Top Banner

of 37

4.Application of Pilot Schemes

Apr 08, 2018

Download

Documents

billymcreal
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/6/2019 4.Application of Pilot Schemes

    1/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Application of Pilot Schemes

    J. GosaliaDoble Engineering Company

  • 8/6/2019 4.Application of Pilot Schemes

    2/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pilot Protection Scheme

    Pilot

    ProtectionSchemes

    Types of pilotschemes

    Types of pilotschemes

    Principle of

    operation

    Principle ofoperation

    Comparison ofdifferent schemes

    Comparison ofdifferent schemes

    What is Pilot

    protectionscheme?

    What is Pilot

    protectionscheme?

  • 8/6/2019 4.Application of Pilot Schemes

    3/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    End Zone Faults

    Zone 1 setting at A & B = 80% of the line length

    Fault at F1: Fault is seen in Zone 1 at A & B. Cleared instantaneously

    Fault at F2:

    Cleared instantaneously at station B but cleared with Zone 2

    time delay from Station A.

    Fault remains on the line for Zone 2 time delay

    End Zone fault it is not cleared instantaneously

    A CB

    F2

    G GF1

  • 8/6/2019 4.Application of Pilot Schemes

    4/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    End Zone Faults : Pilot Scheme

    Fault on the protected line should becleared instantaneously :

    Continuity of supply Limit the Damage & shock to electrical system

    Stability of the system

    Minimize Revenue loss $$$$........Faults on the protected line including end

    zone fault can be cleared by employing pilotscheme Each end communicates with the other end to

    clear faults on the protected line instantaneously

  • 8/6/2019 4.Application of Pilot Schemes

    5/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Direct Transfer Trip Scheme : DTT

    21

    Z1

    Trip

    Z2

    Z3 21

    Z1

    Trip

    Z2

    Z3

    G G

    SignalingChannel

    SignalingChannel

  • 8/6/2019 4.Application of Pilot Schemes

    6/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Direct Transfer Trip Scheme : Logic

    21

    Z1

    Trip

    Z2

    Z3

    Signal Receive

    Signal Send

    Mal operation of the signaling equipmentmay result in an unnecessary tripping

    Mal operation of the signaling equipmentmay result in an unnecessary tripping

    To avoid mal operation, signal receivecan be supervised by the distanceelement Z2 before issuing trip command

    To avoid mal operation, signal receivecan be supervised by the distanceelement Z2 before issuing trip command

  • 8/6/2019 4.Application of Pilot Schemes

    7/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Permissive Under Reach TT Scheme

    21

    Z1

    TripZ2

    SignalReceive

    Signal Send

    &

    Z2t

    Signal is sent to remote terminal if Z1 operates.If signal is received from remote terminal then tripping isissued instantaneously if local Zone 2 see the fault

    Signal is sent to remote terminal if Z1 operates.If signal is received from remote terminal then tripping isissued instantaneously if local Zone 2 see the fault

    G GZ1

    Z2Z1

  • 8/6/2019 4.Application of Pilot Schemes

    8/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Permissive Under Reach TT Scheme

    21

    Z1

    TripZ2

    Signal Receive Signal Send

    &Z2t

    For end Zone fault with the remote breaker open, fault will not becleared instantaneously.Use 52b contact to send the continuous permissive signal toremote end for open breaker.

    For end Zone fault with the remote breaker open, fault will not becleared instantaneously.Use 52b contact to send the continuous permissive signal toremote end for open breaker.

    G G

    Comm52b

  • 8/6/2019 4.Application of Pilot Schemes

    9/37

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    PUTT Scheme : Caution

    Fault near terminal A is not seen by Zone 1 at terminal B No current flows through terminal B Fault is seen as Zone 1 Fault at terminal A

    Breaker at A trips instantaneously

    Now the fault current if fed via line CD and through B.

    Protection at B now sees the fault in Zone 2 but has nopermissive signal from terminal A to trip

    Fault is cleared after Zone 2 timer times out.

    G

    A

    C

    B

    D

  • 8/6/2019 4.Application of Pilot Schemes

    10/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    PUTT Scheme : Solution

    As breaker A opens the permissive signal to B resets

    Now the fault is fed through breakers C,D and B

    Zone 2 at B picks up but has no permission from A to trip

    Solution : Add a time delay on drop out on a permissivesignal receive

    The drop out delay >= Zone 2 pick up time + safety margin

    G

    C D

    A B

  • 8/6/2019 4.Application of Pilot Schemes

    11/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    PUTT : Logic

    21

    Z1

    TripZ2

    Signal Receive Signal Send

    &

    Z2t

    52b

    td

  • 8/6/2019 4.Application of Pilot Schemes

    12/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    PUTT : Limitation

    For Short line followed by a long line: Fault with the fault resistance may not be seen in Zone 1

    PUTT scheme fails to clear the fault on the line

    Fault is cleared in Zone 2 time

    For Short line followed by a long line: Fault with the fault resistance may not be seen in Zone 1 PUTT scheme fails to clear the fault on the line

    Fault is cleared in Zone 2 time

    ZR

    Zs

    Zone 1

    Zone 2

  • 8/6/2019 4.Application of Pilot Schemes

    13/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT Scheme

    21

    Z1

    Z2

    Z3

    G G

    SignalingChannel

    &

    Trip 21

    Z1

    Z2

    Z3

    &

    Trip

    Signaling

    Channel

  • 8/6/2019 4.Application of Pilot Schemes

    14/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT : Logic

    21

    Z1

    Z2

    Z3

    &

    TripTrip

    Signal ReceiveSignal Receive

    Signal SendSignal Send

  • 8/6/2019 4.Application of Pilot Schemes

    15/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT : Fault Resistance Coverage

    Zs

    Zone 1

    Zone 2

  • 8/6/2019 4.Application of Pilot Schemes

    16/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Permissive Overreach TT Scheme

    G

    A

    C

    B

    D

    G

    C sees Zone 2 fault, B sees zone 1 fault

    Fault current flows C-D-B

    D receives permission to trip from C but D sees reverse fault

    Breaker B opens as it sees the fault in Zone 1

    Now the fault current reverses and flows through D-C-A

    D sees Zone 2 fault, C does not see fault and zone 2 resets and

    stop sending permissive signal to D If D Zone 2 picks up before Zone 2 at C resets, D can trip

    If C Zone 2 is slow to reset it can trip for a fault on parallel line

  • 8/6/2019 4.Application of Pilot Schemes

    17/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT : Solution

    21

    Z1

    Z2

    Z3

    &

    TripTrip

    Signal SendSignal Send

    Signal ReceiveSignal Receive

    tp

    Adding a time delay tp in Signal Send will prevent mal operation

    tp > Fast PU local Z2 time slowest reset time of remote Z2 time

    Adding a time delay tp in Signal Send will prevent mal operation

    tp > Fast PU local Z2 time slowest reset time of remote Z2 time

  • 8/6/2019 4.Application of Pilot Schemes

    18/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT Scheme :Remote Breaker Open

    G G

    A sees Zone 2 fault, B does not see fault as it is open

    A can not trip instantaneously as it does not receive thepermissive signal from B

    If the local breaker is open and receives permissive signal fromremote end, the permissive signal can be Echoed back toremote breaker

    Now the breaker A can trip to clear the fault on the line

    A B

  • 8/6/2019 4.Application of Pilot Schemes

    19/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT : Signal Echo Logic

    T1 & T2 &

    Signal SendSignal Send

    Signal ReceiveSignal Receive

    52b52b

    T1 timer avoid sending Echo if breaker is tripped by otherprotection

    T2 avoids continuous Echo

  • 8/6/2019 4.Application of Pilot Schemes

    20/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT : Logic

    Signal ReceiveSignal Receive

    Signal SendSignal Send

    21

    Z1

    Z2

    Z3

    & TripTrip

    FSK logicTrip and

    Guard Freq.

    When Permissivesignal is receivedfrom Remote Endguard frequency is

    lost and trip freq isreceived

    Permissive Trip isissued by signalingequipment to

    protection whenguard frequency islost and tripfrequency is received

    PLCC equipmenttransmit guard andtrip freq. over powerline

    When Permissivesignal is receivedfrom Remote Endguard frequency is

    lost and trip freq isreceived

    Permissive Trip isissued by signalingequipment to

    protection whenguard frequency islost and tripfrequency is received

    PLCC equipment

    transmit guard andtrip freq. over powerline

  • 8/6/2019 4.Application of Pilot Schemes

    21/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT : Caution

    Line Trap

    G

    FSK logicTrip and

    Guard Freq.

    Coupling cap

    G

    FSK logicTrip and

    Guard Freq.

    Coupling cap

    Guard as well as trip frequency can not be transmitted orattenuated due to fault on the power line

    Line Trap

  • 8/6/2019 4.Application of Pilot Schemes

    22/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Un Blocking Scheme

    POTT scheme

    Trip frequency must be received & guard

    frequency must be lost to issue permissive signal

    Un Blocking Scheme

    Enhanced POTT scheme

    If guard frequency is lost then permissive tripsignal is issued only for 100-150 mSecs.

    If Z2 is picked up protection trip during this time

    After this time permissive trip signal is only issuedif guard frequency is lost & trip frequency received

    Very secure and reliable scheme

  • 8/6/2019 4.Application of Pilot Schemes

    23/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT Scheme : Weak In feed

    Fault near the remote terminal is seen as

    Zone 2 at local terminal Needs permissive trip signal from remote end to

    clear the fault

    Remote end has a week source contributing tothe fault : Z2 at remote end does not pick upand no permissive signal is sent at local end

    Fault on the line is not cleared instantaneously

    G

    G

    Z1

    Z2

  • 8/6/2019 4.Application of Pilot Schemes

    24/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    POTT : Weak In Feed

    G

    G

    Z1

    Z2

    Z3

    Signal Receive

    Z3 &

    Echo Signal Send

    Trip local Br.

  • 8/6/2019 4.Application of Pilot Schemes

    25/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Blocking Scheme

    Simple scheme

    Very popular in N. America

    Comm. channel only sends the blockingsignal to remote end to block tripping

    Unlike POTT scheme where guard signal is sentcontinuous

    Z3 is set reverse looking

    Z3 Picks up and sends the blocking signal

    indicating fault is beyond the protected linesection

  • 8/6/2019 4.Application of Pilot Schemes

    26/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Blocking Scheme

    G

    G

    Z1

    Z2

    Z3

    Fault near the remote terminal is seen asZone 2 at local terminal Remote Z3 does not see the fault

    No blocking signal is sent

    Trip is issued after a time delay tp to clear fault

    For fault beyond remote terminal Z3 reverse looking picks up & send block singal

    No trip at local terminal

  • 8/6/2019 4.Application of Pilot Schemes

    27/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Blocking Scheme : Logic

    Z3

    &Signal Send

    G

    G

    Z1

    Z2

    Z3

    Signal Receive

    Z2

    &Trip local Br.

    tp

  • 8/6/2019 4.Application of Pilot Schemes

    28/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Blocking Vs. Permissive Scheme

    Signal Receive: Blockslocal inst. Z2 tripping

    Signaling channel isnormally OFF. onlyON when Z3 picks up

    When Z2 picks up, it

    waits for a time delaytp before issuing trip toensure remoteterminal has a time tosend block signal

    Signal Receive: Blockslocal inst. Z2 tripping

    Signaling channel isnormally OFF. onlyON when Z3 picks up

    When Z2 picks up, itwaits for a time delaytp before issuing trip toensure remote

    terminal has a time tosend block signal

    Signal Receive tripsZ2 instantaneously

    Signaling channel isON all the timesending Guardfrequency and

    changes to trip freq. ifZ2 picks up

    No intentional timedelay for tripping ifpermissive signal isreceived

    Signal Receive tripsZ2 instantaneously

    Signaling channel isON all the timesending Guardfrequency and

    changes to trip freq. ifZ2 picks up

    No intentional time

    delay for tripping ifpermissive signal isreceived

  • 8/6/2019 4.Application of Pilot Schemes

    29/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Blocking Vs. POTT : Comparison

    Intentional time delayadded to avoid overtripping

    Failure of thecommunication channelmay results in over trippingfor an external fault

    Blocking scheme is more

    dependable Single On/Off signaling

    channel in use operating atsingle frequency in bothdirection

    Intentional time delayadded to avoid overtripping

    Failure of thecommunication channelmay results in over trippingfor an external fault

    Blocking scheme is more

    dependable Single On/Off signaling

    channel in use operating atsingle frequency in both

    direction

    No intentional time delayon trip for a fault on the line

    Failure of the

    communication channelmay results in a failure totrip for a fault on the line

    POTT scheme is moresecure

    Separate signaling channelfor each direction ofsignaling

    No intentional time delayon trip for a fault on the line

    Failure of the

    communication channelmay results in a failure totrip for a fault on the line

    POTT scheme is moresecure

    Separate signaling channelfor each direction ofsignaling

    Un Blocking scheme combines security of POTT scheme &

    Dependability of Blocking schemeUn Blocking scheme combines security of POTT scheme &

    Dependability of Blocking scheme

  • 8/6/2019 4.Application of Pilot Schemes

    30/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Selection of Pilot Scheme?

    Deciding factors

    Reliability of signaling channels

    N. America for 115/230 kV lines,blocking scheme is used frequently

    Reliability is quite good

    Operating speed Fault clearing time requirement

    System operating practice

  • 8/6/2019 4.Application of Pilot Schemes

    31/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Special Schemes

    Zone 1 extension scheme

    No communication channel is used

    Economical, Simple Used along with AutoReclosing protection

    95% of all the faults are transient fault

    Phase distance and time over current protection in

    blocking scheme Ground distance protection has limited fault resistance

    coverage

    Little or not fault coverage for short line and/or strong

    source

    Use of time over current for ground fault provides higherfault resistance coverage

  • 8/6/2019 4.Application of Pilot Schemes

    32/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Zone 1 Ext. Scheme

    Zone 1 is set to over reach by setting Z1x

    Z1x reach of AB is set to 20% in to the line section CD If the fault occurs in line section CD, breaker A and C trips High speed Auto Reclose protection closes the breakers

    A & C During the same time, the Z1x reach is pulled back to Z1

    If the fault is permanent on the next line section onlybreaker C will trip and breaker A does not trip

    If the fault is transient, interruption in power transfer isminimal

    G GZ1

    Z1x

    21/79

    A B C D

  • 8/6/2019 4.Application of Pilot Schemes

    33/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Zone 1 Ext. Scheme : Logic

    Auto RecloseIn progress

    Z1

    & Z1 trip.Z1x

    &

    79

  • 8/6/2019 4.Application of Pilot Schemes

    34/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Zone 1 Ext. Scheme: Pros and Cons

    Transient faults on the line are clearedinstantaneously without the need for

    elaborate communication equipmentPermanent end Zone faults are cleared in

    Zone 2 time

    Transient faults in the next line section willcreate unnecessary tripping and reclosingof the circuit breaker This is the main disadvantage when

    interconnected high voltage power system whenseveral feeders can terminate at a single bus

    Transient faults on the line are clearedinstantaneously without the need for

    elaborate communication equipmentPermanent end Zone faults are cleared in

    Zone 2 time

    Transient faults in the next line section willcreate unnecessary tripping and reclosingof the circuit breaker This is the main disadvantage when

    interconnected high voltage power system whenseveral feeders can terminate at a single bus

  • 8/6/2019 4.Application of Pilot Schemes

    35/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Pilot Scheme: 21P and 50/51G

    Blocking scheme : 21P as discussed earlier

    Ground over current uses 50/51 and directional protection Local End:

    Block signal is sent to remote end by non directional groundtime over current element

    The block signal is cancelled if the ground directional elementpicks up for a fault on a line (Forward fault)

    Remote End:

    If high set is picked up (50 HS) and directional element pickedup & block signal is received : Fault is forward

    Wait for a time delay tp for block signal to be removed fromthe remote end for a forward fault

    If the block signal from the local end is cancelled then theprotection trips

    If block signal is not cancelled then fault is on the next linesection and it may trip after a time delay 51G

  • 8/6/2019 4.Application of Pilot Schemes

    36/37

    Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery

    Pilot Scheme: 21P and 50/51G

    Protection A and B: Block signal is sent to remote end by high speed non dir. groundtime over current element

    The block signal is cancelled by the ground directional element

    Block signal is received, 50 HS with directional element picked up.

    Wait for a time delay tp to see if block signal is cancelled

    Once the block signal is cancelled protection A and B trips to clearthe fault on the line

    G GZ1

    21P50/51G

    A B C D

    21P50/51G

  • 8/6/2019 4.Application of Pilot Schemes

    37/37

    Knowledge Is PowerSM

    Apparatus Maintenance and Power Management

    for Energy Delivery