ISOLATIONS IN UPS SYSTEMS
When we speak of UPS isolation it is necessary to be veryprecise in what we understand under isolation in order to avoidmisunderstandings and misinterpretations. There are threetypes of distinct isolations in a UPS System
A) Galvanic Isolation between Input and OutputB) input isolation between Mains and BatteryC) Isolation between the DC-circuit and the UPS Output
8/3/2019 5.5 Isolation EDCP System 080224
3/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 3
C. DC - Component Output Isolation
a. TRANSFORMER-BASED TECHNOLOGY:
In transformer-based UPS-systems the transformer is usedto step up the voltage at the output of the inverter to avoltage compatible with the utility or generator supplyvoltage. Furthermore it is in the nature of the transformer toisolate DC components and therefore the invertertransformer isolates the DC-circuit from the output load.
ISOLATIONS IN UPS SYSTEMS
8/3/2019 5.5 Isolation EDCP System 080224
4/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 4
Figure 1 shows the block-diagram of a transformer-based,double conversion UPS-system. It can be seen from thedrawing that the transformer is on the output of the inverter
and not on the output of the UPS.
+
-
NeutralLine connectinginput and output (no
galvanic isolation betweeninput and output)
Inverter Output-Transformer tostep-up output voltage and blocks
DC-component
Static THYRISTORBypass-Switch
ISOLATIONS IN UPS SYSTEMS
8/3/2019 5.5 Isolation EDCP System 080224
5/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 5
There are two possibilities for the DC-component to pass fromthe UPS to the load when there is an inverter IGBT-fault or a
bypass THYRISTOR fault.
The transformer-based UPS behaves as follows in the two
cases:
a) Inverter IGBT-Fault
b) Bypass THYRISTOR Fault
ISOLATIONS IN UPS SYSTEMS
8/3/2019 5.5 Isolation EDCP System 080224
6/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 6
a) Inverter IGBT-Fault:
If for example the IGBT 2 of the inverter does not
conduct, a DC-component will be generated and in
the transformer-based UPS the output inverter
transformer will isolate the inverter DC-component
from the load.
ISOLATIONS IN UPS SYSTEMS
F1
F2
IGBT 1
IGBT 2
DC-component due toIGBT fault Transformer blocks DC-
component
8/3/2019 5.5 Isolation EDCP System 080224
7/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 7
b) Bypass THYRISTOR FaultIf for example one of the THYRISTORS does notconduct, a considerable DC-component will befeeding the load as the transformer does not isolatethe bypass. The transformer-based UPS does NOTcontrol this DC-component .
ISOLATIONS IN UPS SYSTEMS
+
-
THYRISTOR Notconducting
Static Switch DC-component passes uncontrolled tothe load
Inputsine-wave
8/3/2019 5.5 Isolation EDCP System 080224
8/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 8
C. DC - Component Output Isolation
b. TRANSFORMER-LESS TECHNOLOGY:
As the transformer-less UPS-technology does not provide
an inverter output transformer the DC-component issuemust be handled differently. The DC-component is blockedout the output so that it cannot be fed to the load byhardware and software regulation and control.
ISOLATIONS IN UPS SYSTEMS
8/3/2019 5.5 Isolation EDCP System 080224
9/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 9
Figure 2: Transformer-less UPS block diagram
ISOLATIONS IN UPS SYSTEMS
b. TRANSFORMER-LESS TECHNOLOGY:
The transformer-less UPS behaves as follows in the two
cases:a) Inverter IGBT-Fault
b) Bypass THYRISTOR Fault
8/3/2019 5.5 Isolation EDCP System 080224
10/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 10
ISOLATIONS IN UPS SYSTEMS
F1
F2
IGBT 1
IGBT 2
DC-component dueto IGBT fault
Transformer-less
EDCP-SYSTEM:ELECTRONICDC-PROTECTION SYSTEM
for blocking the DC to reach the load
a) Inverter IGBT-Fault:
If for example the IGBT 2 of the inverter does not conduct,
a DC-component will be generated. The transformer-less
UPS-technology handles the DC-component by means of
a fully redundant EDCP-SYSTEM (ELECTRONIC DC-
PROTECTION SYSTEM), so that probability of a DC-component appearing at the inverter output is practically
ZERO !
8/3/2019 5.5 Isolation EDCP System 080224
11/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 11
ISOLATIONS IN UPS SYSTEMS
b) Bypass THYRISTOR Fault:Furthermore the CONCEPTPOWER is provided with anadditional EDCP-SYSTEM on the bypass side, whichconsists of a SCR-non-conducting-detection-circuit.If one of the static bypass SCRs does not conduct the load
will automatically be transferred to inverter within 2-5msecin order to avoid the DC-component on the load side
DC-Detection and control
system that transfers theload to inverter
+
-THYRISTOR Not
conducting
Static Switch DC-component passesuncontrolled to the load
Inputsine-wave
Transformer-less
EDCP-SYSTEM:
ELECTRONICDC-PROTECTION SYSTEMfor blocking the DC to reach the load
8/3/2019 5.5 Isolation EDCP System 080224
12/13
Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 12
CONCLUSION:
With the advanced electronic technology the EDCP-SYSTEM isextremely reliable. The probability of a DC-component passing through atransformer-less EDCP-SYSTEM is not higher than a transformer going inshort circuit (and allowing the DC-component to pass).
With EDCP-SYSTEM also on the bypass side of the CONCEPTPOWERTransformer-less technology makes the overall protection from the DC-component on the inverter and bypass side more effective than justthrough a transformer on the inverter side
Furthermore NEWAVE has actually over 25000 3-phase transformer-less
UPS-systems in the market operating and being protected by theEDCP-SYSTEM and we have never had a single case of DC-componentappearing on the load.
ISOLATIONS IN UPS SYSTEMS