 Arthit Platform

Page 2: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 2/71

Type of Fire & Gas (F&G) detectors

Installation

 Voting philosophy 

 Automatic action by SIS (Safety Instrumented System)  Automatic action by Addressable Fire Panel (For

 ALQB)

F&G in Turbo Machinery Packages

Deluge System

Fire Water Pumps

Page 3: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 3/71

Flame Detector Fusible Plug Loop

Gas Detector (Point Type)

Gas Detector (Line of Sight)  VESDA (Very Early Smoke Detection Apparatus)

Smoke Detector

Heat Detector

Emergency Shutdown Pushbutton Manual Alarm Call point

Special

Page 4: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 4/71

Page 5: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 5/71

Page 6: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 6/71

Multi spectrum IR Flame Detector

Installation  All decks on APP

Field of View Distance 30 m.

90 degree horizontal

75 degree vertical

Page 7: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 7/71

One flame detector – alarm only 

 At least two flame detector in same fire zone  Activate ESD1 on APP

 Activate deluge valve in that fire zone Start fire water pumps

PAGA tone 2

Page 8: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 8/71

2oo27 Voting of flame detectors

Page 9: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 9/71

2oo2 Voting of flame detectors

Special Action Inhibit FWPs on APP to start Deluge valve NOT activated (no deluge in this fire zone)

Page 10: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 10/71

Page 11: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 11/71

Fusible plugs are fixed temperature heat detectors thatmelt at the required temperature.

Fire detection is due to loss of air/gas pressure in thefusible plug loop.

Melt point is 203 DegF (95 DegC) on AWPs

Melt point is 160 DegF (71 DegC) on APP

Page 12: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 12/71

Fusible plug melt on APP  Activate deluge valve in that fire zone Start fire water pumps (due to fire water ring main pressure

low)

Fusible plug melt on AWP1  Activate ESD1 on AWP1  Activate deluge valve to AWP1 Start fire water pumps (due to fire water ring main pressure

low)

Fusible plug melt on AWPs  Activate ESD1 on AWPs

Page 13: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 13/71

Special Fusible plugs were provided at each riser valve to directly 

close the valves when exposed to a fire.

Page 14: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 14/71

Page 15: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 15/71

Page 16: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 16/71

Page 17: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 17/71

The Deluge system is designed to protect high hazardareas containing a severe fuel hazard with a high heatrelease rate by bringing a large number of opensprayers into action simultaneously in the event of a

fire.

Page 18: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 18/71

P&ID

Page 19: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 19/71

5 Deluge valve for APP 2 for lower deck – always open together

 XV-5650 and XV-5660

2 for main deck – always open together  XV-5670 and XV-5680

1 for upper deck  XV-5690

1 Deluge valve for AWP1  XV-5640

Page 20: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 20/71

How many ways to activate deluge? Fusible plug melt

SIS energize solenoid when confirm fire

Manually press hand switch at local

Manually press push button in CCR 

Page 21: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 21/71

Special Manually press deluge push button in CCR will;

 Activate ESD1 on APP

Start fire water pumps

PAGA tone 2

Note: for AWP1 will be activate ESD1 on AWP1 only 

Page 22: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 22/71

Page 23: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 23/71

The Fire Water Manifold is pressurized at 10 barg by utility waterpumps. When the pressure drops to 6.5 barg or ConfirmedFire/Gas the first Fire Water Pump in the preset start sequencestarts. If the manifold pressure do not build to 10 barg in 30seconds, the second pump starts. If the manifold pressure still

does not reach 10 barg in another 30 seconds, the third pumpstarts. If 1st FW pump start and build pressure to 10 barg within 30s. 2nd

FW pump will not start But if the pressure drop below 10 barg after 30s. 2nd pump will start.

 After 2nd pump start, if pressure drop below 10 barg, 3rd pump willstart. (With 30 seconds delay after 2nd pump started)

This logic is to prevent FW pumps start consecutively within 30seconds

Page 24: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 24/71

Page 25: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 25/71

Page 26: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 26/71

Infrared Hydrocarbon Gas Detector

Installation  All decks on APP

Theory of Operation Certain IR wavelengths are absorbed by the gas

Page 27: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 27/71

Page 28: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 28/71

Page 29: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 29/71

Infrared Hydrocarbon Gas Detector Transmitter

Transmitter produces an intense, collimated infrared beam which is produced by a Xenon arc flash lamp.

Receiver Receiver collects infrared radiation from the transmitter and

performs measurements to enable hydrocarbon gases in thebeam path to be detected.

Installation  All decks on APP

Theory of Operation Certain IR wavelengths are absorbed by the gas

Page 30: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 30/71

One gas detector more than 20% LEL – alarm only 

In process area (within same fire zone) One gas detector more than 20% LEL

 And

One gas detector more than 60% LEL  Activate ESD1

Start fire water pumps

PAGA tone 2

Page 31: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 31/71

Inlet enclosure of turbo machinery (within same firezone) Two gas detector more than 40% LEL (2ooN)

 Activate ESD1

Start fire water pumps PAGA tone 2

Isolate essential power to turbo machinery package

Page 32: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 32/71

In HVAC air inlet LER, SWR (within same fire zone) Two gas detectors more than 40% LEL (2ooN)

 Activate ESD1

Start fire water pumps

PAGA tone 2 Trip HVAC, close fire dampers

Page 33: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 33/71

In LER, SWR (within same fire zone) Two gas detectors more than 40% LEL (2ooN)

 Activate ESD1

Start fire water pumps

PAGA tone 2 Trip HVAC, close fire dampers

Isolate battery of UPS and Battery Charger. (10 s delay) This will lead to black-out. SIS loss power. EDG can not start.

Gas detector in airlock is alarm only 

Page 34: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 34/71

 AQP Main deck One gas detector more than 20% LEL

 And

One gas detector more than 60% LEL  Activate ESD1 Inhibit AQP fire water pump to start

Start fire water pumps on APP

PAGA tone 2

Stop/Inhibit to start EDG Trip AQP HVAC

Page 35: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 35/71

 AQP HVAC air inlet Two gas detectors more than 40% LEL (2ooN)

 Activate ESD1

Inhibit AQP fire water pump to start

Start fire water pumps on APP PAGA tone 2

Stop/Inhibit to start EDG

Trip AQP HVAC

Isolate battery of AQP  All HMI in CCR will power loss

Page 36: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 36/71

 ALQB HVAC air inlet Two gas detectors more than 40% LEL (2ooN)

 Activate ESD1

Start fire water pumps

PAGA tone 2 Trip ALQB HVAC

Trip ALQB UPS and essential power

Page 37: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 37/71

Page 38: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 38/71

Turbo machinery package has “Eagle Quantum”controller as independent F&G system

No detectors voting

No ESD1

Page 39: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 39/71

Feed gas compressors Confirm fire by heat detector Confirm fire by flame detector (3s delay in “eagle quantum”

for confirmation) Shutdown FGC (with blowdown) Release CO2 for package

Release “main” CO2 then wait for 90 seconds. If fire still active, willrelease “reserve” CO2 

Start fire water pumps PAGA tone 2

Isolate all power to package Gas alarm at 5% LEL Confirm gas at 10% LEL

Same action as above except no CO2 release

Page 40: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 40/71

Sale gas compressors Confirm fire by heat detector Confirm fire by flame detector (5s delay in “flame

detector” for confirmation) 

Shutdown SGC (with blowdown) Release CO2 for package

Release “primary” and “extended” 

Start fire water pumps PAGA tone 2

Isolate all power package Gas alarm at 20% LEL Confirm gas at 40% LEL

Same action as above except no CO2 release

Page 41: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 41/71

Power Generators Confirm fire by heat detector Confirm fire by flame detector (5s delay in “flame

detector” for confirmation) 

Shutdown power generator Release CO2 for package

Release “primary” and “extended” 

Start fire water pumps PAGA tone 2

Isolate all power package Gas alarm at 20% LEL Confirm gas at 40% LEL

Same action as above except no CO2 release

Page 42: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 42/71

Page 43: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 43/71

Page 44: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 44/71

Page 45: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 45/71

 Very Early Smoke Detection Apparatus  Work by continually drawing air into the pipe network. The sample

enter to laser detection chamber for smoke detection

Installation  APP LER, APP SWR, APP ESWR, AQP SWR 

 Action  When fire alert  Alarm in CCR  Operator have to investigate the root cause of smoke and try to stop it

 When confirm fire Start fire water pumps

Trip HVAC units and close fire dampers. Isolate normal and essential lighting PAGA tone2

Note: There is no ESD1 in this case.

Page 46: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 46/71

Page 47: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 47/71

Manual Alarm Call point Located around the facility to allow personnel to raise

an alarm.

 Alarm in CCR only.

Panel operator will take necessary action.

Page 48: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 48/71

Page 49: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 49/71

Located principally near main stairways on mainprocess decks.

 Action - Activate ESD1 Close all shutdown valves

Open all blowdown valves

Trip all packages

ESD2 on all wellhead platforms

Start Fire Water Pumps

PAGA tone2

Trip normal power (Main Generators) EDG will start automatically 

Page 50: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 50/71

Page 51: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 51/71

Located at Helideck Access Landing Lifeboat embarkation area Drain Deck

 Action – Activate ESD0 ESD1 ESD1 on all wellhead platforms Stop EDG PAGA tone1 Isolate Battery charger on AQP Delay 30 minutes to isolate UPS on AQP Delay 3 hours to isolate UPS and Battery charger on APP

Page 52: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 52/71

Page 53: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 53/71

Located at In front of LER 

In front of ESWR 

In front of CCR 

This PB is use for isolate power in the room in case of 

fire.

Page 54: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 54/71

LER and ESWR   Activate ESD1

Stop/Inhibit to start EDG

Isolate APP battery charger

120 seconds delay to isolate APP UPS

This will lead to black-out. SIS loss power.

Page 55: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 55/71

CCR   Activate ESD1

Isolate AQP battery charger and UPS

 All HMI in CCR will loss power

Page 56: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 56/71

Page 57: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 57/71

Page 58: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 58/71

Photoelectric sensing detect visible fire particles Located in AQP Workshop, CCR, Raised floors,

Laboratory, Battery room

 Action Confirm smoke in Laboratory (1oo1)

PAGA tone 2

Trip HVAC units and close fire dampers.

Isolate all power sources within the laboratory 

Start fire water pumps

Page 59: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 59/71

 Action Confirm smoke in APP battery room (2oo2)

PAGA tone 2

Close fire dampers.

Start fire water pumps Confirm smoke in AQP battery room (1oo1)

PAGA tone 2

Trip AQP HVAC

Start fire water pumps

Page 60: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 60/71

 Action Confirm smoke in AQP workshop (2ooN in same fire

zone) PAGA tone 2

Trip AQP HVAC and close fire dampers. Isolate all power sources within fire zone

Start fire water pumps

Page 61: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 61/71

Page 62: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 62/71

The outer shell is made of a rapidly expanding alloy which closely follows changes in surrounding air temperature. The inner strutsare made of a lower expanding alloy. Designed to resist thermalenergy absorption and sealed inside the shell, the struts followtemperature changes more slowly.

Designed to activate at a fixed temperature, regardless of the rate of temperature rise.

Set point is 60 DegC.

Page 63: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 63/71

They will be used as the primary means of firedetection in areas where smoke is regularly expectedand accepted (Welding workshop, mechanical

 workshops, EI workshop).

 Action Confirm heat in one fire zone (1ooN)

PAGA tone 2

Trip HVAC units and close fire dampers.

Isolate all power sources within fire zone Start fire water pumps

Page 64: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 64/71

Page 65: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 65/71

Page 66: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 66/71

Page 67: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 67/71

 Autronica AutroSafe on ALQB  Automatic addressing of detectors.

Self-Verify Function for automatic testing of detectors

The system operates on the new AUTROLON

communication bus, enabling networking of all panels,detectors and interfaces to easily form a complex,distributed and totally interactive system - giving theflexibility to adapt to the individual requirements of any 

site.

Page 68: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 68/71

Smoke Detector (optical type) installed in every cabins,offices, recreation area

MAC installed in around the building to allow personnelto raise an alarm

Heat Detector install in galley   VESDA installed in TER 

Flame detectors at Helideck

 Addressable interface unit installed on every floors

 Addressable control panel is in CCR 

Page 69: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 69/71

 Action Confirm fire inside ALQB

 Alarm in CCR with tag and location of fire.

Close fire dampers

Trip ALQB HVAC Start stairwell pressurize fans

Confirm gas outside ALQB (XS-8600; signal from SIS)  Alarm in CCR 

Close fire dampers

Trip ALQB HVAC

NOT Start stairwell pressurize fans

Page 70: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 70/71

 Action Confirm fire inside galley 

 Alarm in CCR with tag and location of fire.

Close fire dampers

Trip ALQB HVAC Start stairwell pressurize fans

Trip galley distribution board (LSB-QP-360)

 All ALQB F&G detection will not alarm to PAGA 

Page 71: 54653358 Fire Gas Detection Philosophy Rev1 Full

8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full

http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 71/71

Please refer to C&E for detail actions for each F&Gdetection