8/6/2019 4.Application of Pilot Schemes
1/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
Application of Pilot Schemes
J. GosaliaDoble Engineering Company
8/6/2019 4.Application of Pilot Schemes
2/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
Pilot Protection Scheme
Pilot
ProtectionSchemes
Types of pilotschemes
Types of pilotschemes
Principle of
operation
Principle ofoperation
Comparison ofdifferent schemes
Comparison ofdifferent schemes
What is Pilot
protectionscheme?
What is Pilot
protectionscheme?
8/6/2019 4.Application of Pilot Schemes
3/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
End Zone Faults
Zone 1 setting at A & B = 80% of the line length
Fault at F1: Fault is seen in Zone 1 at A & B. Cleared instantaneously
Fault at F2:
Cleared instantaneously at station B but cleared with Zone 2
time delay from Station A.
Fault remains on the line for Zone 2 time delay
End Zone fault it is not cleared instantaneously
A CB
F2
G GF1
8/6/2019 4.Application of Pilot Schemes
4/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
End Zone Faults : Pilot Scheme
Fault on the protected line should becleared instantaneously :
Continuity of supply Limit the Damage & shock to electrical system
Stability of the system
Minimize Revenue loss $$$$........Faults on the protected line including end
zone fault can be cleared by employing pilotscheme Each end communicates with the other end to
clear faults on the protected line instantaneously
8/6/2019 4.Application of Pilot Schemes
5/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
Direct Transfer Trip Scheme : DTT
21
Z1
Trip
Z2
Z3 21
Z1
Trip
Z2
Z3
G G
SignalingChannel
SignalingChannel
8/6/2019 4.Application of Pilot Schemes
6/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
Direct Transfer Trip Scheme : Logic
21
Z1
Trip
Z2
Z3
Signal Receive
Signal Send
Mal operation of the signaling equipmentmay result in an unnecessary tripping
Mal operation of the signaling equipmentmay result in an unnecessary tripping
To avoid mal operation, signal receivecan be supervised by the distanceelement Z2 before issuing trip command
To avoid mal operation, signal receivecan be supervised by the distanceelement Z2 before issuing trip command
8/6/2019 4.Application of Pilot Schemes
7/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
Permissive Under Reach TT Scheme
21
Z1
TripZ2
SignalReceive
Signal Send
&
Z2t
Signal is sent to remote terminal if Z1 operates.If signal is received from remote terminal then tripping isissued instantaneously if local Zone 2 see the fault
Signal is sent to remote terminal if Z1 operates.If signal is received from remote terminal then tripping isissued instantaneously if local Zone 2 see the fault
G GZ1
Z2Z1
8/6/2019 4.Application of Pilot Schemes
8/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
Permissive Under Reach TT Scheme
21
Z1
TripZ2
Signal Receive Signal Send
&Z2t
For end Zone fault with the remote breaker open, fault will not becleared instantaneously.Use 52b contact to send the continuous permissive signal toremote end for open breaker.
For end Zone fault with the remote breaker open, fault will not becleared instantaneously.Use 52b contact to send the continuous permissive signal toremote end for open breaker.
G G
Comm52b
8/6/2019 4.Application of Pilot Schemes
9/37
Knowledge Is PowerSMApparatus Maintenance and Power Management
for Energy Delivery
PUTT Scheme : Caution
Fault near terminal A is not seen by Zone 1 at terminal B No current flows through terminal B Fault is seen as Zone 1 Fault at terminal A
Breaker at A trips instantaneously
Now the fault current if fed via line CD and through B.
Protection at B now sees the fault in Zone 2 but has nopermissive signal from terminal A to trip
Fault is cleared after Zone 2 timer times out.
G
A
C
B
D
8/6/2019 4.Application of Pilot Schemes
10/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
PUTT Scheme : Solution
As breaker A opens the permissive signal to B resets
Now the fault is fed through breakers C,D and B
Zone 2 at B picks up but has no permission from A to trip
Solution : Add a time delay on drop out on a permissivesignal receive
The drop out delay >= Zone 2 pick up time + safety margin
G
C D
A B
8/6/2019 4.Application of Pilot Schemes
11/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
PUTT : Logic
21
Z1
TripZ2
Signal Receive Signal Send
&
Z2t
52b
td
8/6/2019 4.Application of Pilot Schemes
12/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
PUTT : Limitation
For Short line followed by a long line: Fault with the fault resistance may not be seen in Zone 1
PUTT scheme fails to clear the fault on the line
Fault is cleared in Zone 2 time
For Short line followed by a long line: Fault with the fault resistance may not be seen in Zone 1 PUTT scheme fails to clear the fault on the line
Fault is cleared in Zone 2 time
ZR
Zs
Zone 1
Zone 2
8/6/2019 4.Application of Pilot Schemes
13/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT Scheme
21
Z1
Z2
Z3
G G
SignalingChannel
&
Trip 21
Z1
Z2
Z3
&
Trip
Signaling
Channel
8/6/2019 4.Application of Pilot Schemes
14/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT : Logic
21
Z1
Z2
Z3
&
TripTrip
Signal ReceiveSignal Receive
Signal SendSignal Send
8/6/2019 4.Application of Pilot Schemes
15/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT : Fault Resistance Coverage
Zs
Zone 1
Zone 2
8/6/2019 4.Application of Pilot Schemes
16/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Permissive Overreach TT Scheme
G
A
C
B
D
G
C sees Zone 2 fault, B sees zone 1 fault
Fault current flows C-D-B
D receives permission to trip from C but D sees reverse fault
Breaker B opens as it sees the fault in Zone 1
Now the fault current reverses and flows through D-C-A
D sees Zone 2 fault, C does not see fault and zone 2 resets and
stop sending permissive signal to D If D Zone 2 picks up before Zone 2 at C resets, D can trip
If C Zone 2 is slow to reset it can trip for a fault on parallel line
8/6/2019 4.Application of Pilot Schemes
17/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT : Solution
21
Z1
Z2
Z3
&
TripTrip
Signal SendSignal Send
Signal ReceiveSignal Receive
tp
Adding a time delay tp in Signal Send will prevent mal operation
tp > Fast PU local Z2 time slowest reset time of remote Z2 time
Adding a time delay tp in Signal Send will prevent mal operation
tp > Fast PU local Z2 time slowest reset time of remote Z2 time
8/6/2019 4.Application of Pilot Schemes
18/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT Scheme :Remote Breaker Open
G G
A sees Zone 2 fault, B does not see fault as it is open
A can not trip instantaneously as it does not receive thepermissive signal from B
If the local breaker is open and receives permissive signal fromremote end, the permissive signal can be Echoed back toremote breaker
Now the breaker A can trip to clear the fault on the line
A B
8/6/2019 4.Application of Pilot Schemes
19/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT : Signal Echo Logic
T1 & T2 &
Signal SendSignal Send
Signal ReceiveSignal Receive
52b52b
T1 timer avoid sending Echo if breaker is tripped by otherprotection
T2 avoids continuous Echo
8/6/2019 4.Application of Pilot Schemes
20/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT : Logic
Signal ReceiveSignal Receive
Signal SendSignal Send
21
Z1
Z2
Z3
& TripTrip
FSK logicTrip and
Guard Freq.
When Permissivesignal is receivedfrom Remote Endguard frequency is
lost and trip freq isreceived
Permissive Trip isissued by signalingequipment to
protection whenguard frequency islost and tripfrequency is received
PLCC equipmenttransmit guard andtrip freq. over powerline
When Permissivesignal is receivedfrom Remote Endguard frequency is
lost and trip freq isreceived
Permissive Trip isissued by signalingequipment to
protection whenguard frequency islost and tripfrequency is received
PLCC equipment
transmit guard andtrip freq. over powerline
8/6/2019 4.Application of Pilot Schemes
21/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT : Caution
Line Trap
G
FSK logicTrip and
Guard Freq.
Coupling cap
G
FSK logicTrip and
Guard Freq.
Coupling cap
Guard as well as trip frequency can not be transmitted orattenuated due to fault on the power line
Line Trap
8/6/2019 4.Application of Pilot Schemes
22/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Un Blocking Scheme
POTT scheme
Trip frequency must be received & guard
frequency must be lost to issue permissive signal
Un Blocking Scheme
Enhanced POTT scheme
If guard frequency is lost then permissive tripsignal is issued only for 100-150 mSecs.
If Z2 is picked up protection trip during this time
After this time permissive trip signal is only issuedif guard frequency is lost & trip frequency received
Very secure and reliable scheme
8/6/2019 4.Application of Pilot Schemes
23/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT Scheme : Weak In feed
Fault near the remote terminal is seen as
Zone 2 at local terminal Needs permissive trip signal from remote end to
clear the fault
Remote end has a week source contributing tothe fault : Z2 at remote end does not pick upand no permissive signal is sent at local end
Fault on the line is not cleared instantaneously
G
G
Z1
Z2
8/6/2019 4.Application of Pilot Schemes
24/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
POTT : Weak In Feed
G
G
Z1
Z2
Z3
Signal Receive
Z3 &
Echo Signal Send
Trip local Br.
8/6/2019 4.Application of Pilot Schemes
25/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Blocking Scheme
Simple scheme
Very popular in N. America
Comm. channel only sends the blockingsignal to remote end to block tripping
Unlike POTT scheme where guard signal is sentcontinuous
Z3 is set reverse looking
Z3 Picks up and sends the blocking signal
indicating fault is beyond the protected linesection
8/6/2019 4.Application of Pilot Schemes
26/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Blocking Scheme
G
G
Z1
Z2
Z3
Fault near the remote terminal is seen asZone 2 at local terminal Remote Z3 does not see the fault
No blocking signal is sent
Trip is issued after a time delay tp to clear fault
For fault beyond remote terminal Z3 reverse looking picks up & send block singal
No trip at local terminal
8/6/2019 4.Application of Pilot Schemes
27/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Blocking Scheme : Logic
Z3
&Signal Send
G
G
Z1
Z2
Z3
Signal Receive
Z2
&Trip local Br.
tp
8/6/2019 4.Application of Pilot Schemes
28/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Blocking Vs. Permissive Scheme
Signal Receive: Blockslocal inst. Z2 tripping
Signaling channel isnormally OFF. onlyON when Z3 picks up
When Z2 picks up, it
waits for a time delaytp before issuing trip toensure remoteterminal has a time tosend block signal
Signal Receive: Blockslocal inst. Z2 tripping
Signaling channel isnormally OFF. onlyON when Z3 picks up
When Z2 picks up, itwaits for a time delaytp before issuing trip toensure remote
terminal has a time tosend block signal
Signal Receive tripsZ2 instantaneously
Signaling channel isON all the timesending Guardfrequency and
changes to trip freq. ifZ2 picks up
No intentional timedelay for tripping ifpermissive signal isreceived
Signal Receive tripsZ2 instantaneously
Signaling channel isON all the timesending Guardfrequency and
changes to trip freq. ifZ2 picks up
No intentional time
delay for tripping ifpermissive signal isreceived
8/6/2019 4.Application of Pilot Schemes
29/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Blocking Vs. POTT : Comparison
Intentional time delayadded to avoid overtripping
Failure of thecommunication channelmay results in over trippingfor an external fault
Blocking scheme is more
dependable Single On/Off signaling
channel in use operating atsingle frequency in bothdirection
Intentional time delayadded to avoid overtripping
Failure of thecommunication channelmay results in over trippingfor an external fault
Blocking scheme is more
dependable Single On/Off signaling
channel in use operating atsingle frequency in both
direction
No intentional time delayon trip for a fault on the line
Failure of the
communication channelmay results in a failure totrip for a fault on the line
POTT scheme is moresecure
Separate signaling channelfor each direction ofsignaling
No intentional time delayon trip for a fault on the line
Failure of the
communication channelmay results in a failure totrip for a fault on the line
POTT scheme is moresecure
Separate signaling channelfor each direction ofsignaling
Un Blocking scheme combines security of POTT scheme &
Dependability of Blocking schemeUn Blocking scheme combines security of POTT scheme &
Dependability of Blocking scheme
8/6/2019 4.Application of Pilot Schemes
30/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Selection of Pilot Scheme?
Deciding factors
Reliability of signaling channels
N. America for 115/230 kV lines,blocking scheme is used frequently
Reliability is quite good
Operating speed Fault clearing time requirement
System operating practice
8/6/2019 4.Application of Pilot Schemes
31/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Special Schemes
Zone 1 extension scheme
No communication channel is used
Economical, Simple Used along with AutoReclosing protection
95% of all the faults are transient fault
Phase distance and time over current protection in
blocking scheme Ground distance protection has limited fault resistance
coverage
Little or not fault coverage for short line and/or strong
source
Use of time over current for ground fault provides higherfault resistance coverage
8/6/2019 4.Application of Pilot Schemes
32/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Zone 1 Ext. Scheme
Zone 1 is set to over reach by setting Z1x
Z1x reach of AB is set to 20% in to the line section CD If the fault occurs in line section CD, breaker A and C trips High speed Auto Reclose protection closes the breakers
A & C During the same time, the Z1x reach is pulled back to Z1
If the fault is permanent on the next line section onlybreaker C will trip and breaker A does not trip
If the fault is transient, interruption in power transfer isminimal
G GZ1
Z1x
21/79
A B C D
8/6/2019 4.Application of Pilot Schemes
33/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Zone 1 Ext. Scheme : Logic
Auto RecloseIn progress
Z1
& Z1 trip.Z1x
&
79
8/6/2019 4.Application of Pilot Schemes
34/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Zone 1 Ext. Scheme: Pros and Cons
Transient faults on the line are clearedinstantaneously without the need for
elaborate communication equipmentPermanent end Zone faults are cleared in
Zone 2 time
Transient faults in the next line section willcreate unnecessary tripping and reclosingof the circuit breaker This is the main disadvantage when
interconnected high voltage power system whenseveral feeders can terminate at a single bus
Transient faults on the line are clearedinstantaneously without the need for
elaborate communication equipmentPermanent end Zone faults are cleared in
Zone 2 time
Transient faults in the next line section willcreate unnecessary tripping and reclosingof the circuit breaker This is the main disadvantage when
interconnected high voltage power system whenseveral feeders can terminate at a single bus
8/6/2019 4.Application of Pilot Schemes
35/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Pilot Scheme: 21P and 50/51G
Blocking scheme : 21P as discussed earlier
Ground over current uses 50/51 and directional protection Local End:
Block signal is sent to remote end by non directional groundtime over current element
The block signal is cancelled if the ground directional elementpicks up for a fault on a line (Forward fault)
Remote End:
If high set is picked up (50 HS) and directional element pickedup & block signal is received : Fault is forward
Wait for a time delay tp for block signal to be removed fromthe remote end for a forward fault
If the block signal from the local end is cancelled then theprotection trips
If block signal is not cancelled then fault is on the next linesection and it may trip after a time delay 51G
8/6/2019 4.Application of Pilot Schemes
36/37
Knowledge Is PowerSMApparatus Maintenance and Power Managementfor Energy Delivery
Pilot Scheme: 21P and 50/51G
Protection A and B: Block signal is sent to remote end by high speed non dir. groundtime over current element
The block signal is cancelled by the ground directional element
Block signal is received, 50 HS with directional element picked up.
Wait for a time delay tp to see if block signal is cancelled
Once the block signal is cancelled protection A and B trips to clearthe fault on the line
G GZ1
21P50/51G
A B C D
21P50/51G
8/6/2019 4.Application of Pilot Schemes
37/37
Knowledge Is PowerSM
Apparatus Maintenance and Power Management
for Energy Delivery