT20A 20AT40A 40AT72D 40AT87A 50
AK3310 Assembly 100
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
21 74-2699
27
26
25
24
23
22
21
20
19
18
17
16
15
14
0 50 100 150 % OF LOAD
SE
CO
ND
AR
Y V
OLT
AG
E
200
M993
Fig. 11. NEMA class 2 transformer voltageoutput limits.
Attach earth ground to W7761 Device terminal 1. See Fig.12, 13 and 14, 16 through 20.
M15269
CONNECT POWER TO TERMINALS 24 AND 25
TRIAC LINESTO ACTUATORSAND CONTACTORS
TRANSFORMER
W7761A
EARTHGROUND
20222425
1
OUTPUTDEVICEPOWER
Fig. 12. Power wiring details for one Excel 10 pertransformer.
M15270
24 VAC120/240 VAC
TRANSFORMER
W7761A
EARTHGROUND
2425
1
W7761A
EARTHGROUND
2425
1
W7761A
EARTHGROUND
2425
1
Fig. 13. Power wiring details for two or more Excel 10s per transformer.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 22
IMPORTANTIf the W7761A Device is used on Heating andCooling Equipment (UL 1995 US only) devicesand the transformer primary power is more than150 volts, connect the transformer secondary toearth ground, see Fig. 14.
M15271
24 VAC
LINE VOLTAGEGREATERTHAN 150 VAC
TRANSFORMER W7761A
EARTHGROUND
EARTHGROUND
1 IF THE W7750 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND ONE SIDE OF TRANSFORMER SECONDARY.
1
1
Fig. 14. Transformer power wiring details for one Excel10 used in UL 1995 equipment (U.S. only).
IMPORTANTNotes on power wiring:• All field wiring must conform to local codes and
ordinances.• To maintain NEC Class 2 and UL ratings, the
installation must use transformers of 100 VA orless capacity.
• For multiple controllers operating from a singletransformer, the same side of the transformersecondary must be connected to the sameinput terminal in each device and the groundterminals (1 on the W7761A) must beconnected to a verified earth ground for eachdevice in the group. See Fig. 13. (Deviceconfigurations are not necessarily limited tothree devices per transformer.)
• For the W7761A Device (which has Triacoutputs), all output devices must be poweredfrom the same transformer as the onepowering the Excel 10 W7761A Device.
• Use the heaviest gauge wire available, up to14 AWG (2.0 mm2) with a minimum of 18 AWG(1.0 mm2) for all power and earth groundconnections.
• To minimize EMI noise, do not run Triac outputwires in the same conduit as the input wires orthe E-Bus communications loop.
• Unswitched 24 Vac power wiring can be run inthe same conduit as the E-Bus cable.
• Make earth ground connections with theshortest possible wire run using 14 AWG(2.0 mm2) wire. A good earth ground isessential for W7761A operation. Ideally,connect the earth ground to the ground bus ata motor control center or circuit breaker panel.However, if the nearest ideal earth ground isinaccessible, consider an alternate source forearth ground. Metal water pipe is generally agood ground, but do not use sprinkler pipe ifprohibited by local codes. Attention must begiven when duct work, conduit, or rebar are tobe considered as ground sources. It is theresponsibility of the installer to assure thatthese structures are tied back to a known earthground.
6WHS����3UHSDUH�:LULQJ�'LDJUDPV
*HQHUDO�&RQVLGHUDWLRQV
The purpose of this step is to assist the applicationengineer in developing job drawings to meet jobspecifications. Wiring details are included for the W7761Adevice the T7770A,B,C,D wall module (sensor—currentfeature that can be used with the RIO Device) and theT7780 DDWM. The drawings detail I/O, power, andcommunication bus wiring connections.
NOTE: For field wiring, when two or more wires are to beattached to the same connector block terminal,be sure to twist them together. Deviation from thisrule can result in improper electrical contact. SeeFig. 15.
The connector block terminals on the W7761A and on theT7770 accept 14 through 22 AWG (2.0 to 0.34 mm2) wire.Table 6 lists wiring types, sizes, and length restrictions forExcel 10 products.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
23 74-2699
3/8(10)
STRIP 3/8 IN. (10 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
1. 2. TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
TWO 14 AWG(2.0 MM2) WIRES
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENINGSCREW. THEN PULL ON EACH WIRE IN ALL TERMINALSTO CHECK FOR GOOD MECHANICAL CONNECTION.
M10086
Fig. 15. Attaching two or more wires at terminal blocks.
Limited by line-losseffects on powerconsumption.(See Line Losssubsection.)
PowerWiring
14 AWG(2.0 mm2)
Any pair nonshielded (useheavier wire for longerruns).
NEC Class 2140°F (60°C)rating
HoneywellAK3754 (14 AWG)twisted pairAK3909 (14 AWG) singleconductor or equivalent
Limited by line-losseffects on powerconsumption.(See Line Losssubsection.)
:����$�'HYLFHV
Fig. 16 through 20 illustrate W7761A Device wiring forvarious configurations. Connections to the wall moduleterminals (4 through 6) and the communications terminals(14 and 15) are made at terminal blocks. Connection foraccess to the E-Bus is provided by plugging the connectorinto the communications jack.
NOTE: If an Excel 10 W7761A Device or Zone Manageris not connected to a good earth ground, thedevice internal transient protection circuitry iscompromised and the function of protecting thedevice from noise and power line spikes cannotbe fulfilled. This can result in a damaged circuitboard and require replacing the device.
See Table 7 for a description of the W7761A terminals.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 24
Table 7 . W7761A I/O Description.
Terminal Terminal Number Description
OUT 8 16 Digital Output 8
OUT 7 17 Digital Output 7
OUT 6 18 Digital Output 6
OUT 5 19 Digital Output 5
OUT 4 20 Digital Output 4
OUT 3 21 Digital Output 3
OUT 2 22 Digital Output 2
OUT 1 23 Digital Output 1
+24Vac (H) 25 Power for the device
COM (N) 24 Return for power to device
E-Bus 15 Echelon® communications screw terminals
E-Bus 14 Echelon® communications screw terminals
DI -4 31 Digital Input 4
DGND 30 Digital Ground
DI -3 29 Digital Input 3
DI -2 28 Digital Input 2
DGND 27 Digital Ground
DI -1 26 Digital Input 1
22 VDC out 13 22 Vdc power supply for auxiliary devices with a maximum current of 50 mA.
AI-6 12 Analog Input 6 voltage or current
AGND 11 Analog ground
AI-5 10 Analog Input 5 voltage or current
AI-4 9 Analog Input 4 resistance
AGND 8 Analog ground
AI -3 7 Analog Input 3 resistance
AI-2 6 Analog Input 2 resistance
GROUND 5 Analog ground
AI-1 4 Analog Input 1 resistance
3 Not Used
2 Not Used
EGND 1 Earth Ground
See Fig. 20 to wire a pneumatic transducer to a W7761A.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
25 74-2699
1 2 3 4 5 6 7 8
E-BUS
24 V
AC
W7761AREMOTE I/ODEVICE
1
2
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
E-BUS
E G
ND GN
D
GN
D
GN
D
NO
T U
SE
D
NO
T U
SE
D
AI-
1 O
HM
AI-
2 O
HM
9 10 11 12 14 J315
31 30 29 28 27 26 25 24 23 22 21 20
24 V
AC
CO
M
E-B
US
JAC
K
22 V
DC
OU
T
19 18 17 16
AI-
3 O
HM
AI-
4 O
HM
AI-
6 V
/mA
OU
T 7
OU
T 6
OU
T 5
OU
T 4
OU
T 8
OU
T 1
OU
T 3
OU
T 2
AI-
5 V
/mA
13
DI-
2
DI-
4
DI-
1
DI-
3
M15276
GN
D
GN
D
TRIAC EQUIVALENT CIRCUIT
24 VAC+
-
2
JACK FOR E-BUS NETWORKACCESS
7 69 8 5 4 3 2 1
T7770AWALL MODULE
GN
D
SE
NS
OR
E-B
US
E-B
US
C7770A AIR TEMPERATURE SENSOR
Fig. 16. Typical T7770A and C7770A wiring diagram.(For note 2, refer to Fig. 15.)
1 2 3 4 5 6 7 8
E-BUS
24 V
AC
W7761AREMOTE I/ODEVICE
1
2
1
+
S
+
SC7600C
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
E-BUS
E G
ND GN
D
GN
D
GN
D
NO
T U
SE
D
NO
T U
SE
D
AI-
1 O
HM
AI-
2 O
HM
9 10 11 12 14 J315
31 30 29 28 27 26 25 24 23 22 21 20
24 V
AC
CO
M
E-B
US
JAC
K
22 V
DC
OU
T
19 18 17 16
AI-
3 O
HM
AI-
4 O
HM
AI-
6 V
/mA
OU
T 7
OU
T 6
OU
T 5
OU
T 4
OU
T 8
OU
T 1
OU
T 3
OU
T 2
AI-
5 V
/mA
13
DI-
2
DI-
4
DI-
1
DI-
3
M12894
GN
D
GN
D
TRIAC EQUIVALENT CIRCUIT
24 VAC+-
C7400A
HUMIDITY(4 TO 20 mA)
ENTHALPY(4 TO 20 mA)
Fig. 17. Typical Humidity and Enthalpy (4 to 20mA)sensor wiring diagram. (For note 2, refer to Fig. 15.)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 26
1 2 3 4 5 6 7 8
E-BUS
24 V
AC
W7761AREMOTE I/ODEVICE
1
2
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
E-BUS
E G
ND GN
D
GN
D
GN
D
NO
T U
SE
D
NO
T U
SE
D
AI-
1 O
HM
AI-
2 O
HM
9 10 11 12 14 J315
31 30 29 28 27 26 25 24 23 22 21 20
24 V
AC
CO
M
E-B
US
JAC
K
22 V
DC
OU
T19 18 17 16
AI-
3 O
HM
AI-
4 O
HM
AI-
6 V
/mA
OU
T 7
OU
T 6
OU
T 5
OU
T 4
OU
T 8
OU
T 1
OU
T 3
OU
T 2
AI-
5 V
/mA
13
DI-
2
DI-
4
DI-
1
DI-
3
M15277
GN
D
GN
D
TRIAC EQUIVALENT CIRCUIT
24 VAC
+-
OCCUPANCY SENSOR(CONTACTCLOSED =OCCUPIED)
WINDOWCONTACT(CONTACT CLOSED = WINDOWCLOSED)
Fig. 18. Typical Window and Occupancy sensor wiringdiagram. (For note 2, refer to Fig. 15.)
1 2 3 4 5 6 7 8
E-BUS
24 V
AC
W7761AREMOTE I/ODEVICE
1
2
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTEDTOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
E-BUS
E G
ND GN
D
GN
D
GN
D
NO
T U
SE
D
NO
T U
SE
D
AI-
1 O
HM
AI-
2 O
HM
9 10 11 12 14 J315
31 30 29 28 27 26 25 24 23 22 21 20
24 V
AC
CO
M
E-B
US
JAC
K
22 V
DC
OU
T
19 18 17 16
AI-
3 O
HM
AI-
4 O
HM
AI-
6 V
/mA
OU
T 7
OU
T 6
OU
T 5
OU
T 4
OU
T 8
OU
T 1
OU
T 3
OU
T 2
AI-
5 V
/mA
13
DI-
2
DI-
4
DI-
1
DI-
3
M15279
GN
D
GN
D
TRIAC EQUIVALENT CIRCUIT
24 VAC+-
24 (
H)
24 (
N)
PW
M
(H 2
4 V
AC
)
PW
M O
UT
PU
T
FR
OM
CN
TR
L
ML7984B
T6 T5 C B W R
PWM VALVE ACTUATOR
FAN
CONTACTOR (24 VAC)
LINE POWER
Fig. 19. Typical PWM Valve Actuator andmiscellaneous fan control to W7761A. (For note 2,
refer to Fig. 15.)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
27 74-2699
1 2 3 4 5 6 7 8
E-BUS
24 V
AC
W7761AREMOTE I/ODEVICE
5
E G
ND GN
D
GN
D
GN
D
NO
T U
SE
D
NO
T U
SE
D
AI-
1 O
HM
AI-
2 O
HM
9 10 11 12 14 J315
31 30 29 28 27 26 25 24 23 22 21 20
24 V
AC
CO
M
E-B
US
JAC
K
22 V
DC
OU
T
19 18 17 16
AI-
3 O
HM
AI-
4 O
HM
AI-
6 V
/mA
OU
T 7
OU
T 6
OU
T 5
OU
T 4
OU
T 8
OU
T 1
OU
T 3
OU
T 2
AI-
5 V
/mA
13
DI-
2
DI-
4
DI-
1
DI-
3
M15278
GN
D
GN
D
TRIAC EQUIVALENT CIRCUIT
24 VAC+-
24 (
H)
24 (
N)
24 (
H)
24 (
N)
INC
RE
AS
E
DE
CR
EA
SE
MMC325 PNEUMATICTRANSDUCER
1
4
3
5
1
2
3
4
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.
REVERSE WIRES (INCREASE/DECREASE) TO REVERSE ACTION(DIRECT/REVERSE).
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN:REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.
OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.
USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE MUST BE 6 FT. (1.8M) OR LONGER.
One E-Bus Termination Module, part number 209541B is required for a single terminated E-Bus or two E-Bus TerminationModule, part number 209541B for a double terminated E-Bus (see Fig. 21). Refer to the E-Bus Wiring Guidelines form, 74-2865 for termination module placement rules.
M15272
PART NO. 209541BTERMINATIONMODULE
PART NO. 209541BTERMINATIONMODULE
W7761A
1415 1415
W7761A
1415
W7761A
BROWNBROWN
ORANGE
ORANGE
Fig. 21. Typical E-Bus termination module wiring diagrams (place a wire nut on each remaining wire that is notconnected to a controller or device).
See Fig. 22 for E-Bus termination wiring options.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
29 74-2699
M12895
W7761A
(D) E-Bus Termination network switches in the Q7740A,B Repeaters(C) E-Bus Termination Module installed at 2 x 4 or 60 mm box-mounted T7770
(E) Installing E-Bus Termination Module at W7751H (terminals 11 and 12)
(F) Twist wires and attach wire nuts to RJ-45 Adaptercables, E-Bus segment wires and Termination Module
to connect to a Q7751A,B Router
(B) Installing E-Bus Termination Module at W7761A
RJ-45PLUG
PART NO. 209541BTERMINATIONMODULE
E-BUS
WIRE NUTS
E-BUS
INSERT INTO TERMINALS 1 AND 2 WITH THE E-BUS WIRE. TERMINATION MODULE IS PHYSICALLY LOCATED BEHIND THE T7770 INSIDE THE 2 X 4 OR 60 MM BOX.
Q7751A E-BUSROUTER
E-BUS
E-BUS
NE
T 2
PART NO. 209541BTERMINATIONMODULE
PART NO. 209541BTERMINATION MODULE
PART NO. 209541BTERMINATION MODULE
O I II
O I II
O I II
O I II
A B
C D
SWITCHES ON SIDE, UNDER Q7740A,B CIRCUIT BOARD.USE SMALL FLAT OBJECT TO MOVE THE SWITCHES AS NEEDED FROM POSITION O (NO TERMINATION)POSITION I (SINGLY TERMINATED)POSITION II (DOUBLY TERMINATED)
SEGMENTS
LABEL ON Q7740B 4 WAY REPEATER
NOTE: Q7740B 4 WAY REPEATER SHOWN, Q7740A 2 WAY REPEATER HAS TWO SWITCHES.
(A) Enabling Internal Termination Network using jumpers in the Q7750A Zone Manager
TERMINAL BLOCKFOR Q7750A ZONE MANAGER
8
7
6
5
4
3
E-BUSE-BUS
INTERNAL TERMINATION
NETWORK
INTERNAL TERMINATION
NETWORK
FIELD INSTALLED JUMPER
FIELD INSTALLED JUMPER
SINGLY TERMINATED SEGMENT
USE FOR DOUBLYTERMINATEDDAISY-CHAIN SEGMENT
Fig. 22. E-Bus termination wiring options.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 30
6WHS����2UGHU�(TXLSPHQW
After compiling a bill of materials through completion of the previous application steps, refer to Table 8 for ordering information.Contact Honeywell for information about Controllers and Wall Modules with no logo.
C7400A1004 Solid State Enthalpy Sensor (4 to 20 mA) For outdoor and return air enthalpy
C7600B1000 Solid State Humidity Sensor (2 to 10 V) For outdoor and return air humidity
C7600C1008 Solid State Humidity Sensor (4 to 20 mA) For outdoor and return air humidity
C7600C1018 Solid State Humidity Sensor (2 to 10 V) For outdoor and return air humidity
MMC325-010,MMC325-020
Pneumatic Retrofit Transducers. Select pressurerange: (010) 0 to 10 psi (68.97 kPa) or (020) 0 to20 psi (137.93 kPa).
Use to control Pneumatic reheat valves
MMCA530 DIN rail adapter for MMC325 Transducers —
MMCA540 Metal enclosure for MMC325 Transducers —
ML7984B3000 Valve Actuator Pulse Width Modulation (PWM) Use with V5011 or V5013 F and G Valves
ML6161B1000 Damper Actuator Series 60 —
M6410A Valve Actuator Series 60 Use with V5812/V5813 Valves
ML684A1025 Versadrive Valve Actuator with linkage, Series 60 Use with V5011 and V5013 Valves
ML6464A1009 Direct Coupled Actuator, 66 lb-in., Series 60 —
ML6474A1008 Direct Coupled Actuator, 132 lb-in. torque, Series60
—
ML6185A1000 Direct Coupled Actuator, 50 lb-in. spring return Series 60
V5812A Two-way terminal unit water valve; 0.19, 0.29,0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or2.9 and 4.9 Cv 3/4 in. npt (19 mm)
Use with M6410 Valve Actuator. Close-off rating for 0.19to 1.9 Cv is 65 psi; for 2.9 and 4.9, Cv is 45 psi.(Coefficient of volume or capacity index Cv = gallonsper minute divided by the square root of the pressuredrop across the valve.)
V5813A Three-way mixing terminal unit hot water valve;0.19, 0.29, 0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt(13 mm) or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)
Use with M6410 Valve Actuator. Close-off rating 0.19 to0.74 Cv is 55 psi; 1.2, and 1.9 Cv is 22 psi; 2.9 and 4.9Cv is 26 psi.
R8242A Contactor, 24 Vac coil, DPDT —
AT72D, AT88A,AK3310, etc.
Transformers —
EN 50 022 DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) Obtain locally: A controller requires 5 in.
— Augat Inc. part number 2TK2D DIN rail (adapter) Purchase from Augat Inc. two DIN rail adapters for eachcontroller
— Serial Interface Cable, male DB-9 to female DB-9or female DB-25.
Obtain locally from any computer hardware vendor.
(continued)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
33 74-2699
Table 8. Excel 10 W7761A Device Ordering Information (continued).
Inputs: 18 AWG (1.0 mm2) five wire cable bundle Standard thermostat wire
HoneywellAK3752(typical orequivalent)
Outputs/Power: 14 to 18 AWG (2.0 to 1.0 mm2) NEC Class 2 140°F (60°C) rating
HoneywellAK3702(typical orequivalent)
18 AWG (1.0 mm2) twisted pair Non-plenum
HoneywellAK3712(typical orequivalent)
16 AWG (1.3 mm2) twisted pair Non-plenum
HoneywellAK3754(typical orequivalent)
14 AWG (2.0 mm2) two conductor Non-plenum
6WHS����&RQILJXUH�'HYLFHV
Excel E-Vision PC Software is used to configure W7761ADevices to match their intended application. The E-VisionUser Guide form, 74-2588 provides details for operatingthe PC software.
In addition to the following information, refer to theInstallation Instructions manual for each product. See theApplicable Literature section for form numbers.
The T7770 Wall Module or the C7770A Air TemperatureSensor has the following specified calibration points, whichare plotted in Fig. 23:
Temperature (°F) Resistance Value (ohms)99 11,52085 16,30170 24,03955 36,28045 48,000
TEMPERATURE (DEGREES)
oF30 40 50 60 70 80 90 100 110
0 10 20 30 40
RE
SIS
TA
NC
E (
OH
MS
)
20K OHM AT 77oF (25oC)
80K
70K
60K
50K
40K
30K
20K
10K
oC
M5874A
Fig. 23. Temperature sensor resistance plots.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 34
$ODUPV
When an Excel 10 has an alarm condition, it reports it tothe central node on the E-Bus (typically, the Excel 10 ZoneManager). See Table 9. Information contained in an alarmmessage is:• Subnet Number:
E-Bus subnet that contains the Excel 10 node that hasthe alarm condition. Subnet 1 is on the Zone Managerside of the router; Subnet 2 is on the other side.
• Node Number:Excel 10 node that has the alarm condition (seeNetwork Status).
• Alarm Type:Specific alarm being issued. An Excel 10 can providethe alarm types listed in Table 9.
NOTE: The node can be reset by switching the node toMANUAL and then to the normal operating mode.
Also, the Excel 10 variables, AlarmLogX where X is 1through 5, that store the last five alarms to occur in thedevice, are available. These points can be viewed throughXBS or E-Vision.
%URDGFDVWLQJ�WKH�6HUYLFH�0HVVDJH
The Service Message allows a device on the E-Bus to bepositively identified. The Service Message contains thedevice ID number and, therefore, can be used to confirmthe physical location of a particular Excel 10 in a building.There are two methods of broadcasting the ServiceMessage from an Excel 10 W7761A Device. One uses ahardware service pin button on the side of the device (seeFig. 24). The other involves using the PC Configurationtool, as follows.
The commissioning tool is used to perform the IDAssignment task (see the E-Vision User’s Guide form,74-2588).
M10094
SERVICEPINBUTTON
Fig. 24. Location of the Service Pin Button.
:����$�'HYLFH�6WDWXV�/('
The LED on the front and center of a W7761A Deviceprovides a visual indication of the status of the device. SeeFig. 25. When the W7761A receives power, the LEDshould appear in one of the following allowable states (seeTable 10):
Table 10. LED States.
AlarmCondition
Hardware orSoftware Failure
Service LED BlinkRate (Cycles per
second)
None None 1
Any alarmcondition
None 2
Don't Care Failed steady ON or OFF
Table 9. Excel 10 Alarms.
Name of alarm or error bitAlarm type
number Meaning of alarm code or error bit
RETURN_TO_NORMAL 128U Return to no alarm after being in an alarm condition. This code is addednumerically to another alarm code to indicate that the alarm condition hasreturned to normal.
ALARM_NOTIFY_DISABLED 255U The alarm reporting has been turned off by the DestManMode. No morealarms are reported via nvoAlarm until DestManMode turns on alarmreporting or upon application restart.
NO_ALARM 0 No alarms presently detected.
INPUT_NV_FAILURE 1 One or more NV inputs have failed in receiving an update within theirspecified FAILURE_DETECT_TIME.
NODE_DISABLED 2 The control algorithm has stopped because the RIO device is inDISABLED_MODE, MANUAL, or FACTORY_TEST mode. No more alarmsare reported when the device is in the DISABLED_MODE. Alarms continueto be reported if the device is in the MANUAL or FACTORY_TEST mode.The control is shut down and disabled until power is cycled or the node isreset. See note 1 below.
SENSOR_FAILURE 3 One or more sensors have failed.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
35 74-2699
1. Off—no power to the processor.2. Continuously On—processor is in initialized state.3. Slow Blink—controlling, normal state.4. Fast Blink—when the Excel 10 has an alarm
condition.
W7761A
STATUSLED
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J3
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
E GND
NOTUSED
NOTUSED
AI-1OHM
GND AI-2OHM
AI-3 OHM
GND A1-4 OHM 22 VDC
OUT
AI-5 V/mA
AI-6 V/mA
GNDE-BUS E-BUS
JACK
DI-4 GND DI-3 DI-2 GND DI-124
VAC
24 VACCOM
1OUT
2OUT
3OUT
4OUT
5OUT
6OUT
7OUT
8OUT
M15280
Fig. 25. LED location on W7761A.
7�����'':0�%\SDVV�3XVKEXWWRQ
See Fig. 26 for the T7780 DDWM bypass pushbuttonlocation (occupied or unoccupied). The T7780 DDWM hastwo methods for generating its neuron ID, shorting twopads or winking.
M11616
T7780A
BYPASSPUSHBUTTON
Fig. 26. Bypass pushbutton location on T7780 DDWM.
1. Pressing the bypass pushbutton whenever a Carat(∇) on the bottom of the LCD display is flashing(Menu Selection Mode).
2. Pressing the bypass pushbutton when the T7780ADDWM is in wink mode (LCD display shows WINKwhen E-Vision sends a Service Message out on theE-Bus).
When the space covered by the T7780 DDWM is inOccupied mode, the sun symbol is shown on the left sideof the LCD display. When the space is in Standby mode,the half-sun symbol is shown. When the space is inUnoccupied mode, the moon symbol is shown.
CARE/E-Vision must be used to configure the W7761device. The inputs and outputs will be configured throughthe application selection menu (see E-Vision user guideform, 74-2588). The RIO does not contain control loops fordirectly controlling the digital outputs, therefore the ZoneManager or some other device has to be bound to theoutputs to perform the control function. Refer to the CAREUser’s Manual form, 74-5587 to add Control Strategy,Switching Logic, or Time Programs for control of the RIOdigital outputs. Refer to the E-Vision user guide (form, 74-2588 for the RIO commissioning procedure andupdating/downloading of the Zone Manager files.
NOTE: The RIO device does not synchronize the floatingdigital outputs. This function (position issynchronized whenever an endpoint is reached(full open or full close).and when the elapsed timesince the last synchronization is 24 hours) mustbe done by the controlling device (such as theZone Manager).
6HQVRU�&DOLEUDWLRQ
The resistive temperature sensors and voltage/currentinputs can all be calibrated. The wall module setpointpotentiometer is not supported on the W7761A. Performthe sensor calibration by adding an offset value (eitherpositive or negative) to the sensed value using E-Visionmenus (see E-Vision user guide form, 74-2588).
When calibrating voltage/current sensors on the W7761A,the offset amount entered by the user is in volts,regardless of the inputs actual engineering units. SeeAppendix E for information on how to derive the propervoltage value to enter as an offset during calibration.
&XVWRP�0DSSLQJ
The RIO default CARE plant contains all available pointsthat are supported on the RIO device. If the RIO plant wascustomized by deleting unused points, then the Custommapping feature will have to be used to add points backinto the plant so that they can be used or monitored byother devices. The following procedures will describe theCustom mapping process for adding analog/digital inputsand digital outputs.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 36
$GGLQJ $QDORJ ,QSXWV � (QWKDOS\ �� WR �� P$�
To add an enthalpy (outdoor or return air) sensor to anRIO plant, the user must add a software point (pseudoanalog) that can be mapped to the actual hardware inputthrough the Custom Mapping function of E-Vision. Thefollowing procedure will instruct the user on adding thepseudo analog and using the Custom Mapping function.This allows the enthalpy input to be used with other Excel10 controllers (referenced) on the E-Bus, used in ZoneManager control strategy or switching logic, or be usedwith Excel 5000 controllers on the C-Bus.
1. With CARE running, open an existing RIO plant. Theuser can go into either switching logic or controlstrategy to add the pseudo analog point. If the userdoes not have an existing control loop throughcontrol strategy, use switching logic to add thepseudo point, otherwise a control loop will have to becreated along with unnecessary RACL to add thepoint. This procedure will use switching logic to addthe pseudo analog point. With the RIO plant havingthe focus, go into switching logic. Select theSoftware Points menu item and then Pseudo Analog.The Create/Select Software Point <Va> dialog boxwill be displayed. Type in a New point name for theenthalpy sensor (such as OaEnthaply) and click onthe OK button. The new point that was just createdwill be added to the screen as the header point forswitching logic table and also added to the Point List. Select the Cancel button to exit the Create/SelectSoftware Point <Va> dialog box. Exit switching logicby selecting the File menu item and Exit. CARE willdisplay the Delete Unused Software Points list box.Click the Cancel button to continue.
2. Go into the Data Point Editor (Controller/Edit/DataPoint Editor) and under Point select the pseudoanalog point that was just created and click the OKbutton. Select the drop down list for the EngineeringUnit and scroll through the list until the mA (mAmatches the engineering unit of the RIO input)engineering units are displayed. Select the mAengineering unit that is shown with one decimalplace (number 66) and click the OK button to savethe selection. Cancel the User Address list box andselect File/Exit to exit out of the Data Point Editor.
3. Translate the Zone Manager and Export the ZoneManager files to E-Vision by selecting the Projectand Export to E-Vision menu items. Type in thename of the Zone Manager Export file when theExport Zone Manager dialog box is displayed. Selectthe project and the Zone manager within that projectthat is being exported and click the Export button.Exit CARE and Start E-Vision. Select theE-Vision project to open and the CARE ExportFilename created above. Once the project is open,select the RIO device that the enthalpy sensor isconnected to and go into the Application Selectionscreen (offline) by selecting the Controller, then theApplication Selection menu items. From the Inputstab of the Application Selection dialog box, addOa_Enthalpy to either analog input 5 or 6 and selectthe OK button to save the selection.
4. Select the Controller menu item and then Importfrom CARE to import the Zone Manager files with thenew pseudo analog point. If this function has alreadybeen performed before, the user will be promptedwith the message CARE Export File has alreadybeen imported, do you want to import again?. SelectYes to continue with the Import. When the import isfinished, E-Vision displays the message CAREExport File has been imported. Select OK tocontinue.
5. Select the Network menu item and then Map C-BusPoints. Select RIO1 as the Controller Type from theMap C-Bus Points dialog box. Under UnmappedCARE, select the name of the RIO device that theenthalpy sensor was added to in CARE. UnderUnmapped Excel 10, select the name of the RIOdevice that the actual enthalpy sensor was added to(both names should be the same). Next, select theCustom button and the Custom Mapping CAREPoints dialog box will be displayed. Select theOaEnthalpy point under CARE Points and CurrentAIunder Excel 10. CurrentAI is the user address in theRIO device that contains the actual sensor value forthe OaEnthalpy (C7400A1004, 4 to 20 mA device).Select the Map button to add the OaEnthalpy pointto the list of Mapped Points. Click on the Closebutton to exit the Custom Mapping CARE Pointsdialog box. Click on the Close button to exit the MapC-Bus Points dialog box.
6. To use the OaEnthalpy custom mapped point withother Excel 10 controllers on the E-Bus, select theNetwork menu item and Refer Excel 10 Points.Select the RIO device name as the Source Excel 10and then scroll down the list of Excel 10 Points: untilyou reach CurrentAI and select it. Select an Excel 10controller from the Destination Excel 10 list. Forexample if the user had selected a CVAHU controllerfrom the Destination Excel 10 list, the user wouldselect from the Excel 10 Points list as the destinationpoint and then click on the Add button to add thepoint association (Binding) between the RIO andCVAHU controllers. If DestOaEnth is already beingused in an association, then the message At Leastone of the output network variables is in an existingconnection and E-Vision will not allow thisassociation to be added. In order to add thisassociation, the user has to remove any otherassociations with the DestOaEnth point. Select theClose button to exit out of the Refer Excel 10 Pointsdialog box. Any controllers involved in the newassociation or change in an existing association willrequire commissioning.
7. Select the Controller menu item and the UpdateZone Manager Files. E-Vision will add the custommapping information to the Zone Manager files.When the Update Zone Manager Files function isdone, commission any controllers that need to becommissioned, then close the E-Vision project andexit out of E-Vision.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
37 74-2699
8. Start CARE and open the Zone Manager that wasjust updated through the Update Zone Manager Filesfunction and start XI584 by selecting the Controller,Tools and XI584 menu items. Once XI584 is started,select the Utilities and File Transfer menu items andselect CARE Import. Select the project and the ZoneManager that was just updated and select Importand click OK on the Select Target Controller dialogbox. When the CARE Import is complete, close theCARE Import dialog box. If this is the initial loadingof the Zone Manager, then it will have to be resetand the CPU address set by the XI581 Emulationfunction (Applications, XI581 Emulation menu).Select the Utilities, File Transfer menu items andselect Download. The Download dialog box will bedisplayed. Check the All selection and click theController button. When the SelectController/Subsystem dialog box is displayed, makesure that the correct CPU address or name is highlighted and select the OK button. Click the Downloadbutton and click Yes to the message Replaceupdated application part in controller (CPU addressor Controller name). When the download iscomplete, exit out of the Download dialog box. Fromthe XI584 main menu, select the Data, Access byUser Address menu items. Type OaEnthalpy in theSearch For User Address and click the Searchbutton. When the OaEnthalpy point displays in theUser Addresses list, click on the point and select theAttributes button. XI584 will now display the value ofthe enthalpy sensor connected to the RIO device.This point can now be used in the Zone Managercontrol strategy or switching logic. This point can beused in other Excel 5000 (C-Bus) controllers byassigning a global analog point in the destinationcontroller with the user address name ofOaEnthalpy. Refer to the CARE User’s Manual form,74-5587 for information on creating global points inExcel 5000 controllers.
$GGLQJ 2WKHU 9ROWDJH�&XUUHQW 6HQVRUV
See Table A-1 for the supported Voltage/Current analoginput sensors that can be connected to the RIO Device.The user must add a software point (pseudo analog - inRIO CARE Plant) that can be mapped to the actualhardware input (RIO Plant) through the Custom Mappingfunction of E-Vision. The procedure described previouslyfor adding an enthalpy ( 4 to 20 mA) sensor should befollowed and instructs the user on adding the pseudoanalog point in the RIO CARE Plant and using the CustomMapping function. From there it can be used with otherExcel 10 controllers (referenced) on the E-Bus, that areused in the Zone Manager control strategy or switchinglogic, or are used with Excel 5000 controllers on the C-Bus.
Table A-1. Supported Voltage And Current InputSensors.
E-Vision EnumeratedName in the Input
Application Selection Tab
RIO Network Variablethat contains the
Hardware Input Value
RA_Hum_C7600C Humidity1 or Humidity2
OA_Hum_C7600C Humidity1 or Humidity2
Filter_Diff_Pres Pressure1 or Pressure2
RA_Hum_C7600B Humidity1 or Humidity2
OA_Hum_C7600B Humidity1 or Humidity2
RA_Enthalpy CurrentAI
OA_Enthalpy CurrentAI
Space_CO2 CO2Level
Voltage_Monitor VoltageAI
$GGLQJ 'LJLWDO ,QSXWV
See Table A-2 for the supported Digital input types thatcan be connected to the RIO Device. The user must add asoftware point (pseudo digital nstate - in RIO CARE Plant)that can be mapped to the actual hardware input (RIOPlant) through the Custom Mapping function of E-Vision.The procedure described previously for adding an enthalpy( 4 to 20 mA) sensor should be followed. The user will adda Pseudo Digital nstate point (<Vd>) in step one instead ofthe Pseudo Analog to the RIO CARE Plant and then usethe Custom Mapping function. From there it can be usedwith other Excel 10 controllers (referenced) on the E-Bus,that are used in Zone Manager control strategy orswitching logic, or are used with Excel 5000 controllers onthe C-Bus.
Table A-2. Supported Digital Input Types.
E-Vision Enumerated Namein the Input Application
Selection Tab
RIO Network Variablethat contains the
Hardware Input Value
Digital Input 1:Active_Short / Active_Open
SrcDigIn1Sts
Digital Input 2:Active_Short / Active_Open
SrcDigIn2Sts
Digital Input 3:Active_Short / Active_Open
SrcDigIn3Sts
Digital Input 4:Active_Short / Active_Open
SrcDigIn4Sts
$GGLQJ 'LJLWDO 2XWSXWV
See Table A-3 for the supported digital output types thatcan be connected to the RIO Device.The user must add a software point (pseudo analog) thatcan be mapped to the actual hardware output through theCustom Mapping function of E-Vision. The followingprocedure will instruct the user on adding the pseudoanalog and using the Custom Mapping function so that theDigital Output can be used in the Zone Manager controlstrategy or switching logic, or be used with Excel 5000controllers on the C-Bus.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 38
1. With CARE running, open an existing RIO plant. Theuser can go into either switching logic or controlstrategy to add the pseudo analog point. If the userdoes not have an existing control loop throughcontrol strategy, use switching logic to add thepseudo point, otherwise a control loop will have to becreated along with unnecessary RACL to add thepoint. This procedure will use switching logic to addthe pseudo analog point. With the RIO plant havingthe focus, go into switching logic. Select theSoftware Points menu item and then Pseudo Analog.The Create/Select Software Point <Va> dialog boxwill be displayed. Type in a New point name for theDigital Output (such as MiscExhFan) and click on theOK button. The new point that was just created willbe added to the screen as the header point forswitching logic table and also added to the Point list.Select the Cancel button to exit the Create/SelectSoftware Point <Va> dialog box. Exit switching logicby selecting the File menu item and Exit. CARE willdisplay the Delete Unused Software Points list box.Click the Cancel button to continue.
2. Go into the Data Point Editor (Controller/Edit/DataPoint Editor) and under Point select the pseudoanalog point that was just created and the OKbutton. Select the drop down list for the EngineeringUnit and scroll through the list until the Pctengineering units are displayed. Select the Pctengineering unit that is shown with one decimalplace (number 55) and the OK button to save theselection. Cancel the User Address list box andselect File/Exit to exit out of the Data Point Editor.
3. Translate the Zone Manager and Export the ZoneManager files to E-Vision by selecting the Projectand Export to E-Vision menu items. Type in thename of the Zone Manager Export file when theExport Zone Manager dialog box is displayed. Selectthe project and the Zone manager within that projectthat is being exported and the Export button. ExitCARE and Start E-Vision. Select the E-Vision projectto open and the CARE Export Filename createdpreviously. Once the project is open, select the RIOdevice that the Digital Output is connected to and gointo the Application Selection screen (offline) byselecting the Controller, Application Selection menuitems. From the Outputs tab of the ApplicationSelection dialog box, select the firstUnused_DigOutput and scroll up until Discrete1 isdisplayed and select it. Select the OK button to savethe selection.
4. Select the Controller menu item and then Importfrom CARE to import the Zone Manager files with thenew pseudo analog point. If this function has alreadybeen performed before, the user will be promptedwith the message CARE Export File has alreadybeen imported, do you want to import again?. SelectYes to continue with the Import. When the import isfinished, E-Vision displays the message CAREExport File has been imported. Select OK tocontinue.
5. Select the Network menu item and then Map C-BusPoints. Select RIO1 as the Controller Type from theMap C-Bus Points dialog box. Under UnmappedCARE, select the name of the RIO device that theDigital Output was added to in CARE.
Under Unmapped Excel 10, select the name of theRIO device that the actual Digital Output was addedto (both names should be the same). Next, select theCustom button and the Custom Mapping CAREPoints dialog box will be displayed. Select theMiscExhFan point under CARE Points andDigOut1Cmd under Excel 10. Select the Map buttonto add the MiscExhFan point to the list of MappedPoints. Click on the Close button to exit the CustomMapping CARE Points dialog box. Click on the Closebutton to exit the Map C-Bus Points dialog box.
6. Re-commission the RIO device that had the custommapping done.
7. Select the Controller menu item and the UpdateZone Manager Files. E-Vision will add the custommapping information to the Zone Manager files.When the Update Zone Manager Files function isdone, close the E-Vision project and exit out ofE-Vision.
8. Start CARE and open the Zone Manager that wasjust updated through the Update Zone Manager Filesfunction and start XI584 by selecting the Controller,Tools and XI584 menu items. Once XI584 is started,select the Utilities, File Transfer menu items andselect CARE Import. Select the project and the ZoneManager that was just updated and select Importand click OK on the Select Target Controller dialogbox. When the CARE Import is complete, close theCARE Import dialog box. If this is the initial loadingof the Zone Manager, then it will have to be resetand the CPU address set by the XI581 Emulationfunction (Applications, XI581 Emulation menu).Select the Utilities, File Transfer menu items andselect Download. The Download dialog box will bedisplayed. Check the All selection and click theController button. When the SelectController/Subsystem dialog box is displayed, makesure that the correct CPU address or name ishighlighted and select the OK button. Click theDownload button and Yes to the message Replaceupdated application part in controller (CPU addressor Controller name). When the download iscomplete, exit out of the Download dialog box. Fromthe XI584 main menu, select the Data, Access byUser Address menu items. Type MiscExhFan in theSearch For User Address and click on the Searchbutton. When the MiscExhFan point displays in theUser Addresses list, click on the point and select theAttributes button. XI584 will now display the value ofthe Digital Output connected to the RIO device. Tocommand the MiscExhFan to the On mode, put thepoint in the Manual mode and enter a value of 1.0 orgreater. To command the MiscExhFan to the Offmode, put the point in the Manual mode and enter avalue of 0.0. This point can now be used in the ZoneManager control strategy or switching logic and TimePrograms. This point can be used in other Excel5000 controllers (C-Bus) by assigning a globalanalog point in the destination controller with theuser address name of MiscExhFan. Refer to theCARE User’s Manual form, 74-5587 for informationon creating global points in Excel 5000 controllers.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
39 74-2699
Table A-3. Supported Digital Output Types.
E-Vision Enumerated Name in the Output Application Selection TabRIO Network Variable that contains the
Hardware Output Value
Float1_Open through Float8_Open (Series 60 - requires two outputsassigned. Float1_Open must be assigned before Float1_Close)
DigOut1Cmd through DigOut8Cmd
Float1_Close through Float8_Close (Series 60 - requires two outputsassigned. Float1_Open must be assigned before Float1_Close)
DigOut1Cmd through DigOut8Cmd
Discrete1 through Discrete8 (Maintained On/Off outputs) DigOut1Cmd through DigOut8Cmd
Modulate1 through Modulate8 (PWM outputs) DigOut1Cmd through DigOut8Cmd
$SSHQGL[�%��6HTXHQFHV�RI�2SHUDWLRQ�
&RPPRQ�2SHUDWLRQV
The Excel 10 W7761A Device contains inputs and outputs,but no control software. All control that would beassociated with the inputs and outputs in the W7761Awould be accomplished though the Excel Zone Managerand would not be suitable for VAV control, temperaturecontrol, or any control function that would require less thana 30 second update rate. The analog and digital sensorscould be shared or bound to other Excel 10 controllers onthe E-Bus or Excel 5000 controllers on the C-Bus throughthe Excel 10 Zone Manager. This would allow the otherExcel 10 controllers to use their physical inputs formonitoring other elements such as return humidity, IAQ,etc. to achieve better control.
5RRP 7HPSHUDWXUH 6HQVRU �5P7HPS�
The T7770A,B,C,D wall module is the room spacetemperature sensor—(current feature that can be usedwith the RIO Device). When it is configured, it provides thetemperature input that can be shared with the W7750 orW7751 controllers. If there are multiple space sensors in aarea controlled by one W7750 CVAHU, then the spacetemperatures can be wired into the W7761A controller andmapped to the Zone Manager. The Zone Manager canaverage all of the space temperatures and then have thatvalue can be bound to the W7750 controlling that area.
:LQGRZ 6HQVRU �6WDWXV:QGZ�
The digital input for a window contact can be wired into theW7761A device and then bound to a W7750 CVAHU todisable its temperature control algorithm if someone hasopened a window or door in the room or area that theW7750 is serving. When a window is detected to be Open(digital input contacts Open equals window open), thenormal temperature control is disabled, and the W7750Controller enters the Freeze Protect mode. Freeze Protectmode sets the space setpoint to 50 °F (10°C) and bringson the fan and heat if the space temperature falls belowthis setpoint. Normal temperature control resumes onwindow closure.
'LUW\ )LOWHU 0RQLWRU
The air filter in the air handler can be monitored by a digitalinput in the W7761A and an alarm issued by the ZoneManager when the filter media needs replacement. Thetwo methods of monitoring the filter are:
1. A differential pressure switch whose contacts areconnected to a digital input on the W7761A and;
2. A 2 to 10V differential pressure sensor wired to avoltage input on the W7761A. If the analog inputsensor is used, its measured value 0 to 5 inw (0 to1.25 kPa) is compared to a user-selectable setpointin the Zone Manager, the comparison is done in theZone Manager - valid range: 0 to 5 inw (0 to 1.25kPa), and the Dirty Filter alarm is issued by the ZoneManager when the pressure drop across the filterexceeds the setpoint.
6HULHV �� 0RGXODWLQJ &RQWURO
Series 60 Control is also commonly referred to as FloatingControl. The Excel 10 W7761A Device can drive Series 60type actuators to control a modulating damper or valveactuator. The W7761A device contains no controlsoftware, so these outputs would have to be bound toeither the Zone Manager or other Excel 10 controllers.When floating control is used, the full-stroke motor drivetime of the actuator must be entered into the configurationparameter DO1FlSpeed (for output 1), DO2FlSpeed (foroutput 2). When Floating control is configured, two digitaloutputs are required, so the user has to change theconfiguration parameter for the appropriate digital outputs.
3XOVH :LGWK 0RGXODWLQJ �3:0� &RQWURO
The Excel 10 W7761A device can drive a PWM-typeactuator to control a modulating actuator. The W7761Adevice contains no control software, so these outputswould have to be bound to either the Zone Manager orother Excel 10 controllers. PWM control positions theactuator based on the length, in seconds, of the pulse fromthe digital output. The controller outputs a pulse whoselength consists of two parts, a minimum and a maximum.The minimum pulse time represents the analog value ofzero percent (also indicates a signal presence) and themaximum pulse length that represents an analog value of100 percent. If the analog value is greater than zeropercent, an additional time is added to the minimum pulsetime. The length of time added is directly proportional tothe magnitude of the analog value. If PWM control is used,the configuration parameters for the PWM operation mustbe specified. These parameters are DO1PWMPeriod andPWMZeroScale, and PWMFullScale.
Example: To find the pulse width of a valve actuator (forexample stroke mid position - 50 percent) with the
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 40
PWMZeroScale = 0.1 seconds, PWMFullScale =25.5 seconds, and the PWMPeriod = 25.6 seconds. Thereare 256 increments available, so the number of incrementsrequired for 50 percent would be (0.5 X 256) or 128. Thetime for each increment for this industry standard pulsetime is 0.1 seconds. The pulse width is the minimum time(0.1 second) + the number of increments (128 times theseconds added 0.1) = 12.9 seconds. The W7750BController would command the valve output on for 12.9seconds every 25.6 seconds to maintain the valve positionat 50 percent.
,QGRRU $LU 4XDOLW\ �,$4� 2YHUULGH
The Excel 10 W7761A Device can monitor an IAQ sensorand that input can be bound to a W7750 CVAHUController that supports an IAQ override feature, that upondetection of poor air quality in the space, allows theeconomizer dampers to be opened above the standardminimum position setting to a value set in EconIAQPos(parameter located in W7750). Two different methods ofdetecting poor air quality are supported, The first is byusing an IAQ switch device connected to a digital input onthe W7761A Device, where a contact closure indicatespoor air quality. This digital input would then be bound tothe W7750 Controller that is serving the area beingmonitored and would initiate the IAQ override mode. Thesecond is through an analog input that connects to a CO2
Sensor (0 to 10V). The measured value of CO2 from thissensor (0 to 2000 ppm) is mapped into the Zone Managerwhere it is compared to a setpoint (parameter located inthe Zone Manager). When the CO2 level is higher than thesetpoint, the Zone Manager can initiate an IAQ alarm. Apseudo digital point in the Zone Manager can be bound tothe W7750 CVAHU Controller which can initiate the IAQoverride mode.
C1. Input/Output Points.C2. Control Parameters.C3. Status Points.C4. Configuration Parameters.C5. Direct Access And Special Points.
Table C0 lists the applicable Engineering Units for theanalog points found in the W7761A.
Tables C1 through C5 list all network variables associatedwith the W7761A Controller and the default User Addressnames. Table C1 lists the Network Variable Inputs andOutputs, which are stored in RAM memory. Table C2 liststhe Control Parameters, which are the values stored in thecontrollers EEPROM memory.
NOTE: Table C2. User Addresses For W7761A ControlParameters. (Control Parameters are stored inEEPROM - limited to 10,000 writes. Do NOT useas outputs from Control Strategies, TimePrograms, or Switching Tables. If these points arechanged more than 10,000 times, irreversiblehardware failure results).
Tables provides point attributes as follows:EngineeringUnits— This field indicates the point valid range
and displayed Engineering Unit. Fordigital points, the valid states and thecorresponding enumerated values areshown.
Default— The value or state of the point oncontroller start-up.
Shareable— The point can be set up for data sharingin Command Multiple Points, ReadMultiple Points, or Refer Excel 10 Pointsas either a data source or a destination.
Mappable— The point can be converted into a C-Buspoint used by C-Bus devices. Amappable point has a one-to-onerelationship with a C-Bus User Address.
DirectAccess— The point is accessible through the
Subsystem Points mechanism in XBS.E-VisionMonitor— These points are viewable within the E-
Vision Controller Monitoring on-linescreen. PAR refers to controlparameters that are set in theApplication Selection dialog boxes in E-Vision.
(continued)
Table C0. Engineering Units For Analog Points.
English Units (Inch-Pound) Standard International Units (SI)
Temperature Degrees Fahrenheit F Degrees Celsius C
Relative Temperature Delta Degrees Fahrenheit DDF Degrees Kelvin K
Relative Humidity Percent % Percent %
Air Flow Cubic Feet per Minute CFM Meters cubed per hour m3h
CO2 Concentration Parts Per Million PPM Parts Per Million PPM
Enthalpy British Thermal Units per Pound of Air btu/lb kiloJoules/kilogram kJ/kg
Differential Pressure Inches of Water Column inw kiloPascal kPa
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
41 74-2699
HardwareConfig— These are points that involve controller
I/O configuration. Any change to HWConfig. points causes the W7761A toperform an application reset; therefore,these points can only be modified off-line.
Manual— These points are used to set thecontroller outputs when in manual mode.The W7761A is placed in manual modethrough a menu selection in the E-VisionController Monitor screen.
Fixable— These input points can be set to aconstant value in the E-Vision ControllerMonitor screen.
NOTES:1. Mapped points can be viewed and changed, if
applicable, on C-Bus devices such as an XI581,XI582 and XI584 and on an XBS central and E-Vision.
2. All Excel 10 points, mappable, calibration,configuration and internal data sharing points,can be viewed and changed, as allowed, viaDirect Access (DA) mode in the XBS subsystemmenu or via XI584.
3. E-Vision - These points are displayed to the userand polled during the E-Vision monitor function.Monitor (M) indicates the point appears in theSoftware list box. Schematic (S) indicates thepoint is to be displayed on the schematic airhandler diagram directly. Calibrate (C) - Thesepoints are calibratible and the calibration dialog(either the temperature or air flow dialog) isdisplayed. These points are displayed in a listboxby selection of the menu item Controller,Calibration. When the user double clicks on thesepoints the calibration dialog is displayed.Parameter (P) - This information is displayed tothe user in the Application Selection screens.These fields are read/write when offline and readonly when online.
4. Manual - These points can be placed in themanual mode. When the user double clicks onthese points the manual dialog is displayed, thiscontains radio buttons; one for Auto and one forManual.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 42
Table C1. Input/Output Points (Left).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X AI1RType specifies which logical sensor is assigned to which physical analog inputsensor channel according to the enumerated list shown in the Eng. Units/Statescolumn.
X X AI2RType: Refer to the description for AI1RType.
X X AI3RType: Refer to the description for AI1RType.
X X AI4RType: Refer to the description for AI1RType.
X X AI5VType specifies which logical voltage or current sensor is assigned to whichphysical analog input sensor channel according to the enumerated list that isshown in the Eng. Units/States column.
X X AI6VType: Refer to the description for AI5VType.
(continued)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 44
Table C1. Input/Output Points (Left Continued).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X X M DestOut1Cmd: DestOut1Cmd through DestOut8Cmd corresponds to DO1 throughDO8. Refer to the Eng. Units/States column for DO1Type for the enumeratedvalues that can be assigned to any output channels.Note that a selection of FLOAT means that the two DO channels are used foroutput. RIO assumes that the tool makes the proper assignment of enumeratedvalues to DO1 through DO8 and also takes the responsibility to avoid assignmentof multiple or overlapping commands on the same output channels. An example ofthe relationship between nviRemoteCmd and ncirioIoSelect is discribed below:RIO is receiving a command to DestOut4Cmd. This can be mapped as one of thethree output types (Discrete, Modulate, Float_Open, or Float_Close) by DO3Type.If the user selects an enumerated value of Discrete2 for DO3Type, this value wouldbe stored in (DO2). Then the DestOut4Cmd will command DO2.
X X X M DestOut2Cmd: Refer to the description for DestOut1Cmd.
X X X M DestOut3Cmd: Refer to the description for DestOut1Cmd.
X X X M DestOut4Cmd: Refer to the description for DestOut1Cmd.
X X X M DestOut5Cmd: Refer to the description for DestOut1Cmd.
X X X M DestOut6Cmd: Refer to the description for DestOut1Cmd.
X X X M DestOut7Cmd: Refer to the description for DestOut1Cmd.
X X X M DestOut8Cmd: Refer to the description for DestOut1Cmd.
X X DI1Sel1Type specifies the sensor type and function connected to DigitalIn0S1through DigitalIn3S1. The valid enumerated list of logical digital states forDigitalIn0S1 is listed in the Eng. Units/States column.
X X DI2Sel1Type: Refer to the description for DI1Sel1Type.
(continued)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 46
Table C1. Input/Output Points (Left Continued).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
DI3Sel1Type ncirioIoSelect DigitalIn2S1 See DI1Sel1Type Eng. Units/Statescolumn for selections.
Unused_DigInput
DI4Sel1Type ncirioIoSelect DigitalIn3S1 See DI1Sel1Type Eng. Units/Statescolumn for selections.
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X DI3Sel1Type: Refer to the description for DI1Sel1Type.
X X DI4Sel1Type: Refer to the description for DI1Sel1Type.
X X DI1Sel2Type specifies the sensor type and function connected to DigitalIn0S2through DigitalIn3S2. The valid enumerated list of logical digital states forDI1Sel2Type is listed in the Eng. Units/States column.
X X DI2Sel2Type: Refer to the description for DI1Sel2Type.
X X DI3Sel2Type: Refer to the description for DI1Sel2Type.
X X DI4Sel2Type: Refer to the description for DI1Sel2Type.
X X DO1Type specifies which logical digital output function is assigned to the digitalphysical output according to the enumerated list that is shown in the Eng.Units/States column.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 48
Table C1. Input/Output Points (Left Continued).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
DO2Type ncirioIoSelect DigitalOut1 Refer to the Eng. Units/Statescolumn for DO1Type for selectionsavailable.
Unused_DigOutput
DO3Type ncirioIoSelect DigitalOut2 Refer to the Eng. Units/Statescolumn for DO1Type for selectionsavailable.
Unused_DigOutput
DO4Type ncirioIoSelect DigitalOut3 Refer to the Eng. Units/Statescolumn for DO1Type for selectionsavailable.
Unused_DigOutput
DO5Type ncirioIoSelect DigitalOut4 Refer to the Eng. Units/Statescolumn for DO1Type for selectionsavailable.
Unused_DigOutput
DO6Type ncirioIoSelect DigitalOut5 Refer to the Eng. Units/Statescolumn for DO1Type for selectionsavailable.
Unused_DigOutput
DO7Type ncirioIoSelect DigitalOut6 Refer to the Eng. Units/Statescolumn for DO1Type for selectionsavailable.
Unused_DigOutput
DO8Type ncirioIoSelect DigitalOut7 Refer to the Eng. Units/Statescolumn for DO1Type for selectionsavailable.
Unused_DigOutput
FiftySixtyHz nciIoSelect FiftySixtyHz SixtyFifty
01
Sixty
SrcCO2Level nvoRemoteCO2 PPM0 to 65535
0
SrcCurrentAI nvoRemoteCurrent milliamps-20.0 to 200.0
0
SrcDigIn1Sts nvoRemoteDigIn(0) DI1Value 0 to 255 0
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X DO2Type:Refer to the description for DO1Type.
X X DO3Type:Refer to the description for DO1Type.
X X DO4Type:Refer to the description for DO1Type.
X X DO5Type:Refer to the description for DO1Type.
X X DO6Type:Refer to the description for DO1Type.
X X DO7Type:Refer to the description for DO1Type.
X X DO8Type:Refer to the description for DO1Type.
X X FiftySixtyHz specifies the power supply frequency. Correctly selecting FiftySixtyHzdecreases the noise picked up by analog sensor wiring from the power supply.When FiftySixtyHz is 1, the power supply frequency is Fifty Hz and whenFiftySixtyHz is 0, the power supply frequency is Sixty Hz.
X X X M SrcCO2Level is an output network variable corresponding to the voltage or currentinput channel (AI5 or AI6) if the selection for a CO2 sensor was made viancirioIoSelect.
X X X M SrcCurrentAI is an output network variable corresponding to the voltage or currentinput channel (AI5 or AI6) if the selection for a current sensor was made viancirioIoSelect.
SrcDigIn1Sts: There are four digital input channels (DI1 through DI4). If any of thefour channels are configured, the corresponding output network variable will beupdated with the value whose data type is SNVT_switch.
X X X M DI1State: There are four digital input channels (DI1 through DI4). If any of the fourchannels are configured, the corresponding output network variable will be updatedwith the value whose data type is SNVT_switch. Refer to the enumerated list that isshown in the Eng. Units/States column.
(continued)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 50
Table C1. Input/Output Points (Left Continued).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
SrcDigIn2Sts nvoRemoteDigIn(1) DI2Value 0 to 255 0
nvoRemoteDigIn(1) DI2State Refer to the DI1State enumerated listshown in the Eng. Units/States column.
ST_NUL
SrcDigIn3Sts nvoRemoteDigIn(2) DI3Value 0 to 255 0
nvoRemoteDigIn(2) DI3State Refer to the DI1State enumerated listshown in the Eng. Units/States column.
ST_NUL
SrcDigIn4Sts nvoRemoteDigIn(3) DI4Value 0 to 255 0
nvoRemoteDigIn(3) DI4State Refer to the DI1State enumerated listshown in the Eng. Units/States column.
ST_NUL
SrcHumidAI5 nvoRemoteHum(0) percent-163 to 163
0
SrcHumidAI6 nvoRemoteHum(1) percent-163 to 163
0
SrcPressAI5 nvoRemotePres(0) inw -131.5 to 131.5kPa (-32.768 to 32.767)
0
SrcPressAI6 nvoRemotePres(1) inw -131.5 to 131.5kPa (-32.768 to 32.767)
0
SrcTempAI1 nvoRemoteTemp(0) degrees F -40 to 240degrees C (-40 to 116)
0
SrcTempAI2 nvoRemoteTemp(1) degrees F -40 to 240degrees C (-40 to 116)
0
SrcTempAI3 nvoRemoteTemp(2) degrees F -40 to 240degrees C (-40 to 116)
0
SrcTempAI4 nvoRemoteTemp(3) degrees F -40 to 240degrees C (-40 to 116)
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
SrcDigIn2Sts: Refer to the description for SrcDigIn1Sts.
X X X M DI2State:Refer to the description for DI1State.
SrcDigIn3Sts: Refer to the description for SrcDigIn1Sts above.
X X X M DI3State:Refer to the description for DI1State.
SrcDigIn4Sts: Refer to the description for SrcDigIn1Sts above.
X X X M DI4State:Refer to the description for DI1State.
X X X M SrcHumidAI5 is an output network variable corresponding to the voltage or currentinput channel (AI5) if the selection for humidity sensor was made via ncirioIoSelectfor AI5.
X X X M SrcHumidAI6 is an output network variable corresponding to the voltage or currentinput channel (AI6) if the selection for humidity sensor was made via ncirioIoSelectfor AI6.
X X X M SrcPressAI5 is an output network variable corresponding to the voltage or currentinput channel (AI5) if the selection for a pressure sensor was made viancirioIoSelect for AI5.
X X X M SrcPressAI6 is an output network variable corresponding to the voltage or currentinput channel (AI6) if the selection for a pressure sensor was made viancirioIoSelect for AI6.
X X X M SrcTempAI1 is an output network variable corresponding to the analog inputchannel (AI1). This NV will contain AI1 temperature value with the OffsetCal1AI1applied to it.
X X X M SrcTempAI2 is an output network variable corresponding to the analog inputchannel (AI2). This NV will contain AI2 temperature value with the OffsetCal1AI2applied to it.
X X X M SrcTempAI3 is an output network variable corresponding to the analog inputchannel (AI3). This NV will contain AI3 temperature value with the OffsetCal1AI3applied to it.
X X X M SrcTempAI4 is an output network variable corresponding to the analog inputchannel (AI4). This NV will contain AI4 temperature value with the OffsetCal1AI4applied to it.
X X X M SrcVoltageAI is an output network variable corresponding to the voltage or currentinput channel (AI5 or AI6) if the selection for a voltage sensor was made viancirioIoSelect.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 52
Table C2. Control Parameters (Left).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
nviInUse is used by a management node to indicate to all other managementnodes that it is logged on, to the Excel 10 node and that they should not try tointeract with any of the Excel 10s network variables. Before the management nodereads or writes any network variables, the management node checks nviInUse fora zero value meaning no other management nodes are already logged on and thata management node may log on, to the node. Then the management node writes anumber, 1 through 65534, to nviInUse and periodically writes the same value toindicate that the management node is still logged on. If there are no writes made tonviInUse for approximately 60 seconds, then the Excel 10 resets nviInUse to zeroto automatically log off the management node. Before interacting with any networkvariables, the management node verifies that the nviInUse has not changed. Themanagement node logs off by writing 0 to nviInUse.During power up, an application restart, or return to on-line from off-line, the Excel10 sets nviInUse to 65535 to indicate to the management node that it has returnedto on-line.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 54
Table C3. Status Points (Left).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
AlarmNode: is the LonWorks node number (in domain entry 1 of the nodes domaintable) assigned to the node.
AlarmSubnet: is the LonWorks subnet number (in domain entry 1 of the nodesdomain table) to which the node is assigned.
AlarmType: is the alarm type being issued. When an alarm condition is no longerTRUE, type is set to the sum of the alarm conditions numeric value and theRETURN_TO_NORMAL numeric value. The type also is recorded inAlarmTypeLog0 through AlarmTypeLog4. When a new alarm is detected, just thecorresponding numeric value for the alarm is reported. Refer to table 9 (Excel 10Alarms) in the System Engineering Guide for all the error conditions that may bereported.
X M AlarmTypeLog0 (0, 1, 2, 3, 129, 130, 131, 255)A supervisory node may poll the AlarmTypeLog output for a short alarm history. Thelast five alarm reports sent via nvoAlarm are reported via AlarmTypeLog. WhenALARM_NOTIFY_DISABLED is entered into the log, further alarms or return tonormals are not entered into the log, until alarm reporting is again enabled. IfnvoAlarm is bound and not being acknowledged, the last alarm report entered intothe AlarmTypeLog is the one that was not acknowledged.See nvoAlarm and for related subjects.type ( n ) specifies the alarm that was issued via nvoAlarm. See nvoAlarm for thealarm types used in AlarmTypeLog. The newest alarm is reported in type( 0 ) andthe oldest is reported in type( 4 ). When a new entry is made to the log, the oldestentry is lost.
X M AlarmTypeLog1:Refer to the description for AlarmTypeLog0.
X M AlarmTypeLog2:Refer to the description for AlarmTypeLog0.
X M AlarmTypeLog3:Refer to the description for AlarmTypeLog0.
X M AlarmTypeLog4:Refer to the description for AlarmTypeLog0.
X M ResSensor1Error(AI1): The nvoError is a polled output containing a list of the currenterrors detected by the node. A search for error conditions in the node is madeperiodically. A diagnostic tool may poll nvoError for all of the current errors. nvoErroruses one bit for each possible error condition. nvoError contains all the detectedcurrent errors even though they may be suppressed for reporting by nvoAlarm.There is a correspondence between the error conditions and alarm types. nvoErrorincludes sensor failure errors and input network variable failure detect errors. Anysensor failure errors result in a SENSOR_FAILURE alarm. Failure to receive anybound network variable periodically results in an INPUT_NV_FAILURE alarm.nvoError tells which sensor(s) or network variable(s) have failed. See nvoAlarm,AlarmTypeLog for related subjects.
(continued)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 56
Table C3. Status Points (Left Continued).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X M ResSensor2Error(AI2): Refer to the description of ResSensor1Error(AI1).
X M ResSensor3Error(AI3): Refer to the description of ResSensor1Error(AI1).
X M ResSensor4Error(AI4): Refer to the description of ResSensor1Error(AI1).
X Software version.
A four byte ASCII string indicating the type of node (model).
X Software version.
X Software version.
The NodeType is a numeric identifier that is stored in EPROM that identifies theExcel 10 node type. Whenever a new software version or upgrade is issued, this isreflected in nroPgmVer which typically is read by a network management node toidentify the node type. The contents of nroPgmVer contain compatible model typeinformation and is fixed at the time when the node software is compiled.
CommFailure:This field is not supported and is set to 0 (FALSE).
disabled: disabled reports 1 if nvoIO mode is set to DISABLED_MODE orFACTORY_TEST mode. Otherwise disabled is set to 0.
ElectricalFault:This field is not supported and is set to 0 (FALSE).
FailSelfTest:This field is not supported and is set to 0 (FALSE).
FeedbackFailure:This field is not supported and is set to 0 (FALSE).
InAlarm: If there are currently any active alarms reported by InAlarm, or InAlarm isset to AlarmNotifyDisabled, then InAlarm is set to True, if not InAlarm is set to False.
InvalidId: If object_id is not a valid object, invalid_id is set to 1 (TRUE) otherwise it isset to 0 (FALSE).
InvalidRequest: If object_request is not a valid request for the object addressed,InvalidRequest is set to 1 (TRUE) otherwise it is set to 0 (FALSE).
(continued)
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 58
Table C3. Status Points (Left Continued).
Engineering Units:English (Metric) or
DigitalState
orValue
ofUser Address NvName Field Name States plus Range State Default
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
ApplicationType identifies the current application number of the Excel 10.
nciDeviceName is an 18 character field used to identify the node uniquely as oneobject at the site or project. The contents of the nciDeviceName is maintained by amanagement node. If nciDeviceName is all ASCII blanks, it is consideredunconfigured.
The time stamp of the last change to the Excel 10 application configuration. Timemeets the ANSI C time stamp requirement specifying the number of secondselapsed since midnight (0:00:00), January 1, 1970. It is represented in the IntelFormat.
VersionNumber identifies the version number of the Excel 10 application.
X M X AILowLimit: This is the low limit value or the lowest value that will be displayed forthis sensor. This value must be between the AIOutputRLow and AIOutputRHigh andlower than the value specified for AIUpperLimit.
X M X AIOutputRHigh: This is the equivalent temperature degrees F (degrees C) value forthe resistance entered for AIResHigh. Using the resistance example for AIResHighof 48,000 ohms, you would enter the equivalent temperature of 45.0 degrees F (7.2degrees C) for the AIOutputRHigh value.
X M X AIOutputRLow: This is the equivalent temperature degrees F (degrees C) value forthe resistance entered for AIResLow. Using the resistance example for AIResLow of11,520 ohms, you would enter the equivalent temperature of 99.0 degrees F (37.2degrees C) for the AIOutputRLow value.
X M X AIResHigh: This is the highest resistance value of the user specified range for acustom resistive input as selected through E-Vision in the input Tab of theApplication selection screen. The user can select between a PT3000(Custom_PT3000) or a 20 Kohm NTC (Custom_20 Kohm NTC) sensor. This value isspecified in ohms with LSB in 10 Ohms. This means that if your high resistancevalue for a 20 Kohm NTC sensor was 48,000 ohms, 45.0 degrees F (7.2 degrees C),the value that would be entered for AIResHigh would be 4800 (the resistance valuedivided by ten).
X M X AIResLow: This is the lowest resistance value of the user specified range for acustom resistive input as selected through E-Vision in the input Tab of theApplication selection screen. The user can select between a PT3000(Custom_PT3000) or a 20 Kohm NTC (Custom_20 Kohm NTC) sensor. This value isspecified in ohms with LSB in 10 Ohms. This means that if the low resistance valuefor a 20 Kohm NTC sensor was 11,520 ohms, 99.0 degrees F (37.2 degrees C), thevalue that would be entered for AIResLow would be 1152 (the resistance valuedivided by ten).
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X M X AIUpperLimit: This is the high limit value or the highest value that will be displayedfor this sensor. This value must be between the AIOutputRLow and AIOutputRHighand higher than the value specified for AILowLimit.
X M P X DeltaC: The default value of delta for all RIO sensor types is set to zero. With thisdefault value, the RIO will send the sensor values at the fastest rate of 2 secondsupdate rate. However, if the user desires to reduce the network traffic or not receivethe noisy sensor values, a delta value can be specified. This value will force the RIOto transmit the sensor value when the current value exceeds the last sent value bythe delta amount. RIO will also send the sensor value whenever the time of updateexceeds nciRioSendT. RIO will send the sensor value at the rate of nciRioSendTregardless of delta change.
X M P X DeltaCO2: Refer to the description for DeltaC.
X M P X DeltaH: Refer to the description for DeltaC.
X M P X DeltaP: Refer to the description for DeltaC.
X M P X DeltaT1: Refer to the description for DeltaC.
X M P X DeltaT2: Refer to the description for DeltaC.
X M P X DeltaT3: Refer to the description for DeltaC.
X M P X DeltaT4: Refer to the description for DeltaC.
X M P X DeltaV: Refer to the description for DeltaC.
X X DO1FlSpeed is how long it takes for the actuator motor to move one cycle of travelfrom closed to open. This value would be required if DO1Type were configured toeither Float_Open or Float_Close.
X X DO2FlSpeed is how long it takes for the actuator motor to move one cycle of travelfrom closed to open. This value would be required if DO2Type were configured toeither Float_Open or Float_Close.
X X DO3FlSpeed is how long it takes for the actuator motor to move one cycle of travelfrom closed to open. This value would be required if DO3Type were configured toeither Float_Open or Float_Close.
X X DO4FlSpeed is how long it takes for the actuator motor to move one cycle of travelfrom closed to open. This value would be required if DO4Type were configured toeither Float_Open or Float_Close.
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X DO5FlSpeed is how long it takes for the actuator motor to move one cycle of travelfrom closed to open. This value would be required if DO5Type were configured toeither Float_Open or Float_Close.
X X DO6FlSpeed is how long it takes for the actuator motor to move one cycle of travelfrom closed to open. This value would be required if DO6Type were configured toeither Float_Open or Float_Close.
X X DO7FlSpeed is how long it takes for the actuator motor to move one cycle of travelfrom closed to open. This value would be required if DO7Type were configured toeither Float_Open or Float_Close.
X X DO8FlSpeed is how long it takes for the actuator motor to move one cycle of travelfrom closed to open. This value would be required if DO8Type were configured toeither Float_Open or Float_Close.
X M X DO1PWMPeriod is a intermittent voltage pulse whose width varies in proportion tothe desired actuator position. The PWM signal has three parameters that have to beconfigured in order for the output to function correctly. The period, is the overall pulselenegth in seconds. The percent_time (signal presence) is the zero percent positionof the actuator output. The actuator requires this signal (pulse width) sent once everyperiod, so that it knows that it is still connected to the controller and where the zeroposition starts. The variable width (delta_time) portion is incremented in proportion tothe signal percentage. There are 255 increments available (for example 0.1 second).Thus, the pulse width will be the minimum width (percent_time) plus the number ofincrements (delta_time/ 255). The smallest time that can be used with the RIOcontroller is 0.1 second. An example stroke at mid position is: 0.1 second(percent_time) + 128 x 0.1 (255/0.5 - 50 percent position) = 12.9 seconds. The periodwould equal the percent_time plus the delta_time (for example 0.1 seconds) + 255 x0.1 seconds = 25.6 seconds.
X M X DO1PWMZero: Refer to the description for DO1PWMPeriod.
X M X DO1PWMFull: Refer to the description for DO1PWMPeriod.
X M X DO2PWMPeriod: Refer to the description for DO1PWMPeriod.
X M X DO2PWMZero: Refer to the description for DO1PWMPeriod.
X M X DO2PWMFull: Refer to the description for DO1PWMPeriod.
X M X DO3PWMPeriod: Refer to the description for DO1PWMPeriod.
X M X DO3PWMZero: Refer to the description for DO1PWMPeriod.
X M X DO3PWMFull: Refer to the description for DO1PWMPeriod.
X M X DO4PWMPeriod: Refer to the description for DO1PWMPeriod.
X M X DO4PWMZero: Refer to the description for DO1PWMPeriod.
X M X DO4PWMFull: Refer to the description for DO1PWMPeriod.
X M X DO5PWMPeriod: Refer to the description for DO1PWMPeriod.
X M X DO5PWMZero: Refer to the description for DO1PWMPeriod.
X M X DO5PWMFull: Refer to the description for DO1PWMPeriod.
Parameter (P), Schematic (S)Hardware Configuration (HW),Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X M P DestManMode: is an input which is used to manually set the physical outputs.DestManMode remains unchanged until another mode has been commanded or anapplication restart has been performed. The valid enumerated values are:MODE_ENABLE enables the node so that the RIO controls the physical outputs asthe normal mode. MODE_ENABLE is the default state after power is restored or anapplication restart occurs. If the mode was MANUAL and DestManMode is set toMODE_ENABLE, the node then goes through application restart.MODE_DISABLED sets the node into the DISABLED mode. The alarmNODE_DISABLED is initiated, and the physical outputs are turned off. The physicalinputs, network variable inputs, and network variable outputs are still functioningwhen the node is in the DISABLED mode.MODE_MANUAL sets the node into the MANUAL mode. The alarmNODE_DISABLED is initiated, and the physical outputs are controlled manually ascommanded by DestManMode. The nodes configuration variables andDestManMode are used to set valves, dampers, and/or digital output to the desiredmanual positions or state(s). The physical inputs, network variable inputs, andnetwork variable outputs are still functioning when the node is in the MANUAL mode.SUPPRESS_ALARMS causes AlarmType to be set to ALARM_NOTIFY_DISABLED,and AlarmTypeLog to no longer record alarms. If alarms are suppressed,UNSUPPRESS_ALARMS causes AlarmType and AlarmTypeLog to be returned toreporting alarms. See nvoAlarm for more details. All unspecified values are the sameas MODE_ENABLE.
Memory size approximation is shown below: (all sizes inbytes)
When memory size is less than 110,000 bytes, the size isOK.
When memory size is between 110,000 and 128,000bytes, the application may be too large. The user mustexpect to reduce the application complexity, reduce thenumber of attached Excel 10s or distribute the Excel 10sover more than one Zone Manager.
When memory size is greater than 128,000, the size is toolarge. The application size must be reduced as describedabove.
$SSUR[LPDWH�0HPRU\�6L]H�(VWLPDWLQJ�3URFHGXUH�
1. Determine the number of points per controllerrequired at the Central (for example, XBS).
NOTE: All remaining points that are not mappedcan be accessed through the Direct Accessfeature.
2. Calculate the number of Excel 10 Zone Managerprogram points that are used in control logic and inthe switching table.
3. Estimate the program complexity of the ZoneManager (one of three levels).
a. No time programs, control logic, or switchingtables.
b. 10K of control logic (one time program, fiveswitching tables, and five control loops).
c. 20K of control logic (multiple time programs,ten switching tables, and ten control loops).
Use Fig. D-1 to determine the number of Excel 10sthat can be connected to the Zone Manager.
NOTE: More than 60 Excel 10s requires a Router.
4. Repeat for each Q7750A Excel 10 Zone Manager ina project.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
74-2699 70
20 60 120
600
700
800
900
600
700
800
900920
765
610
585
740
895
NUMBER OFC-BUS POINTS(EXCEL 10MAPPED POINTSPLUS ZONEMANAGERPOINTS)
(OR LESS) (ADD ROUTER)
NUMBER OF EXCEL 10s
(C)
(A)
NUMBER OFC-BUS POINTS(EXCEL 10MAPPED POINTSPLUS ZONEMANAGERPOINTS)
NO TIME PROGRAM,NO CONTROL LOOPS, NO SWITCHING TABLES.
20K CONTROL PROGRAM(I.E., MULTIPLE TIME PROGRAMS,10 CONTROL LOOPS, 10 SWITCHING TABLES.)
10K CONTROL PROGRAM(FOR EXAMPLE, 1 TIME PROGRAM,5 CONTROL LOOPS, 5 SWITCHING TABLES.)
(B)
M8729
Fig. D-1. Point capacity estimate for Zone Manager.
The exact equation for calculating memory size follows:Memory size = 21,780
+ 4096 (in case of a time program).+ CARE Control Program.+ 14 x time points x Excel 10 units.+ 50 x Excel 10 units.+ map complexity x Excel 10 units x mapped points.+ 57 x C-Bus points.+ 7488 x Excel 10 types.
Where:Time points = number of switch points in time
programper Excel 10.
Excel 10 units = number of attached Excel 10s.C-Bus points = including mapped points and
others; forexample, remote points.
Mapped points = number of mapped points per Excel10,including One-to-Many and Many-to-Onemechanism.
Excel 10 types = number of different Excel 10 types(currently three)
Map complexity =20 = using One-to-Many and not using
points with read/write.30 = average.45 = many points with read/write ability.
$SSHQGL[�(��6HQVRU�'DWD�IRU�&DOLEUDWLRQ
5HVLVWDQFH�6HQVRUV�
Sensor Type:C7100A1015, (and C7170A1002).
Sensor Use:Discharge Air, Outdoor Air Temperature.
Table E-1 lists the points for Sensor Resistance versusTemperature. Fig. E-1 shows the graph of these points.
Table E-8 lists the points for Sensor Voltage versus inputVoltage to A/D. Fig. E-10 shows the graph of these points.
Table E-8. Sensor Voltage Versus Input VoltageTo A/D.
Voltage to A/D Sensor Voltage
0.00 0.00
0.50 0.25
1.00 0.50
1.50 0.75
2.00 1.00
2.50 1.25
3.00 1.50
3.50 1.75
4.00 2.00
4.50 2.25
5.00 2.50
5.50 2.75
6.00 3.00
6.50 3.25
7.00 3.50
7.50 3.75
8.00 4.00
8.50 4.25
9.00 4.50
9.50 4.75
10.00 5.00
0
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
1000 300 500 700 900200 400 600 800 1000
A/D
VO
LTS
VOLTS
SENSOR VOLTAGE VERSUS INPUT VOLTAGE TO A/D
M11612
Fig. E-10. Graph of Sensor Voltage versus inputVoltage to A/D.
Sensor Type:Third party.
Sensor Use:Sensor Voltage (Vdc)/Pressure Inw (kPa) 2 to 10V, 0 to 5inw (0 to 1.25 kPa).
Table E-9 lists the points for Sensor Voltage (Vdc) versusPressure (Inw). Fig. E-11 shows the graph of these points.
EXCEL 10 W7761A REMOTE INPUT/OUTPUT DEVICE
Home and Building Control Home and Building Control Home and Building Control ProductsHoneywell Inc. Honeywell Limited-Honeywell Limitee Honeywell AGHoneywell Plaza 155 Gordon Baker Road Böblinger Straße 17P.O. Box 524 North York Ontario D-71101 SchönaichMinneapolis, MN 55408-0524 M2H 3N7 Phone (49-7031) 637-01
Fax (49-7031) 637-493
74-2699 J.D. 7-98
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. www.honeywell.com
Table E-9. Sensor Voltage (Vdc) Versus Pressure lnw(kPa).