8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
1/44
Measuring Water Supplies for
Michael J. Klemenz, PEFire Protection Engineer
. .
November 2010
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
2/44
Fluid Hydraulics Formulas (10 min) Fire Code of NYS 10 min
NFPA 291- Overview Flow Test Basics (10
min)
Planning a Flow Test (10 min)
Performin a Flow Test 10 min
Calculating Flow Rates (5 min)
&A 5 min
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
3/44
A brief review of Freeman, Bernoulli and
Hazen-Williams is in order to prove thevalidity of common flow-measuring
formulas
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
4/44
For steady state, incompressible, frictionless
flow along a single streamline;
dp/ + gz + V2/2 = constantor
[p1/ + gz1 + V12/2]-[p2/ + gz2 + V22/2]=0
p1/ + gz1 + V12/2 = p2/ + gz2 + V22/2
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
5/44
Determination of the head loss term is not covered
here. However, most fluid mechanics texts containthe derivation of this term using Reynolds Number,
, .
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
6/44
For the flowing head loss across a standard
underwriters playpipe using the measuredflow velocity;
hf = (1-Cv-1)(V2/2g)
where:
hf = head loss across nozzle in ft.Cv= velocity coefficient (dimensionless)
V = Flow velocity in ft/s
g = gravitational acceleration in ft/s2
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
7/44
With Q=AV, apply the Bernoulli Equation,
transpose units [cf/s to gpm], velocity [ft/s toft/min] and combine terms, simplify for
approximation purposes, etc. Freeman
Formula becomes
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
8/44
Q=29.84cd2p
where:
c = coefficient of discharge *
d= diameter of the outlet in inchesp = pitot pressure (velocity pressure) in psi
*Include large orifice coefficient (0.84) if d 4
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
9/44
-
P=4.52 1.85/C1.85d4.87 x L
where:
P= pressure loss from friction in psi= fluid flow rate in m
C= roughness coefficient
d= internal i e diameter in inches
L = pipe length in feet
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
10/44
-
NFPA 13 Table 14.4.4.5
Pipe or Tube C ValueUnlined cast or ductile iron 100
Black steel (dry systems) 100
Black steel (wet systems) 120Galvanized steel 120
Plastic 150
cas or uc e ronCopper tube or stainless steel 150
Concrete 140
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
11/44
-
Since pipe diameter, length and roughness
remain constant regardless of flow rate,
P=K Q1.85
If K is constant, then
P= Q1.85
Use Q1.85 logarithmic graph paper to plot P
vs. Q
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
12/44
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
13/44
Section 508 states requirements for hydrantsand water su lies
Code enforcement official shall be notified
rior to water flow test. Tests shall bewitnessed by the CEO or approved
documentation shall be rovided 508.4
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
14/44
Recommended Practice forFire Flow Testing and Marking of Hydrants
2007 Edition
Provides uidance for waterflow testin usin
pitot tubes and gauges
.This is up to the designer
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
15/44
3.3.2 Residual Pressure. The pressure that exists inthe distribution system, measured at the residual
hydrant at the time the flow readings are taken at
the flow hydrants. 3.3.3 Static Pressure. The pressure that exists at a
given point under normal distribution system
no hydrants flowing.
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
16/44
Flow Test Basics
When is a flow testrequired...? Whenever
NFPA 14 requiresflow test < 9 months
you are designing a
water-based fire
before installation
Tests must besuppress on sys em,
thats whenconducted during
periods of peak water
.recent and accurate Use test equipment in
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
17/44
Flow Test Basics
Flow tests indicate therelative strength of awater su l
Dont assume watersupplier knows proper
Flow tests determine if Protect yourself and your
pump systems are neededto achieve system design
client conduct your own
water flow test
Flow testing can help
Specify that fire protectioncontractor perform a flow
closed underground valves& flow obstructions
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
18/44
Flow Test Basics
Many water systemsexperience normal
Minimum residualpressure = 20 psi
time of day and season Plan for water disposal.
Prevent erosion or damage Flow test measures only
one point during the
dail /seasonal c cle
Avoid or plan for freezing
conditions
Get water supplier to
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
19/44
1. Notify/request water supplier
2. If possible, obtain water utility maps of the water line to be
tested
.protected
4. Select a flow hydrant preferably downstream of the
5. Note any significant elevation differences betweengauge hydrant and building (1 ft. = 0.433 psi)
6. Plan for safe disposal of water
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
20/44
Hydrant Wrench
Ca Assembl Liquid-filled GaugeScale/Ruler/Tape
Pitot Tube & Gauge
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
21/44
1. Record date, time and location of test
2. Remove cap from gauge hydrant. Tighten the * .
3. Install cap gauge.
.
5. Open air release valve to vent air from hydrant. Whenwater emerges, close the air release valve
6. Observe and record the static water pressure indicated onthe gauge
* - .psi static pressure
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
22/44
7. Remove cap from flow hydrant. Tighten the
remaining caps so they dont blow off.
8. Measure the actual internal diameter of hydrantoutlet(s) to be flowed
. ee n er or o ou e o es ma e y ran coe c en(see Figure)
10. O en h drant full and wait for clear water
11. Insert blade of pitot tube into center of stream about the outlet diameter away from the discharging
ou e see gure12. Observe and record the average pitot pressure on the
au e
13. Observe and record the residual pressure at thegauge hydrant
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
23/44
Hydrant Coefficients
Vertical Section Through Hydrant Barrel
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
24/44
14. Flow rate must be sufficient to reduce the residual
pressure to 75% of static pressure
15. Open additional outlets as needed to increase flowrate necessary to achieve pressure reduction
. pp y y ran coe c en o ow ra e ca cu a onresult
17. When usin lar e steamer outlets d 4 a ladditional 0.84 large orifice coefficient
18. Need minimum pitot pressure of 10 psi. If not, use
app ance o sma er ame er .e., p ay p pe,nozzle, etc.)
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
25/44
Gauge Hydrant Flow Hydrant
Static Pressure, P si Outlet Diameter, D (inches)
Residual Pressure, PR(psi)Coefficient, C
Pitot (velocity) Pressure, PV (psi)
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
26/44
Correct pitot position
D
D/2
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
27/44
19. When all readings have been recorded, slowly close
ow y ran o preven wa er ammer one urn
every four seconds). Verify that the hydrant barreldrains
20. Reinstall hydrant cap
. ose gauge y rant an remove cap gauge
22. Verify that the hydrant barrel drains
23. Reinstall hydrant cap
.
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
28/44
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
29/44
Diffuser equipment allows better control of water
No need to feel for hydrant coefficient or measurethe hydrant outlet diameter
Use lengths of 2-1/2 fire hose to get diffuser to catchbasin, ditch or other convenient water termination
Diffuser does not whip around during flow testbecause equal flow forces oppose and cancel
Length of fire hose between hydrant and diffuser doesnot affect overall flow test results
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
30/44
2-1/2 Fire HosePressure Gauge
1-1/8 Insert
Pitot Tube
Hose Monster Appliance
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
31/44
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
32/44
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
33/44
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
34/44
Q=29.84cd2p
where:
c = coefficient of discharge *
d= diameter of the outlet in inchesp = pitot pressure (velocity pressure) in psi
*Include large orifice coefficient (0.84) if d 4
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
35/44
Q2=Q1 x (PS-20)
0.54
(PS-PR)0.54
where:
Q1= measured water flow in gpm
Ps = measured static pressure in psiPR = measured residual pressure in psi
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
36/44
Or use values frompublished tables
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
37/44
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
38/44
D=2-7/16105 psi
18 psi
70 ps
Gauge Hydrant Flow Hydrant
Static Pressure = 105 si Outlet Diameter = 2-7/16 inches
Residual Pressure = 70 psi Coefficient = 0.9 (rounded edge)
Pitot (velocity) Pressure = 18 psi
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
39/44
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
40/44
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
41/44
Other Suggestions
When testing watersupplies served by a If test results are notas expected, look for
fire pump, shut off
jockey pumps and
closed valves, partially
closed valves,
manua y s ar e re
pump so it is running
un ergroun
obstructions, etc.
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
42/44
References
1. Introduction to Fluid
Mechanics 3rd Edition (Fox &
McDonald)
2. Hydraulics for Fire Protection
(Hickey)
3. NFPA 291-2007 Edition(National Fire Protection
Association)
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
43/44
the Old Days
8/4/2019 4.1 Fire Protection Measuring Water Supplies for Fire Protection Systems - Michael Klemenz, UFPE
44/44
Measuring Water Supplies for
Michael J. Klemenz, PEFire Protection Engineer
. .
November 2010