Home Technical Articles Article Categories Contact us Subscribe to articles Subscribe to downloads El. Enginering Guides EE General guides Power Substations Schneider Electric CTs Siemens Basics of EE ABB Drives Guides Industry Automation Relay control/protection Alternative Energy Electrical Software MS Excel Spreadsheets Electrical Design Docs Engineering Resources Video Lectures – Electrical Engineering PLC Programming Training Electric Testing and Maintenance (VIDEO) Network Theorems and Laws - 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 614392 4 Low Voltage Switchboard Partitioning Levels Defined By IEC 61439-2 (photo credit: rgm.cr.it) Reasons for partitioning // There are 4 main reasons for partitioning a switchboard. 1. To protect persons against direct contact with dangerous parts. The minimum degree of protection must be IPXXB. 2. To protect the switchboard against the penetration of solid foreign bodies. The minimum degree of protection must be IP2X. 3. To limit the propagation of an electric arc inside the switchboard by separating the busbars, equipment and connections, 4. To facilitate maintenance operations or switchboard upgrades. Partitioning rules are defined in standard IEC 61439-2. The definition of partitioning depends on
11

4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

Dec 23, 2015

Download

Documents

riddler_007

LV
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 1/11

Home Technical Articles Article Categories Contact us Subscribe to articles Subscribe to downloads El.Enginering Guides

EE General guidesPower SubstationsSchneider Electric CTsSiemens Basics of EEABB Drives GuidesIndustry AutomationRelay control/protectionAlternative Energy

Electrical Software MS Excel Spreadsheets Electrical Design Docs Engineering Resources

Video Lectures – Electrical EngineeringPLC Programming TrainingElectric Testing and Maintenance (VIDEO)Network Theorems and Laws-

4 Low Voltage Switchboard PartitioningForms Defined By IEC 61439­24 Low Voltage Switchboard Partitioning Levels Defined By IEC 61439-2 (photo credit:rgm.cr.it)

Reasons for partitioning //

There are 4 main reasons for partitioning a switchboard.

1. To protect persons against direct contact with dangerous parts.The minimum degree of protection must be IPXXB.

2. To protect the switchboard against the penetration of solid foreign bodies.The minimum degree of protection must  be IP2X.

3. To limit the propagation of an electric arc  inside the switchboard by separating the busbars,equipment and connections,

4. To facilitate maintenance operations or switchboard upgrades.

Partitioning rules are defined in standard IEC 61439-2. The definition of partitioning depends on

Page 2: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 2/11

conditions of use, maintenance and upgrade of the switchboard. This definition is subject toagreement between the switchboard manufacturer  and the end user.

It is based on three essential points:

1. Use products or components that comply with the standard, the various configurations of whichhave been tried and tested,

2. Comply with rules and guidelines laid down by the various manufacturer documents especiallypertaining  to choice and protection,

3. Conduct clearance, bonding continuity with a final inspection recorded in a contract document.

Full compliance with these  recommendations can be validated by a compliance certificate.

The standard defines 4 partitioning levels  (forms) to ensure the protection of persons against directcontact. The form is a solution provided to an IP protection requirement and a client need (Operation,Maintenance, Upgrade).

Separation Form 1Separation Form 2 (2a, 2b)Separation Form 3 (3a, 3b)Separation Form 4 (4a, 4b)

Page 3: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 3/11

Separation Form 1 //

No separation inside the switchboard.

Form 1 partitioning of switchboard

Protection of people and equipment is provided  from the onset by:

The presence of front plates that can only be opened by a specific tool,The locking of doors that give access to live parts,The systematic installation of terminal covers on the Compact NSX circuit-breakers, as well as onthe Interpact INS and INV switches (NSX, INS and INV are Schneider Electric’s devices)The covering of the upstream and downstream pads of  the incoming device, to ensure theoperator’s safety at  all points of the switchboard when the device is open.

Page 4: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 4/11

Go back to Index ↑

Separation Form 2 //

Separation of busbars and functional units inside the switchboard:

Protection of persons against contact with live parts upstream of outgoing devices,Protection against ingress of solid  foreign bodies.

Form 2 partitioning of switchboard

Page 5: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 5/11

There are two variants of form 2: Form 2b provides more safety than form 2a, since  the connectionterminals are separated  from the busbars.

Form 2a

Terminals for external conductors are not separated from the busbars.

Form 2a

Form 2b

Terminals for external conductors are separated from the busbars.

Page 6: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 6/11

Form 2b

Go back to Index ↑

Separation Form 3 //

Form 2 + Separation inside the switchboard of all functional units:

Protection of persons against contact with live parts upstream of outgoing devices,Limitation of the risk of faults between each of the functional units (propagation of electric arcs).

Form 3 partitioning of switchboard

There are two variants of form 3: Form 3b provides more safety than form 3a, since  the connectionterminals are separated  from the busbars.

Form 3a

Terminals for external conductors  are not separated from the busbars.

Form 3a

Page 7: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 7/11

Form 3b

Terminals for external conductors areseparated from the busbars.

Form 3b

Page 8: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 8/11

Go back to Index ↑

Separation form 4 //

Form 3 + Separation inside the switchboard of terminals for externalconductors that are an integral part of each functional unit:

Protection of persons against contact with live parts upstream of outgoingdevices,Limitation of the risk of faults between each of the functional units(propagation of electric arcs).

Form 4 partitioning of switchboard

There are two variants of form 4: To fit the cubicle with gland plates to create form 4a or to coverthe connection pad of outgoing devices to create a form 4b.

Form 4a

Terminals for external conductors are in the same cubicle as the functional unit with which they areassociated.

Form 4a

Form 4b

Terminals for external conductors are not in the same cubicle as the functional unit with which theyare associated, but in protected spaces or individual compartments that are separated and closed.

Form 4b

Go back to Index ↑

Page 9: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 9/11

Good Practice Tips //

Partitioning may be obtained byinsulating the live parts:

Using separators, metal barriers, frontplates, covers or terminal shields,By using devices with molded cases.

The entire switchboard must have adegree of protection of IP2X inaccordance with IEC 61439-1 and 2.If using metal barriers, make sure thatclearances are complied with.

Putting partitions in a switchboardreduces heat dissipation of theswitchboard. It is therefore importantto take this  into account when definingthe heat management solution for theswitchboard. For example form 4switchboard dissipates less heat than aform 1 un-partitioned switchboard.

Barriers must be robust enough toensure that a possible mechanicalstress on these components (reductionin clearance distance, or evenaccidental contact with live parts) does

not cause an accident.

Form 2 configuration– the busbars areseparated from thedevices

If a busbar is installed at the bottom of the switchboard, you must use aform 2 to protect it from the possible drop of a metal object. Rememberto stick a warning label (“do not walk” and “electrical hazard”symbol) on the top of the form.

Warninglabel (“do

Page 10: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 10/11

not walk”and“electricalhazard”symbol)

Reference // How to assemble an electrical switchboard – Technical guide bySchneider Electric (Download guide)

Recommended EE articles //

Share with engineers //

About Author //

Edvard Csanyi

Edvard - Electrical engineer, programmer andfounder of EEP. Highly specialized for design ofLV high power busbar trunking (<6300A) inpower substations, buildings and industryfascilities. Designing of LV/MV switchgears.Professional in AutoCAD programming and web-design. Present on Google+

© 2015 EEP - Electrical Engineering Portal. AllRights Reserved | Privacy Policy | 32 queries in0.200 seconds.Powered by CsanyiGroup

SHARE

TOPGet

PDF

Page 11: 4 Low Voltage Switchboard Partitioning Forms Defined by IEC 61439-2 _ EEP

26/03/2015 4 Low Voltage Switchboard Partitioning Forms Defined By IEC 61439­2 | EEP

http://electrical­engineering­portal.com/4­low­voltage­switchboard­partitioning­forms­defined­by­iec­61439­2 11/11