Manual Part Number 04569270-3 AP4300 Three Phase 7.5 to 20kVA 50 or 60Hz. Series AP4300 UPS POWER PROTECTION AP4300 AP4300 Installation Operation and Maintenance Manual
Oct 30, 2014
Manual Part Number 04569270-3
AP4300 Three Phase
7.5 to 20kVA 50 or 60Hz.
Series AP4300 UPS
POWER PROTECTION
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss dd:mm:yy
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss dd:mm:yy
Installation Operation and
Maintenance Manual
Table of Contents
Important Instructions For Safe Use . . . . . . . . . . . . . . . . . . . . . . . . . . v
Important Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
Chapter 1 - General Description
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Equipment construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Basic Concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Primary Power Path . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Static switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Maintenance bypass line . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
System operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Operation during ‘normal’ conditions . . . . . . . . . . . . . . . . . . . . . 1-2Operation during input power supply failure . . . . . . . . . . . . . . . . . 1-2Operation during abnormal / fault conditions . . . . . . . . . . . . . . . . . 1-3Maintenance bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Electrical switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Circuit breakers and fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Control switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Internal Cutout Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Operator control switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Main control switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Input/Battery fuse holders . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5Output Off Switch (SW2) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6LCD controls - on/off command. . . . . . . . . . . . . . . . . . . . . . . . 1-6Remote Stop Switch(optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6Optional operator controls . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6Emergency Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Operator Control & Display Panel . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7LCD Display, Controls & Screen . . . . . . . . . . . . . . . . . . . . . . . 1-7LED Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8Indicator Bars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9Alarm indicator & horn cancel button. . . . . . . . . . . . . . . . . . . . . 1-9
Chapter 2 - Operating Instructions
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
The Operating procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Fault Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Cold Start Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2NORMAL operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4Setting Date, Time & Language . . . . . . . . . . . . . . . . . . . . . . . 2-4UPS Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Switching the Output Off/On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6Output Off Switch SW2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6Operation from the UPS control panel . . . . . . . . . . . . . . . . . . . . 2-6Switching with External Commands . . . . . . . . . . . . . . . . . . . . . 2-8
Input Power Supply Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8Input Supply Failure when On Load . . . . . . . . . . . . . . . . . . . . . 2-8Input Supply Failure when Off Load . . . . . . . . . . . . . . . . . . . . . 2-9
Applying Power to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Starting up the UPS on battery ( ‘black start’) . . . . . . . . . . . . . . . . . . . 2-11General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
To Put the Load on Maintenance Bypass (MBP) . . . . . . . . . . . . . . . . . . 2-11
Removing Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
IOM Manual
Issue 3 (01/03/98) i
Chapter 3 - Installation Instructions
Safety warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1On Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Weight considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2Extended battery option . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Removal from Shipping Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4Units shipped with batteries . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4Units shipped without batteries. . . . . . . . . . . . . . . . . . . . . . . . 3-5
Final Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Connecting the UPS Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9General introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9Cable sizing consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9Input supply protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9Output Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Terminal connection points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Procedure for connecting the UPS to the power supply . . . . . . . . . . . . . . 3-12Common input/bypass supply system . . . . . . . . . . . . . . . . . . . . 3-12Split input/bypass supply . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Electrical Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Chapter 4 - Options and Features
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Auto-restart Inhibit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Common Bypass Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Remote stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Hot Standby Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Remote Control/ Communications Facilities . . . . . . . . . . . . . . . . . . . . . 4-2RS232 Interface and External Relay Board . . . . . . . . . . . . . . . . . . 4-2SNMP Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5Interface Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5Remote Alarm Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Extended Battery Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7Extended Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7Remote Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Power Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8Input Harmonic Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8Isolation Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8Filter &Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8External Bypass Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8Distribution Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9Frequency Changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
AP4300
ii Issue 3 (01/03/98)
Chapter 5 - Troubleshooting
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Alarm indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Audible Alarm Horn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1LED Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Messages in the LCD Text Window . . . . . . . . . . . . . . . . . . . . . 5-2
Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3Fault Records. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3Alarm Interpretation and Corrective action . . . . . . . . . . . . . . . . . . 5-3
Troubleshooting Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Checking the input and bypass circuit breakers, and battery fuses . . . . . . . . . 5-8Battery fuse check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8Circuit breaker check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Chapter 6 - Maintenance
Routine Maintenance Checks by the Operator . . . . . . . . . . . . . . . . . . . . 6-1Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1Checks at weekly intervals. . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1Checks at monthly intervals . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1Annual checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Annual Maintenance Checks by Service Engineer . . . . . . . . . . . . . . . . . . 6-4Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Chapter 7 - Liebert WarrantyLimited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Life Support Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
AP4300 Series UPS Specification · · · · · · · · · · · · · · · · · · · · · · · · · 8-1
Parameter Settings for the AP4300 · · · · · · · · · · · · · · · · · · · · · · · · 8-3
IOM Manual
Issue 3 (01/03/98) iii
This equipment has been designed and manufactured by Liebert,market leaders in the field of Uninterruptible Power Systems (UPS);
and, if installed and used correctly, will provide years of trouble-free operation.
This manual contains the information necessary for the correct operation and safe installation of theAP4300 Series UPS.
Please read the manual carefully before you attempt to install your UPS, or connect any equipment toit. For your safety it is important that you comply with the instructions for safe use. Please keep this
manual safe for future reference.
PLEASE NOTE:
The AP4300 Series UPS has been designed for Commercial/Industrial use only.
Please refer to warranty for restrictions on use.
This manual describes the following AP4300 series UPS models:
MODEL NUMBER DESCRIPTION PART NUMBERWithout Batteries With Batteries
AP4307 7.5kVA 50 Hz. UPS 75407002 75407102
AP4310 10kVA 50 Hz. UPS 75410002 75410102
AP4315 15kVA 50 Hz. UPS 75415202 75415302
AP4320 20kVA 50 Hz. UPS 75420202 75420302
AP4307 7.5kVA 60 Hz. UPS 75407602 75407652
AP4310 10kVA 60 Hz. UPS 75410602 75410652
AP4315 15kVA 60 Hz. UPS 75415602 75415652
AP4320 20kVA 60 Hz. UPS 75420602 75420652
Importatnt: All models in the UPS range are similar in operation and use. The illustrations in this manual depictthe 10kVA model (AP4310) unless otherwise stated.
If you encounter any problems with the equipment or the procedures contained in this manual you should seekimmediate assistance from the Liebert distributor from whom the equipment was purchased. Alternatively contact
Liebert's Customer Service & Support Department at the address shown below:
Technical Support Department,,Liebert Global Services
Globe Park, Marlow, Bucks,SL7 1YG, U.K.
Telephone +44 (0) 1628 403200 - Fax +44 (0) 1628 403203
This department also arranges service contracts and full commissioning service.
Liebert Corporation pursues a policy of continual product development and reserves the right to make changes toequipment design without notice.
©Copyright 1996 Liebert CorporationUnauthorised reproduction prohibited.
All rights reserved.
AP4300
iv Issue 3 (01/03/98)
Important Instructions For Safe Use
q The UPS must be commissioned by a Liebert approvedengineer before it is put into service. Failure to observe thiscondition will invalidate any implied warranty.
q Do not apply power to this equipment before it has beencommissioned by a Liebert approved engineer. He willvalidate the installation work and install ‘site information’into the microcontroller memory. This information is requiredto substantiate any warranty claims that might be made.
q These units contain no user serviceable parts.Under no circumstances attempt to gain access internally, dueto risk of electrical shock or burn.Do not continue to use your UPS if the front panel indicationsare not in accordance with these operating instructions, or theUPS performance alters in use.Refer all faults to your dealer.
q The UPS is for indoor use only.It must be protected from rain or excessive moisture andinstalled in a clean environment, free from flammable liquids,gasses, or corrosive substances.Do not put drinks, plants, or any other containers holdingliquids, on top of the unit.
q Competent personnel should be consulted if liquid spills intothe product.
q Ventilation grills are provided beneath (and on the left handside on 15/20kVA models) and at the rear of the cabinet. Donot block or cover these openings otherwise overheating mayoccur and UPS operation become unreliable.Never insert any object into these ventilation holes oropenings.
q Do not place magnetic storage media on top of the unit as itcan corrupt the data stored on them.
q The front control and display panel is designed for handoperation. Do not press with sharp or pointed objects.
q The following definitions are given for your information andsafety:
Operator/User
Personnel who have received instruction on the correctoperation of the UPS controls - limited to operation ofSwitch 1, Switch 2 and the Front Control Panel - notpermitted to remove any panels which are retained byscrews.
Competent Personnel
Personnel who are aware of the dangers appropriate toworking with hazardous voltages and are deemed to havesufficient technical skills/training to make electricalconnections, install batteries, close and open circuitbreakers/fuses etc. (i.e. a qualified electrician).
Service Personnel
Engineers who have received the relevant Liebert trainingand are password authorised.
ELECTROMAGNETIC COMPATABILITYThis equipment complies with the requirements of the
EMC Directive 89/336/EEC and the published technicalstandards. Continued compliance requires installation in
accordance with these instructions and the use ofmanufacturer approved accessories only.
WARNINGTHIS IS A CLASS A - UNINTERRUPTIBLE POWER
SYSTEM PRODUCT. IN A DOMESTICENVIRONMENT, THIS PRODUCT MAY CAUSE
RADIO INTERFERENCE, IN WHICH CASE, THEUSER MAY BE REQUIRED TO TAKE ADDITIONAL
MEASURES.
WARNINGTHIS UPS SHOULD NOT BE SUPPLIED FROM
ELECTRICAL POWER SYSTEMSOF THE ‘IT’ (IMPÉDANCE À TERRE) TYPE.(IEC 364 - ELECTRICAL INSTALLATION OF
BUILDINGS)
Note: Where use on ‘IT’ systems is required we offer theoptional input isolation transformersee chapter 4 for more information.
IOM Manual
Issue 3 (01/03/98) v
Important Symbols
Symbols used on the AP4300 series UPS are in twocategories SAFETY and OPERATIONAL, and are
listed below.
SAFETY SYMBOLS.
WARNING - HAZARDOUS VOLTAGE
WEIGHT
MAXIMUM OPERATINGTEMPERATURE 40oC
VALVE REGULATED LEAD ACIDBATTERY (VRLA)
WARNING - THE BATTERY CONTAINSCORROSIVE MATERIAL
OPERATIONAL SYMBOLS.
BATTERY ISOLATION FUSES
READ THE INSTRUCTION MANUAL
CAUTION: NOTE THE FOLLOWINGINSTRUCTION
INPUT AC SUPPLY
UPS AC OUTPUT
AP4300
vi Issue 3 (01/03/98)
Chapter 1 - General Description
1.1 Introduction
This chapter describes the purpose, principle of operation anduser controls of the AP4300 series on-line Uninterruptible PowerSystem (UPS).
The AP4300 series UPS is connected between a critical load,such as a computer, and its input power supply. Its purpose is toprovide the load with well regulated power under all rated loadand input supply conditions; i.e. the power provided by the UPSwill be protected from any voltage or frequency variations on theincoming power supply, or variations in the supply due toelectrical noise, and will continue during periods of input powersupply failure. A battery provides a standby power source for theUPS when the input a.c. supply fails.
1.2 Equipment construction
The equipment is constructed around a steel frame withremovable panels. The right-hand front panel can be lifted off togive easy access to the input & bypass circuit breakers and theoperator control switch, while protecting them from accidentaloperation. The left-hand front, and left-hand side panels arelocated on spigots and secured to the frame by screws.
A display and control panel on the front of the cabinet permits theoperator to monitor the performance of the UPS.
The cabinet houses both the power components and the batteries.It is carried on six wheels. Jacking feet help to support the UPS,and also prevent it from moving once it has been wheeled into itsfinal position. These feet are also used to secure the equipment toits shipping pallet during transit. Dimensions of all availablemodels are given in the Specification at the end of this manual.
Cooling is by a set of internal fans. Air is drawn in through theUPS and exhausted via ventilation grills in the rear and sidepanels. These areas must be kept free of anything that mayimpede the air flow into and out of the unit.
1.3 Principle of operation
1.3.1 Basic Concept
The UPS acts as an AC - DC - AC converter. The arrangement ofthe main components is shown as a block diagram in figure 1-2.
The AC - DC stage comprises three steps; in the first step the a.c. isconverted by a rectifier to d.c.; in the second step a resonantconverter converts the d.c. to high frequency a.c.; and in the thirdstep a rectifier converts the high frequency a.c. to high voltaged.c. A battery, to provide power when the input to the rectifierfails, is charged by a battery charger which is run from theresonant converter.
The DC - AC stage comprises a high frequency inverter whichconverts power from the high voltage d.c. rectifier back to a.c. atthe input supply voltage and frequency.
The use of a high frequency converter and a high d.c. voltagebring advantages of size and weight reduction while permitting awide input voltage range.
The main switch permits the operator to connect the outputterminals directly to an a.c. input supply via the maintenancebypass line, and a static switch permits the UPS to do the sameautomatically, if necessary.
1.3.2 Primary Power Path
The Input rectifier converts the incoming 3-phase 50Hz a.c. inputsupply to d.c. power at a nominal 580V at its output - i.e. theprimary d.c. busbar. The rectifier is uncontrolled and the voltageon the d.c. busbar will vary as the input voltage varies.
The resonant converter comprises a resonant circuit, isolationtransformer and a high frequency rectifier. The rectified 3-phaseinput supply is converted to single phase a.c. power at highfrequency, and then converted to high voltage d.c. by a high
frequency rectifier. The d.c. output is regulated by the convertercontroller to 800V d.c. which is ±400V, with respect to neutral, topower a high frequency transformerless inverter. The inverter
converts the 800V d.c. power to 3-phase, 50Hz, a.c. power at theoutput for use by the critical load. The control electronics ensurethat the inverter output is synchronised with the bypass supply.
Issue 3 (01/03/98) 1-1
AP4300
AP4300
UPS NORMAL NO ALARMShh:mm:ss
dd:mm:yy
Figure 1-1 Front view of the cabinet
Figure 1-2 UPS Basic block diagram
InputRectifier
StaticSwitch
ResonantCircuit
HighFrequencyRectifier
Inverter
Battery
BatteryCharger
BypassSupply
InputSupply
Outputto Load
MaintenanceBypass Line
Main SwitchSW1
High frequency harmonics are filtered so the load sees a clean,sinusoidal waveform with low harmonic distortion.
The battery charger is a.c. coupled to the converter and convertsthe high frequency sine wave to 435V d.c. for charging thebattery. A standard AP4300 system uses one set of thirty-two 12V batteries, connected in series, to provide a nominal batteryvoltage of 384V d.c. (the standard 15/20kVA models contain twosets of thirty-two 12 V batteries). When the input supply becomesunavailable the input rectifier stops maintaining the d.c. busvoltage. The battery then provides power to the primary d.c. bus,and the battery charger becomes inactive.
1.3.3 Static switch
The static bypass (SBP) switch is an electronically-controlled switchwhich, when turned on by the UPS, connects an a.c. input supplydirectly to the UPS output terminals (a load transfer). The load isthen supplied directly from the a.c. input supply. The a.c. supplyto the static switch, annotated ‘bypass supply’ in figure 1-2, canbe taken from the same source as that supplying the inputterminals, or may be taken from a separate source (Split Bypass).
Two conditions cause the static switch to perform a load transfer:
1) when the UPS control electronics automatically shut down the
inverter because of an overload condition or a UPS internal
failure such as an inverter fault; the static switch closes
simultaneously so as to transfer the load to the bypass supply.
2) where the bypass supply to the UPS is taken from a separate
source (Split Bypass), and the battery has discharged after
supplying power to the load following either a failure of the
input power supply to the input terminals or an input
overvoltage.
During start up and normal operation, the inverter control logicensures that, provided the bypass supply voltage and frequencyare within defined limits, the inverter output and the static bypasssupply will be synchronised within specified limits. Transfersbetween the inverter output and the static bypass supply can thentake place without a break in the power supply to the load.However, if the bypass supply voltage or frequency go outsidetheir set limits, the UPS can no longer automatically transfer theload to the bypass, and a message on the LCD display panelwarns of this condition.
Whenever power is supplied to the SBP during a start up or aftera bypass input failure, the control system checks that the supplyvoltage and frequency are within tolerance and that the phaserotation is correct, and then tests the operation of the SBP switchby briefly transferring to bypass. During the test a [UPS ONBYPASS] message is displayed on the LCD panel (see Section 1.7.1.-
LCD Display - Controls & Screen).
CautionWhen the load is being supplied through the static
switch or the maintenance bypass line, it is connecteddirectly to the input power supply and is therefore no
longer protected against power failures or power supplyfluctuations.
1.3.4 Maintenance bypass line
The maintenance bypass line provides a direct connectionbetween the load and the bypass supply for use when the UPS isshut down for maintenance or troubleshooting. The load is switchedto the maintenance bypass line manually with the main controlswitch, SW1.
Note: A manual transfer to bypass is not recommended if abypass alarm is present, unless a message on the LCD
display panel requests it.
1.4 System operation
The resonant converter, battery charger, inverter and static switchare controlled by a microcontroller board. Figures 1-3 to 1-7illustrate the load power paths through the UPS during its majoroperating modes. The resonant converter, the high frequencytransformer and the high frequency rectifier are shown as a singleblock in these diagrams. The solid black lines represent the‘active’ power paths.
1.4.1 Operation during ‘normal’ conditions
During normal operation, the input rectifier provides power, viathe resonant converter and high frequency rectifier, to theinverter. The inverter provides power to the load, and the batterycharger float charges the battery at 435V. See figure1-3
1.4.2 Operation during input power supply failure
If the a.c. input power supply to the UPS fails, the rectifier stopssupplying power to the inverter; the battery is automaticallyconnected to the d.c. busbar via an SCR so that the inverter takesits power from the battery, as shown in figure 1-4; and the batterycharger becomes inactive.
The period for which the load is supplied by the battery after ainput power supply failure (the Autonomy Time) depends uponboth the battery capacity, and the percentage of the rated loadbeing supplied. Refer to the equipment specification at the end ofthis manual.
1-2 Issue 3 (01/03/98)
Chapter 1 - General Description AP4300
Figure 1-3 UPS Normal operation
InputRectifier
StaticSwitch
ResonantConverter
Inverter
Battery
BatteryCharger
BypassSupply
InputSupply
Outputto Load
MaintenanceBypass Line
Main SwitchSW1
Figure 1-4 Operation from the battery after aninput power supply failure
InputRectifier
StaticSwitch
ResonantConverter
Inverter
Battery
BatteryCharger
BypassSupply
InputSupply
Outputto Load
MaintenanceBypass Line
Main SwitchSW1
When the battery is fully discharged, the action taken by the UPSdepends on whether the bypass supply is taken from the samesource as the main input (common bypass), or from a separatesource (split bypass).
Units with split bypass
When the end of battery discharge is reached in a split bypasssystem, the UPS transfers the load to the bypass supply, closingthe static switch and switching off the battery SCR, as shown infigure1-5.
CautionWhen the load is being supplied from the bypass line
through the static switch, it is connected directly to theinput power supply and is therefore no longer protected
against input power supply disturbances.
If, later, the input power supply returns, the input rectifier powersup and the UPS automatically re-starts the inverter, opening thestatic switch to transfer the load back to the inverter. The systemis then in the normal operating condition and recharging thebatteries.
Units with common bypass
When the end of battery discharge is reached in a common bypasssystem, the inverter shuts down and power to the load is lost.
Automatic restart facility:
A UPS with a common bypass will automatically restart if theinput power supply returns after the autonomy time expires,provided the control switches have not been operated in themeantime.
Note: The auto-restart facility may be disabled by an entryon the control panel. If the auto-restart facility has beendisabled, a message on the LCD panel will indicate thiswhen the supply returns. Restart the UPS by using the
controls on the LCD panel to switch the output on. Refer toChapter 2 - Operating Instructions.
1.4.3 Operation during abnormal / fault conditions
If the inverter develops a fault, or suffers a severe overload orovertemperature condition, the UPS automatically transfers thecritical load to the bypass supply by closing the static switch andshutting down the inverter – see figure1-6. The battery chargerwill remain active.
1.4.4 Maintenance bypass.
Setting the main control switch, SW1, to Maintenance Bypassconnects the UPS output terminals directly to the bypass supplyterminals via the internal maintenance bypass line, as shown infig. 1-7, so that the critical load is powered from the bypasssupply. The inverter and converter are shut down and the staticbypass switch disabled.
This isolates the critical load totally from the inverter output so thatUPS faults can be investigated without affecting the power supplyto the load. Refer to the section on the Operator's Controls laterin this chapter for details.
CautionWhen operating on maintenance bypass power, the loadis unprotected against input power supply disturbances.
Therefore the load user should be informed when thismode is selected.
1.5 Electrical switches
1.5.1 Circuit breakers and fuses
Circuit breakers CB1 - CB3 connect the supply from the bypassterminals to the static switch; circuit breakers CB4 - CB6 connectthe supply from the input terminals to the UPS; and the batteryfuses FS1, FS2 are contained in fuse holders carried in a fusedswitch which disconnects the UPS from its batteries (FS3 in the15/20kVA units is used to disconnect the second set of batteriesonly). The fuses are isolated from the circuit when the switch isopened so that the fuses can be replaced safely.
Issue 3 (01/03/98) 1-3
IOM Manual Chapter 1 - General Description
Figure 1-6 UPS Operation on static bypass after an
inverter fault condition.
InputRectifier
StaticSwitch
ResonantConverter
Inverter
Battery
BatteryCharger
BypassSupply
InputSupply
Outputto Load
Maintenance Bypass LineMain Switch SW1
Figure 1-7 UPS Maintenance Bypass Selected.
InputRectifier
StaticSwitch
ResonantConverter Inverter
Battery
BatteryCharger
BypassSupply
InputSupply
Outputto Load
Maintenance Bypass Line Main Switch SW1
Figure 1-5 Split Bypass - Load is transferred to bypass when
end of battery discharge is reached.
InputRectifier
StaticSwitch
ResonantConverter Inverter
Battery
BatteryCharger
BypassSupply
InputSupply
Outputto Load
MaintenanceBypass Line
Main SwitchSW1
CautionFuse holders and circuit breakers should be
opened/closed only by competent personnel whenrequired. It is not necessary to open or close them
during normal operation.
1.5.2 Control switches
The UPS is controlled by the ‘Main Control Switch’ (SW1), which isa four position switch, and an ‘OUTPUT OFF’' switch (SW2). The locationand use of these switches is described later in this chapter.The UPS can also be controlled from the front panel -see section 1.7 .
1.5.3 Internal Cutout Relays
Input Overvoltage Cutout
If the input voltage exceeds 477V, the UPS will isolate the powercomponents from the input by opening the Input OvervoltageCutout Relay, located in the input circuit between the circuitbreakers (CB4 to CB6) and the input rectifier, and will switchto battery operation; refer to Section 1.4.2. - Operation during
input power supply failure for details. Powering the load from theMaintenance Bypass line is not recommended when this relay hasopened in a common bypass system.
Inverter Output Cutout
If an internal fault turns off the resonant converter, the UPS willtransfer the load to bypass automatically. The Inverter OutputCutout Relay, located in the circuit between the inverter outputand the rotary switch, SW1, will open to protect the inverter fromthe possibility of damage due to reverse power from the bypassline.
1.6 Operator control switches
The equipment contains two switches that are used by theoperator, in addition to the pushbuttons on the display panel.These are the Main Control switch and the Output Off switch.Their locations are shown in figs.1-9 & 1-16.
Note: If any alarms are triggered when SW1 is at OFF orMAINT, ignore the alarm, otherwise refer to Chapter 5 -
Troubleshooting for the appropriate action.
1.6.1 Main control switch
The Main Control Switch (SW1) is a four position rotary switchfitted behind the right hand front panel on the front of the UPS(see fig.1-9). The panel is held in place by means of two angledslots cut in each side of the panel. These slots hook overcorresponding spigots on the cabinet frame. Remove this panel by
pushing up on its lower edge and lifting it away from the cabinet, asshown in fig.1-8. The four switch positions are: OFF;
MAINTENANCE (MAINT); TEST; and UPS.
Off position
SW1 is turned to OFF when the output must be turned off. In the OFF
position all SW1 contacts are open (fig.1-10) and there is no powerat the UPS output terminals.
Maintenance position
When SW1 is set to MAINT, it connects the UPS output terminalsdirectly to the bypass supply (fig.1-11) if this supply is available. Itwill power the critical load while leaving the UPS shut down formaintenance or repairs on-site.
1-4 Issue 3 (01/03/98)
Chapter 1 - General Description AP4300
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss
dd:mm:yy
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss dd:mm:yy
Figure 1-8 Removing the front panel to get access to the mainswitch (SW1).
AP4300
ESC
LOAD nn.n KVAO/P VOLTS nnn VacUPS NORMAL NO ALARMShh:mm:ss dd-mm-yy
LOAD nn.n KVAO/P VOLTS nnn VacUPS NORMAL NO ALARMShh:mm:ss dd-mm-yy
TESTMAINT
SW1
OFF UPS
TESTMAINT
SW1
OFF(0)
OFF(0)
UPS
Figure 1-9 View of the cabinet with the front panel removed toshow the location of the main control switch, (SW1).
SW1
TESTMAINT
OFF UPS
TESTMAINT
OFF UPS
Figure 1-10 Power off & SW1 at OFF
UPSPowertrain
Staticbypass
To Load
SW1
TESTMAINT
OFF UPS
TESTMAINT
OFF UPS
Figure 1-11 On maintenance bypass
UPSPowertrain
Staticbypass
To LoadMaintenance bypass
Test position
When set to the TEST position the UPS power train neutral isconnected to the neutral line. The load continues to be powered viathe maintenance bypass (MBP), and the UPS control system starts totest the converter, battery charger, inverter, phase rotation and staticbypass switch in sequence. The default window shows themessage Testing. Each section is enabled when the tests on it arecompleted satisfactorily. Finally, if no faults are found, the staticbypass switch closes automatically. The default window messagechanges to Tests Passed, Turn SW1 to UPS.
Note that the load is still powered via the MBP line (fig.1-12),and will not be connected to the UPS output until switch SW1 hasbeen set to ‘UPS’.
If any problems are found, they will be indicated on the displaypanel, and the UPS will inhibit the transfer of the load to theinverter. This ensures that if SW1 is subsequently set to ‘UPS’while a fault exists, the load will not be supplied by the inverter butby the static bypass. Faults found can then be corrected before theycan affect the power supply to the load. This position is also usefulfor testing the UPS manually after repairs, while the UPS continuesto be powered from the maintenance bypass.
UPS position (normal operation)
When SW1 is set to UPS, the load switches from the maintenance lineto the UPS output without a break in the power supply to theload. A mechanical overlap ensures break free switching; i.e. theload is connected briefly to both the maintenance line and thestatic bypass line during the switchover with SW1.
The load is now supplied by the static bypass line alone (fig.1-13). Finally, the control system, after a six second delay, transfersthe load from the static bypass line to the inverter (fig.1-14).
1.6.2 Input/Battery fuse holders
The UPS circuit breakers for the input and bypass supplies and thefused switches for the battery fuses, (fig.1-15), are located behind thefront detachable panel, (fig. 1-8). These serve as switches whichshould be operated only by competent personnel, when required.There is no need to open or close them during normal operation.
Note: To refit the front panel, first engage the slots on the panelwith the corresponding spigots on the cabinet, and then allow
the panel to drop into place.
Issue 3 (01/03/98) 1-5
IOM Manual Chapter 1 - General Description
SW1
TESTMAINT
OFF UPS
TESTMAINT
OFF UPS
Figure 1-12 Tests OK; static bypass turned on.
UPSPowertrain
Staticbypass
To LoadMaintenance bypass
SW1
TESTMAINT
OFF UPS
TESTMAINT
OFF UPS
Figure 1-13 On UPS
UPSPowertrain
Staticbypass
To LoadMaintenance bypass
SW1
TESTMAINT
OFF UPS
TESTMAINT
OFF UPS
Figure 1-14 On UPS
(After transfer to UPS - i.e. normal operation)
UPSPowertrain
Staticbypass
To LoadMaintenance bypass
TEST
MAINTMAINT
O/P OFF
UPS
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss dd:mm:yy
TESTMAINT
SW1
OFF(0)
OFF(0)
UPS
INPUTBYPASSBATTERYFUSES
CB2 CB3CB1 CB5 CB6CB4FS2FS1
Figure 1-15 Input, bypass and battery fuse locations
1.6.3 Output Off Switch (SW2)
CautionPressing the Output Off pushbutton will turn the
inverter off and remove power from the load.
When this switch ispressed, the controlsystem shuts down theinverter and disablesthe static bypassswitch. The UPSdisplay remains active.The resonant converteris also turned off, but isswitched on for 5minutes at 1 hourintervals to permitbattery charging. Referto later sections forinformation on how torestore power to theload. The Output Offswitch is mounted onthe back panel of theUPS and is recessedinto its housing toreduce the chance ofaccidental operation.
1.6.4 LCD controls - on/off command
CautionSelecting Output Off will turn the inverter off and
remove power from the load.
The Command feature, accessed from the main menu, is provided sothat the operator can switch the UPS on and off by using thecontrols on the LCD display panel. This permits the operator toturn the UPS OFF as part of its day-to-day operation – at the endof the working day for example - without having to repeat the fullstart-up sequence to turn the UPS back ON.
When the output is selected OFF the microcontroller removespower to the load in the same way as when the Output Off switchis pressed and continues to monitor the UPS. When the output is setON, the UPS control system tests the converter, inverter, and staticbypass switch in sequence before switching on the converter andinverter. The UPS output and LED indications then return tonormal.
1.6.5 Remote Stop Switch(optional)
A connection is provided for a switch, which can be locatedremote from the UPS, and which has the same function as theOutput Off switch. When it is operated it shuts down the inverter,and inhibits the static switch so that power is removed from theload.
CautionPressing the Remote Stop pushbutton
will turn the inverter off and remove power from theload.
WARNINGThe mains input, bypass input and battery terminals
still carry lethal voltages after pressing the Remote Stopswitch. Do not remove covers from these parts. Only
competent personnel should remove external panels heldin place with screws.
The Remote Stop switch can be either a latching or a non-latchingswitch. However it has the highest priority so that, if a latchingswitch is used, it must be reset after operation before the UPSoutput can be enabled from any source.
1.6.6 Optional operator controls
The operation of the UPS can be controlled from externallocations if one or more of the available communication options isconnected. Instructions from a remote terminal will be effective onlywhen they are enabled. Any subsequent commands, from whateversource, will over-ride previous commands - but see the notebelow.
Note: Any OFF command will have a higher priority than anON command from another origin. If the UPS does not
respond to the operator controls as expected, ensure that allOFF commands from any connected options have been
unlatched
The additional options are described in Chapter 4 - Options.
1.6.7 Emergency Shutdown
In order to remove power from the output in an emergency, moveSW1 rapidly to position OFF.
1-6 Issue 3 (01/03/98)
Chapter 1 - General Description AP4300
Figure 1-16 View of the back of the
cabinet showingthe location of the
Output Off switch, (SW2).
SW2
1.7 Operator Control & Display Panel
An operator control and display panel, shown in fig.1-17, is fittedon the front of the UPS. It permits the operator to select textdisplays from a menu of options for display on an LCD (LiquidCrystal Display) screen by means of pushbuttons on the panel,and provides information on the basic operational and alarmstatus of the UPS by means of LEDs (Light Emitting Diodes)which can be on, off or flashing on/off.
The operator panel can be considered as two zones. The LEDdisplays form an upper zone, which comprises five separate areas,and the LCD screen and its associated cursor control pushbuttonsform a lower zone. These parts of the screen are identified bylabels in fig.1-17. The key to these labels is given below:
Key to Labels in Fig. 1-17
LED Display LCD & Controls
1. Monitor mimic 6. Cursor up Pushbutton
2. Battery Status 7. Cursor down Pushbutton
3. Load Status 8. LCD Screen
4. Battery Charge State 9. Enter Pushbutton
5. Alarm Indicator/CancelButton
10. Escape Pushbutton
1.7.1 LCD Display, Controls & Screen
Function
The LCD zone consists of an LCD screen with 4 rows of 20characters, and four pushbuttons, as shown in fig.1-17. Thepushbuttons permit the operator either to select options from amenu for display on the screen, or else to change the value ofcertain parameters. The screen shows messages which, forexample, provide status information or, when an alarm occurs,indicate the reason for the alarm.
LCD Screen Pushbuttons
ENTER
Pressing ENTER, when selecting options, displays thenext window in the direction of the arrows on themenu map. The next window is determined by theoption which has been selected in the present window.
When setting parameters, it saves the new parameter values.
ESCAPE
Pressing ESCAPE cancels the most recent actions; i.e.when selecting options it returns the previous windowto the screen; when setting parameters, it exits thewindow without saving the new settings.
UP
The UP pushbutton moves a cursor up the screen overoptions offered on certain windows, and moves arectangular cursor to the next digit on the right whenchanging parameter values in others.
DOWN
The DOWN pushbutton moves a cursor down thescreen over options offered on certain windows, andchanges parameter values in others.
The Menu Options
A map of the routes to the options offered by the menu isprovided in fig.2-2. Options include windows which show statusinformation and windows which permit data to be entered, orparameters for equipment control to be set. The menu map showsthat the routes pass from the main menu through differentintermediate windows to reach the option targeted. The diagramshows each of the windows in the format in which it appears onthe LCD screen. The initialising, default & main menu windowsare described below.
LCD Display Panel Messages
• Initialising Window:
After first connecting power to the UPS (with switch SW1 OFF),the message:
AP4300INITIALISINGPLEASE WAIT
will appear on the LCD screen. It persists for about five secondswhile the control firmware is loaded. It is then followed by amessage showing what the next action should be.
• Default Window:
The message shown below, will be seen on the default screenwhenever the UPS is operating normally (see fig.1-18):
AP4300
UPS NORMAL NO ALARMSdd-mm-yy hh:mm:ss
The top line gives the UPS model number; the third line displaysthe UPS operational status and indicates alarm conditions whenthey occur; and line four normally shows the time and date. If UPor DOWN pushbutton symbols, or both: appear between thetime and date, as shown in the INTERNAL SHUTDOWNwindow in fig.2-2, then two or more faults have been detected.Use the UP/DOWN pushbuttons to scroll through the alarmmessages. Refer to Chapter 5 - Troubleshooting, for moredetails.
Issue 3 (01/03/98) 1-7
IOM Manual Chapter 1 - General Description
ESC
????????????????????????????????????????????????????????????????????????????????
????????????????????????????????????????????????????????????????????????????????
1 2 543
6
7
8
9
10
Figure 1-17 Identification of the main parts ofthe operator
panel
ESC
• Main Menu Window:
The main menu is selected from the default window by pressingthe enter key:
STATUSCOMMANDSSETUPMAINTENANCE
The four windows accessed from the main menu offer furtheroptions which are described in the relevant chapters of thismanual.
The STATUS option gives access to windows which show thepresent values of measured parameters such as input & outputvoltages and current, load etc. These parameters are useful whendetermining the state of the UPS or the causes of alarms, and aredescribed in more detail in Chapter 6 - Maintenance.
The COMMANDS option permits the operator to switch the UPSoutput on and off; to set times when the UPS output switches onand off; to set the conditions when the UPS will respond to ashutdown command from an external system; and to initiatebattery tests. See Chapter 2 - Operating Instructions.
The SETUP option permits the operator to set the date, time andthe language in which messages are displayed. Their use isdescribed in Chapter 2 - Operating Instructions.
The MAINTENANCE option provides the route to the windowswhere a service engineer can configure the UPS to suit itsoperational environment. Entry to these windows requires apassword. This manual does not provide servicing instructionsand the options accessed from this window are therefore notshown on the menu map in fig.2-1. Only trained service engineersshould be authorised with a password. Refer to theCommissioning Manual for details.
Option Selection Mode: If a window from which options can beselected is displayed, a pair of indicator arrows appear at the topof the screen:
The UP /DOWN pushbuttons move these up and down the screenover the options. When the arrows point at a chosen option, pressENTER to display the next window. Press ESCAPE to return theprevious window to the screen.
Parameter Change Mode: If a window where a parameter can bechanged is displayed, the cursor appears as a flashing rectanglesuperimposed on the first digit of the parameter. The function ofthe pushbuttons in this mode of operation is shown below:
SELECT SETADJUST CANCELDD-MM-YY HH:MM:SS0-00-00 00:00:00
Press the DOWN pushbutton to adjust the value of the digitby increasing it. If it goes past the end of its range, it will returnto zero. When the digit is at its required value, press the UPpushbutton to select the displayed value and move the cursorto the next digit. When all digits have been assigned, pressENTER to set, i.e. save, the new value for the parameter: theprevious window returns to the screen. Pressing ESCAPE atany time cancels the new settings and returns the previouswindow to the screen without saving any of the changes.
1.7.2 LED Displays
The basic operational status of the UPS is displayed by means ofLEDs in the five areas, (items 1-5), already identified in the upperzone of the operator panel in fig. 1-17. The LED display permitsthe status of the UPS to be seen when LCD screens other than thedefault window are in use.
The LEDs are identified in fig. 1-18. The meaning of the LEDswhen ON is summarised in the table below.
Meaning of the Operator Panel Indicator LEDs(refer to fig.1-18)
Key LED Colour NormalState
Indication when ON
1 InputPowersupply
Green on Input power supply present
2 StaticSwitch
Amber off Load on bypass
3 Inverter Green on Load on UPS
4 BatteryStatus
Amber off Battery is discharging -UPS is ‘on battery’
5 OverloadIndicator
Amber off Output has exceeded 100%of full load
6 ChargerFault
Amber off Charger is faulty (LEDflashes)
7 Alarm Red off A condition requiringattention has developed(LED flashes) (see below)
8 BatteryCapacityIndicator
Green on State of charge of battery;each of the 5 LEDsrepresents 20 % of batterycapacity (see below)
9 O/PLoad
Indicator
Green on Output load as % full load;each of the 5 LEDsrepresents a fraction of theload (see below)
A number of these LEDs indicate alarms, when they occur, byflashing on/off. Several of these alarms are also accompanied byan audible warning from the alarm horn. In all cases a message inthe LCD default eason for the alarm. Details are given inChapter 5 - Troubleshooting.
1-8 Issue 3 (01/03/98)
Chapter 1 - General Description AP4300
ESC
AP4300
UPS NORMAL NO ALARMSdd-mm-yy hh:mm:ss
AP4300
UPS NORMAL NO ALARMSdd-mm-yy hh:mm:ss
1 2 3 4 59 8 6 7
Figure 1-18 - Identification of the LEDs on the operator panel
ESC
1.7.3 Indicator Bars
Output load indicator
These six LEDs operate as a percentage load indicator bar andindicate the load on the phase with the highest load.
The left-most five LEDs are green and illuminate progressively asthe load increases. The load ranges are 10-20, 20-40, 40-60, 60-80 and 80-100 percent of the UPS full load rating. The sixth LEDis amber and illuminates when the output of any phase exceeds100 percent. This LED is therefore normally accompanied by anOVERLOAD alarm and an audible warning.
If an overload occurs, the UPS automatically transfers the load tothe static bypass supply after a time interval which depends onthe overload magnitude - the greater the overload, the shorter thetime interval.
Battery Capacity Indicator
The first five LEDs are green and operate as a bar indicator toshow the state of battery charge when charging, and to showbattery capacity remaining when the UPS is operating on batterypower. The sixth LED is amber and flashes to indicate when thereis a charger fault.
During battery charging the bar indicator LEDs lightprogressively from left to right until all five LEDs are ON, andthe battery is fully charged; the battery charger then turns OFF.The time taken to reach full charge will depend on the load: thehigher the load, the higher the rate of charge.
When the battery is fully charged, a ‘burn and coast’ routine putsthe battery on charge for one hour every twelve hours. Battery lifeis prolonged when it is kept fully charged in this way.
When the UPS is operating on battery power, the battery barindicates the battery capacity remaining. The bar indicator LEDsprogressively extinguish as the battery discharges, each LEDrepresenting approximately 20% of the rated autonomy time atthe current load.
1.7.4 Alarm indicator & horn cancel button
The audible alarm cancel button carries a red LED that flasheson/off whenever the UPS detects certain fault conditions.
Several fault conditions are also accompanied by an insistentaudible warning signal which can normally be cancelled bypressing the horn cancel button. The LED will continue toindicate the alarm until the fault condition has cleared. Details ofthe audible alarms are given in Chapter 5 - Troubleshooting.
Issue 3 (01/03/98) 1-9
IOM Manual Chapter 1 - General Description
Figure 1-19 Output load indication
Figure 1-20 Battery autonomy indicator
Figure 1-21 Fault indicator and audible alarm cancel button
1-10 Issue 3 (01/03/98)
Chapter 1 - General Description AP4300
Chapter 2 - Operating Instructions
2.1 Introduction
WARNINGOPERATION OF THE CONTROL SWITCH (SW1)
FROM THE “UPS” (ON) POSITION THROUGH TOTHE “OFF” POSITION PASSES THROUGH BOTH
THE “TEST” AND “MAINT” POSITIONS. THEINTERNAL MAINTENANCE BYPASS SYSTEM IS
THEREFORE ACTIVATED DURING THISOPERATION.
IF THE UPS HAD PREVIOUSLY BEEN SWITCHEDOFF BY EITHER THE LOCAL OUTPUT OFF SWITCH
(SW2) OR BY A REMOTE STOP PUSHBUTTONSWITCH, TURNING THE CONTROL SWITCH (SW1)FROM THE “UPS” (ON) POSITION TO THE “OFF”
POSITION WILL ACTIVATE THE INTERNALBYPASS SYSTEM AND THEREFORE APPLY POWER
SUPPLIES TO THE LOAD.IN ORDER TO AVOID ACCIDENTALLY APPLYING
POWER SUPPLIES TO THE LOAD VIA THEINTERNAL BYPASS SYSTEM, ISOLATE THE POWER
SUPPLIES TO THE BYPASS SYSTEM BEFORETURNING THE CONTROL SWITCH (SW1)
THROUGH THE “TEST” OR “MAINT” POSITIONS.
This chapter describes how to switch the UPS manually into anyone of the following five operating modes:
• Normal - i.e. supplying uninterruptible power to the load.
• Output Off - i.e. UPS on, but no power supplied to theload.
• On Maintenance Bypass - i.e. load isolated from inverter.The load is powered directly from the input power supply.
• Power off - i.e. UPS switched off and isolated from the mainssupply.
• On Battery - i.e. UPS running on battery: selectedautomatically after a input power supply failure.
The UPS can also be started up manually On Battery with theUPS controls - i.e. a ‘black start’.
Note: As soon as power is connected to the UPS themicrocontroller and UPS display panel become active and
LED1 will switch ON.
Details of the Control switches, LED display panel and LCDscreen referred to in the procedures can be found in Chapter 1 -
General Description.
The control switches are accessed by removing the right handfront panel. The panel is held in place by means of two angledslots cut in each side of the panel. These slots hook overcorresponding spigots on the cabinet frame. Remove this panel bypushing up on its lower edge and lifting it away from the cabinet,as shown in fig.2-1.
Issue 3 (01/03/98) 2-1
AP4300
ESC
LOAD nn.n KVAO/P VOLTS nnn VacUPS NORMAL NO ALARMShh:mm:ss dd-mm-yy
LOAD nn.n KVAO/P VOLTS nnn VacUPS NORMAL NO ALARMShh:mm:ss dd-mm-yy
TESTMAINT
SW1
OFF(0)
OFF(0)
UPS
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss dd:mm:yy
TESTMAINT
SW1
OFF UPS
SW2
Figure 2-1 Location of the main control switch, (SW1) and Output off switch (SW2).
2.2 The Operating procedures
2.2.1 Introduction
The procedures described in this chapter have been categorisedinto two sections as listed below, (a) for operator use and (b) foruse by personnel deemed competent.
(a) Operator Procedures
1. Starting up the UPS: i.e. cold start (p.2-2).
2. Setting Time, Date and Language (p.2-4).
3. Switching power to the load on or off without ever switching
off the UPS; includes output off switch operation (p.2-6),
control panel commands (p.2-6), and commands from
external systems (p.2-8).
4. Running the UPS On Battery; i.e. when the supply fails (p.2-8).
(b) Competent Personnel Procedures
1. Applying Power to the UPS (p.2-10).
2. Starting up the UPS on battery (’black start’) (p.2-11).
3. Powering the load via the Maintenance Bypass (p.2-11).
4. Removing power from the UPS (p.2-12).
These procedures must be followed without deviating from themin any way. They comprise a sequence of actions and adescription of the corresponding LED indications and LCDmessages that appear on the screen.
2.2.2 Fault Indications
The UPS monitors its internal operation and input/outputparameters continuously, and indicates any abnormal condition onthe operator display panel. Abnormal conditions can be causedeither by an internal malfunction within the UPS (UPS faults), orby problems with the power supply or the load (external faults).When a fault condition is detected, an alarm is triggered.
Alarms are indicated by a warning horn and/or one or moreflashing LEDs on the display panel. A message on the LCDscreen identifies the reason for the alarm. The warning hornsounds when an alarm requires immediate attention from theoperator.
Refer to Chapter 5 - Troubleshooting for a description of thealarms and the action to be taken in response to them.
Important notes
Note 1: The operator controls and LED indicators referredto in these procedures are fully described in Chapter 1.
Note 2: When applying power to the UPS, if the displays donot respond as indicated in the procedures, and unprotected
power to the load is required, select MAINTENANCE andseek assistance. Otherwise shut down the UPS immediatelyby turning switch SW1 to OFF, and then remove power from
the UPS.
2.3 Cold Start Procedure
Starts up the UPS from the DE-ENERGISED or
MAINTENANCE states, and takes it to the NORMAL state.
WARNINGTHE FOLLOWING PROCEDURE WILL APPLYPOWER TO YOUR LOAD AND DISTRIBUTION
SYSTEMS. ENSURE IT IS SAFE TO DO SO.
During start-up, the LEDs indicate the current UPS state. Analarm is triggered if a fault is found, and the start up screenindicates the position to which the switch should then be set.Press the alarm reset push-button on the display panel to cancelthe audible alarm, if required. Refer to Chapter 5 -
Troubleshooting for more information about alarms.
1. Pre-Start checks
Remove the UPS front ‘lift-off’ panel; see fig.2-1.
The main control switch (SW1) is either in the OFF or
MAINT position. If it is in the OFF position proceed as
below; otherwise proceed to step 3.
Ensure that the input and bypass circuit breakers and battery
fuse holders are CLOSED. If they are open, refer to section
2.7.
Ensure that the UPS input power supply, and bypass supply
where a split bypass system is used, are switched ON
externally. If they are off, refer to section 2.7.
The LCD display will be displaying the start up screen, and a
message indicates that the rotary switch (SW1) should be
turned to TEST:
AP4300TURN SW1 TO TESTUPS OUTPUT OFF14-02-95 14:35:00
2. Select MAINTENANCE with SW1.
The load is connected directly to the bypass supply via the
MBP line, and the third line on the LCD display changes:
AP4300TURN SW1 TO TESTON MAINTENANCE B/P14-02-95 14:35:00
3. Select TEST with SW1.
The UPS starts a self-test routine while the load is supplied by
the MBP line. The message on the start up screen on the LCD
Display Panel indicates that testing is in progress:
TESTINGPLEASE WAITON MAINTENANCE B/P14-02-95 14:35:00
2-2 Issue 3 (01/03/98)
Chapter 2 - Operating Instructions AP4300
CautionWait until the message:
turn SW1 to ******appears on the display before
taking any further action.
If testing fails at any stage, an error message appears on line 1
of the start up screen, together with an error code:
TESTS ABORTED NNTURN SW1 TO MAINTON MAINTENANCE B/P14-02-95 14:35:00
The two hexadecimal digits (indicated by: NN) in the error
message permit the cause of the test failure to be identified
(see Chapter 5 - Troubleshooting).
If the tests proceed satisfactorily, the converter starts up,
followed by the inverter a few seconds later; the inverter LED
switches on; and the UPS fans start. The SBP switches on to
transfer the UPS output to bypass; the bypass LED switches
on; and the inverter LED switches off. Note that the load is
not supplied via the SBP at this stage because the UPS output
has not been connected to the load; i.e. SW1 has not been
switched to UPS. The load is still connected to the MBP.
The message on the screen indicates that SW1 should be
turned to UPS.
TESTS PASSEDTURN SW1 TO UPSON MAINTENANCE B/P14-02-95 14:35:00
4. Select UPS with SW1.
The load is connected to the UPS output in a break free
operation and is initially supplied by the static bypass line.
Provided the bypass and inverter outputs are synchronised
and within specified limits, and there is no overload, the load
is transferred to the inverter after a 6 second delay. The
bypass LED switches OFF, and the inverter LED switches
ON.
The LCD Display Panel startup screen is replaced by the
‘Default’ screen, shown below:
AP4300
UPS NORMAL NO ALARMS14-02-95 14:35:00
5. Refit the UPS front panel.
The panel is held in place by means of two angled slots cut in
each side of the panel, as shown in fig.2-1. Present the panel
to the UPS so that these slots hook over corresponding spigots
on the cabinet frame. Let the panel drop into place. If
necessary press its top edge firmly back into the cabinet.
2.3.1 NORMAL operation
During ‘NORMAL’ operation LED1 is ON, to indicate that theinput power supply is available (and within specification) andLED3 is ON to indicate that the UPS is supplying the load.The battery capacity bar indicates the charge in the battery.The percentage load bar indicates the proportion of the maximumload being supplied.
Note: When the UPS is started from cold for the first time,the indicated battery capacity may not be as specified untilthe battery is fully charged; i.e. until it has been on charge
for twenty-four hours.
Issue 3 (01/03/98) 2-3
IOM Manual Chapter 2 - Operating Instructions
2.4 Settings
2.4.1 Introduction
At any time after power has been applied to the UPS successfully,the operator adjustable settings - date, time and language - can bereset if necessary. The date and time are included on the defaultand alarm history screens. The language which is selecteddetermines which language is used for displaying LCD messages.
2.4.2 Setting Date, Time & Language
When it is necessary to change the date, time or language used inthe screens, display the default window, and press the ENTER
pushbutton to display the main menu window:
STATUSCOMMANDSSETUPMAINTENANCE
Use the UP / DOWN pushbuttons to point at the SETUP option in themain menu, and press ENTER. The screen below appears:
SET DATE AND TIMESELECT LANGUAGE
(Press ESC to return to the default display when necessary).
Set Date and Time
Select SET DATE AND TIME to display a screen where the clockand calendar settings can be reset by using the UP/DOWNpushbuttons.
SELECT SETADJUST CANCELDD-MM-YY HH:MM:SS0-00-00 00:00:00
The digits below DD-MM-YY represent the pairs of digits forentering the Day, Month and Year for the date. Similarly thosebelow HH:MM:SS represent the pairs of digits for enteringHours, Minutes and Seconds for time. A flashing cursor in theform of a grey rectangle will be seen over the first DAY digit.
1. Increment the first DAY digit by pressing the DOWN
pushbutton until the correct digit is displayed.
Note: If you step past your intended number, keep pressingthe pushbutton to scroll through to zero and repeat the
operation.
2. Advance the cursor to the next digit by pressing the UP
pushbutton.
3. Repeat steps 1 and 2 until the date digits are set
correctly.
4. When the date is set, the cursor moves on to the time
digits. Repeat the procedure for the time and, when
completed, exit by pressing the ENTER key. Pressing
ENTER resets the internal clock to the new time and date
and returns the SETUP screen to the display.
Notes:
1. The procedure can be abandoned at any stage withoutresetting the date and time by pressing ESC.
2. Take care that out of range numbers (e.g. month 13) arenot set inadvertently.
Set Language
The language in which messages are displayed on the LCD screenis selected from this screen (i.e. SETUP).
1. Move the cursor, with the UP / DOWN pushbuttons, to
SELECT LANGUAGE, and press ENTER, to display the
LANGUAGES window:
ENGLISH ESPANOLFRANCAIS DEUTSCHITALIANO
2. Move the cursor, with the UP / DOWN pushbuttons, to
point at the language required, and press ENTER. The
selected language is now set and the SETUP screen
returns to the display.
Note: The procedure can be abandoned at any stage withoutresetting the language by pressing ESC.
2.4.3 UPS Configuration
The UPS is configured for its application by assigning values tovarious parameters from configuration screens which areaccessed from the MAINTENANCE option on the main menuscreen. Only a Liebert approved commissioning engineer shouldset up the configuration. It must not be changed subsequently,except by an authorised engineer. The operator does not need tohave access to these screens, and so access is protected by meansof a password.
Figure 2-2. shows a map of all screens that can accessed by theoperator.
2-4 Issue 3 (01/03/98)
Chapter 2 - Operating Instructions AP4300
Issue 3 (01/03/98) 2-5
IOM Manual Chapter 2 - Operating Instructions
SETDATEANDTIMESELECTLANGUAGE
FRANCAISITALIANO
ENGLISH ESPANOLDEUTSCH
ENTERPASSWORD
SELECTADJUST
SETCANCEL
****
BATTERYINFORMATION
OUTPUTBYPASSBATTERYINTERNAL
OUTPUTFREQUENCYFREQUENCY(Hz)50.0
SYNCHRONISED
OUTPUTCONTROLOUTPUTOFFOUTPUTON
TIMEDOPCONTROL
DELAYEDOPOFFDELAYEDOPON
CANCELDELAY
BATTERYTESTTESTBATTERY
LASTTESTRESULT
OUTPUTCONTROLTIMEDOPCONTROLSHUTDOWNCONDITIONBATTERYTEST
UPSNORMAL NOALARMS14-02-94 14:35:00
FAULT
TESTSPASSEDTURNSW1TOUPSONMAINTENANCEB/P
14:35:0014-02-94
14:35:0014-02-94
TURNSW1TOMAINTONMAINTENANCEB/P
TESTSABORTED NN
STATUSCOMMANDSSETUPMAINTENANCE
OUTPUTVOLTSL-LL1-2400
L3-1400
L2-3400
OUTPUTVOLTSL-NL3240
L2240
L1240
BYPASS
FREQUENCY(HZ)50.0
L1240
L3240
L2240
OUTPUTPOWERKW
0.88 0.88089L1 L3L2
TOTAL 2.65KW
OUTPUTPOWERKVA
0.87 0.870.87L1 L3L2
TOTAL 2.61KVA
OUTPUTCURRENTAMPSL1
1.4L31.4
L21.5
TIME 00:41:24420 100 ON
VOLTS CAP%CHARGER
DCBUSVOLTS
800PRIMARYSECONDARY400
TORETURN
SELECTADJUST
SETCANCEL
DD-MM-YY00-00 -00
HH:MM:SS00 :00 :00
SHUTDOWNCONDITIONONBATTERYATANYTIME
DCBUSTEMPERATURESINFORMATION
ERRORPAGEUPSSTATUSEVENTHISTORY
ERRORPAGE(status)(UPSaction)(message/fault)
UPSSTATUSCONVERTER ONINVERTER ONBATTERYCHARGERON
COMMUNICATION
FAULTATANYTIME
AP4310FATALERROR
CALLFORSERVICE01793553355
#XX
NOMESSAGE
14-02-94 14:35:00
NOREPORT
NORMAL
STARTUPTESTSOK
INITIALISATIONTESTSOK
14:35:0014-02-94
AP4300TURNSW1TOTESTUPSOUTPUTOFF
SWITCHONATMAINISOLATOR
CLOSEBATTERY
FUSES
AP4300INITIALISING
PLEASEWAIT . . .
INV AMB
MAG
CONV BAT 23
24
40
42
38
Figure 2-2 Map of the displays on the LCD screen accessible by the operator
2.5 Switching the Output Off/On
This section describes how to switch the UPS output off in a way
that enables it to be switched on again without repeating the full
start-up sequence.
The facility is provided for use as part of day-to-day operationwhen the UPS output is turned off only for a short period, (i.e. put intoStandby mode); e.g. at the end of the working day, when the UPSis turned off overnight. The battery is kept charged up while theUPS is in Output Off mode.
The UPS output can be switched off by operating SW2 on theback of the UPS, by using the controls on the UPS control panel, or bysending commands from an external system via an optionalcommunications interface.
When the output is selected OFF the microcontroller removespower to the load from the UPS output terminals by switching theinverter off; it also inhibits the static switch, but continues tomonitor the UPS. When the output is set ON, the inverterswitches on, and the UPS output and LED indications then returnto normal.
2.5.1 Output Off Switch SW2
CautionPressing the Output Off pushbutton will
cut off power to the load.
1. To switch output off - Press SW2 and hold it pressed briefly.
The bypass and inverter LEDs switch OFF, while the input LED
stays ON.
If the default screen is not displayed, press Escape on the LCD
control panel several times until it is. The screen will show that the
output is OFF:
AP4300
UPS OUTPUT OFF14-02-95 14:35:00
The DOWN arrow on the fourth line shows that another status
message has also been triggered. Pressing the DOWN button
displays it:
AP4300
LOCALLY STOPPED14-02-95 14:35:00
The message LOCALLY STOPPED shows that the UPS was
switched off with SW2.
WARNINGIF THE DISPLAY DOES NOT INDICATE THAT THE
UPS OUTPUT IS OFF AND LOCALLY STOPPED,THEN REMOVE THE LIFT'OFF COVER, AND
TURN SW1 TO OFF.
2. To return to normal operation, use the operator panel controls (see
below).
2.5.2 Operation from the UPS control panel
Immediate Switching
The operator can switch the UPS output ON or OFF, without usingthe main switch, SW1, by using the controls on the LCD controlpanel instead.
1. Select COMMAND from the main menu display to obtain the
Control screen. The cursor is at OUTPUT CONTROL:
OUTPUT CONTROLTIMED OP CONTROLSHUTDOWN CONDITIONBATTERY TEST
2. Press Enter; the display below appears:
OUTPUT CONTROLOUTPUT OFFOUTPUT ON
To turn the UPS output off:
CautionSelecting the ‘OUTPUT OFF’ will cut off power
to the load.
With the cursor set at OUTPUT OFF, press Enter; the display
asks for confirmation:
OUTPUT CONTROLOUTPUT OFFOUTPUT ONPRESS TO CONFIRM
Press Enter a second time. The inverter LED switches off as
the inverter shuts down, and the load loses power.
Press Escape several times to return to the default window.
The message:
AP4300
UPS OUTPUT OFF14-02-95 14:35:00
will appear. the UPS will stay in this state, with the battery on
charge, until either the UPS output is switched on, or the
input power supply fails.
2-6 Issue 3 (01/03/98)
Chapter 2 - Operating Instructions AP4300
To turn the UPS output on:
WARNINGTHE FOLLOWING PROCEDURE WILL APPLYPOWER TO YOUR LOAD AND DISTRIBUTION
SYSTEMS. ENSURE IT IS SAFE TO DO SO.
Select COMMANDS from the main menu display to obtain
the Output Control screen. Press the Down button to set the
cursor at OUTPUT ON, and press Enter; the display asks for
confirmation:
OUTPUT CONTROLOUTPUT OFFOUTPUT ONPRESS TO CONFIRM
Press Enter a second time. The inverter LED switches on
briefly, as the inverter starts supplying the load; the bypass
LED switches on, and the inverter LED switches off as a
bypass test is performed; if the default screen is selected (by
pressing Escape several times) it will indicate the UPS status
as:
UPS ON BYPASS
while the test is in progress; finally the inverter LED switches
on and the bypass LED switches off, as the bypass test is
completed and the inverter supplies the load. At the end of the
sequence, which is completed in about ten seconds, the
default window indicates the status as:
UPS OUTPUT ON
Scheduled Switching
This facility permits times when the UPS automatically switchesthe output on, and/or switches it off, to be set.
Select COMMANDS from the main menu display; move thecursor to TIMED OP CONTROL (Timed Output Control) andpress Enter. Three options are presented on the screen:
DELAYED OP ONDELAYED OP OFFCANCEL ALL DELAYS
To set a time when the UPS output will switch ON - (DELAYED
OP ON)
WARNINGSETTING PARAMETERS FOR DELAYED OP ONWILL APPLY MAINS VOLTAGE TO THE LOADEQUIPMENT AT THE DESIGNATED TIME(S).
IF APPROPRIATE A NOTICE STATING WHEN THISWILL HAPPEN SHOULD BE PLACED BESIDE ALL
LOAD EQUIPMENT.
The cursor will be aligned with DELAYED OP ON; press Enter.The screen which allows a date and time to be set is displayed:
SELECT SETADJUST CANCELDD-MM-YY HH:MM:SS0-00-00 00:00:00
Refer to Section - Setting Date, Time & Language on p.2-4 fordetails of how to set these parameters. The character in the areabetween the time and date settings indicates how often the outputswitches on. The switching frequency selected can be one of thefour options shown in the table below. The character thatindicates each option is also shown in the table.
1 Single occasion; i.e. only at the set time on the setdate.
1
2 Daily occasion; i.e. at the set time on the set dateand at the same time every day afterwards, untilcancelled.
D
3 Weekly occasion; i.e. at the set time on the setdate and at the same time on the same day everyweek afterwards, until cancelled.
W
4 Cancel current selection
Notes:1. The default setting is: ; i.e. no times selected for
switching the output on.2. The time & date must always be set in the future.
To select the switching frequency, press the UP pushbutton afterthe time has been set, so that the cursor moves to the position forthe character for the switching frequency; press the DOWN
pushbutton to scroll round the options until the correct character isdisplayed; press the UP pushbutton to move the cursor to the dataarea for the date and set the required date as described inSection 2.4.2 referred to above.
When this screen is first displayed it will show the switchingfrequency and the time and date currently set for it. If thecharacter shown is cancel, then the actual time will be shown,stopped at the moment when the screen was entered.
To set a time when the UPS output will switch OFF -
(DELAYED OP OFF)
CautionSetting parameters for DELAYED OP OFF will
cut off power to the load at the designated time(s).
Move the cursor down so that it is aligned with DELAYED OPOFF; press Enter. The screen which allows a date and time to beset is displayed, as described above; follow the same procedure,but the switching action now will switch the output off instead ofon.
Issue 3 (01/03/98) 2-7
IOM Manual Chapter 2 - Operating Instructions
To delete all automatic switching settings - (CANCEL ALL
DELAYS)
Select COMMANDS from the main menu display; move thecursor to TIMED OP CONTROL (Timed Output Control) andpress Enter. Move the cursor down to CANCEL ALL DELAYS andpress Enter. The display asks for confirmation:
DELAYED OP ONDELAYED OP OFFCANCEL ALL DELAYSPRESS TO CONFIRM
Press Enter to confirm (ESC to cancel). The previous screen (theCOMMANDS menu) returns.
2.5.3 Switching with External Commands
General
The UPS output can be switched on or off by means of commandsfrom an external system via an optional SNMP card or an RS232interface connected to the communications board in the UPS. Theseare described in Chapter 4 - Optional Equipment. The user canset how the UPS will respond when it receives an externalshutdown command - see below.
Shutdown Condition
The Shutdown Condition setting determines what the state of the
UPS must be before it will switch the output off when an operator
sends a shutdown command. One of two conditions can be
selected:
1. On Battery - The UPS will switch the output off only if it is
running on battery when the operator sends the shutdown
command.
2. At Any Time - The UPS will switch the output off at any
time, (i.e. it can be running on the input power supply or on
battery power) when the operator sends the shutdown
command.
Procedure
With the COMMANDS menu on the display. Set the cursor atSHUTDOWN CONDITION, and press Enter. The screen shownbelow will appear:
SHUTDOWN CONDITIONON BATTERYAT ANY TIME
Move the cursor to the option required by using the up/downpushbuttons. Select the ON BATTERY option if the UPS output mustonly be switched off when it is running on battery power; selectthe AT ANY TIME option if the UPS output must be switched offwhen the UPS is running on either the input power or batterypower.
After selecting the required option, press Enter. The display asksfor confirmation:
SHUTDOWN CONDITIONON BATTERYAT ANY TIME
PRESS TO CONFIRM
Press Enter to confirm (ESC to cancel). The previous screen (theCOMMANDS menu) returns.
Status display
When the default screen is next displayed after the UPS outputhas been switched off by an external command, the status will beshown on line 3 of the screen; e.g. after a command from anexternal system to switch the output off, the default screen shows:
AP4300
UPS OUTPUT OFF14-02-95 14:35:00
The UPS will stay in this state with the battery on charge untileither it is switched on, or the input power supply fails.
2.6 Input Power Supply Failure
2.6.1 General
When the input power supply fails, the UPS runs On Battery. Youshould consider shutting down your load in a controlled manner –e.g. save data.
The way in which the UPS responds to a input power supplyfailure depends on whether it is on-load or off-load when theinput power supply failure occurs.
2.6.2 Input Supply Failure when On Load
If the UPS loses its input power supply the amber battery-on-load indicator (LED 4) will illuminate; the warning hornwill sound a single half second long tone every 10 seconds andcannot be cancelled. On a common bypass system, LED2 willflash, indicating a loss of the bypass supply, and LED 1 willswitch off.
Note: For units with a separate bypass supply, LED 2 willnot flash while the bypass supply is present, but will be OFF.
The battery time remaining, at the present load, is shown on thesecond line of the LCD panel as follows:
AP4300TIME 03:50:40
UPS ON BATTERY14-02-95 14:35:00
As the battery discharges, the battery time decreases, and thebattery capacity bar LEDs extinguish progressively from theright; each LED represents 20% of capacity. When the batteryautonomy time remaining falls below a user set value (set duringcommissioning), the warning horn will beep every 5 secs.
If the input power supply returns before the battery time expiresthe battery charger switches on automatically, and the UPSreturns to normal operation after a short time delay.
When the battery becomes discharged, the UPS will attempt totransfer the load to bypass. If the bypass is available (split bypasssystem) the transfer will succeed. If no bypass is available(common bypass system) the UPS turns the output off which willalso remove power from the control circuits.
2-8 Issue 3 (01/03/98)
Chapter 2 - Operating Instructions AP4300
Re-starting from a input power supply failure on load
Common bypass system
Autorestart Enabled (default):- An Automatic Restart facility
ensures that a UPS with a common bypass will automatically
restart if the input power supply returns after the autonomy
time expires, provided the control switches have not been
operated in the meantime. The facility can be disabled during
commissioning if necessary.
CautionCheck the battery capacity after each discharge. If thebattery has been heavily discharged the UPS will shut
down without warning, with loss of power to the load, ifa second power failure occurs whilst the autonomy time
is zero.
A unique feature of the AP4300 permits the operator to
observe the battery condition by referring to the BATTERY
screen.
From the main menu window align the cursor with STATUS and
press the ENTER key. Select BATTERY on the screen that is
displayed and press the ENTER key. The state of the battery will
be shown in the following form:
BATTERY INFORMATIONVOLTS CAP % CHARGER
420 0 ONTIME 00:00:00
This display shows that the battery is unable to support the
load if a failure was to occur: the battery capacity is zero, and
the autonomy time at the current load is zero.
Autorestart Disabled:- The auto-restart facility may have
been disabled on commissioning. When the supply returns
with the auto-restart disabled, the LCD panel will show the
message:
UPS OUTPUT OFF
Restart the UPS by using the controls on the LCD panel to
switch the output on. Refer to Operation from the control
panel - Immediate Switching on p.2-6.
Split bypass system
When the input supply returns, the input rectifier powers up
and the UPS automatically re-starts the inverter, opening the
static switch to transfer the load back to the inverter. The
system is then in the normal operating condition and
recharging the batteries.
2.6.3 Input Supply Failure when Off Load
If the input supply fails after the UPS output has beenswitched off - i.e. an OUTPUT OFF message is displayed on thedefault screen - the amber battery-on-load indicator (LED 4) willilluminate; the warning horn will sound; and LED2 will respond inthe same way as when there is a Failure On Load, described above.
The default screen shows the autonomy time remaining, on thesecond line:
AP4300TIME 03:50:40
UPS ON BATTERY14-02-95 14:35:54
The autonomy time slowly counts down as battery power isconsumed. When a period of fifteen minutes has elapsed after theinput supply first failed, the control system shuts down the UPSto conserve battery power. The LCD screen goes blank and theLEDs extinguish.
Re-starting from a failure off load
When the input supply is restored, the screen below will be seenon the display:
AP4300
UPS OUTPUT OFF14-02-95 15:51:00
It is recommended that the UPS is then started using one of thefollowing methods:
a) Use the controls on the operator panel and follow the
procedure to turn the UPS output on under Operation from
the control panel - Immediate Switching on p.2-6.
b) Switch the UPS output on by means of a command from an
external system sent over a communications link; refer to
section on p.2-8.
Issue 3 (01/03/98) 2-9
IOM Manual Chapter 2 - Operating Instructions
The following procedures of Chapter 2 are for competent personnel only
2.7 Applying Power to the UPS
Starts the UPS from the POWER OFF state and sets it in the DE-ENERGISED state ready for a ‘Cold Start’.
WARNINGENSURE THE EQUIPMENT HAS BEEN
COMMISSIONED BY A LIEBERT APPROVEDSERVICE ENGINEER BEFORE PROCEEDING.
1. Initial checks
Remove the UPS front ‘lift-off’ panel – see fig.2-1.
Ensure that the main control switch (SW1) is in the OFF
position.
Ensure that the optional Remote Switch, if connected, is set
at on.
Ensure that the input, and bypass circuit breakers (fig.3-17)
are CLOSED.
WARNINGIF YOU CLOSE THE BATTERY FUSE HOLDERSWHEN SW1 IS AT UPS AND AUTO-RESTART IS
ENABLED, THE UPS WILL FOLLOW THE STARTUP SEQUENCE AUTOMATICALLY; ENERGISE THE
OUTPUT; AND POWER THE LOAD VIA THE UPS.
2. Close the battery fuse holders, FS1 & FS2 (fig.3-17) & FS3
(15/20kVA).
The battery, and on-battery LEDs will switch on. If the UPS
detects an internal fault, the following screen appears:
AP4300INT FAILURE XXXXCALL FOR SERVICE
Otherwise, after about five seconds, the initialising message:
AP4300INITIALISINGPLEASE WAIT
will appear on the LCD screen. It persists for approximately 2secs while the control firmware is initialised.
If all is well, then the start-up screen:
AP4300TURN SW1 TO TESTUPS OUTPUT OFF14-02-95 14:35:00
is displayed and the procedure should continue with step 3
below.
If, instead of the start-up screen, the screen below is
displayed:
SETUP DATA ERRORRELOADING DEFAULTS
PRESS TO CONTINUE
then the system has detected that the parameter settings have
become corrupted during initialisation, and a SETUP error
message has been generated. Press Enter to accept (user has
no option); the screen below is then displayed:
OUTPUT WILL RUN AT230V
PRESS TO CONTINUE
CautionIf the load will be damaged by being supplied with
power at 230V then open the battery fuse holders andcall for a service engineer to reset the parameters.
If an output voltage of 230V is acceptable, press Enter to
accept; the default parameter settings (listed in the table of
parameter settings at the end of this manual) will be reloaded.
While the new data is being loaded and checked, the LEDs on
the load & battery bargraphs repeatedly switch on & off
successively from one end to the other and back again. They
continue cycling in this way, with the sequences in the upper
and lower bargraphs switching in opposite directions, until
the parameters have been re-loaded, when the start-up screen
shown above is displayed. Continue with the procedure at
step 3 below.
3. Power up the UPS by switching the input power supply ON at
the external isolator(s).
The on-battery LED will switch off, and the input LED will
switch on; the start-up screen shown above continues to be
displayed and indicates the position to which the main control
switch should be turned next. This will be ‘TURN SW1 TO
TEST’ if no problems have been detected. After each switch
operation during start up, the position to which the main
control switch should be turned next is updated.
The cold start procedure in the operator section can now befollowed.
2-10 Issue 3 (01/03/98)
Chapter 2 - Operating Instructions AP4300
2.8 Starting up the UPS on battery ( ‘blackstart’)
2.8.1 General
While it is possible to start the UPS from ‘cold’ without thesupply connected, this is not a normal way to start up.
2.8.2 Procedure
Starts the UPS from the POWER OFF state, sets it in the ON-
BATTERY state and supplies the load with power.
WARNINGENSURE THE EQUIPMENT HAS BEEN
COMMISSIONED BY A LIEBERT APPROVEDENGINEER BEFORE PROCEEDING.
1. Initial checks
Check that input power is not available.
Remove the UPS front ‘lift-off’ panel – see fig.2-1.
Ensure that the main control switch (SW1) is in the OFF
position.
Ensure that the optional Remote Switch, if connected, is set at
on.
2. Turn SW1 to UPS.
3. Close the battery fuse holders, FS1 & FS2 and FS3 (15/20kVA
units).
The battery, and on-battery LEDs will switch on. After about five
seconds, the initialising message:
AP4300INITIALISINGPLEASE WAIT
will appear on the LCD screen. It persists for approximately 2
secs while the control firmware is initialised. Replace the
UPS front ‘lift-off’ panel removed in step 1 above,
– see fig.2-1.
4. Turn the UPS output on.
WARNINGTHE FOLLOWING PROCEDURE WILL APPLYPOWER TO YOUR LOAD AND DISTRIBUTION
SYSTEMS. ENSURE IT IS SAFE TO DO SO.
Select COMMANDS from the main menu display to obtain theOutput Control screen. Press the Down button to set the cursor atOUTPUT ON, and press Enter; press Enter a second time to confirm.Refer to section for full details. The inverter is now supplyingthe load.
2.9 To Put the Load on Maintenance Bypass(MBP)
These instructions describe how to shut down the UPS while the
load continues to be powered via the MBP line.
CautionThe load will not be protected from variations in theinput power supply when supplied via the MBP line.
CautionThe following actions will shut down the UPS.
Note: In the following procedure ignore the second line on theLCD screen; it shows where SW1 should be turned next if the
UPS is being started up.
1. Select the default screen on the LCD Display Panel, and
remove the UPS front ‘lift-off’ panel –see fig.2-1.
2. Select TEST with SW1.
WARNINGIF THE OUTPUT OF THE UPS HAS BEEN TURNED
OFF, TURNING SW1 TO TEST WILL RE-APPLYINPUT POWER TO THE LOAD
EQUIPMENT/DISTRIBUTION SYSTEM. ENSURETHAT IT IS SAFE TO DO SO.
The load is transferred briefly to the static bypass while the
switch is operated and then to the MBP supply line.
The LEDs indicate the current status - i.e. LED(1) ON, LED(2,
3) OFF.
The LCD screen shows the current status of the UPS on its
third line; i.e. load on maintenance bypass:
TESTS PASSEDTURN SW1 TO UPSON MAINTENANCE B/P14-02-95 14:35:00
3. Turn SW1 to MAINT position.
The LEDs indicate that the UPS status is the same as in step 2
above.
The LCD screen also shows that the current status is
unchanged:
AP4300TURN SW1 TO TESTON MAINTENANCE B/P14-02-95 14:35:00
The UPS is now supplying the load via its MBP line.
4. Isolation of the internal components of the UPS.
Open the input and bypass circuit breakers, CB1 to CB6.
Open the battery fuse carriers, FS1 & FS2.
The LCD display and all LEDs will switch off as the power to
the internal components of the UPS decays.
It is safe to remove the battery fuses and for trained electricians tocarry out maintenance on the UPS while it is on MBP. Note thatthe only parts of the UPS that are still live are the terminals and the‘hot box’ behind them.
Issue 3 (01/03/98) 2-11
IOM Manual Chapter 2 - Operating Instructions
2.10 Removing Power
Follow the procedure in steps 1-4 above, and then follow the
procedure below to isolate the UPS and LOAD totally from the
power supply.
CautionThe following actions will remove power from the load.
5. Turn SW1 to O/P OFF to remove power from the LOAD
completely.
WARNINGTHE INPUT, BYPASS INPUT, AND UPS OUTPUT
TERMINALS STILL CARRY LETHAL VOLTAGES.DO NOT REMOVE COVERS FROM THESE PARTS.
ONLY COMPETENT PERSONNEL SHOULDREMOVE PANELS FASTENED WITH SCREWS.
6. Isolate the UPS from its external supplies by opening the
input power isolator external to the UPS, and, in a split bypass
system, the external bypass power isolator also.
Refer to Section 2.7 - Applying Power to the UPS, on p.2-10 torestart the UPS from this state.
2-12 Issue 3 (01/03/98)
Chapter 2 - Operating Instructions AP4300
Chapter 3 - Installation Instructions
These instructions are for use by competent personnel only.
3.1 Safety warnings
WARNINGDo not switch on electrical power to the UPS equipment oroperate any of its switches before it has been commissionedby an authorised engineer. Failure to observe this condition
will invalidate any implied warranty.
WARNING - Battery hazardsSpecial care should be taken when working with the
batteries associated with this equipment.When connected together, the battery terminal
voltage will exceed 380Vdc and is potentially lethal.Eye protection should be worn to prevent injury from
accidental electrical arcs.If a battery leaks electrolyte, or is otherwise physicallydamaged, it should be placed in a container resistant tosulphuric acid and disposed of in accordance with local
regulations.If electrolyte comes into contact with the skin the
affected area should be washed immediately.
WARNINGTHE UPS IS HEAVY AND IS FITTED WITH
CASTORS – TAKE CARE TO PREVENTMOVEMENT WHEN UNBOLTING THE
EQUIPMENT FROM ITS SHIPPING PALLET.ENSURE SUFFICIENT PERSONNEL TRAINED INMOVING HEAVY EQUIPMENT ARE AVAILABLE
WHEN REMOVING THE UPS FROM ITS SHIPPINGPALLET. REFER TO THE INSTRUCTIONS IN
SECTION 3 - REMOVAL FROM SHIPPING PALLET.
WARNINGTake care that the UPS does not tip over when it is beingmoved. The position of its centre of gravity is shown in
Fig.3-1.
WARNINGOPERATION OF THE CONTROL SWITCH (SW1)
FROM THE “UPS” (ON) POSITION THROUGH TOTHE “OFF” POSITION PASSES THROUGH BOTH
THE “TEST” AND “MAINT” POSITIONS. THEINTERNAL MAINTENANCE BYPASS SYSTEM IS
THEREFORE ACTIVATED DURING THISOPERATION.
IF THE UPS HAD PREVIOUSLY BEEN SWITCHEDOFF BY EITHER THE LOCAL OUTPUT OFF SWITCH
(SW2) OR BY A REMOTE STOP PUSHBUTTONSWITCH, TURNING THE CONTROL SWITCH (SW1)FROM THE “UPS” (ON) POSITION TO THE “OFF”
POSITION WILL ACTIVATE THE INTERNALBYPASS SYSTEM AND THEREFORE APPLY POWER
SUPPLIES TO THE LOAD.IN ORDER TO AVOID ACCIDENTALLY APPLYING
POWER SUPPLIES TO THE LOAD VIA THEINTERNAL BYPASS SYSTEM, ISOLATE THE POWER
SUPPLIES TO THE BYPASS SYSTEM BEFORETURNING THE CONTROL SWITCH (SW1)
THROUGH THE “TEST” OR “MAINT” POSITIONS.
3.2 Installation Considerations
3.2.1 Introduction
These installation instructions provide all the information neededfor positioning the UPS (including environmental requirements),for fitting the batteries, and for connecting the input and outputpower cables.
This equipment complies with the requirements of the EMCdirective 89/336/EEC and the published technical standards.Continued compliance requires installation in accordance withthese instructions and the use of manufacturer approvedaccessories. The external communication cabling assemblies mustbe of the shielded type. The shield must be grounded at the UPSend.
3.2.2 On Delivery
The UPS can be supplied either with or without batteriesinstalled. Battery installation instructions are given later in thischapter for use when the UPS is delivered without batteries.
Carry out a thorough external inspection to verify that the UPS iscomplete and free of damage. Report any damage to the shipperimmediately.
Remove and store the packaging.
3.2.3 Environment
The UPS may be installed in a computer room or other largeoffice environment or in a general plant equipment room. It mustbe located in a cool, dry, dust-free environment with sufficientventilation to keep its ambient temperature below 40oC (104oF).(Note: Operating in temperatures above 25oC (77oF) will reducebattery life). Its environment must also be free of excessive moisture(i.e. no water condensation), flammable vapours, chemical fumes orcorrosive gasses or liquids.
The specification, in Appendix A gives details of the UPS heatemission. If necessary, the room should be equipped with aventilation system to assist cooling. A suitable air filtrationsystem should be used for the incoming air where the UPS is tooperate in a dirty environment.
3.2.4 Position
The UPS is force-cooled with the aid of internal cooling fans.Cooling air enters from the back and from around the base of the
Issue 3 (01/03/98) 3-1
AP4300
ESC
LOAD nn.n KVAO/P VOLTS nnn VacUPS NORMAL NO ALARMShh:mm:ss dd-mm-yy
LOAD nn.n KVAO/P VOLTS nnn VacUPS NORMAL NO ALARMShh:mm:ss dd-mm-yy
AP4300
ESC
LOAD nn.n KVAO/P VOLTS nnn VacUPS NORMAL NO ALARMShh:mm:ss dd-mm-yy
LOAD nn.n KVAO/P VOLTS nnn VacUPS NORMAL NO ALARMShh:mm:ss dd-mm-yy
Figure 3-1 Position of the centre of gravity of the UPS cabinet
complete with batteries.
UPS, and is exhausted through a ventilation grill located at thetop of the back panel; there must be a minimum gap of 300mmbehind the equipment to allow adequate air flow. See figure 3-2.
Maintenance requires unhindered access to the UPS right handside, and you should allow for a clearance there of approximately1000mm. To aid manoeuvrability on all models and forventilation on the 15/20kVA models, a clearance of 100mm isrequired on the left hand side.
Being mounted on castors, the UPS can be installed without sideaccess provided its input and output power cables are held insuitably flexible conduits. The UPS can then be pulled forward togain access for servicing.
3.2.5 Weight considerations
With batteries fitted, the 7.5kVA and 10kVA models weigh 250kg,and the 15kVA and 20kVA models weigh 432kg. This will make itdifficult to move the equipment over certain floor surfaces (e.g.carpet pile) with the batteries fitted. This should be taken intoaccount when preparing for its installation, and when decidingwhether or not to pull the UPS forward for servicing.
If point loading forces must be considered, note that the weight ofthe UPS acts at six wheels and two jacking feet.
3.2.6 Extended battery option
The UPS uses Valve regulated batteries which are housedinternally. However if the installation includes an Extended Batteryoption, the additional batteries are contained in a separate batterycabinet which is attached to the left hand side of the mainequipment. Batteries are fitted into this cabinet from the front, soit is only necessary to provide the 100mm clearance on the left asstated above for the UPS. Detailed installation instructions for theextended battery cabinet are provided with the fitting instructionssupplied in the kit.
3.3 Removal from Shipping Pallet
The UPS will be delivered on a pallet (Fig.3-3).
It is secured to its pallet by means of three brackets. Two (threeon 15/20kVA units) screws fasten the front of the UPS to a frontbracket (Fig.3-4), and an anchor bolt screws up from beneath thepallet base board into each of two jacking feet brackets (Fig.3-5).There is one jacking foot on each side of, and towards the rear ofthe UPS.
Two wood blocks bolted to the pallet, one in front of, and onebehind the UPS, prevent movement of the UPS on the pallet. The15/20kVA units also have side guide rails fitted.
Removal Procedure
WARNINGENSURE THE PALLET IS PLACED ON LEVEL
GROUND BEFORE REMOVING THE UPS.
1. Remove the right hand front panel (Fig.3-6).
2. Undo the screws holding the front bracket to the UPS cabinet
(Fig.3-4).
WARNINGTHE FOLLOWING ACTIONS WILL PERMIT THEUPS TO MOVE ON THE PALLET, WHICH WILL
TILT SO THAT THE UPS CAN ROLL OFF.THE UPS IS HEAVY (WEIGHT WITH BATTERIES
OF 7.5 & 10KVA MODELS= 250KG, 15 & 20KVAMODELS= 432KG).
YOU ARE ADVISED TO OBTAIN ASSISTANCE TOENSURE IT IS KEPT UNDER CONTROL WHILE
BEING MANOEUVRED OFF THE PALLET.
3. Undo the three wood screws fastening the rear wooden block
to the top of the pallet base (on the 15/20 kVA units remove
the six bolts), and remove the wood block (Fig. 3-7).
4. Undo the two bolts fastening the pallet feet to the pallet base
(Fig. 3-7).
3-2 Issue 3 (01/03/98)
Chapter 3 - Installation Instructions AP4300
AP4300AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss
dd:mm:yy
300mm
minim
um
gap
1000 mm minimum access
for fixed installation
100mmminimum gap
Figure 3-2 Locating the UPS
Figure 3-3 Rear view of UPS on its pallet
Jacking feet
pallet foot
Side guide rail
Jacking feet
Wood bolster
5. Undo the two anchor bolts clamping the jacking feet to the
pallet (Fig. 3-5). The heads of the anchor bolts are accessed
from below the pallet base board.
The UPS is now free to move on the pallet.
WARNINGTHE FOLLOWING ACTIONS WILL PERMIT THE
UPS TO ROLL OFF THE PALLET UNDER ITS OWNWEIGHT WITH CONSIDERABLE MOMENTUM.TAKE CARE THAT THE UPS DOES NOT STRIKE
ANY PART OF THE BODY AS IT MOVES.WHEN THE FRONT WHEELS, WHICH COME OFFTHE PALLET LAST, ROLL OFF THE END OF THEPALLET, THE OTHER END MAY JUMP UPWARDS
AND COULD CAUSE INJURY. DO NOT STANDBEHIND THIS END OF THE PALLET WHILE THE
UPS ROLLS OFF.
6. Raise the two jacking feet as high as possible by rotating
them anticlockwise.
7. Ensure that the wheels of the
UPS are aligned so that it stays
square to the pallet when it
rolls off, and will not tilt
sideways.
Stop the UPS from moving by
pushing it against the wooden
block in front of the UPS, in
the direction of the arrow in
Fig.3-8. Remove the two rear
feet and the wooden bolster
assembly by knocking them
away from beneath the pallet.
Hold the UPS steady until the
pallet has settled. It will
balance in a level position
because the centre of gravity of the UPS is located close to its
centre line.
WARNINGTHE FOLLOWING ACTIONS WILL PERMIT THEUPS TO ROLL OFF THE PALLET RAPIDLY AND
WITH CONSIDERABLE MOMENTUM IF IT IS NOTRESTRAINED. ENSURE NO EQUIPMENT IS
IMMEDIATELY IN FRONT OF THE UPS, AND THATALL PERSONNEL ARE AWARE OF THE DANGER.
8. Stand at the side of the
pallet and push the UPS
gently backwards. The pallet
will suddenly tilt (Fig. 3-9),
and act as a ramp with a
steep incline (30% approx.).
The UPS will run down on
to the floor. Restrain the
UPS as it rolls down, to
prevent it running off the
pallet too rapidly.
Issue 3 (01/03/98) 3-3
IOM Manual Chapter 3 - Installation Instructions
Figure 3-4 Detail of the front anchor bracket showing the
position of the screws fastening the UPS to it
Bracket screws
Front bracket
Figure 3-5 Detail of the jacking foot showing the position of the
bolt anchoring the UPS to its pallet
Jackingfoot
wood screws
Bolster bolt
Anchorbolt
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss
dd:mm:yy
Figure 3-6 Remove the right
hand front panel by pushing
upwards on its bottom edge.
Figure 3-7
Figure 3-8
Figure 3-9
3.4 Batteries
3.4.1 Check
Before you install the UPS check whether or not the unit has beenshipped with batteries already fitted.
If batteries are already fitted, their security must be checkedvisually; if they have not been fitted, they must be installed at thisstage.
WARNINGHAZARDOUS VOLTAGE - BATTERY STRINGS CAN
BE VERY DANGEROUS AND GREAT CARESHOULD BE EXERCISED AT ALL TIMES.
NOTE THE SAFETY WARNING ON BATTERYHAZARDS ON P.1 OF THIS CHAPTER.
BATTERIES MUST BE INSTALLED BY A QUALIFIEDELECTRICIAN.
3.4.2 Introduction
General
Battery blocks are six-cell, valve regulated, lead acid batteriesand are carried on seven trays, positioned one above the other inone or two columns on the left hand side of the cabinet, as shown inFigs 3-11 & 3-12. The top tray in a column carries two battery blocks,and the bottom six trays carry five battery blocks each, so that asingle column is made up of a string of thirty-two battery blocksconnected in series to give a nominal voltage of 384V.
Battery blocks are secured in the trays with three captive boltsclamping a plastic bar over their tops, (Fig. 3-15), except in thetop tray where there is only one bolt.
7.5kVA & 10kVA models
A string of thirty-two battery blocks are installed in a singlecolumn on the left hand side of the cabinet, as shown in Fig.3-11& 3-16.
15kVA & 20kVA models
Two strings of thirty-two battery blocks are installed in two columnson the left hand side of the cabinet, as shown in Figs. 3-12 & 3-19.The battery strings in the two adjacent columns are connected inparallel to give the same nominal battery voltage of 384V.
Fuses
Fuses protect the battery from excessive currents when the UPS isoperating. They are carried in switched fuse holders which areprovided in both the positive, (FS2), and the negative, (FS1), batterylines. In the 15/20kVA models FS3 is added, which isolates thesecond string of batteries when fitted. (see fig.3-18). The fuse holdersare opened when installing the UPS in order to isolate the battery.
Fuse sizing
The ratings for the battery fuses are shown in the specification.When replacing fuses ensure that correctly rated fuses are used.
3.4.3 Units shipped with batteries
(For units shipped without batteries, follow steps 1 to 4 below toremove the front and side panels and battery fuses, and then go to thenext section 3.4.4).
Removal of UPS panels
1. Remove the front detachable panel by pushing up its bottom edge,
(Fig. 3-6).
WARNINGBEFORE PROCEEDING, ENSURE THAT THE
BATTERY FUSES, FS1, FS2 AND, IN 15 & 20 KVAMODELS, FS3, HAVE BEEN REMOVED FROM THE
BATTERY FUSE HOLDERS AND THAT THESEFUSE HOLDERS ARE OPEN. POSITIONS ARE
SHOWN IN FIG.3-17.
2. The battery fuses are
packaged separately in a
polythene bag, located
behind the power
compartment cover plate
(see Fig.3-20). Do not fit
them at this stage but keep
them for fitting later in
these instructions.
3. Remove the left hand front
panel, (Fig. 3-10), by
removing the screw (1)
which clamps the flange on
its lower edge to the
cabinet frame, and pulling
the bottom of the panel
away from the cabinet (2).
The panel is held at the top
by means of a tab along its
top edge which fits in a slot in the overhang of the top cover
on the cabinet. The tab is released by allowing the panel to
drop (3) when it is pulled away from the cabinet.
4. Remove the left hand side panel, by releasing three screws at
the front and three on the back of the cabinet; refer to Figs.3-
11 (7.5kVA & 10kVA models) & 3-12 (15kVA & 20kVA
models).
3-4 Issue 3 (01/03/98)
Chapter 3 - Installation Instructions AP4300
TEST
MAINT
O/P OFF
UPS
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss dd:mm:yy
1
2
3
Figure 3-10 Removal of Left
hand front panel.
Figure 3-11 Removal of left
hand side panel.
Figure 3-12 15kVA & 20kVA
models.Battery chamber
access.Remove the left hand side
panel by releasing three screws
on the front and three on the
back of the cabinet.
Checks
5. Carry out the following checks:
a) Check that each battery tray is seated securely on its
rails with the six (three each side) tray guide tabs
locating correctly on the cabinet rails and that the
batteries on each tray are positioned as shown in
Figs.3-15 & 3-16.
b) Check that the battery vents are not obstructed by the
clamping bar (Figs.3-15).
c) Check that the interlinking cables are connected as
shown in Figs.3-15 & 3-16.
6. Replace the left hand side panel and then the left hand front
panel by reversing the procedures described in steps 3 & 4
above.
3.4.4 Units shipped without batteries.
Battery Installation
The batteries must be installed before connecting power cables to theUPS.The recommended battery is a Yuasa NP11-12 or equivalent.
Important Note: Check how many 12V battery blocks havebeen delivered. One string of thirty two is required for the
7.5 & 10kVA models; Normally two strings of thirty two arerequired for the 15 & 20kVA models.
1. Follow steps 1 to 4 described above to remove the front and
side panels and battery fuses.
2. Remove the front horizontal strut(s) and two vertical retaining
brackets in front of the column of battery trays (Fig.3-13) by
removing the screws securing them. Note in the 15 & 20kVA
models there is a second set of vertical brackets on the left
hand side and three horizontal struts, which must also be
removed. Remove the battery trays by sliding them forward
from the front of the UPS. The battery cables, clamps and
bolts are stowed in the trays. Carefully store the battery
mounting hardware until required.
3. Five battery blocks are fitted in the six lower trays, and two
blocks are fitted in the top tray in each column (see Fig.3-16).
Batteries are secured with three captive bolts clamping a
plastic bar over their tops, (Fig.3-15), except for the top tray
which uses one bolt. Fit the batteries as follows:
Note:
Before fitting each battery block, use a suitable voltmeter tocheck that the voltage between its terminals is between
12.5V and 13.0V.
a) Push the clamp bolts through the square slots in the base
of each tray, and locate each bolt head in its captive slot.
b) Set the battery tray on the work area as shown in Fig.3-
14, so that two clamp bolts are on the far side of the
battery stop.
c) Fit the battery blocks on each tray with the terminals on
the left hand side of the tray, as shown in Figs. 3-15 &
3-16.
7.5kVA & 10kVA models: Fit thirty-two battery blocks
in seven trays to make up one column of battery blocks.
Fit two battery blocks in the tray that will be fitted on
the top level of the column of battery blocks, and five
battery blocks in each of the six trays that will be fitted
on the other levels (Fig.3-16).
15kVA & 20kVA models: Fit the first string of thirty
two battery blocks into seven trays to make up one
column of battery blocks. Fit two battery blocks in the
tray that will be fitted on the top level of the column of
battery blocks, and five battery blocks in each of the six
trays that will be fitted on the other levels. Repeat this
instruction for the second string.
d) Batteries are secured in the trays with three captive bolts
clamping a plastic bar over their tops, (Fig.3-15), except
in the top tray where only one bolt is used. Place the
clamp bar over the top of the batteries in each tray, and
ensure that each bolt feeds through its corresponding hole
in the bar.
Note: The clamp bar must be positioned so that it runsbetween the middle and the right hand vents on each battery
as shown in Fig.3-15.
Issue 3 (01/03/98) 3-5
IOM Manual Chapter 3 - Installation Instructions
Figure 3-13 Release the battery trays by removing the screws
holding the struts and retaining brackets in front of them; the
screws holding the left hand brackets are hidden from view in
the diagram.
Note: There is a second pair of brackets in the 15kVA & 20kVA
models, fastened similarly, in front of the left hand column.
Figure 3-14 Battery tray details and orientation.
Batterystop
Clamp bolt
Rail guide(front)
Rail guides
Rail guides(back)
e) Fit a flat washer, locking washer and a nut to the end of
each bolt (Fig.3-15) and tighten down sufficiently to
hold the batteries so that they cannot move in the tray
(recommended torque loading is 2.5Nm).
Battery cabling
1. Cable up the batteries in each tray as follows:
Important Note:
The battery cables are fitted with ‘Fast-on’ connectors.When connecting the cables to the batteries make sure that
the battery tab fits correctly into the connector and notbetween the connector and its insulation.
a) Connect the interlinking cables, marked no.62, between
each of the batteries on each tray as shown in Fig.3-15.
b) Fit a long interlinking cable, marked no.61, to the positive
terminal of the battery at the rear of each tray use cable
ties as indicated in fig.3-15. Leave the front end of the
cable unconnected.
2. a) Refit the battery trays in the battery compartment and
push them fully back on their rails; ensure that the tray
guide tabs (Fig.3-14) are correctly located on the
cabinet rails. Ensure the tray containing two battery
blocks is fitted onto the top set of cabinet rails.
b) Refit the vertical retaining brackets and front horizontal
strut(s) shown in Fig.3-13.
3. Connect the cables between the battery sets in different trays:
7.5 & 10kVA models: Start with the bottom tray and connect
the free end of the long interlinking cable, marked no.61, on
each tray to the front (i.e. negative) terminal of the battery at
the front of the tray immediately above in the same column. See
Fig.3-16. Continue in this way until the trays on all the levels in
the column have been connected.
15 & 20kVA models: Carry out the above procedure on the
right hand column and then on the left hand column of battery
trays.
Battery string voltage checks - 15 & 20kVA models only
When the battery blocks in each column have been connected upto form two battery strings, the voltage across each battery stringmust be checked before connecting them together.
Measure the total voltage of each battery string with a voltmeterset on a DC range above 450V, as described below.
1. Measure and note the voltage of the battery string in the right
hand column by placing the positive meter lead on the
positive terminal (the rear terminal) of the rear battery on the
top tray in the column, and then placing the negative meter
lead on the negative terminal (the front terminal) of the front
battery on the bottom tray in the same column.
Refer to Fig.3-16 The total battery voltage should be between
+384Vdc and +416Vdc.
3-6 Issue 3 (01/03/98)
Chapter 3 - Installation Instructions AP4300
+
-+
-+
-+
-+
-
62
62
62
62
61
Figure 3-15 Battery tray with battery blocks and clamp bar in
position and interlinking cables connected (All models)
recommended torqueloading is 2.5Nm
Clamp bar
battery vent
cable tie
interlinkingcables
Connection to next tray up
++
+
+
+
+
+
-
-
-
-
-
-
-
61
61
61
61
61
61
-ve +ve
B
A
Figure 3-16 Single battery string showing inter row connectors
marked No. 61 and string positive and negative connections.
MeterTerminals
-ve Meter Probe
+ve Meter Probe
BATTERY FUSESINPUTBYPASS
BA
TT
-
BA
TT
+
U3
V3
W3
N3
N2
N4
N1
U2
U1
V2
V1
W2
E1
E2
E3
W1
CB2 CB3CB1FS2FS1 CB5 CB6CB4FS3
SW1TESTMAINT
O/P OFF UPS
Figure 3-17 Detail of the 15 & 20kVA UPS showing the
position of FS1, FS2 & FS3.
FS3
FS1
FS2
2. Repeat step 1 above on the battery string in the left hand
column.
3. If these checks are satisfactory, further connections to the
batteries must be made before continuing with the voltage
checks.
Connection of the UPS cables to the battery string(s)
(7.5 & 10kVA models only)
WARNINGENSURE THE BATTERY FUSES FS1 AND FS2 ARE
NOT FITTED AND THE FUSED SWITCHES AREOPEN.
1. Push the connector on the free end of the red cable marked
no.60 (labelled A in Fig.3-16) that enters from the slot in the
top right hand corner of the cabinet on to the positive (rear)
terminal of the rear battery on the top tray.
2. Connect the free end of the black cable marked no.59
(labelled B in Fig.3-16) that enters from the slot in the bottom
right hand corner of the cabinet to the negative (front)
terminal of the front battery on the bottom tray.
3. Refit the left hand side panel by reversing the procedure
described in step 4 of para.3.4.3, (refer to Fig.3-11).
This completes the battery connections. The total battery
voltage must now be checked before continuing with the UPS
installation. Turn to p.8 and follow the procedure given in the
section: Total Battery Voltage Check.
Connection of the UPS cables to the battery string(s)
15 & 20kVA models only:
WARNINGFUSEHOLDERS FS1, FS2 & FS3 MUST BE OPENWITH THE FUSES REMOVED. DO NOT FIT ANY
FUSES IN THEIR HOLDERS OR CLOSE ANY FUSEHOLDERS UNTIL INSTRUCTED.
1. Connect up the cables to the positive terminal of each battery
string as shown in Fig.3-19, i.e.:
a) Push the connector at the end of the red cable marked
no.55 onto the rear positive terminal of the rear battery
on the top tray of the right hand string. Locate cable
marked no 57 which enters the right hand battery
compartment from its top right hand corner and connect
to cable no 55, using the connectors provided.
b) Repeat the above operation on the left hand battery
string, connecting cable marked no 67 to the battery and
its other end to cable marked no 60.
2. Voltage Difference Check:
Note:- FusesAn additional battery fuse, FS3, is provided in the positive
line between the two battery strings in the 15 & 20kVA units.The fuse protects the two battery strings from excessive
currents flowing between them if they are unevenlydischarged. Fig. 3-17 shows the position of the fuse-holdersFS1, FS2 & FS3 . The block diagram in Fig.3-18 shows how
they are connected to the two battery strings.
Check the difference in voltage between the two battery
strings with a voltmeter set on a DC range above 450V, as
follows:
a) Insert the fuse in fuse holder FS3 and close the fuse
holder.
b) Measure the voltage between the front (negative)
terminals of the front battery block in the bottom tray in
the left and the right hand columns. Refer to Fig.3-19.
c) Open fuse holder FS3; remove and retain the fuse; leave
the fuse-holder open.
WARNINGTHE VOLTAGE READING SHOULD BE IDENTICALTO THE DIFFERENCE IN THE READINGS NOTEDEARLIER (BATTERY STRING VOLTAGE CHECKS)AND MUST NOT EXCEED 32V. IF THE VOLTAGE
DIFFERENCE IS GREATER THAN 32V, THEBATTERIES HAVE BEEN CONNECTED
INCORRECTLY. DISCONNECT THE BATTERYCABLES 55 TO 57 AND 60 TO 67, AND CORRECT
THE BATTERY CABLING SO THAT ASATISFACTORY VOLTAGE INDICATION IS
OBTAINED.
Issue 3 (01/03/98) 3-7
IOM Manual Chapter 3 - Installation Instructions
FS2
55 57
56
5859
65 64 67 60
FS1
FS3
+-
+-
Figure 3-18 Electrical block diagram of the main components in
the battery circuit of the 15 & 20kVA models
To Negative of d.c. bus
To converter SCR
right handstring
Left handstring
++
+
+
+
+
+
-
-
-
-
-
-
-
++
+
+
+
+
+
-
-
-
-
-
-
-
+ve -ve
67
60
55 57
FS2
FS3
Figure 3-19 15 & 20kVA models only:Measuring the voltage
difference between the two battery strings
+ve meter probe
Meterterminals
-ve meter probe
If the voltage difference checks are satisfactory, proceed to thenext step to complete the connections to the batteries.
3. Final battery cable connections (15 & 20kVA models contd.)
Connect up the cables to the negative terminal of each battery
string as follows:
WARNINGFUSEHOLDERS FS1, FS2 & FS3 (FIG.3-17) MUST BE
OPEN WITH THE FUSES REMOVED.
a. Push the fast-on connector of the black cable marked no
58 onto the front negative terminal of the front battery
on the bottom tray of the right hand string. Locate the
black cable marked no 59 which enters the right hand
battery compartment at its bottom right hand corner and
connect it to cable marked no 58 using the connector
provided.
b. Repeat step a above on the left hand string using cable
marked no 64 to the battery and its other end to cable
marked no 65.
c. Refit the left hand side panel (refer to Fig.3-12) by
reversing the procedure described in step 4 of para.3.4.3.
Total Battery Voltage Check -All UPS models
Check the total battery voltage with a suitable voltmeter asfollows:
1. Remove the terminal block cover plate - see Fig.3-20 in order
to gain access to the battery fuse holder terminals.
2. 15 & 20kVA models only - Insert a 30A fuse in fuse holder
FS3 beside the battery compartment (Fig.3-17) and close it.
3. Set the voltmeter on a DC range above 450V.
WARNINGDO NOT FIT FUSES IN BATTERY FUSE-HOLDERSFS1 OR FS2. ENSURE THESE FUSE HOLDERS ARE
LEFT OPEN.
Measure the voltage between the upper screw terminals of thebattery fuses FS1 (negative meter lead), and FS2 (positive meterlead); refer to Fig.3-21. The total battery voltage must be between400Vdc and 416Vdc.
WARNINGENSURE THAT THE METER INDICATES A
POSITIVE VOLTAGE POLARITY. IF A NEGATIVEVOLTAGE IS INDICATED, DISCONNECT THE
EXTENDED BATTERY CABINET CABLES FROMTHE UPS, AND CORRECT THE EXTENDEDBATTERY CABLING SO THAT A POSITIVE
VOLTAGE INDICATION IS OBTAINED.
4. Replace the terminal block cover removed from the UPS in
step 1 above.
5. Refit the left hand front panel by reversing the procedure
described in step 3 of para.3.4.3, (Fig.3-10).
This completes the Battery Installation procedure. Continue theUPS installation by going to Section 3-5 - Final Positioning.
3-8 Issue 3 (01/03/98)
Chapter 3 - Installation Instructions AP4300
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss
dd:mm:yy
TESTTEST
MAINT
O/P OFF
UPS
Figure 3-20 UPS Power cable entry
Powercompartment
cover plate
FusedSwitches(batteryfuses)
CircuitBreakers
Main TerminalBlock
Gland Plate
Cable Entry Aperture
BA
TT
-B
AT
T+
U3
V3
W3
N3
N2
N1
U2
U1
V2
V1
W2
E1
E2
E3
W1
TESTMAINT
SW1
O/P OFF UPS
INPUTBYPASS
CB2 CB3CB1 CB5 CB6CB4
BATTERYFUSES
FS2FS1
+ve -ve
Figure 3-21 Terminals on the UPS on which the meter probes
must be placed to measure the total battery voltage.
FusedSwitchesFS1 &FS2(Battery
Fuses)
3.5 Final Positioning.
1. Wheel the UPS near to its final position but leave adequate
room around it for work.
2. The brackets (2 off) which secure the UPS to its shipping
pallet also serve as ‘jacking feet’ to prevent the UPS from
moving once it is in position.
Important: The jacking feet support a large proportion ofthe equipment weight when the feet are screwed down
tightly.
3. Move the UPS to its final position and screw down both
jacking feet as far as possible.
Important: If the installation was shipped with batteriesfitted and includes an ‘extended' battery option or ‘remote'
battery option these should be connected at this pointfollowing the appropriate instructions supplied with these
options.
3.6 Connecting the UPS Power Cables
3.6.1 General introduction
Power cables connect to screw terminals on a terminal blockwhich is located behind the power compartment front cover plate– see Fig.3-20. They enter the UPS at the front, from beneath, andpass through a gland plate which covers an aperture in the cabinetfloor. Cables used for all input and output distribution shouldenter the UPS via flexible metal conduit which must beterminated at the gland-plate on the UPS. The gland-plate mustfirst be removed and drilled to suit the glands or bushes for thecables. Ensure that the glands are sized so that they hold thecables securely. If the intention is to run the cables to the UPSabove the floor, instead of from below, then the cable must becarried in a flexible metal conduit, and a suitable 60° or 90°elbow must be used where the cable enters the UPS.
A block diagram of the electrical circuit is shown in Fig.3-29.
3.6.2 Cable sizing consideration
The UPS must be installed in compliance with local regulations.
Before cabling-up, careful consideration must be given toselecting the appropriate size power cables and input circuitprotection device – see table 3-1 below.
Note: The maximum cable size that can be connected to theUPS power terminal blocks is 10mm²
Input / Output cables
The UPS requires a 380V/415V three phase input supply andproduces a 380V/415V three phase output. The input, output andbypass cables are all rated the same.
Bypass cables
The bypass supply can either be connected to the UPS inputsupply (common bypass) or it can be linked to a separate threephase power source (split bypass). Figures 3-25 to 3-28 showthese configurations.
Neutral cables
It is important to size the neutral cable according to the type ofload connected. Some loads can give a neutral current equal totwice the line current.
Important: If the intention is to install the UPS in a positionwhere it will be moved away from nearby furniture etc. in
order to gain access for servicing purposes, its power cablesmust be of sufficient length to permit this. When it is in itsworking position the surplus cable must be stowed safely
beneath the equipment.
3.6.3 Input supply protection.
WARNINGTHIS UPS DOES NOT INCORPORATE AUTOMATIC
BACKFEED PROTECTION. A WARNING LABELMUST BE FITTED TO ALL PRIMARY POWER
ISOLATORS STATING:ISOLATE UNINTERRUPTIBLE POWER SUPPLY
BEFORE WORKING ON THIS CIRCUIT
All supplies to the UPS must be provided with three phase powerisolators, each of which can break all its supply lines to the UPSsimultaneously; a split bypass system will require two isolators.The isolator(s) must be located within two metres of the UPS.
Note: The UPS internal input and bypass circuit breakersare type C (IEC 898). The overload characteristics of theinput isolators supplying these circuit breakers must be
selected accordingly.
Refer to table 3-1 in order to choose site supply fuses, circuitbreakers and power isolators appropriate to the UPS currentratings.
On start-up the UPS will take a half cycle inrush current of 7 to 8times the rated current. This must be taken into account whenselecting the overload protection device at the input mains supplydistribution point. To avoid random tripping on start-up, werecommend that the input mains supply is protected with an MCBcapable of withstanding this initial inrush. (An MCB specified asbeing either ‘TYPE 4’ (British Standard) or rated to ‘CURVE D’(IEC 898) is suitable for this purpose.)
Table 3-1 - Power Cable & Fuse Current Ratings
Model Rating 7.5kVA
10kVA
Max input current @ 380V (-15%) (includingbattery charging*)
16A 20A
Maximum bypass current @ 220V (-15%) 14A 18A
Rating for circuit breaker on supply to inputterminals (& to bypass terminals in splitbypass system):Note: Circuit Breaker type ‘C’ (or slower) isrecommended.
minimum 25Amaximum 32A
Table 3-1a - Power Cable & Fuse Current Ratings
Model Rating 15kVA
20kVA
Max input current @ 380V (-15%) (includingbattery charging*)
32A 40A
Maximum bypass current @ 220V (-15%) 28A 36A
Rating for circuit breaker on supply to inputterminals (& to bypass terminals in split bypasssystem):Note: Circuit Breaker type ‘C’ (or slower) isrecommended.
minimum 50Amaximum 63A
Issue 3 (01/03/98) 3-9
IOM Manual Chapter 3 - Installation Instructions
CautionThis equipment is fitted with RFI suppression filters.Earth leakage exceeds 3.5mA but is less than 200mA.
Transient and steady-state earth leakage currents, whichmay occur when starting the equipment, should be taken
into account when selecting instantaneous RCCB orRCCD devices.
Note also that the earth leakage currents of the load willbe carried by this RCCB or RCCD.
WARNINGHIGH LEAKAGE CURRENT - EARTH
CONNECTION IS ESSENTIAL BEFORECONNECTING THE INPUT SUPPLY
THIS EQUIPMENT MUST BE EARTHED INACCORDANCE WITH LOCAL ELECTRICAL CODES.
3.6.4 Output Protection
CautionWhere the load consists of a number of loads, care mustbe exercised that the correct type of rating of protection
is used.Ensure that individual loads are protected and that thecorrect discrimination is maintained between different
load elements.
3.7 Terminal connection points
Fig. 3-22 shows the position of the power cable connectionterminals behind the power compartment cover plate which mustfirst be removed. The input and bypass cables are connecteddirectly to the terminal block. Note that the terminal blocks forthe input phases (U1, V1, W1), and bypass phases (U2, V2, W2),are fitted with bridging links which are removed when the UPS issupplied with a separate bypass supply. Use the proceduresdescribed below for connecting power cables to both the 10 andthe 20 kVA units.
WARNINGTHE BRIDGING LINK FITTED ACROSS THE
NEUTRAL TERMINAL BLOCKS N1, N2 & N3 ON 10KVA UNITS (FIG.3-24) AND ACROSS N1 & N2, AND
N3 & N4 ON 20KVA UNITS (FIG.3-26) MUST NOT BEREMOVED ON A COMMON BYPASS SYSTEM SEE
FIGURE 3-23.
3-10 Issue 3 (01/03/98)
Chapter 3 - Installation Instructions AP4300
BA
TT
-B
AT
T+
U3
V3
W3
N3
N2
N1
U2
U1
V2
V1
W2
E1
E2
E3
W1
TESTMAINT
SW1
O/P OFF UPS
INPUTBYPASS
CB2 CB3CB1 CB5 CB6CB4
BATTERYFUSES
FS2FS1
Figure 3-22
Detail showing power cable connection terminals, fuse locations
and circuit breakers accessed after removing the front panel.
Key to terminal labels
Input Supply U1, V1, W1, N1
Bypass Supply U2, V2, W2, N2
Output U3, V3, W3, N3
Earth E1, E2, E3
Note: The terminal arrangements for the 20kVA unit include an
extra neutral terminal - N4 (see Fig.3-26).
FusedSwitches(BatteryFuses)
ExtendedBattery
Connectors
BypassCircuit
Breakers
InputCircuit
Breakers
EarthConnectionTerminals
CommonBypassLinks
NeutralBridging
Link
PowerConnection
Terminal Block
Neutral linking
Figure 3-23 shows various input alternatives and the arrangementof the bypass links and specifically the neutral link. The upperrow of drawings show the 7.5/10kVA configurations and thelower row shows the 15/20kVA configurations. The UPS powertrain does not require a neutral input, however, it is essential thatthe bypass has a neutral as this is used not only when the systemis in bypass but as a reference by the UPS power train. Thelinking should be arranged as follows:-
Figure AShows a standard common bypass system with a 4 wire and earthinput supply - all links should be fitted.
Figure BShows a Split bypass system with a 3 wire and earth input supplyto the UPS power train and a 4 wire and earth input supply to thebypass - the U, V & W links should be removed; the neutral linkcan be left in position.
Figure CShows a split bypass system with a 4 wire and earth input supplyto the UPS power train and a 3 wire and earth input supply to thebypass - the U, V & W links should be removed; it is essentialthat the neutral links are left in position
Figure DShows a split bypass system with a 4 wire and earth input supplyto the UPS power train and a 4 wire and earth input supply to thebypass - the U, V & W links should be removed; The neutral linkbetween N1 and N2 should also be removed, on the 7.5/10kVAunit this would involve removing the three terminal link andremoving with cutters the N1/N2 link and then refitting the linkonto N2 and N3 terminals.
Connections to Extended and Remote battery cabinets
The black and the red connectors on the leads from the externalbattery cabinet must be connected to their correspondingconnectors on the leads from the terminals directly below thebattery fuses, labelled - and + in figs.3-24 & 3-26 i.e. black toblack and red to red.
The Extended Battery cabinet contains fuses in both its positiveand negative output lines. They are held in the same type of fuseholders as those used in the UPS FS1 and FS2 positions. Thisprovides protection and enables the Extended Batteries to beisolated independently from the internal batteries for servicingetc.
The terminal for the negative connection from theExtended/Remote battery is connected directly to the UPS internalDC busbar negative rail. The terminal for the positive connectionfrom the Extended/Remote battery is connected through FS2, andis therefore connected to the UPS internal DC busbar positive railvia FS2. FS2 therefore carries both the internal and extended orremote battery currents.
The batteries are connected in this way for safety reasons; whenthe UPS battery fuse holders (FS1/FS2) are opened, the positiveterminals of both the internal and extended/remote batteries aredisconnected from the DC busbar.
Full fitting instructions are provided with the option pack.
The UPS internal batteries are protected by fuses FS1 & FS2. Theoptional Extended battery units by its own fuses FS1 and FS2, aRemote battery must be equipped with equivalent fuses to protectthe external batteries.
Where a Remote Battery option is used, an isolator and overloadprotection device must be located as close to the batteries aspossible.
Issue 3 (01/03/98) 3-11
IOM Manual Chapter 3 - Installation Instructions
7,5/10 kVA
N1
N2
N3
U1
U2
V1
V2
W1
W2
N1
N2
N3
U1
U2
V1
V2
W1
W2
A B
N1
N2
N3
U1
U2
V1
V2
W1
W2
N1
N2
N3
U1
U2
V1
V2
W1
W2
C D
15/20 kVA
N1
U1
U2
V1
V2
W1
W2
N2
N4
N3
L6
N1
U1
U2
V1
V2
W1
W2
N2
N4
N3
L6
A B
N1
U1
U2
V1
V2
W1
W2
N2
N4
N3
L6
N1
U1
U2
V1
V2
W1
W2
N2
N4
N3
L6
C D
Figure 3-23 Bridging links for common and split bypass with
three and four wire inputs.
4 wire andearth input
4 wire andearth input
Bypass 4 wireand earth
input
Bypass 4 wireand earth
input
UPS 3 wire andearth input
UPS 3 wire andearth input
Bypass 3 wireand earth
input
Bypass 3 wireand earth
input
UPS 4 wireand earth
input
UPS 4 wireand earth
input
Bypass 4 wireand earth
input
Bypass 4 wireand earth
input
UPS 4 wire andearth input
UPS 4 wire andearth input
+-
U3
V3
W3
N3
N2
N1
U2
U1
V2
V1
W2
E1
E2
E3
W1
Figure 3-24 Terminals for extended battery connections
To Extended/RemoteBattery Connections
CommonBypass Links
PowerConnectionTerminals
BLACK
RED
3.8 Procedure for connecting the UPS to thepower supply
WARNINGBEFORE PROCEEDING WITH CABLING-UP THE
UPS, ENSURE THAT YOU ARE AWARE OF THELOCATION AND OPERATION OF THE
DISTRIBUTION PANEL ISOLATORS THATCONNECT MAINS POWER TO THE UPS.
VERIFY THAT THESE ISOLATORS ARE OPEN,AND THAT ALL NECESSARY SAFETY MEASURES
TO PREVENT THEIR CLOSURE HAVE BEENTAKEN.
ENSURE THAT THE MAIN ROTARY SWITCH, SW1,IS SET AT OFF.
BEFORE CONNECTING THE SUPPLY CABLES TOTHE UPS, A PERMANENT SIGN MUST BE PLACED
AT THE ISOLATOR FROM WHICH THE CABLESARE RUN, STATING THAT THE ISOLATOR IS
SUPPLYING A UPS. IT IS IMPORTANT THAT THISISOLATOR IS ONLY OPERATED WITH THE
AUTHORITY OF THE UPS USER.
3.8.1 Common input/bypass supply system
This procedure should be followed if the same power source isused for both the UPS input and the bypass supply. Use it for boththe 10 and the 20kVA units.
1. Ensure that the fuse holders FS1 & FS2, and circuit breakers
CB1 to CB6 are open.
2. Remove the power compartment front cover plate –see
Fig.3-20.
3. Connect the input earth to one of the main earth terminals
(E1, E2, E3) shown in figs. 3-25/26. The output earth wires
must also be connected to one of these earth terminals.
4. Connect the output cables to the UPS output terminals U3,
V3, W3, and N3 on 10kVA units (Fig.3-25); an additional
neutral link is provided on 20kVA units (Fig.3-26). Be sure to
observe the correct phase rotation.
5. Connect the input cables from the supply distribution panel to
the UPS input terminals U1, V1, W1, N1 shown in figs.3-
25/26. Be sure to observe the correct phase rotation. Replace
the terminal block cover plate and all panels removed earlier.
3.8.2 Split input/bypass supply
This procedure should be followed if the UPS input and bypassinput are supplied from different three phase supplies. Use it forboth the 10 and the 20 kVA units.
1. Ensure that the fuse holders FS1 & FS2, and circuit breakers
CB1 to CB6 are open.
2. Remove the power compartment front cover plate – see
Fig.3-20.
3. Remove the U1/U2, V1/V2, W1/W2 links as shown in
figs. 3-27 & 28. Leave the bridging links fitted to the earth
terminal blocks (E1, E2 & E3) and the neutral terminal blocks
refer to figure 3-23.
4. Connect the input earth to one of the main earth terminals
(E1, E2, E3) shown in figs. 3-27/28. The output earth wires
must also be connected to an earth terminal.
3-12 Issue 3 (01/03/98)
Chapter 3 - Installation Instructions AP4300
BA
TT
-
BA
TT
+
U3
V3
W3
N3
N2
N1
U2
U1
V2
V1
W2
E1
E2
E3
W1
U V W N N U V W
Figure 3-25 Power cable connections - 10kVA unit in common
bypass configuration
3 phaseoutput andneutral toload
CommonBypassLinks
Earth Terminals
PowerConnectionTerminals
3 phase inputsupply and neutral
BA
TT
-
BA
TT
+
U3
V3
W3
N3
N2
N4
N1
U2
U1
V2
V1
W2
E1
E2
E3
W1
U V W N N N U V W
Figure 3-26 Power cable connections - 20kVA unit in common
bypass configuration
3 phaseoutput andneutral to
load
CommonBypassLinks
Earth Terminals
PowerConnectionTerminals
3 phase inputsupply and neutral
U V W N
U
N
V
W
U
V
W
U3
V3
W3
U2
U1
V2
V1
W2
E1
E2
E3
W1B
AT
T-
BA
TT
+
N3
N2
N1
Figure 3-27 Power cable connections - 10kVA unit in
split bypass configuration
3 phase outputand neutral to
load
Commonbypass links
removed fromU, V, W
terminals
Earth Terminals
PowerConnectionTerminals
3 phaseinputsupply
Neutral Bridging Linkrefer to figure 3-23.
EarthBridging
Link
3phasebypasssupply
&neutral
5. Connect the output cables to the UPS output terminals U3,
V3, W3, and N3 on 10kVA units (Fig.3-27); an additional
neutral link is provided on 20kVA units (Fig.3-28). Be sure to
observe the correct phase rotation.
6. Connect the bypass cables from the supply distribution panel
to the UPS bypass terminals U2, V2, W2 & N2 as shown in
figs.3-27/28. Be sure to observe the correct phase rotation.
7. Connect the input cables from the supply distribution panel to
the UPS input terminals U1, V1, W1 & N1 as shown in figs.
3-27/28. Be sure to observe the correct phase rotation.
Replace the terminal block cover plate and all panels removed
earlier.
3.9 Commissioning
Now that the unit has been correctly installed it must becommissioned by a Liebert approved engineer. He will validatethe installation work and install ‘site information’ into the UPSmicrocontroller memory. This information is required tosubstantiate and validate any subsequent warranty claims thatmight be made. Refer to the Commissioning Manual.
3.10 Electrical Details
3.10.1 Introduction
The main components in the UPS are shown in the block diagramof the circuit in Fig.3-29. The converter, battery charger, inverterand static switch are controlled by the microcontroller.
Key to labels in Fig.3-29
A Input Filter G Output Filter
B 3-phase rectifier (into580V bus)
H Battery Charger
C Resonant Circuit &Switches
J Battery String
D HF Transformer (T1) K 2nd Battery string(15/20kVA units only)
E 1-Phase Rectifier(into 800V bus)
L Static Switch
F 3-phase Inverter M Input links
Issue 3 (01/03/98) 3-13
IOM Manual Chapter 3 - Installation Instructions
N
U
V
W
N
U
V
W
BA
TT
-
BA
TT
+
U3
V3
W3
N3
N2
N4
N1
U2
U1
V2
V1
W2
E1
E2
E3
W1
U V W N
Figure 3-28 Power cable connections - 20kVA unit in split
bypass configuration
3 phaseoutput andneutral to
load
Commonbypass links
removed fromU, V, W
terminals
Earth Terminals
PowerConnectionTerminals 3 phase
inputsupply
Neutral Bridging Linkrefer to figure 3-23.
EarthBridging
Link
3phasebypasssupply
&neutral
3-1
4Issu
e3
(01
/03
/98
)
Ch
apter
3-
Installation
Instru
ctions
AP
4300
AP4300
ESC
AP4300 INITIALISINGPLEASE WAIT...
S1-E
S1-B
S1-A
S1-C
S1-D
S1-G
U3
V3
W3
U1
V1
W1
N1
B
L
M
U2
V2
W2
FS2FS1FS3
H
J
A C D E F
CB1
CB2
CB3
CB4
CB5
CB6
N3
N2
N4
L6
K
Fig
ure
3-2
9E
lectric
al
blo
ck
dia
gra
m
Bypa
ssS
upplyInputS
upply
Output
Maintenance Bypass
Remove links for SplitBypass system
Remote Stop Option
15/20kVA units only2nd battery string
Output offSwitch SW2
I/P Over voltageCut-out Relay
MICROCONTROLLER BOARD INTERFACE
OPTIONS
InverterOutput Cut-out Relay
Static Bypass
MainControlSwitchSW1
Chapter 4 - Options and Features
4.1 Introduction
A number of options and features are available on the AP4300series UPS; these are listed below.
• Auto-restart Inhibit (feature).
• Common Bypass Links (feature).
• Remote Stop (option).
• Hot Standby Configuration (feature).
• RS232 Interface and External Relay Board (feature).
• RS232 Compatible Software (SiteNet) (option).
• SNMP Interface (option).
• Remote Alarm Monitor (option).
• Extended Battery (option).
• Remote Battery (option).
• Input Filter (option).
• Isolation Transformer (option).
• Bypass Enclosure (option).
• Output Distribution Module (option).
• Frequency Changer (Option).
All options are supplied complete with installation and operatorinstructions.
4.2 Standard Features
4.2.1 Auto-restart Inhibit
The UPS has an Auto-restart facility fitted as standard. If thiscapability is not required, the commissioning engineer will inhibit itby setting a parameter during commissioning.
4.2.2 Common Bypass Links
The input terminals to the rectifier are separate from the staticbypass line terminals, so that different power supplies can be usedfor the two inputs. This arrangement is referred to as ‘splitbypass’. An alternative arrangement, referred to as ‘commonbypass’, where the corresponding phases on these two sets ofinput terminals are connected by means of links, is used whereonly one power supply is available. The UPS is supplied with thecommon bypass links fitted. The connecting links for thecommon bypass must be removed during installation if a splitbypass arrangement is required - refer to the Chapter 3.
4.2.3 Remote stop
A remote stop circuit can be connected to an RJ12 connector onthe inner panel behind the right hand detachable (‘lift-off’) panelon the front of the UPS.
The remote stop kit consists of a 10 metre length cable with aRJ12 connector on one end and a junction box for connection tothe users normally closed switch on the other end. When selectedopen the switch provides a remote output OFF control.
4.2.4 Hot Standby Configuration
The AP4300 can be used in a ‘HOT STANDBY’ to provideincreased security for the load. One UPS is connected in theCommon input/Bypass Configuration, and is used to supply asecond unit which is connected in a split bypass configuration.
Issue 3 (01/03/98) 4-1
L1
L1
L2
L2
L3
L3
E
E
N
N
Figure 4-1 Hot Standby Configuration
Unit 1(Common
Input/BypassConfiguration)
(see 3.8.1)
Unit 2(Split BypassConfiguration)
(see 3.8.2)
LOAD
4.3 Remote Control/ Communications Facilities
4.3.1 RS232 Interface and External Relay Board
Introduction
The COMMUNICATIONS BOARD is fitted as standard andprovides two sets of volt free relay contacts, an interface for a setof “direct action” signals conforming to RS232D voltage levels,and a local RS232D serial port.
The local RS232D serial port permits signals about the state ofthe UPS to be transmitted to a wide range of computers, whichcan then transmit control signals back to the UPS when required.The computers may be located close to the UPS or remotely.Communication with computers over short distances is achievedby connecting them directly to the RS232 interface.Communication with remotely located computers, i.e. overgreater distances, requires the use of a modem and telephone line.
Note: When employing the communications features of theAP4300, SiteNet software and cable kits are available for
use with most operating systems.When using the communications connector, only Liebertsoftware and connecting cables should be used. If using
other than Liebert cable or software, only terminals 2, 3 and7 (send, receive, ground) should be connected. Use of the
other terminals may change the operational state of the UPSor cause a shutdown.
Communications with the UPS is not guaranteed withunauthorised software and cables.
Note: Any connection to a telecommunications network mustbe via an approved modem complying with clause 6 of BS
EN 60950:1994 or BS EN 41003:1997.
The relay contacts on the COMMUNICATIONS board permit thestatus of the UPS and major UPS alarms to be transmitted to otherdevices such as an external alarm panel located remote to the unit,or to the power supply monitoring features of the *IBM AS400computer systems, *Novell, *UNIX or other common operatingsystems.
* Registered Trade Marks
Connectors
The AP4300 communication board is fitted with two 25 wayfemale D type connectors as shown in Figs. 4-2 & 4-4. The topconnector is labelled COMM'S; the lower connector is labelledRELAY.
The DB25 socket labelled RELAY connects only to a set of relaycontacts on the board. The DB25 socket labelled COMM'Sconnects to a second set of relay contacts, to lines carrying the“direct action” signals and also to the RS232D serial interface asshown in figure 4-3.
The outputs from the relay contact closures permit informationabout the state of the UPS to be sent, via a cable, to externalindicating panels etc. The relays are operated by the followingUPS states:
On UPS On battery
On bypass Low battery
The RS232D “direct action” signals are used by the UPS toindicate to an attached system when the UPS state changes; andby the attached system to control the UPS.
The relay contacts and interface signals are assigned to theconnector pins as set out in figure 4-3 and the table below:
Cable Termination
The DB25 connector on the UPS end of the cable must be a rightangle outlet as shown in Fig.4-4. The front cover of the UPScannot be fitted correctly if a ‘straight-out’ connector is used.
4-2 Issue 3 (01/03/98)
Chapter 4 - Options and Features AP4300
PL1
PL3
Figure 4-2 Location of the communications assembly in the
UPS
Remote Stop Connection
PL3 RelayConnector
PL1 Comms.Connector
TxD
N.C.N.O.
N.O.N.C.
RxD
Outputs
Inputs
15
24
181617
1011
9
2
3
21
13
19
12
14
7GND
N.C.N.O.
N.O.N.C.
15
24
181617
1011
9
Figure 4-3 DB25 Connectors Comms (PL1) and Relay (PL3)
Output Communication Lines.
UPS ON
ON BYPASS
ON BATTERY
COMMON
LOW BATTERY
COMMON
Transmit data (from external system)
Receive data (to external system)
0 volt for use with Serial data linesand RS232 compatible lines
LOW BATTERY
POWER FAIL
INVERTER SHUTDOWN HIGH
INVERTER SHUTDOWN LOW
ON/OFF (High/Low)
RS232 levelcontrol signals
25 Way ‘D' TypeConnector PL1
25 Way 'D' TypeConnector PL3
DB25 Pin Definition: The pin out for both DB25 connectors isshown below.
PinNo.
Signal name Direction
COMMSConnector
PL1
RELAYConnector
PL3
1 Not Used Not Used
2 TXD Not Used
3 RXD Not Used
4 Not Used Not Used
5 Not Used Not Used
6 Not Used Not Used
7 Signal Common Not Used
8 Not Used Not Used
9 Low Battery Relaycommon
Low Battery Relaycommon
10 Low Battery Relay NC Low Battery RelayNC
From UPS
11 Low Battery Relay NO Low Battery RelayNO
From UPS
12 Shutdown, Active Low Not Used To UPS
13 Power Fail (ActiveHigh)
Not Used From UPS
14 ON/OFF (High/Low) Not Used To UPS
15 On UPS Relay NO On UPS Relay NO From UPS
16 On Battery Relay NO On Battery Relay NO From UPS
17 Relays Common Relays Common
18 On Battery Relay NC On Battery Relay NC From UPS
19 Shutdown, Active High Not Used To UPS
20 Not Used Not Used
21 Low Battery (ActiveHigh)
Not Used From UPS
22 Not Used Not Used
23 Not Used Not Used
24 On Bypass Relay NO On Bypass Relay NO From UPS
25 Not Used Not Used
Relays
The relays provide volt free contact closures for connection toAS400 minicomputers and/or connection to Novell networks.
Contact ratings:1A at 30Vdc0.5A at 125Vdc0.3A at 110Vac.
Four relays are used, each having a double pole change-overcontact. They are energised by changes in the state of the UPS asshown below; the signals are used by the systems shown inbrackets:
ON UPS (AS400 Interface)ON BYPASS (AS400 Interface)ON BATTERY (AS400 and NOVELL interface)LOW BATTERY (AS400 and NOVELL interface)
The function of the relay contact connections are listed below:
Relay Contact NormalState
Function
On UPS Relay NO Contact is closed when theUPS is operational
On Bypass Relay NO Contact closes when theUPS activates the staticbypass
On Battery Relay NO Contact is closed when theUPS is using power from itsinternal batteries (utility hasfailed)
On Battery Relay NC Contact is opened when theUPS is deriving power fromits internal batteries (utilityhas failed)
Low Battery Relay NO Contact closes when thebattery voltage reaches agiven threshold, andindicates a limited timeperiod before the UPS shutsdown.
Low Battery Relay NC Contact opens when thebattery voltage reaches agiven threshold, andindicates a limited timeperiod before the UPS shutsdown.
Relays Common - A common connection forthe ON UPS, ONBATTERY and ONBYPASS relays.
Low Battery Relaycommon
- A common connection forthe LOW BATTERY relay.This connection is separatefrom the ‘Relays Common’to maintain compatibilitywith the UPStation GXinterface.
“Direct Action” signals(RS232D interface)
The “direct action” signals are used by the UPS to indicate achange of state to a connected system (monitoring signals), andby the system to control the UPS (control signals).
The signal excursions will conform to the RS232D standard; i.e. ahigh is a voltage level between +3 and +15 volts and a low is avoltage level between -3 and -15 volts.
Description of the Monitoring & Control signals
Monitoring signals (i.e. sent by the UPS to an external system)
Power Fail (Active High - pin 13)This output is normally held at an RS232 low level and is set toan RS232 high level if the utility supply fails.
Low Battery (Active High - pin 21)This output is normally held at an RS232 low level and is set toan RS232 high level if the battery voltage drops to a pre-setvoltage level. This indicates a limited time before the UPS shutsdown.
Control signals (i.e. sent to the UPS by an external system):
ON/OFF (High/Low - pin 14)An RS232 high level signal on this pin will turn the UPS on (if it isoff), and an RS232 low level signal will turn the UPS off (if it is on).If the UPS is ON and the interface cable is disconnected the UPSwill remain ON. If the UPS is OFF and the interface cable isdisconnected the UPS will remain OFF.
Issue 3 (01/03/98) 4-3
IOM Manual Chapter 4 - Options and Features
Shutdown (Active High - pin 19)An RS232 high level on this input causes the UPS to shutdown.The utility must have failed and the signal must be present for 2seconds. Disconnecting the interface cable will not cause the UPS toshut down.
Shutdown (Active Low - pin 12)An RS232 low level on this input causes the UPS to shutdown.The utility must have failed and the signal must be present for 2seconds. Disconnecting the Interface cable will not cause the UPS toshut down.
Note: The two shutdown signals are logically OR'd within the UPS;either one of these must be present for 2 seconds before theyshutdown the UPS. The conditions for the shutdown are set by theuser on the UPS control panel and can be selected from:
a) Shutdown the UPS if the utility has failed and the UPS is on
battery.
b) Shutdown the UPS whatever its condition.
Action ‘a’ is the default.
Signal Common
A common reference for all active interface signals.
• Remote communications
The TxD transmit data signal (from external system) to pin 2The RxD receive data signal (to external system) to pin 3The signal common signal - common reference for all interfacesignals to pin 7.
Serial Communications
To provide a straight forward connection to an attached systemthe above signals will be arranged to configure the interface sothat the UPS behaves as a DCE (Data CommunicationsEquipment).
If the attached system employs a 25 way ‘D’ type connector, thenus connections:-
UPS· · · · · · · · · · System
2 · · · · · · · · · · · 2
3 · · · · · · · · · · · 3
7 · · · · · · · · · · · 7
If the attached system employs a 9 way ‘D’ type connector, thenuse connections:-
UPS· · · · · · · · · · System
2 · · · · · · · · · · · 3
3 · · · · · · · · · · · 2
7 · · · · · · · · · · · 5
The serial communication employs propriety protocol.
Cable connection Procedure
• Preparation
CautionThe load will not be protected from an input power
supply failure during the following procedure.
1. Remove the ‘lift off’ perforated cover from the front of
the UPS cabinet.
2. Follow the procedure To Put the Load on Maintenance
Bypass given in the Operator Manual to isolate the
internal components of the UPS, while continuing to
supply the load with power.
3. Ensure that all the circuit breakers (CB1 - CB6) and
battery fuse holders (FS1, FS2) are open.
• Cable connection
4. Insert the 25-way D-type connector at the end of the
cable into the socket marked RELAY or COMM’S (as
appropriate) on the communications option board.
5. Run the cable down to the bottom of the cabinet so that
it will leave the UPS from beneath the front lift off
cover and connect it to the external communication
equipment.
6. Use the Cold Start Procedure given in chapter 2 to start
up the UPS.
7. Replace the ‘lift off’ perforated cover removed earlier
from the front of the UPS cabinet in step 1 above.
4-4 Issue 3 (01/03/98)
Chapter 4 - Options and Features AP4300
Figure 4-4 The communications option assembly
(cables and connectors not included)
RecommendedRight-angleDB25 cableconnectors
4.3.2 SNMP Interface
An SNMP interface is available to allow the UPS to be used withnetwork systems.
The AP4300 Ethernet SNMP option is equipped with two 25 wayfemale D type connectors, one RJ12 connector and one RJ45connector.
The RJ12 connector, labelled SETUP, provides a serial (RS232)interface to the SNMP board and is used to set up the SNMPboard parameters.
The RJ45 connector, labelled NETWORK, provides a twisted pairinterface to the network.
The DB25 connectors are labelled COMM'S and RELAY, theaction of the relays in the RELAY connector duplicates the actionof the relays in the COMM'S connector, the COMM'S connectoralso contains all the relevant interface signals, as described below.
Relay Section
The relay section provides volt free contact closures which arenecessary for connection to AS400 minicomputers and/orconnection to Novell networks.
To fulfil all the necessary requirements four relays are used, eachhaving a double pole change-over contact. These relays willconvey information on:
ON UPS (AS400 Interface)
ON BATTERY (AS400 and NOVELL interface)
LOW BATTERY (AS400 and NOVELL interface)
ON BYPASS (AS400 Interface)
Control/Monitoring signal section
The direct action signals are used by the UPS to signal change ofstate and by the attached system to control the UPS.
The signal functions are:
POWER FAIL (from UPS, active high)
LOW BATTERY (from UPS, active high)
SHUTDOWN(ACTIVE HIGH) (to UPS)
SHUTDOWN(ACTIVE LOW) (to UPS)
ON/OFF (to UPS, high/low)
The signal excursions will conform to the RS232D standard, i.e. ahigh is a voltage level between +3 and +15 volts and a low is avoltage level between -3 and -15 volts.
4.3.3 Interface Software
Both SiteNet® 1 and SiteNet® 2 are available for all majoroperating platforms. Please contact your dealer for furtherinformation.
SiteNet 1® - (Shutdown Management)
SiteNet 1 prevents unexpected server shutdowns by automaticallymonitoring UPS activity and closing down protected devices ifthe input power supply remains off or the battery back-upbecomes low. Connection is via a proprietary cable that runsbetween the UPS and serial port on the server.
When the input supply fails SiteNet 1 notifies the users that theprotected equipment is running on battery power, providing anon-screen count down of the time remaining. If the input powersupply returns the shutdown sequence ends and the users arenotified.
SiteNet 1 can be programmed to dial out on a modem and notifyupon defined events such as input power failure. SiteNet 1 alsooffers real time monitoring of power events so you can monitorand analyse recent and past power history.
SiteNet® 2 -Power Surveillance and shutdown
SiteNet 2 provides ongoing monitoring and control, via a twoway graphical interface, between network servers and the systemsUPS. Under normal conditions. SiteNet 2 provides real-timemonitoring of power flow and critical power data such as voltageand battery temperature. The UPS status can be displayed in threedifferent formats: system animation, power flow and metering.
The Event Manager allows you to customise the monitoringevents and pre-program responses to power problems. SiteNet 2can, for example be programmed to broadcast multiple useralerts, and provide a countdown timer so users can completeback-ups and disconnect from the server before the automaticshutdown occurs. The software can also dial a pager to alertnetwork administrators, shut down the server, and log events.
All this can be accomplished from a single location. Thiscapability includes scheduled on/off control, the initiation ofdiagnostic routines, or down loading power event history foranalysis. These routines can be performed with a user command,or executed automatically according to a pre-set schedule.
SiteNet SNMP Manager
SiteNet SNMP Manager is a snap-in application for your networkmanagement software. SNMP Manager seamlessly incorporatesthe Liebert UPS with your existing network management systemto provide user friendly screens to monitor and control power.
SiteNet SNMP Manager gives you everything you need tooversee network power with ease and precision.
Issue 3 (01/03/98) 4-5
IOM Manual Chapter 4 - Options and Features
4.3.4 Remote Alarm Monitor
The Remote Alarm Monitor (RAM) offers the following features:
1. Up to eight alarm/status indications
2. Each indicator can be selected to be red, amber or green.
3. Each indication can be accompanied by an audible warning.
4. Each indication can be electronically latched (indication
remains even if the condition changes).
5. Audio alarm silence push button both local and remote.
6. Alarm indication test/reset push button both local and remote.
7. Ability to change alarm legend and company logo labels.
8. Operates from 220V - 240V a.c.
9. Battery back-up option.
The unit normally includes individual alarms for:
UPS ON
UPS ON BATTERY
LOW BATTERY
UPS ON BYPASS
UPS ALARM CONDITION.
Plus 3 Spare ALARM positions
The system is provided in an enclosure for wall mounting andcomes complete with installation instructions.
4-6 Issue 3 (01/03/98)
Chapter 4 - Options and Features AP4300
UPS ON
ACFAIL
LOWBATTERY
ONBYPASS
SPARE
SPARE
SPARE
SPARE
LAMP
TEST/RESET
ALARM
SILENCE
150mm
20
0m
m
75mm
Figure 4-5 Remote Alarm Monitor
Weight 1.2 kg
4.4 Extended Battery Options
The ‘Extended Battery’ option is a separate cabinet containingfurther batteries that can be connected to the UPS to increase itstotal battery capacity and therefore the system autonomy time.
4.4.1 Extended Battery
The battery cabinet for this option is of the same height and depthas the UPS, and is attached to the left hand side of the UPS. Up to4 battery cabinets can be connected to the AP4310 UPS and upto8 battery cabinets to the AP4320 UPS. The extra batteries canincrease the autonomy time by up to approximately 1 hour.
The battery cabinet can contain either one 11Ah set of batteries ortwo 11Ah sets of batteries
Weights (kg)
Empty Battery Cabinet 70
Cabinet with one 11Ah set 200
Cabinet with two 11Ahr sets 330
Dimensions (mm)
Width 386
Height 1100
Depth 663
4.4.2 Remote Battery
This option is similar to the extended battery option, but in thiscase the additional battery capacity is much larger, taking theautonomy time up to approximately 8 hours. Due to the size ofthe additional batteries they are housed in a much larger cabinet(or on a special battery rack) which is located away from theUPS.
Due to the numerous battery configurations available for thisoption it is not possible to cover every installation possibility inthis manual, please consult your dealer for advice. The followingpoints should be taken into consideration when planning yourinstallation.
Battery Isolation And Protection
External batteries must be fused in both positive and negativelines as close to the battery terminals as practical.
Fuses shall have a voltage rating suitable for operation at 440V,the d.c. level of the battery.
A suitable off load isolator must be fitted at the battery end toallow isolation by the service engineer .
Where fuses can be safely withdrawn, they may act as the meansof isolation.
Fused isolators or circuit breakers may also be used.
The cable rating between the battery and UPS shall be sized togive a maximum volt drop of 2V at currents stated in table below,irrespective of the battery autonomy time for the application.
Model 7,5kVA 10kVA 15kVA 20kVA
Max. battery current 19A 25A 37,5 50A
RFI ( EMC ) CONSIDERATIONS
To reduce the risk of radio frequency interference to other parts ofthe installation external batteries and associated wiring should beshielded.
The shielding for the battery can be either a steel cabinet or a rackcladded with steel panels wherever practical. Whichever is used,all panels should be bonded together and to earth for safety. Inaddition to the safety earth a separate earth conductor from thebattery enclosure to the UPS should be fitted to provide thelowest impedance path possible to RFI noise.
Wiring should be shielded by conduit , trunking or the cablingused must be screened.
Where these recommendations are not implemented a minimumradius of 10 metres to any sensitive electronic equipment isrecommended.
Safety Labelling
Warning labels should be fixed to the UPS to warn of an externalbattery, unless by its placement it is obvious to the personnelworking on the UPS where isolation is available.
The external battery enclosure must have a label on the outside towarn the Fire Authorities that lead-acid batteries are containedwithin and also advise the voltage level inside the enclosure.
VENTILATION
Adequate ventilation of battery enclosures must be provided todisperse any build up of gases vented by the battery.
Weight
Ensure that the battery installation weight does not exceedloading capacity of the floor.
Issue 3 (01/03/98) 4-7
IOM Manual Chapter 4 - Options and Features
4.5 Power Options
4.5.1 Input Harmonic Filter
Introduction
The optional input harmonic filter can be added to the UPS toimprove the UPS power factor and reduce the amount ofelectrical noise reflected back into the input three phase supply.
The filter which is free standing and clipped onto the left handside of the UPS is contained in a cabinet whose styling, colourand size matches that of the 4300 UPS. The cabinet is designedsuch that it can contain either the Input Filter or the IsolationTransformer or both the filter and transformer.
Specification
Input voltage range: 400V + 20% -15% 3ph.3 wire and earth.
Frequency : 50Hz. or 60Hz. ±10%.
Supply Impedance : ≥5% (at UPS rated load).(including cables)
Supply voltagedistortion : <1,5% (at zero load).
Input power factor : ≥0,98 (at rated load)≥0.8 (at zero UPS load).
Input currentharmonics : <10% Thd (at rated load and with
the input supply stated above).
Filter protection : 3 phase circuit breaker in the trap.
4.5.2 Isolation Transformer
Introduction
The Isolation transformer is designed for use on electricalsystems of the ‘IT’ (Impédance à Terre) type.
The Isolation transformer is double wound with a ratio of 1:1.The output winding is star connected to re-establish ground.Connection DY11.
Specification
Input voltage range: 400V ±20% 3ph. 3 wire and earth.
Frequency : 50Hz. or 60Hz. ±10%.
Output regulation : <2% zero to full load under allconditions.
Neutral current : 200% of full line current.
Crest factor : 3 : 1 (Maximum) .
4.5.3 Filter &Transformer
Specification
Inrush current : Will not exceed 10 times thenominal full load peak current for10ms.
Operating Ambient : 0 to +40oC Continuously rated.Temperature
Storage &Transportation : -25oC to +70oC.
Relative Humidity : 95% non - condensing.
Max. operatingaltitude abovesea-level : 1000m. 1% load derating for each
without derating 100m above 1000m up to 3000m.
Ventilation : Natural air cooling -cabinet requires 150mm free spaceat the rear of unit.
Dimensions:
Option Width(mm)
Depth(mm)
Height(mm)
Weight(kg)
Filter 550 650 1100 70
Transformer 550 650 1100 255
Both 550 650 1100 320
4.5.4 External Bypass Enclosure
The Bypass cabinet allows the user to completely remove theUPS from the system, whilst still maintaining power supplies tothe load equipment.
The Change-over switch is a make before break type and can bekey operated. (i.e. A key fitted in the UPS Main Switch S1 cannot be removed until the switch is selected to internalMaintenance bypass. Once removed the key can be inserted intothe change-over switch to allow operation.)
4-8 Issue 3 (01/03/98)
Chapter 4 - Options and Features AP4300
Figure 4-6 Simple line diagram of External Bypass System
External Bypass System Enclosure
Inputisolator
Change-overswitch
UPS disconnect Sockets
Internal Bypass Line
Main Switch S1
StaticSwitch
UPS
Output toLoad
4.5.5 Distribution Cabinet
The Distribution Cabinet permits several loads to be connected bymeans of output sockets on the rear of the cabinet.
The Distribution Cabinet is fitted on the left hand side of the UPScabinet and is available in either a no Break neutral or Breakneutral configuration.
The basic cabinet (A and D Series) contains an input cable, maincircuit breaker, pre-drilled cable landing plate for bottom cableexit, and a 16 pole panel board without output circuit breakers.(the user to fit own circuit breakers and to directly connect theoutput cables as required).
In addition to the above, the C & F series cabinet contains two16A three phase, neutral and ground and six 16A single phase,neutral and ground CEE17 type industrial output sockets. Eachoutput is protected with circuit breakers which are accessedthrough a panel on the left hand side of the cabinet.
Where required cabinets can be supplied with variouscombinations of the above configurations.
4.5.6 Frequency Changer
The AP4300 can be used as a frequency changer. The standard50Hz. unit can be converted to allow 60Hz. input and give 50Hz.output. The 60Hz. unit can be converted to allow 50Hz. input andgive 60 Hz. output.
The following instructions are for converting the AP4300 into afrequency changer.
WarningTHIS WORK MUST ONLY BE CARRIED OUT BY A
LIEBERT AUTHORISED SERVICE ENGINEER.HIGH VOLTAGES ARE PRESENT WITHIN THIS
UNIT, ENSURE THAT THE APPROPRIATEPRECAUTIONS AS DETAILED IN YOUR MANUALHAVE BEEN TAKEN BEFORE ANY COVERS ARE
REMOVED.
• For conversion to 50Hz. INPUT and 60Hz. OUTPUT use
standard 60Hz. Unit.
• For conversion to 60Hz. INPUT and 50Hz. OUTPUT use
standard 50Hz. Unit.
Installation Instructions
1. Gain access to the UPS Microcontoller Board following the
instructions contained in the AP4300 Service Manual.
2. Refer to figure 4-8 and ensure the link between pins 3 and 4
of LK6 is fitted.
3. Ensure that the correct firmware processor is fitted for the
output frequency required.
50 Hz. Output = Part number 02117670.
60 Hz. Output = Part number 02117671.
4. Remove the common bypass links from the main input
terminal block. Remove links as follows:
Link between U1 and U2; V1 and V2; W1 and W2.
Note: Do not remove the Neutral links. When connecting theUPS to the input power supply, ensure connections are
made to the input terminals U1, V1 and W1.
5. Refit the Display Panel.
6. Start the UPS normally as instructed in your IOM manual.
7. Refit the front cover.
The UPS should now be operating as a frequency changer.The
bypass facility is no longer available.
Issue 3 (01/03/98) 4-9
IOM Manual Chapter 4 - Options and Features
AP4300
AP4300UPSNORMALNOALARMS hh:mm:ssdd:mm:yy
Figure 4-7 Distribution cabinet fitted to an AP4320
CircuitBreakerAccess
AP4320UPS
DistributionCabinet
4-10 Issue 3 (01/03/98)
Chapter 4 - Options and Features AP4300
Figure 4-8 AP4300 Micro controller board
Microcontroller firmware
Chapter 5 - Troubleshooting
5.1 Introduction
WARNINGUNDER FAILURE CONDITIONS, THE UPS WILL
AUTOMATICALLY TRANSFER TO THE INTERNALBYPASS SYSTEM.
POWER SUPPLIES TO THE LOAD WILL BEMAINTAINED EVEN WHEN THE UPS IS
INDICATING “OUTPUT OFF”.THE UPS STATUS ON THE CONTROL & DISPLAY
PANEL REFERS TO THE OUTPUT OF THE STATICINVERTER RATHER THAN THE COMPLETE UPS.
ALWAYS CHECK FOR A VOLTAGE AT THEOUTPUT TERMINALS BEFORE ATTEMPTING TO
SERVICE THE UPS OR THE LOAD.
Problems indicated on the UPS can be divided into two groups:
1. External faults: i.e. abnormalities in the conditions in which
the UPS operates, and which the user can usually resolve: e.g.
input power supply failure, ambient temperature too high.
2. Internal Faults: i.e. defects which develop within the UPS
itself, and which need specialist attention. The highly
integrated design of the AP4300 UPS prevents the user from
curing internal faults.
As soon as any abnormal conditions or faults are detected, theUPS automatically takes action, if necessary, to protect the loadand/or the UPS itself; at the same time it triggers alarm signals onthe operator display panel. The horn sounds and/or LEDs switchto indicate the nature and urgency of the alarm. Text messagesindicate the nature of the fault on the default screen when this isdisplayed on the LCD Display Panel. Charts at the end of thischapter enable the user to interpret these messages, and soidentify which problems can be resolved by the user and whichrequire attention from a UPS specialist.
The UPS microcontroller board contains a battery-backedmemory which keeps a record ( ‘Event History’) of previousalarms. This is for service personnel to use when establishing theoriginal cause of a fault.
WARNINGSOME OF THE INSTRUCTIONS CONTAINED INTHE CHARTS AT THE END OF THIS CHAPTERINVOLVE CHECKING INTERNAL FUSES. THIS
SHOULD BE UNDERTAKEN (AFTER THEEQUIPMENT HAS BEEN SHUT DOWN) BY
COMPETENT PERSONNEL ONLY WHO AREFAMILIAR WITH THE LAY-OUT AND OPERATIONOF THE EQUIPMENT AND FULLY CONVERSANT
WITH THE AREAS OF POTENTIAL HAZARD.
5.2 Alarm indications
5.2.1 Audible Alarm Horn
The horn will make one of five different sounds, according to theurgency of the alarm. The pattern of the audible signals isdescribed in table 5- below. All follow the same basic pattern; i.e.an on period of 0.5secs at intervals of either 1s or 10s, dependingon the urgency of the alarm.
The audible warning can be cancelled immediately by pressingthe horn cancel button (except when the UPS is running OnBattery - see Section 2.6.2 - Input Supply Failure On Load).The LED continues to indicate until the fault clears.
Table 5.1 - Alarm sound identification
AlarmType
Description of Sound Priority
1 Rising Pitch for 0.5s, at 1s intervals “Red Alert”
2 Two tones (high-low) for 0.25s each, at 1sintervals
“Urgent”
3 Single tone for 0.5s, at 1s intervals “Problem”
4 Single tone for 0.5s, at 10s intervals Low
5.2.2 LED Indications
The meanings, and the colour of each of the LEDs on the operatorpanel shown in fig.5-1 are summarised in the table below.
If the UPS input power supply is available (and withinspecification) and the UPS is operating normally, only greenLEDs should be lit, as described in Chapter 1 - GeneralDescription. LED1 (input supply available) and LED3 (load oninverter) indicate correct operation on the module mimic; thenumber of green LEDs lit on the autonomy bar indicates the stateof charge of the battery; and the number of green LEDsilluminated on the percentage load bar depends on the load on themost heavily loaded phase.
After the detection of an alarm condition, LEDs switch on or off,or flash on/off, according to the nature of the fault as shown inthe table below.
Meaning of the Operator Panel Indicator LEDs(refer to fig.5-1)
Key LED Colour NormalState
Indication whenON
1 InputSupply
Green on Input Power supplypresent.
2 StaticSwitch
Amber off Load is on bypass.
3 Inverter Green on Load is on UPS.
4 BatteryStatus
Amber off Battery is discharging,UPS on battery.
5 OverloadIndicator
Amber off Output has exceeded100% of full load.
6 ChargerFault
Amber off Charger is faulty(LED flashes).
7 Alarm Red off A condition requiringurgent attention has
developed (LEDflashes).
8 LowBattery
Indicator
Green on State of charge of battery;this LED will be on whilebattery capacity is above
10%. It flashes whencapacity falls below 10%.
Issue 3 (01/03/98) 5-1
5.2.3 Messages in the LCD Text Window
When the UPS is operating normally the message shown on thedisplay panel in fig.5-1, appears in the Default Screen. The topline gives the UPS model nº; the third line displays the UPSoperational status; and the fourth line normally shows the dateand time.
When an alarm is triggered, status messages and/or an errormessage will be shown on the default screen. If this screen is noton the display when an alarm is indicated, press ESC repeatedlyto show the Default Screen.
Status messages:
Status messages are shown on the third line of the screen, asindicated above. When an operator action, an environmentalchange, or a UPS problem changes the state of the UPS, the newstatus is indicated by a message on this line as shown in theexample below:
AP4310
UPS ON BYPASS14-02-95 14:35:00
If UP or DOWN pushbutton symbols, or both: appearbetween the time and date, as shown above, then there are two ormore status messages. Use the UP/DOWN pushbuttons to scrollthrough these messages. Refer to para 5.3 Troubleshooting
Procedure for help.
The Error Message:
If the UPS takes action in response to a fault developing, then thetop line on the default screen changes to display an errormessage, which shows what action has been taken by the UPS(e.g. emergency shutdown). The second line of the screen tells theoperator to select the error page for more information. The thirdline continues to display status messages; e.g.:-
EMERG SHUTDOWN NNREFER TO ERROR PAGEUPS OUTPUT OFFDD-MM-YY HH:MM:SS
The ‘action’ taken will be one of the following:
General fault Tests aborted
Emergency transfer toinverter
Emergency transfer to bypass
Fatal error Emergency shutdown
The ERROR PAGE, is a screen which permits a service engineerto analyse the internal state of the UPS, and to identify the activealarm. Follow the procedure given in Chapter 6 - Maintenancefor displaying the Information Screen:
ERROR PAGEUPS STATUSEVENT HISTORY
Select the Error Page.
The nature of the information on each of the lower three lines issummarised below:
line 2: UPS Status
line 3: Action taken by the UPS (error message)
line 4: Reason/fault description.
Refer to para 5.3 Troubleshooting Procedure for help with
the action to take according to the reason/fault description on
line 4.
When there are no problems, the error page appears as shown
below:
ERROR PAGENORMALNO REPORTNO MESSAGES
Event History:
The event history screen is accessed from the information screen(see Chapter 6 - Maintenance). It permits details of thecircumstances of previous fault (i.e. conditions which generate anerror message) to be obtained. Up to 100 events can be stored.The format of the information obtained is shown below:
DD-MM-YY HH:MM:SS#XXSTATE NORMALBAT TEMP SENS FAULT
In each case, if UP/DOWN pushbutton symbols: appearbetween the time and date, as shown above, then there are two ormore events recorded. Use the UP/DOWN pushbuttons to scrollthrough them; XX denotes the number of the event, in thechronological sequence of the events, on the display. The UPSstatus is indicated in text on line 3.
The reason/fault for the UPS action (i.e. the error message) ispresented as text on line 4.
5-2 Issue 3 (01/03/98)
Chapter 5 - Troubleshooting AP4300
ESC
AP4300
UPS NORMAL NO ALARMSdd-mm-yy hh:mm:ss
AP4300
UPS NORMAL NO ALARMSdd-mm-yy hh:mm:ss
1 2 3 4 58 6 7
Figure 5-1 Position of the LEDs on the operator panel that
indicate alarms or provide status information.
Notes:
1. The Tests aborted error message appears only if an alarm
condition is detected during the start-up test. The instruction
line then shows to which position switch SW1 must be
turned:
TESTS ABORTED NNTURN SW1 TO MAINTON MAINTENANCE B/P
DD-MM-YY HH:MM:SS
2. If a fault occurred during start-up, or communications
between the microcontroller and the UPS have failed during
normal operation the following alarm message appears on the
display:
AP4300INT FAILURE FFNNCALL FOR SERVICE44-1793 553355
The user cannot correct this fault and the UPS supplier must becalled. Whether or not the 'phone no. to call and other details aredisplayed during start-up depends on how far initialisation hadprogressed before the fault was detected. If a communicationsfault triggered the alarm then the LCD display may freeze, sincecommunications may be inoperative, but the UPS will continue tooperate.
5.3 Troubleshooting Procedure
5.3.1 Fault Records
When a UPS fault occurs, first observe and record the UPS Statusparameter values, i.e. the present values of the UPS bypass &output voltage and current and other electrical parameters. Referto Chapter 6 - Maintenance for details of the procedure. Detailsof any loads being started or shed at the time that the faultoccurred should also be recorded.
5.3.2 Alarm Interpretation and Corrective action
The right hand column of the charts on the next five pages showshow the messages that appear on the default screen should beinterpreted, and also provides information on what action to take.
Status messages are listed in alphabetical order in Table 5.2 -
Interpretation of Status Messages; if several status messages areactive and you are unable to identify the reason, then seekimmediate assistance.
Interpretations of Error Messages are given in Tables 5.3 & 5.4-;if you are unsure as to how to undertake the actions detailed, or,as in most cases, you are advised to seek qualified assistance,contact the site engineer, or the UPS supplier for further advice.
WARNINGUNDER NO CIRCUMSTANCES SHOULD YOU
REMOVE THE UPS COVER PANELS OTHER THANTHE FRONT LIFT-OFF COVER. THIS EQUIPMENT
CONTAINS POTENTIALLY LETHAL VOLTAGESEVEN WHEN IT IS DISCONNECTED FROM THE
INPUT SUPPLY.
CautionIf a problem cannot be resolved by taking the actionsgiven, then fully trained assistance should be soughtimmediately. Do not under any circumstances make
internal circuit adjustments or interfere with the circuitboards in any way.
WARNINGIF THE NOMINAL SET INPUT SUPPLY VOLTAGE
EXCEEDS 120% THE UPS WILL SHUT DOWNOPERATION. DO NOT SWITCH TO MAINTENANCE
BYPASS OR YOU MAY CAUSE CONNECTEDEQUIPMENT TO BE DAMAGED.
Issue 3 (01/03/98) 5-3
IOM Manual Chapter 5 - Troubleshooting
5.4 Troubleshooting Charts
WARNINGTHE ACTIONS DESCRIBED SHOULD BE CARRIED OUT BY COMPETENT PERSONNEL. REMEMBER THAT THE
UPS EQUIPMENT CONTAINS POTENTIALLY LETHAL VOLTAGES EVEN WHEN DISCONNECTED FROM ITS INPUTPOWER SUPPLY.
DO NOT UNDERTAKE ANY ACTION NOT DESCRIBED
Table 5.2 - Interpretation of Status Messages
Status Message Interpretation & Actions
AMBIENT TOO HOT Ambient temperature has exceeded its preset limit. This is a warning that the ambient temperature isgetting too high. If it continues to rise the UPS will transfer to bypass, if available, and shut down ifnot.1. Check that UPS room ventilation system is operating correctly.2. Check there is no obstruction of the inlet and outlet grills of the UPS and that there is sufficient
clearance around the unit.3. Seek qualified assistance if no cause can be identified.
BATTERY CHARGE FAULT There is a problem with the battery charger. The batteries may be charging at the wrong voltage, andpossibly not at all. On battery operation after an input supply failure is still possible, but the batterieswill not be recharged when the input supply returns. Autonomy time will therefore not return tonormal.Seek qualified assistance.
BATTERY ON TEST A battery test, initiated at the UPS control panel, is in progress.
BATTERY TOO HOT Battery temp is above recommended maximum for correct operation. Whilst in this state, the batterycharger will not operate.Check battery ventilation system is operating correctly.
BATTERY VOLTS HIGH The battery voltage is greater than the set limit, probably because a faulty battery was fitted when abattery string was replaced.Check the voltages on each tray/battery block and replace any found defective.
BATTERY VOLTS TOO LOW This alarm will usually appear when the UPS is operating on batteries under an input supply failurecondition. It warns that the end of battery autonomy time is near (i.e. is less than 10% of nominal).NB: At the end of the autonomy time the load will transfer to the bypass supply if available; i.e. with a
split bypass system, in which case LED2 will be off.If the bypass supply is not available (e.g. with a common bypass system) LED2 will be flashing.Shut down your load in a controlled manner because power to the load will soon be lost.
CONVERTER HEATSINKTOO HOT
The temperature of the converter heat sink has risen above its warning value. If the temperaturecontinues to rise, the UPS will transfer to bypass, if available and shut down if not.1. Ensure unrestricted airflow around the unit - e.g. no blocked ventilation grills.2. Check fan operation.3. Check for AMBIENT OVERHEAT alarm indication and reduce ambient temperature if necessary.4. Reduce the UPS load if excessive.5. If (1) to (4) are satisfactory seek qualified assistance.
DIAGNOSTIC LINK ON May appear when servicing the UPS. For use only by service engineers.
EMERGENCY TRANSFERTO BYPASS
The inverter has developed a fault and transferred the load to bypass.1. Observe any other alarms (e.g. excessive load or overtemperature) and take necessary actions.2. Seek qualified assistance if no problems are found.
EMERGENCY TRANSFERTO INVERTER
A fault has occurred while the load was on bypass which transferred the load to the inverter.1. Observe any other alarms and take necessary actions.2. Seek qualified assistance.
END OF DISCHARGE Battery voltage has fallen below an acceptable minimum value.The alarm usually appears when the UPS has been operating on batteries under a input power failurecondition and indicates that the battery autonomy time has ended. The load will have transferred to thebypass supply (if available - i.e. a split bypass system). Otherwise, (common bypass system) the UPSwill have shut down and power to the load will have been lost.Alternatively, it may be because of a battery fuse failure or a charger fault.1. Check battery fuses FS1 and FS2 - refer to paragraph 5.5.2. If fuses have failed, or there is a charger fault, seek qualified assistance.
INVERTER HEATSINK TOOHOT
The temperature of the inverter heat sink has risen above its warning value. If the temperaturecontinues to rise, the UPS will transfer to bypass, if available and shut down if not.Carry out the checks given above for converter heatsink too hot (table 5.2).
5-4 Issue 3 (01/03/98)
Chapter 5 - Troubleshooting AP4300
Table 5.2 - Interpretation of Status Messages - contd.
Status Message Interpretation & Actions
LOCALLY STOPPED SW2 on the back of the UPS has been pressed and consequently the UPS output has been switchedoff.Switch the output on when required, if it is safe to do so; follow the operating instructions inchapter 2.
OUTPUT OVERLOAD The load is too large for the UPS to supply for an indefinite period. The time for which the UPS cansupport the overload will depend on the magnitude of the overload - the greater the overload, theshorter the time interval. If this time is exceeded, a transfer to bypass will be performed if the bypassis available. If it is not, the unit will shut down.Refer to the Output Overload Ability information given under Output Data in the AP4300 SeriesSpecification at the end of this manual.1. Check for an overload and shed any excess load.2. If load is not indicated as being excessive, or the indications persist, seek qualified assistance.
OUTPUT HIGH FAIL The output voltage has become too high due to an inverter fault, and has exceeded the permitted level.The load will transfer to bypass if the condition persists.Seek assistance if condition persists.
OUTPUT SHORT CIRCUIT A short circuit fault exists on one or more of the output lines.1. Correct the short circuit.2. If no short circuit is found on the output lines, seek qualified assistance.
PHASE ROTATION ERROR The phase sequence of the supply on the power cables connected to the bypass line is incorrect. This faultshould only appear either when first starting up after installation, or after repairs to the bypass power sourcewhen phases have been reconnected incorrectly after a cable break.Disconnect power from the bypass line and correct the wiring.Your local service agent's representative must be present when first starting up your UPS system.
PRIMARY DC BUS LOWWARNING
Either missing or low input power supply and battery discharged.Check the input supply voltage and if this is found to be correct then seek qualified assistance.
REMOTELY STOPPED The remote STOP button (option) has been pressed and consequently the UPS output has beenswitched off:1. Determine if remote stop has really been operated.2. Check continuity of remote stop line.
UPS ON BATTERY Battery is discharging -e.g. because the input power supply is absent and the battery has taken over. Thefive autonomy LEDs switch off progressively from the right as the time remaining before batteryshutdown reduces.1. Check that the input supply is present.2. Check the UPS input circuit breakers (CB4, CB5 & CB6) - refer to paragraph 5.5.3. If (1) and (2) are satisfactory then seek assistance.
UPS ON BYPASS The load has been transferred to the bypass supply due to a fault or status malfunction:Note: The UPS will periodically transfer to bypass to check the integrity of the static bypass circuitry.
It should remain in this state for a maximum of 6 seconds after which a re-transfer to inverter willtake place.
Observe other indications (e.g. excessive load or overtemperature) and take appropriate actions.
UPS OUTPUT OFF The UPS is active but its output has been switched OFF using one of the methods described inchapter 2.1. Check if the UPS output has been turned OFF - e.g. from a remote location. If it has, find out the
reason and then turn it on when it is safe to do so. Refer to the operating instructions in chapter 2.If the output does not switch on, turn SW1 back to MAINT and restart the UPS. Refer to theoperating instructions in chapter 2.
2. If the above actions do not overcome the problem, seek qualified assistance.
UPS OVERTEMPERATURE Temperature of one or more of the UPS internal sensors has reached its fail level. The UPS will transferto bypass immediately, if the bypass supply is available.1. Check if there are any other status messages indicating excessive temperature by scrolling through
them on the default screen.2. Carry out the checks given above for converter heatsink too hot (table 5.2).
Issue 3 (01/03/98) 5-5
IOM Manual Chapter 5 - Troubleshooting
Table 5.3 - Interpretation of Error Messages
Status Message Interpretation & Actions
BYPASS SCR SHORT CCT Internal power component problem.1. Transfer the load to the maintenance bypass following the appropriate operating instructions.2. Seek qualified assistance immediately.
BYPASS SCR OPEN CCT Internal power component problem.1. Leave the UPS running. Do not operate SW1 or SW2 under any circumstances as this will power
down the load.2. Seek qualified assistance immediately.
INPUT LOW FAIL The input supply is low and the battery is not supporting the primary DC Bus, so the voltage on theprimary DC Bus has fallen below its fail level.1. Check the state of the input, the input circuit breakers and battery fuses refer to paragraph 5.5.2. If these are OK then seek qualified assistance. Also see status message [UPS ON BATTERY] in
table 5.2 for other possible messages.
INPUT HIGH FAIL The input supply voltage on one or more of the INPUT terminals is too high (i.e. greater than 120%).1. Problem could be due to genuine high input supply voltage, or surge(most likely if it corrects
itself). Check if voltage is above 120% of nominal on the input supply.2. If this alarm occurs during initial start-up check that the voltage is correctly set for the local
working voltage. (see installation instructions).3. If neither of the above then seek qualified assistance. Note warning on page 5-4.
BYPASS LO FAIL While on bypass for whatever reason, the UPS has detected that the bypass volts on one or more ofthe phases has fallen below its fail level. The UPS will have performed an emergency transfer toinverter, if available, or shut down if not.1. Could be due to genuine low voltage on the bypass supply2. Check if the bypass circuit breakers: CB1, CB2 & CB3 have tripped open, - refer to
paragraph 5.5.3. If neither of the above then seek qualified assistance.
BYPASS HI FAIL While on bypass for whatever reason, the UPS has detected that the bypass volts on one or more ofthe phases has risen above its fail level. The UPS will have performed an emergency transfer toinverter, if available, or shut down if not.Could be due to genuine high bypass. Check if voltage is above 120% of nominal on the bypasssupply. If it is not, seek assistance..
PHASE ROT. ERROR Refer to this message in table 5.2.
OUTPUT HI FAIL Refer to this message in table 5.2.
OUTPUT LO FAIL Output voltage has fallen below the allowed minimum on one or more phases.Either an internal voltage regulation problem exists or there has been a sudden increase in load.Load will transfer to bypass if condition persists.Seek assistance if the load is not excessive and cannot be transferred back to the inverter.
OUTPUT SHORT CIRCUIT Refer to the message OUTPUT SHORT CIRCUIT in table 5.2.
O'LOAD TIMEOUT Load current on one or more output phases has exceeded the permitted level for too long. The UPShas transferred the load to the bypass.1. Shed excess load2.If load is not indicated as being excessive seek qualified assistance.
WAITING FOR BYPASS Automatic tests (SW1 in TEST position) cannot proceed due to one or more of the bypass phasesbeing absent.1. Check bypass supply voltage and circuit breakers.2. Seek assistance if all three phases are present.
END OF DISCHARGE Battery has reached end of discharge, following a input supply failure. UPS will have shutdown, (in acommon bypass system), or transferred to bypass (split bypass system).
SW1 IN WRONG POS. An attempt has been made to start the UPS with the rotary switch SW1 set at UPS without autorestartenabled.
DC OFFSET TIMEOUT The UPS has detected DC on the output of one or more phases. The UPS will have transferred theload to the bypass.Seek qualified assistance.
BP SCR OPEN CCT (2) Refer to BYPASS SCR OPEN CCT above.
* * * * HI TEMP FAIL Refer to UPS OVERTEMPERATURE in table 5.2.
EOD (IP Ø MISSING) One of the input phases is not supplying power, probably because a fuse has failed in the supply.Check that all input supply fuses are OK, all input circuit breakers are closed and connections to allinput terminals are tight.
5-6 Issue 3 (01/03/98)
Chapter 5 - Troubleshooting AP4300
Table 5.4 - Interpretation of Error Messages
Error Message Interpretation & Actions
AMB TEMP SENS FAULT
SELECT SWITCH 1 TO THE MAINTENANCE BYPASS POSITION AND SEEKQUALIFIED ASSISTANCE FOR ALL THESE ERROR MESSAGES
BATTERY CHRG. FAULT
BATTERY NOT CHARGING
BAT TEMP SENS FAULT
COMMS FAILURE (CAN)
COMMS FAILURE (422)
CONTROL PWR OFF FAIL
CONV. FEEDBACK ERROR
CONVERTER NOT OK
CONV TEMP SENS FAULT
DC2 MIDPOINT HI FAIL
EMERG BYPASS FIRING
INTERFACE RESET
INV TEMP SENS FAULT
MAG TEMP SENS FAULT
NO OUTPUT VOLTS
NVRAM RELOADED
OUTPUT SHORT CCT.
SEC. DC BUS HIGH FAIL
SEC. DC BUS LOW FAIL
SETUP DATA ERROR
SETUP DATA RELOADED
TOO MANY CONV. RST.
VCE SAT FAIL
Issue 3 (01/03/98) 5-7
IOM Manual Chapter 5 - Troubleshooting
5.5 Checking the input and bypass circuitbreakers, and battery fuses
A number of alarms may be triggered by a circuit breaker opening ora fuse failure; e.g: Battery volts too low, UPS on battery & BypassIP volts low.
Circuit breakers and fuses are accessible after removing the ‘lift-off’right hand front panel. The positions of the fused switches (FS1-FS2)which carry the battery fuses and the circuit breakers for the bypasssupply (CB1-CB3) and the input power supply (CB4-CB6), areshown in fig.5-2.
WARNINGONLY PERSONNEL WHO ARE TRAINED AND
DEEMED COMPETENTSHOULD CHECK FUSES OR OPERATE CIRCUIT
BREAKERS.TRANSFER THE LOAD TO THE MAINTENANCE
BYPASS SUPPLY BEFORE CARRYING OUT A FUSECONTINUITY CHECK.
5.5.1 Battery fuse check
Open the fuse holders of the fuses in question and extract thefuses from the holder. Check the continuity of the fuses with asuitable meter, and replace any fuses found to be defective.
CautionEnsure any defective fuses are replaced by fuses of thesame TYPE and RATING (i.e. 30A) as the fuse being
removed.Never increase the fuse rating.
5.5.2 Circuit breaker check
The switch levers of any circuit breakers which have tripped opendue to an excessive current passing through them will be in thedown position.
Before closing any tripped circuit breakers, ensure that it is safeto do so.
5-8 Issue 3 (01/03/98)
Chapter 5 - Troubleshooting AP4300
TEST
MAINT
O/P OFFO/P OFF
UPS
AP4300
AP4300UPS NORMAL NO ALARMShh:mm:ss dd:mm:yy
TESTMAINT
SW1
OFF(0)
OFF(0)
UPS
INPUTBYPASSBATTERYFUSES
CB2 CB3CB1 CB5 CB6CB4FS2FS1
Figure 5-2 Input and bypass circuit breaker and battery fuse
holder locations
Chapter 6 - Maintenance
6.1 Routine Maintenance Checks by theOperator
6.1.1 Introduction
The UPS uses solid state components with the only moving partsbeing the cooling fans, switches and relays, so it is essentially‘maintenance free’. However the checks in this chapter will help tomaintain the reliability of the UPS module and battery. Werecommend an annual service of the unit by an engineer approvedby the manufacturer, preferably under a service contract.
Scheduled maintenance requirements, beyond ensuring that theUPS remains cool and clean, are minimal. However, a welldocumented program of regular inspection will help to ensureoptimum performance and also help to detect certain minorproblems before they develop into a major fault.
6.1.2 Checks at weekly intervals
1. Ensure that the ventilation space around the base and the back
of the UPS is not obstructed.
2. Check the function of all the LEDs and pushbuttons on the
panel by carrying out a Front Panel Test. Press each pushbutton
in turn for two seconds. All the LEDs should switch on and the
audible alarm should sound with each pushbutton. Cancel the
alarm and record the result.
If the default screen is on the display when a test is made, the
top line of the screen will indicate the UPS type in the
following format:
AP43XX NN.N ii/oo ±b
UPS NORMAL NO ALARMS25-09-95 10:15:00
XX = chassis type (XX=10 or 20)
NN.N = UPS output rating.
ii = input frequency
oo = output frequency
±b = battery presence (i.e. +b=battery fitted; - b=battery
not fitted, e.g. when the UPS is used as a line
conditioner).
6.1.3 Checks at monthly intervals
In addition to the weekly checks, use the procedure following tocheck and record the present values of the UPS status parametersas listed:
1. Output voltage and frequency on each phase.
2. Output current & output load (kW & kVA) on each phase.
Note: If the output currents differ significantly from the values
previously logged then, if possible, record the size, type and
location of any load connected to (or removed from) the UPS
since the previous inspection.
3. Bypass supply voltage on each phase, and the frequency.
4. Battery float charge voltage and capacity.
5. Voltage on the primary and secondary DC bus.
Ambient and battery temperatures, temperatures on the
inverter & converter heatsinks (& on the converter magnetics
in 20kVA units).
State of the converter, charger & inverter.
UPS status parameters
The values of the status parameters are displayed on the LCDpanel by selecting options from the windows reached via the mainmenu & status windows, (see the menu map in fig.6-1). If any of thevalues differ greatly from those previously logged, for no apparentreason, seek advice from your Distributor or Service Agent.
From the default window, press ENTER to display the main menuwindow:
STATUSCOMMANDSSETUPMAINTENANCE
The cursor will be aligned with STATUS. Press ENTER to select thestatus window. The menu of UPS status categories is displayed:
OUTPUTBYPASSBATTERYINTERNAL
Output parameters
Select OUTPUT by pressing ENTER to display the first of a setof six screens which can be displayed in rotation by pressingENTER successively. Press ESC to return to the STATUS screen.These screens display, in sequence:
OUTPUT VOLTS (L-N)OUTPUT VOLTS (L-L)OUTPUT LOAD (kVA) on each of the phases L1, L2, L3OUTPUT LOAD (kW) }OUTPUT CURRENTINVERTER OUTPUT FREQUENCY.
The inverter output frequency screen also carries a messagestating whether the UPS output and bypass supplies aresynchronised.
Bypass
Return to the status window and select BYPASS to display thebypass supply voltage and frequency levels:
BYPASSL1 L2 L3240 240 240FREQUENCY (HZ) 50.1
Issue 3 (01/03/98) 6-1
6-2 Issue 3 (01/03/98)
Chapter 6 - Maintenance AP4300
SETDATEANDTIMESELECTLANGUAGE
FRANCAISITALIANO
ENGLISH ESPANOLDEUTSCH
ENTERPASSWORD
SELECTADJUST
SETCANCEL
****
BATTERYINFORMATION
OUTPUTBYPASSBATTERYINTERNAL
OUTPUTFREQUENCYFREQUENCY(Hz)50.0
SYNCHRONISED
OUTPUTCONTROLOUTPUTOFFOUTPUTON
TIMEDOPCONTROL
DELAYEDOPOFFDELAYEDOPON
CANCELOR DELAY
BATTERYTESTTESTBATTERY
LASTTESTRESULT
OUTPUTCONTROLTIMEDOPCONTROLSHUTDOWNCONDITIONBATTERYTEST
UPSNORMAL NOALARMS14-02-94 14:35:00
FAULT
TESTSPASSEDTURNSW1TOUPSONMAINTENANCEB/P
14:35:0014-02-94
14:35:0014-02-94
TURNSW1TOMAINTONMAINTENANCEB/P
TESTSABORTED NN
STATUSCOMMANDSSETUPMAINTENANCE
OUTPUTVOLTSL-LL1-2400
L3-1400
L2-3400
OUTPUTVOLTSL-NL3240
L2240
L1240
BYPASS
FREQUENCY(HZ)50.0
L1240
L3240
L2240
OUTPUTPOWERKW
0.88 0.88089L1 L3L2
TOTAL 2.65KW
OUTPUTPOWERKVA
0.87 0.870.87L1 L3L2
TOTAL 2.61KVA
OUTPUTCURRENTAMPSL1
1.4L31.4
L21.5
TIME 00:41:24420 100 ON
VOLTS CAP%CHARGER
INV AMBMAG
CONV BAT
423840
2423
DCBUSVOLTS
800PRIMARYSECONDARY400
TORETURN
SELECTADJUST
SETCANCEL
DD-MM-YY00- 00 -00
HH:MM:SS00 :00 :00
SHUTDOWNCONDITIONONBATTERYATANYTIME
DCBUSTEMPERATURESINFORMATION
ERRORPAGEUPSSTATUSEVENTHISTORY
ERRORPAGE(status)(UPSaction)(message/fault)
UPSSTATUSCONVERTER ONINVERTER ONBATTERYCHARGERON
COMMUNICATION
FAULTATANYTIME
AP4310FATALERROR
CALLFORSERVICE01793553355
#XX
NOMESSAGE
14-02-94 14:35:00
NOREPORT
NORMAL
STARTUPTESTSOK
INITIALISATIONTESTSOK
14:35:0014-02-94
AP4300TURNSW1TOTESTUPSOUTPUTOFF
SWITCHONATMAINISOLATOR
CLOSEBATTERY
FUSES
AP4300INITIALISING
PLEASEWAIT . . .
Figure 6-1 Map of the displays on the LCD screen accessible by the operator
Battery parameters
Selecting BATTERY from the status window displays the batteryvoltage, capacity, and autonomy time at the current load, and thecharger status:
BATTERY INFORMATIONVOLTS CAP % CHARGER420 100 ON
TIME 00:41:24
Internal parameters
Select INTERNAL from the status window to display furtheroptions:
DC BUSTEMPERATURESINFORMATION
Select DC BUS to show the voltage levels on the two DC buses:
DC BUS VOLTSPRIMARY SECONDARY
400 800TO RETURN
Select TEMPERATURES to display the battery (BAT) andambient (AMB) temperatures, and the temperatures on theconverter (CONV) and inverter (INV) heatsinks, and, on 20kVAunits only, the converter magnetics (MAG):
CONV 40 BAT 23INV 38 AMB 24MAG 42
Select INFORMATION to gain access to windows from whichinformation on the past and present state of the UPS can beobtained:
ERROR PAGEUPS STATUSEVENT HISTORY
Select UPS STATUS to show the state of the three major blocksof the UPS:
UPS STATUSCONVERTER ONINVERTER ONBATTERY CHARGER ON
The ERROR PAGE & EVENT HISTORY windows are usedwhen an alarm has been triggered, and enable the cause of thealarm, and the events leading up to it, to be analysed. Refer toSection 5.2.3 in Chapter 5 - Troubleshooting.
6.1.4 Annual checks
1. Carry out the monthly checks given above.
2. Carry out a battery test as follows:
From the default window, press ENTER to display the main
menu window. Select COMMANDS. and press ENTER:
OUTPUT CONTROLTIMED OP CONTROLSHUTDOWN CONDITIONBATTERY TEST
Select BATTERY TEST and press ENTER:
BATTERY TESTTEST BATTERY
LAST TEST RESULT
The cursor points at TEST BATTERY. Press ENTER to start the
battery test. If the battery is satisfactory, the word: PASS
appears on the screen.
Issue 3 (01/03/98) 6-3
IOM Manual Chapter 6 - Maintenance
6.2 Annual Maintenance Checks by ServiceEngineer
6.2.1 Introduction
These checks entail working inside the UPS, and should beundertaken only by a Liebert trained engineer who is familiarwith the UPS operation and lay-out, and who is aware of thepotential hazards.
SAFETY PRECAUTIONSWhen working on the UPS remember that it will containlive voltages at ALL TIMES unless it has been isolatedfrom the external input power supply, and the internal
batteries (and external batteries, if fitted) have beendisconnected. It is essential that the safety and
precautionary notes contained throughout this manualare read and fully understood before touching any UPS
internal component part.
The service engineer would complete the following checks:
UPS
Carry out a thorough visual examination of the UPS power
components and sub-assemblies, paying particular attention to
the following:
Electrolytic capacitors -
Check for signs of leakage, buckling etc.
Magnetic components -
Check for signs of overheating, security of fixture and
signs of cracking in ferrite components.
Cables and connections -
Check all cables for chafing, fraying or signs of
overheating. Also check that all cable connections are
tight and all printed circuit board connectors are secure.
Printed circuit boards -
Check the cleanliness and integrity of the circuit boards
and replace if any signs of deterioration are found.
CautionA lithium battery powered chip (part no.02101065) is
carried on the interface board. If this board is replaced,either dispose of the chip in accordance with the
manufacturer's instructions, or else contact your localdistributor for disposal instructions.
DO NOT DISPOSE OF THE CHIP THROUGH THEDOMESTIC REFUSE SERVICE.
Batteries
WARNING - BATTERY HAZARDSSPECIAL CARE SHOULD BE TAKEN WHEN
WORKING WITH THE BATTERIES ASSOCIATEDWITH THIS EQUIPMENT.
WHEN CONNECTED TOGETHER, THE BATTERYTERMINAL VOLTAGE WILL EXCEED 380VDC AND
IS POTENTIALLY LETHAL.IT MAY BE NECESSARY TO DISCONNECT THEINTER-TRAY LINKS IN ORDER TO GAIN FULL
ACCESS TO THE BATTERY TRAYS. DO THIS WITHEXTREME CAUTION.
EYE PROTECTION SHOULD BE WORN TOPREVENT INJURY FROM ACCIDENTAL
ELECTRICAL ARCS.IF A BATTERY LEAKS ELECTROLYTE, OR IS
OTHERWISE PHYSICALLY DAMAGED, ITSHOULD BE PLACED IN A CONTAINER
RESISTANT TO SULPHURIC ACID AND DISPOSEDOF IN ACCORDANCE WITH LOCAL
REGULATIONS.IF ELECTROLYTE COMES INTO CONTACT WITH
THE SKIN, THE AFFECTED AREA SHOULD BEWASHED IMMEDIATELY.
Check the batteries carefully, paying particular attention to thefollowing:
General condition -
Examine the battery cases for signs of deformation,
cracks or general physical deterioration.
Battery block voltage -
Check the voltage of each battery block with a meter.
This should be greater than 12.6 volts d.c.
Cables and connections -
Examine the cables for signs of deterioration and ensure
that all connections are securely fastened.
General
If necessary, thoroughly clean inside the UPS using a vacuum
cleaner.
Re-assemble the UPS, and start it up following the procedures
in Chapter 2 - Operating Instructions.
If possible, check the battery autonomy time by turning the
UPS input supply OFF while the UPS is on-load. Ensure that
the UPS operates on battery correctly and check that the
available battery autonomy time meets the specification.
Refer to the procedure in Chapter 2 - Operating Instructions.
Turn the UPS input supply ON again as soon as these checks
have been made.
6-4 Issue 3 (01/03/98)
Chapter 6 - Maintenance AP4300
Chapter 7 - Liebert Warranty
LIMITED WARRANTY
Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the“purchaser”): the enclosed Uninterruptible Power System (UPS) and components are free from defects in materials and workmanshipunder normal use, service and maintenance FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF ORIGINAL PURCHASEfrom Liebert or the Liebert Dealer/Retailer. THE FOREGOING WARRANTY IS THE ONLY WARRANTY GIVEN AND NOOTHER WARRANTY IS PROVIDED, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITYOR FITNESS FOR A PARTICULAR PURPOSE. Certain aspects of disclaimers are not applicable to consumer products acquired byindividuals and used for personal, family, or household purposes (as distinguished from industrial or other purposes). Local laws maynot allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. This warranty gives youspecific legal rights, and you may have other rights which vary according to local law.
Certain repairs or services are the responsibility of the purchaser and the purchaser is expected to pay for them. This warranty doesnot extend either to products with removed or altered serial numbers or to any losses or damages due to an act of god or sourceexternal to the product, misuse, accident, abuse, neglect, negligence, unauthorised modification, alteration, or repair, use beyond ratedcapacity, or improper installation, maintenance, application or use, including without limitation, use in a manner contrary to theaccompanying instructions or applicable codes. The battery must be recharged every four (4) to six (6) months when not in use.
The warranty will be invalidated unless the UPS has been commissioned by Liebert CS&S or an engineer who has been trained onthe product in an approved Liebert Training Centre.
Warranty does not apply to consumable parts such as lamps and fuses. Warranty of batteries only applies to batteries that have beensold by Liebert and installed as an integral part of the UPS system.
If the UPS fails to conform with the above warranty within the stated period, Liebert will repair or replace the UPS, at Liebert'soption. Replacement parts will only carry the benefit of the unexpired portion of the main equipment warranty. Purchaser to makewarranty claim, should on first instance contact the Dealer/Retailer from whom the unit was purchased, supplying the model type,rating and serial number along with a fault description.
LIFE SUPPORT APPLICATIONS
Due to the diversity of applications and considerations to be applied in each case, Liebert does not recommend or knowingly sell itsproducts for such use.
The responsibilty for risk assessment and management in applications where the malfunction or failure of the UPS could bereasonably be expected to give rise to risk of human life shall be the sole responsibility of the purchaser. Liebert accepts no liabilityfor consequential harm in such applications.
Issue 3 (01/03/98) 7-1
7-2 Issue 3 (01/03/98)
Chapter 7 - Liebert Warranty AP4300
AP4300 Series UPS Specification
INPUT DATA UNITS AP4307 AP4310 AP4315 AP4320
Input line voltage (nominal) V ac 400V 3 Phase
Continuous input voltage Operational range V ac 320V to 480V*
Input bypass voltage line and neutralTolerance
V ac 400V 3 Phase (programmable to 380 or 415V)default: ±10% (programmable to ±15%)
Input kVA at maximum rated load including battery charging kVA 8,1 10,4 16 21
Power factor at rated kW load - ³0.95 ³0.95
Max input power at rated kW load including battery charging kW 7,7 9,8 15,2 20
Nominal input current at rated kW load, including batterycharging (i.e. @ 400V supply)
A 11,7 15,0 23,4 30
Max input current at rated kW load, including battery charging(i.e. @ 320V supply)
A 14,5 18,6 29,0 37,2
Nominal Input frequency Hz 50 or 60
Max permissible input frequency variation for synchronisedoperation
Hz ±5
Conducted and radiated EMC levels - EN 55022 A
Compliant safety standards - EN 50091-1
Compliant immunity standards - EN 50082-1IEC 801( Parts 2, 3, 4 & 5.)
Note 1: Unless otherwise specified all voltage and current values stated in this specification are rms.
*Note2: Below 320V ±2% unit will transfer to battery
Above 480V ±2% unit will transfer to battery
INTERMEDIATE DC CIRCUIT DATA UNITS AP4307 AP4310 AP4315 AP4320
Number of valve regulated lead acid batteries (12V) - 32 2 x 32
Type of battery (recommended) Yuasa NP 11-12 (or equivalent)
Nominal battery float voltage @ 20oC Vdc 437 ±0.5%
End of battery discharge voltage Vdc 320 ±1%
Battery capacity (default)** Ahr 11 2 x 11
Battery autonomy time (Typical) mins. 17 14 17 14
Maximum charging current A mean 2.8 5.6
Battery fuse rating (FS1 & FS2) and (FS3) A 30(Bussman KLM-30A
500Vd.c.)
50(Bussman FWP-50A14F
700Vd.c.)
**Note 3: Battery Capacity
Battery performance depends on the ambient battery temperature. Capacity and autonomy times are quoted for a new battery operating at 20°C.
Battery capacity is increased by 1% for every 1°C increase in temperature up to 25°C.
If a battery is used at a temperature above 25°C, its life is reduced; consequently its capacity and UPS autonomy time will reduce more rapidly over a
period of time. Battery float voltage is compensated (by 3mV per °C per cell).
Issue 3 (01/03/98) 8-1
OUTPUT DATA UNITS AP4307 AP4310 AP4315 AP4320
Output voltage Nominal Vac 3 Phase - 400Vadjustable 361V to 436V
1 Phase - 230Vadjustable 200V - 250V
Output voltage regulation % ±1
Voltage Balance (L-N, L-L)Balanced Load100% unbalanced load
% ±1±2
Output voltage distortion with 100% linear load % <3,0
Phase BalanceBalanced Load100% unbalanced load
120° ±1°120° ±°
Output frequency Hz 50 or 60
Output frequency tolerance while synchronised to input mainssupply
Hz ±5
Maximum rated output kVA (balanced load)Maximum rated output power (balanced load)
kVAkW
7,56
108
1512
2016
Nominal UPS efficiency at 100% linear load, not includingbattery charging
% 88 89 87 89
Output overload ability (for kW and for kVA)(load will transfer to static bypass if times are exceeded)
% up to110% continuous125% for 10 mins
150% for 60 seconds200% for 5 seconds
Inverter output peak current limit (max. transient) A pk 45 90
Continuous Bypass rating A 14 18 28 36
Internal overload protection on static bypass (Type C circuitbreaker)
A 20 40
MECHANICAL CHARACTERISTICS UNITS AP4307 AP4310 AP4315 AP4320
Dimensions: WidthHeightDepth
mm4271100682
6571100682
Weight (without batteries) kg 122 176
Weight (with batteries) kg 250 432
Colour - RAL 7035/7038
Ventilation - internal fans - 4 fans 6 fans
Enclosure - IP22
Airflow m3/hr 130 325
Operating temperature (range) °C 0 to +40
Max altitude for full rating m 1000
Nominal heat dissipation (fully charged battery) kW 1,2 1,3 2,3 2,6
Acoustic noise level for rated load at 1 metre dBA <54 58
Relative Humidity - 0-90% non-condensing
This equipment is manufactured byLiebert Swindon Limited, Elgin Drive, Swindon,
Wilts SN2 6DX, United KingdomTelephone: +44 (0) 1793 553355 Fax: +44 (0) 1793 553400
a BS EN ISO9001:1994 registered company.
8-2 Issue 3 (01/03/98)
AP4300 Series UPS Specification AP4300
Parameter Settings for the AP4300
This table permits a record to be kept of any changes made to the software default settings during commissioning.The commissioningengineer will enter the values of any changed parameters and sign where indicated.
Parameter Range Setting
Max Min Default New Setting
OUTPUT VOLTS
HIGH FAIL 264 231 253
NOMINAL VOLTS 250 200 230
LOW WARN 216 198 207
LOW FAIL 204 187 195
BYPASS VOLTS
HIGH FAIL 276 253 265
HIGH WARN 264 242 253
LOW WARN 216 198 207
LOW FAIL 204 187 195
PRIMARY DC BUS (DC Volts)
HIGH FAIL 705 645 660
HIGH WARN 705 619 650
LOW WARN 400 320 390
LOW FAIL 300 300 300
SECONDARY DC BUS (DC Volts)
HIGH FAIL 840 820 840
HIGH WARN 840 820 820
LOW WARN 760 740 760
LOW FAIL 740 660 700
BATTERY VOLTAGES
HIGH FAIL 488 431 460
HIGH WARN 468 413 441
NOM FLOAT 462 408 437
NOMINAL 427 377 402
LOW WARN 391 328 350
LOW FAIL 330 290 310
EOD VOLTS 340 300 320
Issue 3 (01/03/98) 8-3
Parameter Range Setting
Max Min Default New Setting
BATTERY CAPACITY (Ampere Hours)
CAPACITY 240 1 12
BATTERY WARNING TIME (Seconds)
LOW BAT WARN TIME 1800 60 300
TEMPERATURES (Deg °C)
FAIL 75 55 65
INVERTER 65 50 55
CONVERTER 70 50 55
BATTERY 40 30 35
AMBIENT 40 30 30
PHASE LOCKED LOOP (PLL)
OP frequency (Hz x 10) - fixed by firmware installed
FREQUENCY 500
Capture Range (Hz x 10)
CAPTURE RG 50 1 20
Lock Range on Inverter (Hz x 10)
LOCK (INV) 50 1 25
Lock Range on Bypass (Hz x 10)
LOCK (BYP) 50 1 50
Slew Rate (Hz per sec x 10)
SLEW 20 1 10
In Phase Range (msec)
IN LOCK 200 120 120
MISCALLANEOUS
DUMMY 0 (not used)
SHUTDOWN ALLOWED 0
LAST OP STATE 1
AUTORESTART 1 0 1
Note: Parameter settings which are not normally changed are indicated by a tint in the corresponding cell in the New Setting column.
UPS MODEL....................................................................Name:......................................................................................................
SER. NO...........................................................................Signature............................................................Date..............................
8-4 Issue 3 (01/03/98)
Parameter Settings for the AP4300 AP4300
Keeping Business in BusinessTM
AP4300 Three Phase
7.5 to 20 kVA 50 or 60Hz.
Series AP4300 UPS
The Company Behind The Products
With more than 500,000 installations around the globe,Liebert is the world leader in computer protectionsystems. Since its founding in 1965, Liebert hasdeveloped a complete range of support and protectionsystems for sensitive electronics
+ Environmental systems close-control airconditioning from 1.5 to 600 tons.
+ Power conditioning and UPS with power rangesfrom 400 VA to more than 1000 kVA.
+ Integrated systems that provide both environmentaland power protection in a single, flexible package.
+ Monitoring and control - on-site or remote - fromsystems of any size or location
+ Service and support, through more than 100 servicecentres around the world and a 24 hour CustomerResponse Centre
While every precaution has been taken to ensure accuracy and completeness in this manual,Liebert Corporation assumes no responsibility and disclaim all liability for damagesresulting from use of this information or for any errors or omissions.
©1997 Liebert Corporation. All rights reserved throughout the world.Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.
Liebert CorporationGlobe Park, Marlow,
Buckinghamshire SL7 1YG
United Kingdom
Tel: +44 (0) 1628 403200
Fax: +44 (0) 1628 403203
Liebert Français124 Avenue Galliéni,
93170 Bagnolet, France
Tél: +33 (0) 1 43 60 0177
Fax: +33 (0) 1 43 60 7007
Liebert GmbHLiebigstraße 9, D-85551 Kirchheim,
B.München, Deutschland
Tel: +49 (0) 89 991 9220
Fax: +49 (0) 89 904 3151
Liebert BVBosstraat 96, Postbus 9100,
6070 AC Swalmen, Netherland
Tel: +31 (0) 475 504050
Fax: +31 (0) 475 502876
Liebert SiceVia G Rossini 6,
20098 San Giuliano Milanese,
Milano, Italia
Tel: +39 (0) 2 982501
Fax: +39 (0) 9844633
Liebert Web Sitehttp:/www.liebert.com