PRO-D
IALOG +
61AF 022-105Nominal heating capacity 22-105 kW
The new generation of Aquasnap high-temperature heat pumps was
designed for commercial applications such as the heating of
offices, apartments and hotels as well as domestic hot water
production in new and refurbished buildings.
FeaturesThe main features of this product range are:
Energy savingsThe 61AF range is certified to the Eurovent energy
efficiency class A with a coefficient of performance (COP) of over
4. This complies with the COP required by the Ecolabel
certification.
Ease-of-installationThe high-temperature Aquasnap heat pumps
incorporate a hydronic module with a multi-speed pump, as standard.
An optional hydronic module with a variable-speed pump that
automatically adapts to the system requirements is also
available.
Easy integrationThe low noise levels of the 61AF heat pump and
its very compact chassis reduce the noise disturbance from the
unit.
Application flexibilityThe operating range allows outside
temperatures down to -20C and leaving water temperatures up to 65C
for domestic hot water applications.
Availability - Intelligent unit control permits unit operation
in extreme conditions, minimising unit shut-down times.
- Hot water production at 65C is available continuously.
Carrier quality is your guarantee for the safety and durability
of the installation.
The new generation of high-temperature heat pumps incorporates
the latest technological features: - scroll compressors with vapour
injection - low-noise fans made of a composite material -
auto-adaptative microprocessor control - electronic expansion valve
- multi-speed pump.
The high-temperature Aquasnap heat pumps can be equipped with a
hydronic module that is integrated into the heat pump chassis,
limiting the installation to straight-forward operations like the
wiring and the connection of the hot water supply and return
piping.
High-Temperature Monobloc Air-to-Water Heat Pumpswith Integrated
Hydronic Module
-
Quiet operation Compressors
- Low-noise scroll compressors with low vibration level. - The
compressor assembly is installed on an independent chassis and
supported by anti-vibration mountings.
- Dynamic suction and discharge piping supports, minimising
vibration transmission (Carrier patent).
Evaporator section - Vertical evaporator coils - Protection
grilles on anti-vibration mountings to protect the heat exchanger
against possible shocks.
- Latest-generation low-noise Flying Bird fans, made of a
composite material (Carrier patent), are now even quieter and do
not generate intrusive low-frequency noise.
- Rigid fan installation for reduced start-up noise (Carrier
patent).
Easy and fast installation Integrated hydronic module
(option)
- Multi-speed centrifugal water pump, based on the pressure loss
of the hydronic installation.
- Water filter protects the water pump against circulating
debris.
- Pump protected against cavitation by a pressure transducer
that measures the entering water pressure.
- Overpressure valve, set to 4 bar. - Thermal insulation and
frost protection down to -20C, using an electric resistance heater
(see table of options).
Physical features - The unit has a small footprint and a low
height (1329 mm) allowing it to blend in with any architectural
styles.
- The unit is enclosed by easily removable panels, covering all
components (except condensers and fans).
Simplified electrical connections - Single power supply point
without neutral. - Main disconnect switch with high trip capacity.
- Transformer for safe 24 V control circuit supply included.
Fast commissioning - Systematic factory operation test before
shipment. - Quick-test function for step-by-step verification of
the instruments, electrical components and motors.
Economical operation Increased energy efficiency
- The exceptional energy efficiency level (COP) of the
high-temperature Aquasnap heat pumps in the heating mode is the
result of a long qualification and optimisation process.
- The electronic expansion device (EXV) allows operation at a
lower condensing pressure (COP optimisation).
- Dynamic superheat management for better utilisation of the
condenser surface.
Reduced maintenance costs - Maintenance-free scroll compressors
with vapour injection.
- Pro-Dialog+ control offers fast diagnosis of possible
incidents and their history.
Environmental care Ozone-friendly R-407C refrigerant
- Chlorine-free refrigerant of the HFC group with zero ozone
depletion potential.
- Very efficient - ensures an increased energy efficiency ratio
(COP).
Leak-tight refrigerant circuit - Brazed refrigerant connections
for increased leak-tightness.
- Reduction of leaks due to elimination of capillary tubes
(TXVs).
- Verification of pressure transducers and temperature sensors
without transferring refrigerant charge.
Superior reliability State-of-the-art concept
- Cooperation with specialist laboratories and use of limit
simulation tools (finite element calculations) for the design of
the critical components, e.g. motor supports, suction/discharge
piping etc.
Auto-adaptive control - Control algorithm prevents excessive
compressor cycling and permits reduction of the water quantity in
the hydronic circuit (Carrier patent).
Exceptional endurance tests - Corrosion resistance tests in salt
mist in the laboratory. - Accelerated ageing test on components
that are submitted to continuous operation: compressor piping, fan
supports.
- Transport simulation test in the laboratory on a vibrating
table.
2
-
Pro-Dialog+ controlPro-Dialog+ combines intelligence with
operating simplicity. The control constantly monitors all machine
parameters and precisely manages the operation of compressors,
expansion devices, fans and of the condenser water pump for optimum
energy efficiency.
Energy management - Seven-day internal time schedule clock:
permits unit on/off control and operation at a second set
point.
- Set point reset based on the outside air temperature or the
return water temperature or on the water heat exchanger delta
T.
- Master/slave control of two heat pumps operating in parallel
with operating time equalisation and automatic change-over in case
of a unit fault (option).
- Start/stop based on the outside air temperature.
Ease-of-use
- The new backlighted LCD interface includes a manual control
potentiometer to ensure legibility under any lighting
conditions.
- The information is displayed clearly in English, French,
German, Italian and Spanish (for other languages please consult
Carrier).
- The Pro-Dialog+ navigation uses intuitive tree-structure
menus, similar to the Internet browers. They are user-friendly and
permit quick access to the principal operat-ing parameters: number
of compressors operating, suction/discharge pressure, compressor
operating hours, set point, air temperature, entering/leaving water
temperature.
- As standard the unit includes a board for the control of a
boiler and four electric resistance heater stages.
Pro-Dialog+ operator interface
Circuit B Total Capacity
PRO-DIALOG+
Remote operating mode with volt-free contacts (standard)
A simple two-wire communication bus between the RS485 port of
the Aquasnap high-temperature heat pumps and the Carrier Comfort
Network offers multiple remote control, monitoring and diagnostic
possibilities.
Carrier offers a vast choice of control products, specially
designed to control, manage and supervise the operation of a
heating system. Please consult your Carrier representative for more
information on these products. - Start/stop: opening of this
contact will shut down the heat pump.
- Dual set point: closing of this contact activates a second
heating set point (example: unoccupied mode).
- Demand limit: closing of this contact limits the maximum heat
pump capacity to a predefined value.
- User safety: this contact is connected in series with the
water flow switch and can be used for any customer safety loop.
- Water pump control. - Alert indication: this volt-free contact
indicates the presence of a minor fault.
- Alarm indication: this volt-free contact indicates the
presence of a major fault that has led to the shut-down of the
refrigerant circuit.
Remote interface (accessory)This accessory includes a box that
can be mounted inside the building. The power supply is provided
via a 220 V/24 V transformer supplied. This interface allows access
to the same menus as the unit interface and can be installed up to
300 m from the 61AF unit.
Flying Bird IV fan
3
-
Options and accessoriesOptions No. Description Advantages
UseAnti-corrosion protection, traditional coils
3A Fins made of pre-treated aluminium (polyurethane or
epoxy)
Improved corrosion resistance, recommended for marine
environments
61AF 022-105
Unit with discharge air ducts 11 Fans with available pressure -
max. 100 Pa Enhances unit adjustment during installation (e.g.
under a roof)
61AF 022-105
Low noise level 15 Acoustic compressor enclosure Noise emission
reduction 61AF 022-105Very low noise level 15LS Acoustic compressor
enclosure and
fan speed reduction, when ambient air temperature is above
20C.
Noise emission reduction 61AF 022-105
Soft starter 25 Electronic compressor starter Reduced compressor
start-up current 61AF 022-105Frost protection down to -20C 42
Electric heater on the hydronic module (option
116)Hydronic module frost protection at low outside
temperature
61AF 022-105with option 116F
Low-pressure single-pump hydronic module
116F See hydronic module chapter Easy and fast installation 61AF
022-105
JBus gateway 148B Two-directional communications board, complies
with JBus protocol
Easy connection by communication bus to a building management
system
61AF 022-105
BacNet gateway 148C Two-directional communications board,
complies with BacNet protocol
Easy connection by communication bus to a building management
system
61AF 022-105
LonTalk gateway 148D Two-directional communications board,
complies with LonTalk protocol
Easy connection by communication bus to a building management
system
61AF 022-105
Heating system control* 157 Additional remotely installed
control box, allows control of the various heating system
components
Allows control of pre-configured heating systems 61AF
022-105
Water screw connection between the customers condenser and the
unit
265 Victaulic screw connection at the condenser (standard on
sizes 022-030)
Permits customer connections to be screwed to the unit 61AF
035-055
Welded water connection between the customers condenser and the
unit
267 Welded Victaulic connection Permits customer connections to
be welded to the unit 61AF 035-055
Accessories Description Advantages UseRemote user interface
Remotely installed user interface (via
communication bus).Remote heat pump control up to 300 m 61AF
022-105
JBus gateway communication Two-directional communications board,
complies with JBus protocol
Connection by communication bus to a building management
system
61AF 022-105
BacNet gateway communication Two-directional communications
board, complies with BacNet protocol
Connection by communication bus to a building management
system
61AF 022-105
LonTalk gateway communication Two-directional communications
board, complies with LonTalk protocol
Connection by communication bus to a building management
system
61AF 022-105
Twinning (lead-lag kit) Unit equipped with an additional
field-installed leaving water temperature sensor, allowing
master/slave operation of two units connected in parallel
Operation of two units connected in parallel with operating time
equalisation
61AF 022-105
* Option available in 2011.
Electrical data and operating conditions notes: 61AF 022-105
units have a single power connection point located immediately
upstream of the main disconnect switch. The control box includes
the following standard features: - a main disconnect switch, -
starter and motor protection devices for the compressor, the fan
and the
pump, - the control devices. Field connections: All connections
to the system and the electrical installations must be in full
accordance with all applicable local codes. The Carrier 61AF
units are designed and built to ensure conformance with
these codes. The recommendations of European standard EN 60204-1
(machine safety - electrical machine components - part 1: general
regulations - corresponds to IEC 60204-1) are specifically taken
into account, when designing the electrical equipment.
Notes: Generally the recommendations of IEC 60364 are accepted
as compliance
with the requirements of the installation directives.
Conformance with EN 60204-1 is the best means of ensuring
compliance with the Machinery Directive 1.5.1.
Annex B of EN 60204-1 describes the electrical characteristics
used for the operation of the machines.
The operating environment for the 61AF units is specified
below:1. Environment* - Environment as classified in EN 60721
(corresponds to
IEC 60721): - outdoor installation* - ambient temperature range:
-20C to +40C, class 4K4H - altitude: 2000 m - presence of hard
solids, class 4S2 (no significant dust present) - presence of
corrosive and polluting substances, class 4C2 (negligible)2. Power
supply frequency variation: 2 Hz.3. The neutral (N) conductor must
not be connected directly to the unit (if
necessary use a transformer).4. Overcurrent protection of the
power supply conductors is not provided with
the unit.5. The factory-installed disconnect switch is of a type
suitable for power
interruption in accordance with EN 60947-3 (corresponds to IEC
60947-3)6. The units are designed for connection to TN networks
(IEC 60364). For IT
networks the earth connection must not be at the network earth.
Provide a local earth, consult competent local organisations to
complete the electrical installation.
Caution: If particular aspects of an actual installation do not
conform to the conditions described above, or if there are other
conditions which should be considered, always contact your local
Carrier representative.
* The required protection level for this class is IP43BW
(according to reference document IEC 60529). All 61AF units are
protected to IP44CW and fulfil this protection condition.
4
-
Physical data61AF 022 030 035 045 055 075 105Nominal heating
capacity* kW 20.8 25.7 32.2 43.6 52.2 66.7 102Power input kW 5.8
7.3 9.2 11.8 14 19.4 28.1Coefficient of performance (COP) kW/kW 3.6
3.5 3.5 3.7 3.7 3.4 3.6Eurovent class, heating A A A A A A ANominal
heating capacity** kW 21.2 26.1 32.8 43.8 52.8 64.7 102Power input
kW 4.9 6.1 7.8 9.9 11.9 16.1 23.6Coefficient of performance (COP)
kW/kW 4.3 4.3 4.2 4.4 4.4 4.0 4.3Eurovent class, heating A A A A A
B AOperating weight***Standard unit (without hydronic kit) kg 343
396 421 509 533 900 1020Standard unit (plus hydronic module option)
kg 349 403 436 524 549 926 1046Sound levelsSound power level 10-12
W**** dB(A) 81 82 83 83 84 84 85Sound pressure level at 10 m dB(A)
50 51 51 51 53 52 53Compressor Hermetic scroll 48.3 r/sQuantity 1 1
1 1 1 2 2Number of capacity stages 1 1 1 1 1 2 2Refrigerant
R-407CCharge kg 8.0 8.8 9.7 10.0 13.2 22.0 26.5Capacity control
Pro-Dialog+Minimum capacity % 100 100 100 100 100 50 50Condenser
Direct-expansion plate heat exchangerWater volume l 4.9 6.4 8.2 9.6
12.1 16.4 22.7Max. water-side operating pressure without hydronic
module kPa 1000 1000 1000 1000 1000 1000 1000Max. water-side
operating pressure with hydronic module kPa 400 400 400 400 400 400
400Fan Axial with rotating shroud, Flying Bird IVQuantity 1 1 1 1 1
2 2Total air flow (high speed) l/s 3800 3800 3800 3800 3800 7600
7600Speed, standard unit r/s 12 12 12 12 12 12 12Speed, unit with
option 11 r/s 16 16 16 16 16 16 16Evaporator Grooved copper tubes
and aluminium finsHydronic module (option 116)Three-speed single
pump Pump, Victaulic screen filter, safety valve, purge valves
(water and air), cavitation presssure sensorWater connections
with/without hydronic module VictaulicConnections inch 1-1/4 1-1/4
1-1/2 1-1/2 1-1/2 2 2Outside diameter mm 42.4 42.4 48.3 48.3 48.3
60.3 60.3Chassis paint colour Colour code: RAL 7035
* Standardised Eurovent conditions: entering leaving condenser
water temperature = 40C/45C, outside air temperature db/wb = 7C/6C
** Standardised Eurovent conditions: entering leaving condenser
water temperature = 30C/35C, outside air temperature db/wb = 7C/6C
*** Weight shown is a guideline only. To find out the unit
refrigerant charge, please refer to the unit nameplate.. **** In
accordance with ISO 9614-1 and certified by Eurovent. The values
have been rounded and are for information only and not
contractually binding For information, calculated from the sound
power level Lw(A) Units 61AF 022 and 61AF 030 include two sleeves
for a 1-1/4 Victaulic to 1-1/4 screw connection as standard.
Electrical data61AF - standard unit (without hydronic module)
022 030 035 045 055 075 105Power circuitNominal power supply
V-ph-Hz 400-3-50Voltage range V 360-440Control circuit supply 24 V,
via internal transformerMaximum start-up current (Un)*Standard unit
A 104.6 102.6 131.0 171.0 191.0 154.5 221.5Unit with electronic
starter option A 56.1 55.1 70.0 90.8 101.2 101.5 142.5Unit power
factor at maximum capacity** 0.82 0.82 0.82 0.82 0.82 0.82
0.82Maximum unit power input** kW 8.7 11.6 12.9 14.6 16.8 25.8
33.7Nominal unit current draw*** A 14.3 16.9 20.2 23.2 27.9 39.7
55.1Maximum unit current draw (Un)**** A 16.1 21.3 24.1 27.1 31.1
47.5 61.5Maximum unit current draw (Un-10%) A 21.1 28.4 32.2 36.4
42.0 63.7 83.3Customer-side unit power reserve Customer reserve at
the 24 V control power circuitShort-circuit stability and
protection See table on the next page
* Maximum instantaneous start-up current (maximum operating
current of the compressor + fan current + locked rotor current of
the compressor). ** Power input, compressor and fan, at the unit
operating limits (saturated suction temperature 10C, saturated
condensing temperature 65C) and nominal voltage of 400 V (data
given on the unit
nameplate). *** Standardised Eurovent conditions: condenser
entering/leaving water temperature = 40C/45C, outside air
temperature db/wb = 7C/6C. **** Maximum unit operating current at
maximum unit power input and 400 V (values given on the unit
nameplate). Maximum unit operating current at maximum unit power
input and 360 V.
5
-
Short-circuit stability current, main disconnect without fuse
(TN system*) 61AF - standard unit (main disconnect switch) 022 030
035 045 055 075 105Value with unspecified upstream
protectionShort-term current at 1 s (Icw) kA rms 0.6 0.6 0.6 1.26
1.26 1.26 2Admissible peak current (Ipk) kA pk 4.5 4.5 4.5 6 6 6
10Maximum value with upstream protection by Siemens circuit
breakerConditional short-circuit current (Icc) kA rms 5.4 7 7 7.7
7.7 6.1 10Siemens circuit breaker - Compact range 32 40 40 50 63 80
100Reference number** 5SY6332-7 5SY6340-7 5SY6340-7 5SY4350-7
5SY4363-8 5SP4380-7 5SP4391-7Maximum value with upstream protection
by fuses (gL/gG)Conditional short-circuit current (Icc) kA rms 17
50 50 50 50 14.5 22Siemens fuse (gL/gG) 40 40 40 63 63 80 125
* Earthing system type ** If another current limitation
protection system is used, its time-current and thermal constraint
(It) trip characteristics must be at least equivalent to those of
the recommended Siemens circuit
breaker. Contact your nearest Carrier office. The short-circuit
stability current values above are in accordance with the TN
system.
20
25
30
35
40
45
50
55
60
65
70
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45Entering air
temperature, C
Leav
ing
wat
er te
mpe
ratu
re,
C
Plate heat exchanger water flow rate61AF Flow rate, l/s
Minimum Maximum*with hydronic module
Maximum**without hydronic module
022 0.4 1.6 1.8030 0.5 1.7 2.4035 0.7 3.3 3.1045 0.8 3.3 3.8055
0.9 3.2 4.6075 1.2 5.9 6.4105 1.6 6.1 8.5
* Maximum flow rate at an available pressure of 15 kPa. **
Maximum flow rate at a water temperature difference of 3 K in the
plate heat exchanger.
Note: For a domestic hot water application (leaving water
temperature = 65C), the water temperature difference must be at
least 8 K.
Full load
Operating range61AF Minimum MaximumCondenserEntering water
temperature at start-up C 8 57Leaving water temperature during
operation C 30 65Entering/leaving water temperature difference K 3
**EvaporatorEntering air temperature, standard unit* C -20
40Entering air temperature, unit with option 11 C -15 40
* Outside temperature: For transport and storage of the 61AF
units the minimum and maximum allowable temperatures are -20C and
+50C. It is recommended that these temperatures are used for
transport by container.
** Refer to the minmum unit flow rate.
Note: Do not exceed the maximum operating temperature.
Operating limits
6
-
Dimensions/clearances61AF 022-035 units with and without
hydronic module
Legend
All dimensions are in mm
Required clearances for air flow
Recommended space for maintenance
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
Power cable connection61AF 045-055 units with and without
hydronic module
NOTES:A Non-certified drawings. Refer to the certified
dimensional drawings
supplied with the unit or available on request, when designing
an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity refer to the
certified dimensional drawings.
B In multiple-unit installations (maximum four units), the side
clearance between the units should be increased from 1000 to 2000
mm.
C The height of the solid surface must not exceed 2 m.
1000
1000
1000
1000
13271110
1330
300
1114
1000
1000
1000
1000
2100
1330
300
7
-
1000
1000
1000
1000
1330
2100
2053
300
2261
2273
1
1
1
2
Dimensions/clearances (continued)61AF 075-105 units with and
without hydronic module
Legend
All dimensions are in mm
Required clearances for air flow
Recommended space for maintenance
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
Power cable connection
NOTES:A Non-certified drawings. Refer to the certified
dimensional drawings
supplied with the unit or available on request, when designing
an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity refer to the
certified dimensional drawings.
B In multiple-unit installations (maximum four units), the side
clearance between the units should be increased from 1000 to 2000
mm.
C The height of the solid surface must not exceed 2 m.
8
-
Heating capacities
Application data Standard units, refrigerant R407CCondenser
entering/leaving water temperature difference: 5 K for EWT <
55CCondenser entering/leaving water temperature difference: 10 K
for EWT 55CCondenser fluid: waterRelative humidity: 87%Fouling
factor: 0 (m2 K)/W - 0.18 x10-4 (m2 K)/W
Performances in accordance with EN 14511
Outside air temperature, C-20 -15 -10 -5 0 2 5
61AF EWT Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap
Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp
C kW kW l/s kPa kW kW l/s kPa kW kW l/s kPa kW kW l/s kPa kW kW
l/s kPa kW kW l/s kPa kW kW l/s kPa022 25 10.2 4.80 0.49 1 12.1
4.80 0.58 2 13.9 4.80 0.67 2 15.9 4.80 0.76 3 18.0 4.60 0.87 4 19.0
4.60 0.91 4 20.4 4.60 0.98 5030 10.1 5.70 0.58 1 13.1 5.70 0.58 1
16.0 5.70 0.77 2 19.0 5.80 0.91 3 21.9 5.60 1.05 3 23.2 5.60 1.11 4
25.2 5.70 1.21 4035 15.6 6.60 0.75 1 18.1 6.80 0.87 2 21.0 6.90
1.01 3 24.3 7.00 1.16 3 27.7 6.90 1.33 4 29.2 7.00 1.40 5 31.6 7.00
1.52 5045 20.0 8.50 0.96 1 24.4 8.70 1.17 3 28.5 9.00 1.37 3 33.1
9.20 1.59 5 38.1 9.10 1.83 6 40.1 9.10 1.93 6 41.3 9.00 1.98 7055
25.6 9.40 1.23 2 29.9 10.0 1.43 3 34.5 10.4 1.66 4 39.8 10.7 1.91 5
45.3 10.8 2.17 6 47.5 10.8 2.28 6 50.3 10.9 2.42 7075 32.0 14.0
1.54 2 37.6 14.4 1.80 3 43.8 14.7 2.10 4 50.7 14.9 2.44 5 58.3 14.7
2.80 7 61.6 14.8 2.96 7 63.1 14.8 3.03 8105 47.6 19.3 2.29 4 54.9
19.9 2.64 5 64.0 20.4 3.08 6 74.1 20.9 3.56 8 85.4 21.2 4.10 11
90.2 21.2 4.33 12 97.6 21.7 4.69 14022 30 9.8 5.20 0.47 1 11.8 5.20
0.57 2 13.9 5.20 0.67 2 15.8 5.20 0.76 3 17.9 4.90 0.86 3 18.8 4.90
0.90 4 20.2 4.90 0.97 4030 10.2 5.90 0.49 1 13.1 6.00 0.62 1 15.9
6.00 0.76 2 18.8 6.10 0.91 3 21.7 6.00 1.04 3 22.9 6.10 1.10 4 24.8
6.10 1.19 4035 15.7 7.10 0.76 1 18.2 7.30 0.87 2 20.9 7.50 1.01 2
24.1 7.60 1.16 3 27.5 7.60 1.32 4 29.0 7.60 1.39 4 31.2 7.70 1.50
5045 18.7 9.10 0.89 1 23.4 9.30 1.12 3 28.2 9.60 1.36 3 32.7 9.80
1.57 4 37.6 9.80 1.81 6 39.6 9.80 1.90 6 41.8 9.80 2.01 7055 25.6
10.0 1.23 2 29.8 10.6 1.43 3 34.4 11.1 1.65 4 39.5 11.5 1.90 5 45.0
11.7 2.16 6 47.2 11.7 2.27 6 50.4 11.8 2.43 7075 31.8 14.9 1.53 2
37.3 15.4 1.79 3 43.4 15.8 2.09 4 50.3 16.1 2.42 5 57.8 16.0 2.78 6
61.0 16.0 2.93 7 63.8 16.1 3.07 8105 47.8 20.6 2.30 3 55.1 21.4
2.65 5 63.9 22.0 3.07 6 73.9 22.6 3.55 8 84.9 22.9 4.09 10 89.7
23.0 4.31 12 97.2 23.4 4.67 13022 35 10.0 5.50 0.48 1 11.9 5.50
0.57 2 13.9 5.50 0.67 2 15.7 5.60 0.76 3 17.8 5.30 0.86 3 18.6 5.30
0.90 4 20.0 5.30 0.96 4030 10.4 6.20 0.50 1 13.2 6.30 0.63 1 15.9
6.40 0.76 2 18.7 6.60 0.90 2 21.5 6.50 1.03 3 22.7 6.50 1.09 4 24.6
6.60 1.18 4035 15.9 7.70 0.77 1 18.3 7.90 0.88 2 21.0 8.10 1.01 2
24.0 8.30 1.16 3 27.4 8.20 1.32 4 28.8 8.30 1.39 4 30.9 8.40 1.49
5045 18.7 9.60 0.89 1 23.3 9.90 1.11 3 28.0 10.2 1.35 3 32.3 10.5
1.56 4 37.2 10.6 1.79 5 39.1 10.6 1.88 6 42.1 10.7 2.03 7055 25.7
10.6 1.24 2 29.8 11.3 1.44 3 34.3 11.9 1.65 3 39.3 12.3 1.89 4 44.7
12.6 2.16 6 46.9 12.6 2.26 6 50.2 12.8 2.42 7075 31.7 15.9 1.53 2
37.1 16.4 1.79 3 43.2 16.9 2.08 4 49.9 17.4 2.41 5 57.3 17.3 2.76 6
60.5 17.5 2.91 7 64.7 17.6 3.12 8105 48.1 22.0 2.32 3 55.4 23.0
2.67 5 64.0 23.8 3.08 6 73.8 24.5 3.56 8 84.7 24.9 4.08 10 89.4
25.0 4.31 11 96.8 25.4 4.66 13022 40 10.1 5.90 0.48 1 12.0 5.90
0.58 2 14.0 6.00 0.67 2 15.8 6.00 0.76 3 17.7 5.80 0.86 3 18.6 5.80
0.90 4 19.9 5.80 0.96 4030 9.5 6.60 0.45 1 12.5 6.70 0.60 1 15.4
6.90 0.74 2 18.4 7.20 0.88 2 21.4 7.10 1.03 3 22.5 7.10 1.09 3 24.4
7.20 1.18 4035 16.1 8.30 0.78 1 18.5 8.60 0.89 2 21.1 8.80 1.02 2
24.0 9.00 1.16 3 27.3 9.00 1.32 4 28.6 9.00 1.38 4 30.7 9.10 1.48
5045 19.1 10.3 0.91 1 23.5 10.6 1.12 3 27.9 11.0 1.35 3 32.1 11.3
1.55 4 36.7 11.5 1.77 5 38.7 11.5 1.87 6 41.7 11.7 2.01 6055 25.9
11.5 1.25 2 30.0 12.2 1.45 3 34.4 12.8 1.66 3 39.2 13.3 1.89 4 44.6
13.6 2.15 5 46.7 13.6 2.25 6 50.0 13.9 2.41 7075 31.7 17.0 1.53 2
37.1 17.6 1.79 3 43.0 18.2 2.08 4 49.7 18.8 2.40 5 57.0 18.8 2.75 6
60.1 19.0 2.90 7 65.0 19.3 3.13 8105 48.5 23.5 2.34 3 55.9 24.7
2.70 5 64.4 25.8 3.11 6 74.0 26.7 3.57 8 84.8 27.1 4.09 10 89.4
27.3 4.31 11 96.6 27.8 4.66 13022 45 10.4 6.30 0.50 1 12.2 6.40
0.58 2 14.1 6.50 0.68 2 15.9 6.50 0.77 3 17.8 6.40 0.86 3 18.6 6.40
0.90 4 19.9 6.40 0.96 4030 9.3 7.10 0.44 1 12.3 7.30 0.59 1 15.3
7.40 0.73 2 18.3 7.80 0.88 2 21.4 7.70 1.03 3 22.5 7.80 1.09 3 24.3
7.90 1.17 4035 15.9 9.00 0.76 1 18.7 9.30 0.90 2 21.2 9.50 1.03 2
24.1 9.70 1.16 3 27.2 9.70 1.32 4 28.6 9.80 1.38 4 30.6 10.0 1.48
5045 17.0 11.1 0.81 1 21.8 11.5 1.04 3 28.0 11.9 1.35 3 32.0 12.3
1.55 4 36.5 12.4 1.76 5 38.4 12.6 1.86 5 41.3 12.7 2.00 6055 25.8
12.7 1.23 2 30.4 13.3 1.47 3 34.7 13.9 1.67 3 39.3 14.3 1.90 4 44.5
14.7 2.15 5 46.7 14.8 2.26 6 49.8 15.0 2.41 6075 31.8 18.1 1.54 2
37.1 18.9 1.79 3 43.1 19.7 2.08 4 49.6 20.3 2.40 5 56.8 20.5 2.75 6
59.9 20.7 2.89 7 64.7 21.1 3.13 8105 49.0 25.0 2.37 3 56.6 26.6
2.73 5 64.9 27.9 3.14 6 74.5 29.0 3.60 8 85.0 29.7 4.11 10 89.6
29.9 4.33 11 96.8 30.4 4.67 13022 50 10.7 6.80 0.51 1 12.5 6.90
0.60 2 14.3 7.00 0.69 2 16.1 7.10 0.78 3 18.0 7.00 0.87 3 18.7 7.00
0.91 4 19.9 7.00 0.97 4030 10.5 7.60 0.50 1 13.2 7.90 0.63 1 16.0
8.10 0.76 2 18.8 8.50 0.90 2 21.5 8.50 1.04 3 22.6 8.60 1.09 3 24.3
8.70 1.18 4035 16.3 9.70 0.78 1 18.9 10.0 0.92 2 21.4 10.3 1.04 2
24.2 10.5 1.17 3 27.2 10.6 1.32 4 28.6 10.7 1.38 4 30.5 10.9 1.48
4045 18.9 12.1 0.90 1 23.3 12.5 1.11 3 27.7 12.8 1.32 3 32.1 13.3
1.55 4 36.4 13.6 1.76 5 38.2 13.7 1.85 5 41.1 13.9 1.99 6055 26.6
14.1 1.27 2 31.0 14.6 1.50 3 35.1 15.2 1.70 3 39.6 15.6 1.92 4 44.6
16.0 2.16 5 46.7 16.1 2.26 6 49.8 16.4 2.41 6075 32.0 19.4 1.55 2
37.3 20.4 1.81 3 43.2 21.2 2.09 4 49.7 22.0 2.41 5 56.8 22.3 2.75 6
59.8 22.6 2.90 6 64.6 23.0 3.13 7105 49.7 26.7 2.41 3 57.5 28.7
2.78 5 65.7 30.3 3.18 6 75.3 31.7 3.65 8 85.7 32.6 4.15 10 90.1
32.9 4.36 11 97.2 33.5 4.71 12022 55 - - - - - - - - 14.9 8.30 0.36
1 16.7 8.50 0.41 1 18.5 8.40 0.45 1 19.2 8.50 0.47 1 20.4 8.50 0.49
1030 - - - - - - - - 16.6 9.60 0.40 1 19.2 10.2 0.46 1 21.9 10.2
0.52 1 23.0 10.3 0.56 1 24.6 10.5 0.60 1035 - - - - - - - - 20.9
12.1 0.50 1 24.1 12.4 0.58 1 27.3 12.4 0.65 1 28.6 12.5 0.70 1 30.6
12.7 0.74 1045 - - - - - - - - 28.7 15.3 0.68 1 32.7 15.9 0.79 1
36.6 16.1 0.89 1 38.4 16.3 0.93 1 41.1 16.6 1.00 2055 - - - - - - -
- 36.6 18.4 0.89 1 40.2 18.7 0.96 1 45.2 19.1 1.08 1 47.2 19.2 1.15
2 50.3 19.5 1.22 2075 - - - - - - - - 43.9 24.3 1.07 1 50.3 25.2
1.22 1 57.2 25.7 1.39 2 60.2 26.0 1.46 2 64.8 26.5 1.57 2105 - - -
- - - - - 67.7 34.6 1.64 2 77.2 36.4 1.87 2 87.5 37.5 2.12 3 91.9
37.9 2.23 3 98.6 38.6 2.39 3
Legend EWT Entering water temperatureCap kW Heating capacity
Unit kW Unit power input Flow l/s Condenser water flow rateDp kPa
Condenser pressure drop
9
-
Heating capacitiesOutside air temperature, C7 10 15 20 25 30
35
61AF EWT Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap
Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp Cap Unit Flow Dp
C kW kW l/s kPa kW kW l/s kPa kW kW l/s kPa kW kW l/s kPa kW kW
l/s kPa kW kW l/s kPa kW kW l/s kPa022 25 21.5 4.60 1.03 5 23.0
4.60 1.11 6 23.2 4.60 1.11 6 23.2 4.60 1.11 6 23.2 4.50 1.11 6 23.2
4.50 1.11 6 23.2 4.50 1.11 6030 26.5 5.70 1.27 5 28.6 5.70 1.37 6
32.1 5.70 1.54 7 35.3 5.60 1.70 8 38.7 5.90 1.85 10 42.1 5.70 2.01
12 42.1 5.70 2.01 12035 33.3 7.10 1.60 6 36.0 7.20 1.73 7 40.4 7.30
1.94 8 38.2 7.40 1.83 7 39.6 7.50 1.89 8 41.8 7.60 2.00 9 41.8 7.60
2.00 9045 42.8 9.10 2.04 7 44.6 9.10 2.13 8 47.8 9.20 2.28 9 50.9
9.30 2.43 10 54.0 9.40 2.58 11 57.1 9.50 2.73 13 57.1 9.50 2.73
13055 51.4 10.9 2.47 7 52.4 10.9 2.50 8 55.1 11.0 2.63 8 58.9 11.1
2.81 10 62.7 11.2 2.99 11 66.5 11.3 3.18 12 66.5 11.3 3.18 12075
64.1 14.8 3.08 8 66.2 14.8 3.18 9 69.7 14.8 3.35 9 73.3 14.9 3.52
10 76.9 14.9 3.70 11 80.6 14.9 3.87 12 84.3 14.9 4.05 13105 102
21.9 4.90 15 109 22.3 5.23 17 121 23.2 5.81 21 123 23.3 5.92 22 126
23.4 6.03 22 128 23.6 6.14 23 130 23.7 6.25 24022 30 21.2 4.90 1.02
5 22.8 4.90 1.09 5 23.5 4.90 1.13 6 23.5 4.90 1.13 6 23.5 4.90 1.13
6 23.5 4.90 1.13 6 23.5 4.90 1.13 6030 26.1 6.10 1.26 5 28.1 6.10
1.35 5 31.7 6.20 1.53 7 34.9 6.20 1.68 8 38.4 6.40 1.84 10 41.8
6.50 2.00 11 41.8 6.50 2.00 11035 32.8 7.70 1.58 6 35.4 7.80 1.70 6
39.8 8.00 1.92 8 42.9 8.10 2.05 9 46.2 8.30 2.21 10 50.4 8.40 2.41
12 50.4 8.40 2.41 12045 43.6 9.90 2.08 7 46.1 9.90 2.20 8 50.2 10.1
2.40 10 54.4 10.2 2.60 11 58.6 10.3 2.80 13 62.8 10.4 3.00 15 62.8
10.4 3.00 15055 51.9 11.9 2.49 7 53.2 12.0 2.54 8 56.7 12.2 2.71 9
61.2 12.3 2.92 10 65.7 12.5 3.14 12 70.2 12.7 3.35 13 70.2 12.7
3.35 13075 64.7 16.1 3.11 8 66.7 16.2 3.21 8 70.1 16.2 3.37 9 73.7
16.3 3.55 10 77.3 16.3 3.72 11 81.0 16.4 3.90 12 84.7 16.4 4.07
13105 102 23.6 4.89 15 108 24.0 5.20 16 120 24.8 5.76 20 124 25.1
5.99 21 127 25.2 6.10 22 129 25.3 6.21 23 131 25.5 6.32 24022 35
20.9 5.30 1.01 5 22.5 5.40 1.08 5 23.9 5.40 1.15 6 23.9 5.30 1.15 6
23.9 5.30 1.15 6 23.9 5.30 1.15 6 23.9 5.30 1.15 6030 25.9 6.70
1.25 4 27.8 6.70 1.34 5 31.3 6.80 1.51 6 34.6 6.80 1.67 8 38.1 7.10
1.82 9 41.5 7.20 1.98 11 41.5 7.20 1.98 11035 32.5 8.50 1.56 5 35.0
8.60 1.68 6 39.3 8.70 1.90 7 42.3 8.90 2.02 8 45.5 9.10 2.17 10
49.6 9.20 2.37 12 49.6 9.20 2.37 12045 44.1 10.8 2.11 7 47.0 10.8
2.25 8 52.0 11.0 2.48 10 56.9 11.1 2.72 12 61.9 11.2 2.96 14 66.9
11.3 3.19 17 66.9 11.3 3.19 17055 52.0 12.9 2.51 7 53.5 13.1 2.56 8
57.3 13.3 2.74 9 62.2 13.6 2.97 10 67.1 13.8 3.21 12 72.0 14.1 3.44
14 72.0 14.1 3.44 14075 65.6 17.7 3.16 8 67.3 17.7 3.24 8 70.8 17.8
3.41 9 74.3 17.9 3.58 10 77.8 18.0 3.75 11 81.5 18.0 3.93 12 85.2
18.1 4.10 13105 102 25.7 4.90 14 108 26.1 5.20 16 119 26.8 5.73 19
126 27.3 6.07 21 128 27.4 6.18 22 130 27.5 6.29 23 133 27.6 6.40
24022 40 20.8 5.80 1.00 4 22.3 5.80 1.07 5 24.4 5.80 1.18 6 24.4
5.80 1.18 6 24.4 5.80 1.18 6 24.4 5.80 1.18 6 24.4 5.80 1.18 6030
25.7 7.30 1.24 4 27.6 7.30 1.33 5 30.9 7.40 1.49 6 34.4 7.50 1.66 7
37.8 7.80 1.81 9 41.2 8.00 1.97 11 41.2 8.00 1.97 11035 32.2 9.20
1.55 5 34.6 9.30 1.67 6 38.9 9.50 1.88 7 41.8 9.70 2.00 8 45.0 9.90
2.15 9 49.0 10.1 2.34 11 49.0 10.1 2.34 11045 43.6 11.8 2.08 7 46.6
11.9 2.22 8 51.5 12.1 2.46 10 56.4 12.3 2.69 12 61.3 12.5 2.93 14
66.2 12.7 3.16 16 66.2 12.7 3.16 16055 52.2 14.0 2.52 7 53.8 14.2
2.57 8 58.0 14.5 2.77 9 63.2 14.9 3.02 10 68.4 15.2 3.27 12 73.7
15.6 3.52 14 73.7 15.6 3.52 14075 66.7 19.4 3.22 8 68.1 19.4 3.28 8
71.6 19.5 3.45 9 75.1 19.7 3.62 10 78.6 19.8 3.79 11 82.2 19.9 3.97
12 85.9 20.0 4.14 13105 102 28.1 4.90 14 108 28.5 5.22 16 119 29.2
5.74 19 128 29.8 6.17 22 130 30.0 6.27 22 132 30.1 6.38 23 135 30.2
6.49 24022 45 20.8 6.40 1.00 4 22.1 6.40 1.07 5 24.7 6.40 1.19 6
24.9 6.40 1.21 6 24.9 6.40 1.21 6 24.9 6.40 1.21 6 24.9 6.40 1.21
6030 25.5 8.00 1.23 4 27.4 8.10 1.33 5 30.7 8.20 1.49 6 34.3 8.40
1.66 7 37.6 8.70 1.80 9 41.1 8.90 1.96 10 41.1 8.90 1.96 10035 32.0
10.1 1.55 5 34.3 10.2 1.66 6 38.5 10.4 1.86 7 41.2 10.6 1.97 8 44.2
10.9 2.11 9 48.1 11.1 2.30 11 48.1 11.1 2.30 11045 43.3 12.8 2.07 7
46.2 13.0 2.21 8 51.1 13.3 2.44 9 55.9 13.6 2.67 11 60.8 13.9 2.90
13 65.6 14.1 3.14 15 65.6 14.1 3.14 15055 52.0 15.2 2.51 7 53.6
15.4 2.56 7 57.5 15.8 2.75 8 62.6 16.2 2.99 10 67.7 16.6 3.23 12
72.8 16.9 3.48 13 72.8 16.9 3.48 13075 67.8 21.3 3.28 8 69.3 21.3
3.35 9 72.5 21.5 3.50 9 76.1 21.7 3.68 10 79.6 21.8 3.85 11 83.2
22.0 4.02 12 86.9 22.1 4.20 13105 102 30.8 4.92 14 109 31.3 5.25 16
120 32.1 5.77 19 130 32.8 6.29 22 132 33.0 6.40 23 135 33.1 6.51 23
137 33.3 6.62 24022 50 20.8 7.10 1.01 4 22.1 7.10 1.07 5 24.5 7.10
1.19 6 25.6 7.10 1.24 6 25.6 7.10 1.24 6 25.6 7.10 1.24 6 25.6 7.00
1.24 6030 25.5 8.80 1.23 4 27.4 8.90 1.33 5 30.6 9.10 1.48 6 34.1
9.30 1.65 7 37.3 9.60 1.78 8 40.7 9.90 1.94 10 40.7 9.90 1.94 10035
31.9 11.0 1.55 5 34.1 11.1 1.65 5 38.1 11.4 1.84 7 40.6 11.6 1.94 7
43.5 11.8 2.08 8 47.1 12.1 2.25 10 47.1 12.1 2.25 10045 43.1 14.1
2.06 6 45.9 14.3 2.19 7 50.7 14.6 2.42 9 55.5 15.0 2.65 11 60.3
15.3 2.88 13 65.0 15.7 3.11 15 65.0 15.7 3.11 15055 51.9 16.5 2.52
7 53.4 16.8 2.55 7 57.2 17.2 2.74 8 62.2 17.6 2.97 10 67.1 18.0
3.21 11 72.1 18.4 3.44 13 72.1 18.4 3.44 13075 67.9 23.3 3.29 8
70.8 23.5 3.43 9 73.7 23.7 3.57 9 77.3 23.9 3.74 10 80.9 24.2 3.91
11 84.5 24.4 4.09 12 88.1 24.6 4.27 13105 102 33.9 4.94 14 110 34.5
5.31 16 120 35.4 5.82 19 132 36.3 6.37 22 135 36.5 6.55 23 138 36.7
6.66 24 140 36.9 6.77 25022 55 21.1 8.60 0.51 1 22.4 8.60 0.54 1
24.5 8.70 0.60 2 26.9 8.70 0.65 2 27.1 8.70 0.66 2 27.1 8.70 0.66 2
27.1 8.70 0.66 2030 25.7 10.6 0.62 1 27.4 10.8 0.67 1 30.6 11.1
0.74 2 33.8 11.3 0.82 2 37.0 11.7 0.88 2 40.2 12.0 0.96 3 40.2 12.0
0.96 3035 31.8 12.9 0.77 1 33.9 13.0 0.82 2 37.4 13.3 0.91 2 39.7
13.6 0.95 2 42.2 14.0 1.01 2 45.5 14.3 1.09 3 45.5 14.3 1.09 3045
42.8 16.8 1.02 2 45.5 17.0 1.09 2 49.9 17.5 1.19 2 54.3 17.9 1.30 3
58.7 18.4 1.40 3 63.1 18.8 1.51 4 63.1 18.8 1.51 4055 52.3 19.6
1.27 2 53.6 19.9 1.28 2 57.3 20.3 1.37 2 62.1 20.7 1.48 3 66.9 21.1
1.60 3 71.6 21.5 1.71 3 71.6 21.5 1.71 3075 68.0 26.8 1.65 2 73.1
27.2 1.77 2 75.8 27.4 1.84 3 79.4 27.6 1.93 3 83.0 27.9 2.01 3 86.6
28.1 2.10 3 90.2 28.3 2.19 4105 103 39.1 2.51 4 111 39.6 2.69 4 122
40.4 2.96 5 133 41.2 3.23 6 139 41.6 3.38 6 142 41.7 3.44 7 144
41.8 3.49 7
Legend EWT Entering water temperatureCap kW Heating capacity
Unit kW Unit power input Flow l/s Condenser water flow rateDp kPa
Condenser pressure drop
Application data Standard units, refrigerant R407CCondenser
entering/leaving water temperature difference: 5 K for EWT <
55CCondenser entering/leaving water temperature difference: 10 K
for EWT 55CCondenser fluid: waterRelative humidity: 87%Fouling
factor: 0 (m2 K)/W - 0.18 x10-4 (m2 K)/W
Performances in accordance with EN 14511
10
-
Hydronic module (option 116)Typical hydronic circuit diagramThe
hydronic module option reduces the installation time.
The heat pump is factory-equipped with the main hydronic
components required for the installation: screen filter, water
pump, safety valve, water pressure transducer, flow switch. The
Pro-Dialog+ control allows integration of system and water pump
protection devices (insufficient water flow rate, water pressure,
water flow rate etc.).
The pump supplied with the hydronic module is a multi-speed
pump.
An automatic pump start-up algorithm protects the heat exchanger
and the hydronic module piping against frost down to -10C outside
air temperature, as standard. If necessary, increased frost
protection down to -20 C is possible by adding heaters to the
hydronic module piping (see option 42).
The hydronic module option is integrated into the heat pump
without increasing its dimensions and saves the space normally used
for the water pump.
Legend
Components of the unit and hydronic module1 Victaulic screen
filter2 Pressure sensor Note: Gives pump suction pressure
information (see installation manual)3 Safety valve4 Water drain
valve 5 Shut-off valve6 Water pump7 Temperature sensors, BPHE inlet
Note: Gives heat exchanger entering temperature information (see
installation manual)8 Pressure gauge Note: Allows measuring of the
pump suction pressure, the pump leaving pressure and the
heat exchanger leaving pressure9 Temperature sensor, BPHE outlet
Note: Gives heat exchanger leaving temperature information (see
installation manual)10 Automatic air vent 11 Flow switch12 Plate
heat exchanger frost protection heater13 Plate heat exchanger
Installation components14 Temperature probe well15 Air vent16
Flexible connection17 Shut-off valve18 Screen filter (obligatory
for a unit without hydronic module)19 Pressure gauge20 Water flow
control valve21 Charge valve22 Frost protection bypass valve (when
shut-off valves [17] are closed during winter)
--- Hydronic module (unit with hydronic module)
Notes: Units without hydronic module (standard units) are
equipped with a flow switch and two
temperature sensors (7 and 9). For units equipped with hydronic
module, the pressure sensor located upstream of the pump
to prevent cavitation is installed on a connection without
Schraeder valves. Depressurise and drain the system before any
intervention.
Physical and electrical data, units with hydronic module 61AF
022 030 035 045 055 075 105Operating weight*Unit with hydronic
module kg 349 403 436 524 549 926 1044Hydronic moduleMaximum
operating pressure kPa 400 400 400 400 400 400 400Water filter
Victaulic screen filterPumpsWater pump TOP-S 25 TOP-S 25 TOP-S40
TOP-S40 TOP-S40 TOP-S50 TOP-S50Shaft power input kW 0.18 0.18 0.35
0.35 0.35 0.45 0.45Power input** kW 0.42 0.42 0.63 0.63 0.63 0.95
0.95Nominal operating current draw A 0.4 0.4 0.6 0.6 0.7 1.3
1.5Maximum current draw at 400 V*** A 0.8 0.8 1.3 1.3 1.3 1.7
1.7Water connections (with hydronic module)Connections inch 1-1/4
1-1/4 1-1/2 1-1/2 1-1/2 2 2Outside diameter mm 42.4 42.4 48.3 48.3
48.3 60.3 60.3
* Weight shown is a guideline only. To find out the unit
refrigerant charge, please refer to the unit nameplate. ** To
obtain the maximum power input for a unit with hydronic module, add
the maximum unit power input to the pump power input. *** To obtain
the maximum operating current draw for a unit with hydronic module,
add the maximum unit current draw to the pump current draw.
1
21
19
19
22
17
17
14
14
15
16
16
20
18
11 10 9
23 6 7
5
124
8
4
5
5
134
Hydronic module
11
-
Units with fans with available pressure for indoor installation
(option 11)This option applies to 61AF units installed inside the
building in a plant room. For this type of installation the cold
air leaving the air-cooled evaporators is discharged by the fans to
the outside of the building, using a duct system.
The installation of a duct system at the air evaporator
discharge line causes a pressure drop due to the resistance caused
by the air flow.
Therefore more powerful fan motors than those used for the
standard units are installed in the units with this option. For
each installation of a unit installed inside a plant room the duct
pressure drops differ, depending on the duct length, duct section
and direction changes. 61AF units equipped with fans with available
pressure are designed to operate with air discharge ducts with
maximum pressure drops of 100 Pa.
Fan discharge connection A square flange is supplied mounted on
the unit. An available standard round flange can easily be
installed at the fan discharge, if the installer prefers the use of
a round connection duct.
The unit is supplied with a grille on the discharge side. This
grille has to be removed before connection to the duct system.
It is advisable to make the connection to the duct system with a
flexible sleeve. If this recommendation is not observed, a lot of
vibration and noise may be transmitted to the building
structure.
Applicable rules for units incorporated into an air duct
system
Ensure that the suction or discharge inlets are not
accident-ally obstructed by the panel positioning (e.g. low return
or open doors etc.).
Electrical data for 61AF units with option 11
61AF - units with option 11 (without hydronic kit)
022 030 035 045 055 075 105
Power circuitNominal power supply V-ph-Hz 400-3-50Voltage range
V 360-440Control circuit supply 24 V, via internal
transformerMaximum start-up current (Un)*Standard unit A 107,1
105,1 133,5 173,5 193,5 159,5 226,5Unit with electronic starter
option A 58,6 57,6 72,5 93,3 103,7 106,5 147,5Unit power factor at
maximum capacity** 0,82 0,82 0,82 0,82 0,82 0,82 0,82Maximum unit
power input** kW 9,8 12,7 14 15,7 17,9 28 35,9Nominal unit current
draw*** A 16,4 19 22,3 25,3 30 43,9 59,3Maximum unit current draw
(Un)**** A 18,5 23,7 26,5 29,5 33,5 52,3 66,3Maximum unit current
draw (Un-10%) A 23,2 30,5 34,3 38,5 44,1 67,9 87,5Customer-side
unit power reserve Customer reserve at the 24 V control power
circuitShort-circuit stability and protection See table on page
6
* Maximum instantaneous start-up current (maximum operating
current of the compressor + fan current + locked rotor current of
the compressor). ** Power input, compressor and fan, at the unit
operating limits (saturated suction temperature 10C, saturated
condensing temperature 65C) and nominal voltage of 400 V (data
given on the unit
nameplate). *** Standardised Eurovent conditions: condenser
entering/leaving water temperature = 40C/45C, outside air
temperature db/wb = 7C/6C. **** Maximum unit operating current at
maximum unit power input and 400 V (values given on the unit
nameplate). Maximum unit operating current at maximum unit power
input and 360 V.
12
-
Dimensions/clearances, units with option 1161AF 022-035 units
with and without hydronic module
Legend
All dimensions are in mm
Required clearances for air flow
Recommended space for maintenance
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
Power cable connection
NOTES:A Non-certified drawings. Refer to the certified
dimensional drawings supplied with the unit or available on
request,
when designing an installation. For the location of fixing
points, weight distribution and coordinates of the centre of
gravity refer to the certified dimensional drawings.
B In multiple-unit installations (maximum four units), the side
clearance between the units should be increased from 1000 to 2000
mm.
C The height of the solid surface must not exceed 2 m.
1110
300
1280
1327
1371
2
2
1
1
1000
1000
1000
1000
13
-
Dimensions/clearances, units with option 11 (continued)61AF
045-055 units with and without hydronic module
NOTES:A Non-certified drawings. Refer to the certified
dimensional drawings supplied with the unit or available on
request,
when designing an installation. For the location of fixing
points, weight distribution and coordinates of the centre of
gravity refer to the certified dimensional drawings.
B In multiple-unit installations (maximum four units), the side
clearance between the units should be increased from 1000 to 2000
mm.
C The height of the solid surface must not exceed 2 m.
1114
300
1000
1000
1000
1000
2079
1371
1
1
2
2
Legend
All dimensions are in mm
Required clearances for air flow
Recommended space for maintenance
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
Power cable connection
14
-
Dimensions/clearances, units with option 11 (continued)61AF
075-105 units with and without hydronic module
NOTES:A Non-certified drawings. Refer to the certified
dimensional drawings supplied with the unit or available on
request,
when designing an installation. For the location of fixing
points, weight distribution and coordinates of the centre of
gravity refer to the certified dimensional drawings.
B In multiple-unit installations (maximum four units), the side
clearance between the units should be increased from 1000 to 2000
mm.
C The height of the solid surface must not exceed 2 m.
1371
2100 2273
300
1000
1000
1000
10001
1 2
2
Legend
All dimensions are in mm
Required clearances for air flow
Recommended space for maintenance
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
Power cable connection
15
-
Available static system pressurePlate heat exchanger pressure
drop - for pure water at 20C
Water flow rate, l/s
Pre
ssur
e dr
op, k
Pa
1 61AF 022 2 61AF 030 3 61AF 035 4 61AF 045
61AF 022-045
0
5
10
15
20
25
30
0 1 2 3 4 5
12
34
0
10
20
30
40
50
0 2 4 6 8 10
1
2
3
Water flow rate, l/sP
ress
ure
drop
, kPa
61AF 055-105
1 61AF 055 2 61AF 075 3 61AF 105
16
-
Water flow rate, l/s
Pre
sssu
re h
ead,
kPa
1 61AF 022-030 (speed 1) 2 61AF 022-030 (speed 2): selected 3
61AF 022-030 (speed 3)
Water flow rate, l/s
Pre
sssu
re h
ead,
kPa
1 61AF 035-055 (speed 1) 2 61AF 035-055 (speed 2): selected 3
61AF 035-055 (speed 3)
61AF Condenser water flow rate, l/s
Minimum Maximum*022 0.4 1.8030 0.5 2.4035 0.7 3.1045 0.8 3.8055
0.9 4.6075 1.1 6.4105 1.5 8.5
* Maximum flow rate at a water temperature difference of 3 K in
the plate heat exchanger (unit without hydronic module)
The 61AF units are equipped with a fixed-speed pump with three
different speeds.
These speeds can be manually adjusted by changing the speed
terminal board inside the terminal box (this operation can only be
carried out by approved personnel). The speed initially selected
corresponds to standard use for heating water loops. If this speed
needs to be changed, the pressure/flow curves for the three speeds
are shown below.
61AF 022-030 61AF 035-055
Pump pressure/flow rate curves for units with hydronic module -
for pure water at 20C
0
20
40
60
80
100
0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5
1
2
3
0
20
40
60
80
100
120
0 0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,01
1
2
3
0
20
40
60
80
100
120
0 0,4 0,8 1,2 1,6 2,0 2,4 2,8 3,2
1
2
3
61AF 075-105
Water flow rate, l/s
Pre
sssu
re h
ead,
kPa
1 61AF 075-105 (speed 1) 2 61AF 075-105 (speed 2): selected 3
61AF 075-105 (speed 3)
17
-
020
40
60
80
100
0,5 1,0 1,5 2,0 2,5 3,0 3,5
3
21
01020
304050
607080
90100
0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8
21
Water flow rate, l/s
Ava
ilabl
e pr
essu
re, k
Pa
Water flow rate, l/s
1 61AF 035 2 61AF 045 3 61AF 055
Ava
ilabl
e pr
essu
re, k
Pa
1 61AF 022 2 61AF 030
Available static system pressure (cont.)Available system
pressure for units with hydronic module - for pure water at 20C
The available pressure curves for the 61AF units are given for
the speed initially selected. If the speed is changed by the user,
the curves below do not apply.
61AF 022-030 61AF 035-055
0
20
40
60
80
100
1 2 3 4 5 6
1 2
61AF Condenser water flow rate, l/sMinimum Maximum*
022 0.4 1.6030 0.5 1.7035 0.7 3.3045 0.8 3.3055 0.9 3.2075 1.1
5.9105 1.5 8.5
* Maximum flow rate at an available pressure of 15 kPa (unit
with hydronic module).
Water flow rate, l/s
Ava
ilabl
e pr
essu
re, k
Pa
1 61AF 075 2 61AF 105
61AF 075-105
18
-
Order No.: 16110-20, 03.2011. Supersedes order No.: 16110-20,
10.2010. Manufactured by: Carrier SCS, Montluel,
France.Manufacturer reserves the right to change any product
specifications without notice. Printed in the Netherlands.The cover
photo is solely for illustration purposes and is not contractually
binding.
Carrier is participating in the Eurovent Certification Programme
for liquid chilling packages. Products are as listed in the
Eurovent Directory of Certified
Products or on the Internet site
www.eurovent-certification.com.