640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
152316
orientation
project number
scale
date
sheet title
sheet number
date description07.22.15
1/8" = 1'-0"
Title Sheet
7/22/15
A001
415 W. Huron St.
Speedwagon Propertiesowner
Chicago,IL 60654
Issue for Zoning Review
Mechanical, Plumbing, Electrical Engineer
DEVELOPER
ARCHITECT
Speedwagon Properties
Pappageorge Haymes Partners
Stearn-Joglekar, Ltd.STRUCTURAL
W-T Engineering
Eriksson EngineeringCIVIL
Chicago, IL
415 W. Huron St.Adaptive Reuse and Residential Conversion
with New Penthouse Addition
Issue for Zoning Review2015-07-22
Drawing IndexA001! ! Title SheetA002! ! General Notes / SymbolsA003! ! Zoning Data
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
152316
orientation
project number
scale
date
sheet title
sheet number
date description07.22.15
1/8" = 1'-0"
Zoning Data
7/22/15
A004
415 W. Huron St.
Speedwagon Propertiesowner
Chicago,IL 60654
Issue for Zoning Review
Business
Commercial
Manufacturing
Residential
Planned Development
Planned Manufacturing
Downtown Core
Downtown Service
Downtown Mixed
Downtown Residential
Transportation
Parks & Open Space
Zoning Boundaries
ZoningCHICAGO LANDMARKS
Chicago Landmarks
Landmark Districts
Chicago Historic ResourcesSurvey - Buildings subject toDemolition-Delay Ordinance
Red
Orange
Historic Preservation Lakefront
Pedestrian Streets
Buildings
Parcels
Streets
Curbs
Water Forest Preserve
Cemetery City Boundary
Municipalities
Zoning Map Created on: 4/23/2015 10:05 A.M.
Address
415 W HURON ST
Information provided on the City of Chicago web site should not be used as a substitute for legal, accounting, real estate, business, tax, or otherprofessional advice. The City of Chicago assumes no liability for any damages or loss of any kind that might arise from the use of, misuse of, orthe inability to use the City web site and-or the materials contained on the web site. The City of Chicago also assumes no liability for improper orincorrect use of materials or information contained on its web site. All materials that appear on the City of Chicago web site are distributed andtransmitted as is, without warranties of any kind, either express or implied, and subject to the terms and conditions stated in this disclaimer.
415 W. Huron Totals Remarks
Allowable Existing Proposed
Net Site Area SF 48.05x 100.29’ Nom. 4,821 4,821 Per SLS Ltd. Survey 101129-2 dated 07.11.2015
Zoning District DX-5 DX-5 DX-5 No Change
PD or Lake Front Protection District No No No
Maximum Permitted FAR 5 4.30 6.00 Affordable Housing Bonus applicable up to Maximum of 1
Additional FAR
Maximum Permitted FAR SF 24,105 20,717 28,925 4,820 SF of Additional FAR Required via Affordable
Housing Bonus
Maximum Permitted FAR SF Data By Floor
Basement N/A N/A N/A >50% Below Grade1st Floor 4,748 SF 2,923 New Parking Not Included in FAR2nd Floor 4,748 SF 4,748 New Residential Use Within Existing Building Envelope3rd Floor 4,748 SF 4,748 New Residential Use Within Existing Building Envelope4th Floor 4,748 SF 4,748 New Residential Use Within Existing Building Envelope5th Floor 4,748 SF 4,748 New Residential Use Within Existing Building Envelope
New 6th Floor 0 4,010 New Residential in Penthouse Addition Lower LevelNew 7th Floor 0 3,000 New Residential in Penthouse Addition Upper Level
28,925 Total Proposed FAR
Maximum Permitted Ht FT
No Limit By Zoning Ord.
5 Stories Existing, Approx.
72ft to Exist Roof
Proposed 2 Story Addition, Total of 7 Stories, Approx. 102ft to New Roof
CZO PD reqs17-8-0500 states that buildings 130 ft or higher are governed by the Planned Development requirements. Height to underside of Existing Elev PH roof estimated to be 80ft.
MLA 200sf/DU No Change
Dwelling Qty 24 Max None 5 Proposed
Parking CZO17-10-0208
1:1 0 1:1 Bike Parking 1 per two auto spaces. 1 HC parking space required.
Side Yard Setback None None None
Rear Yard Setback
30% Lot Depth = 17.8’ 0
No Change Existing Building Abuts Alley at Rear Property Line. New addition lower level (6th Floor) to follow rear yard setback of Existing Building below. New addition upper level (7th Floor) to have 21’ setback.
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
152316
orientation
project number
scale
date
sheet title
sheet number
date description07.22.15
1/8" = 1'-0"
Site / Roof Plan
7/22/15
A101
415 W. Huron St.
Speedwagon Propertiesowner
Chicago,IL 60654
Issue for Zoning Review
1 2 3 4 5 6 7
A
A.1
B
C
D
B.1
21'-15/8" 62'-6" 16'-8"
100'-35/8"
16'-8
"9'
-0"
5'-0
"4'
-0"
13'-4
"
48'-0
"
PRO
PERT
Y LI
NE
PRO
PERT
Y LI
NE
PROPERTY LINE
PROPERTY LINE
PenthouseDuplex
Lower RoofDeck
PenthouseDuplex
Upper RoofDeck
ElevatorOvertravel
New Addition Flush withFace of Existing BuildingRear Setback at Lot Line18
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
New NanaWall FoldingGlass Wall System inExisting Masonry Openingthis Bay. Inspect ExistingLintel and Sill and Repairas Req'd. ProvideGuardrail at 3'-6" HighAbove Finish Floor.
Existing Windows to beReplaced w/ New Low-EInsulated AluminumWindow System in ExistingMasonry Openings.Inspect Existing Lintels andSills and Repair as Req'd.
Gas Grill withExhaust Hood
Sliding Glass Doors withSidelights and Transoms
PRO
PERT
Y LI
NE
PRO
PERT
Y LI
NE
PROPERTY LINE
PROPERTY LINE
1A501
1A501
2A401
1A401
DW RG
F
Existing Chimney to beRemoved. New CompositeConcrete and Steel Infill Slab.Typ. Patch Ceiling with T&Gto Match Adjacent Existing.
New Low-E InsulatedAluminum Window System inExisting Masonry OpeningThis Bay. VIF. Inspect ExistingLintel and Repair as Req'd.
Existing Freight Elevator to beRemoved. New CompositeConcrete and Steel Infill Slab. Typ.Patch Ceiling with T&G to MatchAdjacent Existing.
Existing Masonry Wall. ProvideNew Openings and Lintels asReq'd for New Windows. InfillExisting Openings, Tuckpointand Repair Existing Masonry toMatch Adjacent as Req'd.
KitchenExhaust Riser
New Low-E InsulatedAluminum Window System,Lintel and Cast Stone Sill inNew Masonry Opening.
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
152316
orientation
project number
scale
date
sheet title
sheet number
date description07.22.15
1/8" = 1'-0"
7th Floor Duplex Addition Upper Level Plan
7/22/15
A206
415 W. Huron St.
Speedwagon Propertiesowner
Chicago,IL 60654
Issue for Zoning Review
1 2 3 4 5 6 7
A
A.1
B
C
D
B.1
DN
6 7 8 9
10 114 53
123456789
10 11 12 13 14 15 16 17 18
16'-8
"9'
-0"
5'-0
"4'
-0"
13'-4
"
48'-0
"
21'-15/8" 62'-6" 16'-8"
100'-35/8"
Roof DeckBelow
PenthouseRoof Deck
PRO
PERT
Y LI
NE
PRO
PERT
Y LI
NE
PROPERTY LINE
PROPERTY LINE
1A501
1A501
2A401
1A401
DW F
Plumbing and Electrical forHot Tub Upgrade Option
Gas Service for Built inGrill Upgrade Option
Provide Alternate Pricing forFloor to Ceiling RetractableNana Wall Window System
Skylight Above Staircase
NewElevator
Penthouse DuplexUpper Level
NewNorthStair
RecreationRoom
Bath3
Bedroom 3Suite
Shower /Changing
RoomCatering /Wet Bar
Multi-PurposeMedia /FitnessRoom
Bath4
GuestBedroom
Suite / Office
WIC
WIC
Closet
PowderRoom
WICMech.
Gas Service for Built inFire Pit Upgrade Option
New Tempered GlassRailing System Min. 42"Above Terrace Deck.
Monumental ArchitecturalStaircase w/ GlassHandrails Open to Below
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
152316
orientation
project number
scale
date
sheet title
sheet number
date description07.22.15
1/8" = 1'-0"
Elevations
7/22/15
A401
415 W. Huron St.
Speedwagon Propertiesowner
Chicago,IL 60654
Issue for Zoning Review
A A.1 B B.1 C D
1st Floor+4'-4"
2nd Floor+17'-4"
3rd Floor+30'-4"
4th Floor+43'-4"
5th Floor+56'-4"
Penthouse Duplex Lower Level+74'-6"
Penthouse Duplex Upper Level+86'-6"
Penthouse Roof+98'-6"
13'-4" 4'-0" 5'-0" 9'-0" 16'-8"
Existing Masonry Wall.Inspect Existing Masonry andProvide Allowance forTuckpointing and Repairs.
Existing Windows to beReplaced w/ New Low-EInsulated AluminumWindow System in ExistingMasonry Openings.Inspect Existing Lintels andSills and Repair as Req'd.
Existing Fire Escape andDoors to be Removed. Protect,Patch and Repair ExistingMasonry. Infill Door Openingwith Matching Masonry to Sillof New Window.
Existing Chimney tobe Removed
Existing Freight Elevatorto be Removed
New Openings and Lintelsin Existing Masonry Wall.
New Openings and Lintelsin Existing Masonry Wall.
New Openings and Lintelsin Existing Masonry Wall.
Existing Freight Elevatorand Loading Dock Doorsand Concrete Stoops to beRemoved.
New Low-E InsulatedAluminum WindowSystem, Lintels, and CastStone Sills in NewMasonry Openings.
New Insulated OverheadDoors in New MasonryOpenings. Provide NewLintels as Req'd.
Alley+0'-0"
Provide New Guardrail at 3'-6"Min. Above Finish Deck Level.
Existing Masonry Parapet.Verify Height in Field. Patchand Repair As Required.
New Face Brick Clad 2-StoryPenthouse Addition Underside of Penthouse Duplex
Upper Level Ceiling
D C B.1 B A.1 A
Existing Masonry Wall.Inspect Existing Masonry andProvide Allowance forTuckpointing and Repairs.
Existing Windows to beReplaced w/ New Low-EInsulated AluminumWindow System in ExistingMasonry Openings.Inspect Existing Lintels andSills and Repair as Req'd.
Existing Masonry Parapet.Verify Height in Field. ProvideNew Guardrail at 3'-6" Min.Above Finish Deck Level.
New NanaWall FoldingGlass Wall System inExisting Masonry Opening.Inspect Existing Lintel andSill and Repair as Req'd.Provide Guardrail at 3'-6"High Above Finish Floor.
Existing Door, Sidelights,and Transom to be Replacedwith New Low-E InsulatedAluminum System in ExistingMasonry Opening
Existing Windows to beReplaced w/ New Low-EInsulated AluminumWindow System in ExistingMasonry Openings.Inspect Existing Lintels andSills and Repair as Req'd.
Sidewalk+0'-0"
New Face Brick Clad 2-StoryPenthouse Addition Set BackFrom Existing Facade
1st Floor+4'-4"
2nd Floor+17'-4"
3rd Floor+30'-4"
4th Floor+43'-4"
5th Floor+56'-4"
Penthouse Duplex Lower Level+74'-6"
Penthouse Duplex Upper Level+86'-6"
Penthouse Roof+98'-6"
Existing Windows to beReplaced w/ New Low-EInsulated AluminumWindow System in ExistingMasonry Openings.Inspect Existing Lintels andSills and Repair as Req'd.
Existing Fire Escape andDoors to be Removed. Protect,Patch and Repair ExistingMasonry. Infill Door Openingwith Matching Masonry to Sillof New Window.
Existing Chimney tobe Removed
New Openings and Lintelsin Existing Masonry Wall.
Underside of Penthouse DuplexUpper Level Ceiling
0 4' 8' 12'SCALE: 3/16" = 1'-0"2 South Elevation at Alley0 4' 8' 12'SCALE: 3/16" = 1'-0"1 North Elevation at Street
640 n lasalle street 312 337 3344 architecturesuite 400 312 337 8009 f urban planningchicago il 60654 interiors
pappageorgehaymes partners, ltd. expressly reservesits common law copyright and other property rightsin these plans. These plans are not to be reproduced,changed or copied in any form or manner whatsoever,nor are they to be assigned to any third party, withoutfirst obtaining the expressed written permissionand consent of pappageorgehaymes partners ltd.
These drawings may have been reproduced at a sizedifferent than originally drawn. Owner and Architectassume no responsibility for use of incorrect scale.Contractor shall verify all existing conditions prior toproceeding with construction and notify architectimmediately of any discrepancies or conflicts.
152316
orientation
project number
scale
date
sheet title
sheet number
date description07.22.15
1/8" = 1'-0"
Building Section
7/22/15
A501
415 W. Huron St.
Speedwagon Propertiesowner
Chicago,IL 60654
Issue for Zoning Review
1 2 3 4 5 6 7
10'-0" 25'-5" 10'-0"
21'-15/8" 62'-6" 16'-8"100'-35/8"
Existing Slab to beRemoved
New Reinforced ConcreteRamp over CompactedGranular Fill
New 3HR Rated CeilingAssembly
PenthouseRoof Deck
Unit 4
Unit 3
Unit 2
Unit 1 DuplexUpper Level
W. Huron St.18' Public Alley
Existing 5 StoryBuilding (East)
Existing 3 StoryBuilding (West)
Existing Freight Elevator tobe Removed
AlleyEL: +0'-0"
Existing Basement SlabEL: -6'-10"
New Concrete ToppingEL: -5'-10"
8% BlendSlope
16% Slope
8% BlendSlope
New 3HR Rated WallAssembly
New PenthouseAddition Unit 5Duplex Lower
Level
Unit 1 DuplexLower Level
New Transfer Beams andColumns (Beyond)
New 3HR RatedCeiling Assembly
BasementParking
SidewalkEL: +0'-0"
Existing 1st FloorEL: +4'-4"
New Low-E InsulatedAluminum Window Systemand Lintels in ExistingMasonry Wall
Existing Masonry Wall.Provide New Openings andLintels as Req'd for NewWindows. Infill ExistingOpenings, Tuckpoint andRepair Existing Masonry toMatch Adjacent as Req'd.
New Acoustical Flooring System.2" Keene Quiet Qurl GypsumTopping System 65/075 N MT w/Hardwood Finish Flooring over3/4" Plywood Sheathing and CorkSubfloor Underlayment
Provide New TPO Roof OverMfr. Recommended Cover Bd.Confirm Condition of ExistingSheathing and Insulation.Confirm Positive Pitch toDrain @ Min. 1/4" / Ft. Slope.Verify Coping Condition andHeights Throughout.
New 2'x2' Precast ConcretePedestal Paving System.
Existing Windows to beReplaced w/ New Low-EInsulated AluminumWindow System in ExistingMasonry Openings.Inspect Existing Lintels andSills and Repair as Req'd.
Existing 2nd FloorEL: +17'-4"
Existing 3rd FloorEL: +30'-4"
Existing 4th FloorEL: +43'-4"
Existing 5th FloorEL: +56'-4"
Existing Roof H.P.EL: +73'-0" VIF
Existing Foundations toRemain, VIF
Existing Tongue andGroove Decking. Patchand Repair to MatchAdjacent. SandblastFinish, Typ.