SENTRON Back-up protection 10/2017 Edition 3VA Molded Case Circuit Breakers siemens.com/3VA
12

3VA Molded Case Circuit Breakers - Siemens

Feb 24, 2023

Download

Documents

Khang Minh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 3VA Molded Case Circuit Breakers - Siemens

SENTRON

Back-up protection

10/2017Edition

3VA Molded Case Circuit Breakers

siemens.com/3VA

Margin Margin

Bufferzone

blue dark 100 % Stone gray 100%

Siemens Sans, Roman, 36/30/26 pt, whiteAbsatzformat: 01 System

Siemens Sans, Roman, 13/12/11 pt, whiteAbsatzformat: 03 Titel

Siemens Sans, Bold, 11/12/13 pt, whiteAbsatzformat: 04 Dokuklasse

Wird mehr Text verwendetVerlaufsfeld nach oben erweitern. Abstände vonRand zu Text einhalten!

Siemens Sans, Bold, 9 pt, blackAbsatzformat: 06 URL

2 x

Siemens Sans, Bold18/16/14 pt, whiteAbsatzformat: 02 Produkt

Siemens Sans, Bold11/9/7,5 pt, whiteAbsatzformat: 05 Ausgabe

1/10x

1/10x

1/10x

1/14x

1/10x

1/5x

1/5x

1/28x

1/20x

1/20x

1/5x

1/28x

1/20x

1/20x

1/20x

1 x

wenn möglich in gleicher Schriftgruppe bleiben!

groß361813139

11

mittel3016121299

klein261411119

7,5

SystemProduktgruppeTitel DokuklasseURL Ausgabe

Titelseite OHNE Beschnitt in RGBAlle Schriften sind als Absatzformat hinterlegt!!!

Page 2: 3VA Molded Case Circuit Breakers - Siemens

Table of contents3VA Back-up protection tables

1 3VA Molded Case Circuit Breakers - Miniature Circuit Breaker→ 1.1 3VA1 - 5SY→ 1.2 3VA2 - 5SY→ 1.3 3VA1 - 5SL→ 1.4 3VA2 - 5SL→ 1.5 3VA1 - 5SU1→ 1.6 3VA2 - 5SU1→ 1.7 3VA1 - 5SJ4…-.HG..

2 Molded Case Circuit Breakers 3VA - 3VA→ 2.1 3VA1 - 3VA1(1-pole)

Back-up-Schutztabellen_en_06102017.xlsx Introduction Druckdatum: 06.10.2017

Page 3: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

Size

Icu [kA]

Cha

ract

eris

tic

I cn[k

A]

I cu[k

A]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

2 30 30 30 30 30 30 30 30 30 60 60 60 60 40 40 40 40 40 40 40 35 35 354 30 30 30 30 30 30 30 30 30 60 60 60 60 40 40 40 40 40 40 40 35 35 356 30 30 30 30 30 30 30 30 30 60 60 60 60 40 40 40 40 40 40 40 35 35 35

10 25 25 25 25 25 25 25 25 25 60 60 60 60 40 40 40 40 40 25 25 25 25 2513 25 25 25 25 25 25 25 25 60 60 60 40 40 40 40 40 25 25 25 25 2516 25 25 25 25 25 25 25 60 60 40 40 40 40 40 25 25 25 25 2520 25 25 25 25 25 25 60 40 40 40 40 40 25 25 25 25 2525 25 25 25 25 25 40 40 40 40 40 25 25 25 25 2532 25 25 25 25 40 40 40 40 25 25 25 25 2540 20 20 20 25 25 25 25 25 25 25 2550 15 15 25 25 25 25 20 20 2063 15 20 20 20 20 20 202 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 654 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 656 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 65

10 30 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 65 6513 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 6516 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 6520 30 30 30 30 30 30 65 65 65 65 65 65 65 65 50 50 5025 30 30 30 30 30 65 65 65 65 65 65 65 50 50 5032 30 30 30 30 65 65 65 65 65 65 50 50 5040 30 30 30 45 45 45 45 45 35 35 3550 25 25 45 45 45 45 30 30 3063 25 30 30 30 30 30 30

40 6 70 70 70 70 70 70 70 70 70 70 70 70 70 70

30 10 35 35 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 70 70 7013 35 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 70 7016 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 7020 35 35 35 35 35 35 70 70 70 70 70 70 70 70 55 55 5525 35 35 35 35 35 70 70 70 70 70 70 70 55 55 5532 35 35 35 35 70 70 70 70 70 70 55 55 2540 35 35 35 50 50 50 50 50 40 40 4050 30 30 50 50 50 50 35 35 3563 30 35 35 35 35 35 350,3 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 450,5 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 45

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 05/2017

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y4

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y7

1535

10B

20

36 (S) /55 (M) / 70 (H)

Upstream molded case circuit breaker 3VA1

Line protection

TM210 / TM220 / TM240

100 A 160 A 250 A

16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H)

15B

2025

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y6(w

ithou

t5SY

60)

B

6

3015

10

Back-up protection not required

0,5 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 451 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 45

1,6 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 452 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 453 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 454 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 455 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 456 30 30 30 30 30 30 30 30 30 60 60 60 60 45 45 45 45 45 45 45 45 45 458 25 25 25 25 25 25 25 25 25 60 60 60 60 40 40 40 40 40 30 30 30 30 30

10 25 25 25 25 25 25 25 25 25 60 60 60 60 40 40 40 40 40 30 30 30 30 3013 25 25 25 25 25 25 25 25 60 60 60 40 40 40 40 40 30 30 30 30 3015 25 25 25 25 25 25 25 60 60 40 40 40 40 40 30 30 30 30 3016 25 25 25 25 25 25 25 60 60 40 40 40 40 40 30 30 30 30 3020 25 25 25 25 25 25 60 40 40 40 40 40 30 30 30 30 3025 25 25 25 25 25 40 40 40 40 40 30 30 30 30 3030 25 25 25 25 40 40 40 40 30 30 30 30 3032 25 25 25 25 40 40 40 40 30 30 30 30 3040 20 20 20 25 25 25 25 25 25 25 2550 15 15 25 25 25 25 20 20 2063 15 20 20 20 20 20 20

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y6(w

ithou

t5SY

60)

C 6

3015

10

Back-up-Schutztabellen_en_06102017.xlsx 1.1) 3VA1 - 5SY 2 von 11 Druckdatum: 06.10.2017

Page 4: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

Size

Icu [kA]

Cha

ract

eris

tic

I cn[k

A]

I cu[k

A]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 05/2017

36 (S) /55 (M) / 70 (H)

Upstream molded case circuit breaker 3VA1

Line protection

TM210 / TM220 / TM240

100 A 160 A 250 A

16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H)

0,3 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 650,5 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 651 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 65

1,6 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 652 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 65

2,5 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 653 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 65

3,5 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 654 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 655 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 656 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 658 30 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 65 65

10 30 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 65 6513 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 6515 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 6516 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 6520 30 30 30 30 30 30 65 65 65 65 65 65 65 65 50 50 5025 30 30 30 30 30 65 65 65 65 65 65 65 50 50 5030 30 30 30 30 30 65 65 65 65 65 65 65 50 50 5032 30 30 30 30 65 65 65 65 65 65 50 50 5035 30 30 30 45 45 45 45 45 35 35 3540 30 30 30 45 45 45 45 45 35 35 3545 30 30 45 45 45 45 30 30 3050 25 25 45 45 45 45 30 30 3060 25 25 30 30 30 30 30 3063 25 30 30 30 30 30 300,3 70 70 70 70 70 70 70 70 70 70 70 70 70 700,5 70 70 70 70 70 70 70 70 70 70 70 70 70 701 70 70 70 70 70 70 70 70 70 70 70 70 70 70

1,6 70 70 70 70 70 70 70 70 70 70 70 70 70 702 70 70 70 70 70 70 70 70 70 70 70 70 70 703 70 70 70 70 70 70 70 70 70 70 70 70 70 704 70 70 70 70 70 70 70 70 70 70 70 70 70 706 70 70 70 70 70 70 70 70 70 70 70 70 70 708 35 35 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 70 70 70

10 35 35 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 70 70 70

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y7 30C 15

5040

C

2015

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y4 10

35

Back-up protection not required

10 35 35 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 70 70 7013 35 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 70 7016 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 7020 35 35 35 35 35 35 70 70 70 70 70 70 70 70 55 55 5525 35 35 35 35 35 70 70 70 70 70 70 70 55 55 5532 35 35 35 35 70 70 70 70 70 70 55 55 5540 35 35 35 50 50 50 50 50 40 40 4050 30 30 50 50 50 50 35 35 3563 30 35 35 35 35 35 350,30,51

1,623 70 70 70 70 70 70 70 70 70 70 70 70 70 704 70 70 70 70 70 70 70 70 70 70 70 70 70 706 70 70 70 70 70 70 70 70 70 70 70 70 70 708 70 70 70 70 70 70 70 70 70 70 70 70 70 70

10 70 70 70 70 70 70 70 70 70 70 70 70 70 7013 35 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 70 7016 35 35 35 35 35 35 35 70 70 70 70 70 70 70 70 70 70 70 7020 35 35 35 35 35 35 70 70 70 70 70 70 70 70 55 55 5525 35 35 35 35 35 70 70 70 70 70 70 70 55 55 5532 35 35 35 35 70 70 70 70 70 70 55 55 5540 35 35 35 50 50 50 50 50 40 40 4050 35 35 50 50 50 50 35 35 3563 35 35 35 35 35 35 35

Note: Miniature circuit breaker without suffix; e.g. CC, RC, YA, MBIndependent of any Back-up value in this table, the maximum available current of the circuit where the upstream breaker is used may not exeed it's short circuit rating (Icu)

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y7

2520

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y8 C -

7050

4030

25

Back-up protection not required

Back-up protection not required Back-up protection notrequired

Back-up-Schutztabellen_en_06102017.xlsx 1.1) 3VA1 - 5SY 3 von 11 Druckdatum: 06.10.2017

Page 5: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

SizeIcu [kA]

Cha

ract

eris

tic

I cn[k

A]

I cu[k

A]In [A] 25 40 63 100 25 40 63 100 160 160 250

0,3 55 55 55 55 55 55 55 55 55 55 550,5 55 55 55 55 55 55 55 55 55 55 551 55 55 55 55 55 55 55 55 55 55 55

1,6 55 55 55 55 55 55 55 55 55 55 552 55 55 55 55 55 55 55 55 55 55 553 55 55 55 55 55 55 55 55 55 55 554 55 55 55 55 55 55 55 55 55 55 555 55 55 55 55 55 55 55 55 55 55 556 55 55 55 55 55 55 55 55 55 55 558 55 55 55 55 55 55 55 55 55 55 5510 55 55 55 55 55 55 55 55 55 55 5513 55 55 55 55 55 55 55 55 55 55 5515 55 55 55 55 55 55 55 55 55 55 5516 55 55 55 55 55 55 55 55 55 55 5520 55 55 55 55 55 55 55 40 4025 55 55 55 55 55 55 55 40 4030 55 55 55 55 55 55 4032 55 55 55 55 55 55 4040 35 35 35 35 35 25 2550 35 35 35 20 2063 20 20 20 20 200,3 60 60 60 60 60 60 60 60 60 60 600,5 60 60 60 60 60 60 60 60 60 60 601 60 60 60 60 60 60 60 60 60 60 60

1,6 60 60 60 60 60 60 60 60 60 60 602 60 60 60 60 60 60 60 60 60 60 60

2,5 60 60 60 60 60 60 60 60 60 60 603 60 60 60 60 60 60 60 60 60 60 60

3,5 60 60 60 60 60 60 60 60 60 60 604 60 60 60 60 60 60 60 60 60 60 605 60 60 60 60 60 60 60 60 60 60 606 60 60 60 60 60 60 60 60 60 60 608 60 60 60 60 60 60 60 60 60 60 6010 60 60 60 60 60 60 60 60 60 60 6013 60 60 60 60 60 60 60 60 60 60 6015 60 60 60 60 60 60 60 60 60 60 6016 60 60 60 60 60 60 60 60 60 60 6020 60 60 60 60 60 60 60 45 4525 60 60 60 60 60 60 60 45 4530 60 60 60 60 60 60 4532 60 60 60 60 60 60 4535 40 40 40 40 40 30 3040 40 40 40 40 40 30 3045 40 40 40 25 2550 40 40 40 25 2560 25 25 25 25 2563 25 25 25 25 25

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y4

B,C

55 (M) / 85 (H) / 110 (C) / 150 (L)

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 12/2016

Upstream molded case circuit breaker 3VA2

Line protection

ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

100 A 160 A 250 A

3015

10

10

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y6

B,C 6

3520

15

Back-up-Schutztabellen_en_06102017.xlsx 1.2) 3VA2 - 5SY 4 von 11 Druckdatum: 06.10.2017

Page 6: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

SizeIcu [kA]

Cha

ract

eris

tic

I cn[k

A]

I cu[k

A]In [A] 25 40 63 100 25 40 63 100 160 160 250

55 (M) / 85 (H) / 110 (C) / 150 (L)

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 12/2016

Upstream molded case circuit breaker 3VA2

Line protection

ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

100 A 160 A 250 A

0,3 65 65 65 65 65 65 65 65 65 65 650,5 65 65 65 65 65 65 65 65 65 65 651 65 65 65 65 65 65 65 65 65 65 65

1,6 65 65 65 65 65 65 65 65 65 65 652 65 65 65 65 65 65 65 65 65 65 653 65 65 65 65 65 65 65 65 65 65 654 65 65 65 65 65 65 65 65 65 65 656 65 65 65 65 65 65 65 65 65 65 658 65 65 65 65 65 65 65 65 65 65 6510 65 65 65 65 65 65 65 65 65 65 6513 65 65 65 65 65 65 65 65 65 65 6516 65 65 65 65 65 65 65 65 65 65 6520 65 65 65 65 65 65 65 50 5025 65 65 65 65 65 65 65 50 5032 65 65 65 65 65 65 5040 45 45 45 45 45 35 3550 45 45 45 30 3063 30 30 30 30 300,3 65 65 65 65 70 70 70 70 70 70 700,5 65 65 65 65 70 70 70 70 70 70 701 65 65 65 65 70 70 70 70 70 70 70

1,6 65 65 65 65 70 70 70 70 70 70 702 65 65 65 65 70 70 70 70 70 70 703 65 65 65 65 65 65 65 65 65 65 654 65 65 65 65 65 65 65 65 65 65 656 65 65 65 65 65 65 65 65 65 65 658 65 65 65 65 65 65 65 65 65 65 6510 65 65 65 65 65 65 65 65 65 65 6513 65 65 65 65 65 65 65 65 65 65 6516 65 65 65 65 65 65 65 65 6520 65 65 65 65 65 65 65 50 5025 65 65 65 65 65 65 65 50 5032 65 65 65 65 65 65 5040 45 45 45 45 45 35 3550 45 45 45 30 3063 30 30 30 30 30

Note: Miniature circuit breaker without suffix; e.g. CC, RC, YA, MB

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y8

C

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

Y7

B,C 15

Independent of any Back-up value in this table, the maximum available current of the circuit where the upstream breakeris used may not exeed it's short circuit rating (Icu)

-

7050

4030

2550

4030

2520

Back-up-Schutztabellen_en_06102017.xlsx 1.2) 3VA2 - 5SY 5 von 11 Druckdatum: 06.10.2017

Page 7: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

Size

Icu [kA]

Cha

ract

eris

tic

I cn[k

A]

I cu[k

A]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

1 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 252 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 253 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 254 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 256 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 258 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 2510 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 2513 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 1516 25 25 25 25 25 25 25 60 60 60 60 60 60 60 60 60 35 35 3520 25 25 25 25 25 25 50 50 50 50 50 50 50 50 45 45 4525 25 25 25 25 25 50 50 50 50 50 50 50 45 45 4532 25 25 25 50 50 50 50 50 45 45 4540 25 25 25 40 40 40 40 40 30 30 3050 20 20 35 35 35 35 25 25 2563 20 25 25 25 25 25 250,3 30 30 30 30 30 30 30 30 30 60 60 60 60 60 60 60 60 60 60 60 60 60 600,5 30 30 30 30 30 30 30 30 30 60 60 60 60 60 60 60 60 60 60 60 60 60 601 30 30 30 30 30 30 30 30 30 60 60 60 60 60 60 60 60 60 60 60 60 60 60

1,6 30 30 30 30 30 30 30 30 30 60 60 60 60 60 60 60 60 60 60 60 60 60 602 30 30 30 30 30 30 30 30 30 60 60 60 60 60 60 60 60 60 60 60 60 60 603 30 30 30 30 30 30 30 30 30 60 60 60 60 60 60 60 60 60 60 60 60 60 604 30 30 30 30 30 30 30 30 30 60 60 60 60 60 60 60 60 60 60 60 60 60 606 30 30 30 30 30 30 30 30 30 60 60 60 60 60 60 60 60 60 60 60 60 60 608 25 25 25 25 25 25 25 25 25 60 60 60 60 60 60 60 60 60 60 60 60 60 6010 25 25 25 25 25 25 25 25 25 60 60 60 60 60 60 60 60 60 60 60 60 60 6013 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 1516 25 25 25 25 25 25 25 60 60 60 60 60 60 60 60 60 35 35 3520 25 25 25 25 25 25 50 50 50 50 50 50 50 50 45 45 4525 25 25 25 25 25 50 50 50 50 50 50 50 45 45 4532 25 25 25 50 50 50 50 50 45 45 4540 25 25 25 40 40 40 40 40 30 30 3050 20 20 35 35 35 35 25 25 2563 20 25 25 25 25 25 25

Note: Miniature circuit breaker without suffix; e.g. CC, RC, YA, MBIndependent of any Back-up value in this table, the maximum available current of the circuit where the upstream breaker is used may not exeed it's short circuit rating (Icu)

10

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

L4

16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H)36 (S) /

55 (M) / 70 (H)

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 12/2016

10BUpstream molded case circuit breaker 3VA1

Line protection

TM210 / TM220 / TM240

100 A 160 A 250 A

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

L4 C 10 10

Back-up-Schutztabellen_en_06102017.xlsx 1.3) 3VA1 - 5SL 6 von 11 Druckdatum: 06.10.2017

Page 8: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

SizeIcu [kA]

Cha

ract

eris

tic

I cn[k

A]

I cu[k

A]In [A] 25 40 63 100 25 40 63 100 160 160 250

1 20 20 20 20 20 20 20 20 20 20 202 20 20 20 20 20 20 20 20 20 20 203 20 20 20 20 20 20 20 20 20 20 204 20 20 20 20 20 20 20 20 20 20 206 20 20 20 20 20 20 20 20 20 20 208 20 20 20 20 20 20 20 20 20 20 2010 20 20 20 20 20 20 20 20 20 20 2013 10 10 10 10 10 10 10 10 10 10 1016 55 55 55 55 55 55 55 55 55 30 3020 45 45 45 45 45 45 45 40 4025 45 45 45 45 45 45 45 45 4032 45 45 45 45 45 45 4040 35 35 35 35 35 25 2550 30 30 30 20 2063 20 20 20 20 200,3 55 55 55 55 55 55 55 55 55 55 550,5 55 55 55 55 55 55 55 55 55 55 551 55 55 55 55 55 55 55 55 55 55 55

1,6 55 55 55 55 55 55 55 55 55 55 552 55 55 55 55 55 55 55 55 55 55 553 55 55 55 55 55 55 55 55 55 55 554 55 55 55 55 55 55 55 55 55 55 556 55 55 55 55 55 55 55 55 55 55 558 55 55 55 55 55 55 55 55 55 55 5510 55 55 55 55 55 55 55 55 55 55 5513 10 10 10 10 10 10 10 10 10 10 1016 55 55 55 55 55 55 55 55 55 30 3020 45 45 45 45 45 45 45 40 4025 45 45 45 45 45 45 45 45 4032 45 45 45 45 45 45 4040 35 35 35 35 35 25 2550 30 30 30 20 2063 20 20 20 20 20

Note: Miniature circuit breaker without suffix; e.g. CC, RC, YA, MB

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 01/2017

Upstream molded case circuit breaker 3VA2

Line protection

ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

100 A 160 A 250 A55 (M) / 85 (H) / 110 (C) / 150 (L)

Independent of any Back-up value in this table, the maximum available current of the circuit where the upstream breaker isused may not exeed it's short circuit rating (Icu)

1010

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

L4 C 10

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

L4 B 10

Back-up-Schutztabellen_en_06102017.xlsx 1.4) 3VA2 - 5SL 7 von 11 Druckdatum: 06.10.2017

Page 9: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

Size

Icu [kA]

Cha

ract

eris

tic

I cn[k

A]

I cu[k

A]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

35 6 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 658 30 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 65 65

10 30 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 65 6513 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 6516 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 6520 30 30 30 30 30 30 65 65 65 65 65 65 65 65 50 50 5025 30 30 30 30 30 65 65 65 65 65 65 65 50 50 5032 30 30 30 30 45 45 45 45 45 45 35 35 3540 30 30 30 45 45 45 45 45 35 35 35

25 6 25 25 25 25 25 25 25 25 25 30 30 30 30 30 30 30 30 30 30 30 30 30 308 20 20 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 25 25 25

10 20 20 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 25 25 2513 20 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 25 2516 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 2520 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 2525 20 20 20 20 20 25 25 25 25 25 25 25 25 25 2532 20 20 20 20 25 25 25 25 25 25 25 25 25

10 40 15 15 15 20 20 20 20 20 20 20 20

Note: Independent of any Back-up value in this table, the maximum available current of the circuit where the upstream breaker is used may not exeed it's short circuit rating (Icu)

Dow

nstre

amFI

/LS-

brea

ker

5SU

1..3

/5SU

1..6

B,C

4,5

/6

15

36 (S) /55 (M) / 70 (H)

Dow

nstre

amFI

/LS-

brea

ker

5SU

1..4

B,C 10

2015

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 05/2017

Upstream molded case circuit breaker 3VA1

Line protection

TM210 / TM220 / TM240

100 A 160 A 250 A

16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H)

Back-up-Schutztabellen_en_06102017.xlsx 1.5) 3VA1 - 5SU1 8 von 11 Druckdatum: 06.10.2017

Page 10: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

SizeIcu [kA]

Cha

ract

eris

tic

I cn[k

A]

I cu[k

A]In [A] 25 40 63 100 25 40 63 100 160 160 250

35 6 60 60 60 60 60 60 60 60 60 60 608 60 60 60 60 60 60 60 60 60 60 6010 60 60 60 60 60 60 60 60 60 60 6013 60 60 60 60 60 60 60 60 60 60 6016 60 60 60 60 60 60 60 60 60 60 6020 60 60 60 60 60 60 60 45 4525 60 60 60 60 60 60 60 45 4532 60 60 60 60 60 60 4540 40 40 40 40 40 30 30

25 6 55 55 55 55 55 55 55 55 55 55 558 55 55 55 55 55 55 55 55 55 55 5510 55 55 55 55 55 55 55 55 55 55 5513 55 55 55 55 55 55 55 55 55 55 5516 55 55 55 55 55 55 55 55 55 55 5520 55 55 55 55 55 55 55 40 4025 55 55 55 55 55 55 55 40 4032 55 55 55 55 55 55 40

10 40 35 35 35 35 35 25 25

Note

Nac

hgeo

rdne

ter

FI/L

S-Sc

halte

r5S

U1.

.3/5

SU1.

.6

B,C

4,5

/6

15

Independent of any Back-up value in this table, the maximum available current of the circuit where the upstreambreaker is used may not exeed it's short circuit rating (Icu)

Nac

hgeo

rdne

ter

FI/L

S-Sc

halte

r5S

U1.

.4

B,C 10

2015

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 05/2017

Upstream molded case circuit breaker 3VA2

Line prootection

ETU320 / ETU330 / ETU340 / ETU350 / ETU550 / ETU560 / ETU850 / ETU860

100 A 160 A 250 A55 (M) / 85 (H) / 110 (C) / 150 (L)

Back-up-Schutztabellen_en_06102017.xlsx 1.6) 3VA2 - 5SU1 9 von 11 Druckdatum: 06.10.2017

Page 11: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

Size

Icu [kA]

Cha

ract

eris

tic

I cu[k

A]

In [A] 16 20 25 32 40 50 63 80 100 16 20 25 32 40 50 63 80 100 125 160 160 200 250

6 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 6510 30 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 65 6513 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 6515 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 6516 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 6520 30 30 30 30 30 30 65 65 65 65 65 65 65 65 50 50 5025 30 30 30 30 30 65 65 65 65 65 65 65 50 50 5030 30 30 30 30 65 65 65 65 65 65 50 50 5032 30 30 30 30 65 65 65 65 65 65 50 50 5035 30 30 30 45 45 45 45 45 35 35 3540 30 30 30 45 45 45 45 45 35 35 3545 25 25 45 45 45 45 30 30 3050 25 25 45 45 45 45 30 30 3060 25 30 30 30 30 30 3063 25 30 30 30 30 30 300,3 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 650,5 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 651 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 65

1,6 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 652 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 653 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 654 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 655 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 656 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 65 658 30 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 65 65

10 30 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 65 6513 30 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 65 6515 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 6516 30 30 30 30 30 30 30 65 65 65 65 65 65 65 65 65 65 65 6520 30 30 30 30 30 30 65 65 65 65 65 65 65 65 50 50 5025 30 30 30 30 30 65 65 65 65 65 65 65 50 50 5030 30 30 30 30 30 65 65 65 65 65 65 65 50 50 5032 30 30 30 30 65 65 65 65 65 65 50 50 5035 30 30 30 45 45 45 45 45 35 35 3540 30 30 30 45 45 45 45 45 35 35 3545 30 30 45 45 45 45 30 30 3050 25 25 45 45 45 45 30 30 3060 25 25 30 30 30 30 30 3063 25 30 30 30 30 30 30

Note: Independent of any Back-up value in this table, the maximum available current of the circuit where the upstream breaker is used may not exeed it's short circuit rating (Icu)The values specified for 5SJ4…-.HG.. are not according to UL but are the manufacturer's specification according to IEC 60947-2 and apply for voltage Ue=230/400 V AC .

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

J4…

-.HG

..

C 10

36 (S) /55 (M) / 70 (H)

Dow

nstre

amm

inia

ture

circ

uitb

reak

er5S

J4…

-.HG

..

B 10Siemens AGBack-up protection[kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 05/2017

Upstream molded case circuit breaker 3VA1

Line protection

TM210 / TM220 / TM240

100 A 160 A 250 A

16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H)

Back-up-Schutztabellen_en_06102017.xlsx 1.7) 3VA1 - 5SJ4...-.HG.. 10 von 11 Druckdatum: 06.10.2017

Page 12: 3VA Molded Case Circuit Breakers - Siemens

Trip unit

Size

Icu [kA]

Trip

Uni

t

Size

I cu[k

A]

In [A] 25 32 40 50 63 80 100 25 32 40 50 63 80 100 125 160 160 200 250

16 36 36 36 36 36 36 36 55 55 55 55 55 55 55 55 55 36 36 3620 36 36 36 36 36 36 55 55 55 55 55 55 55 55 36 36 3625 36 36 36 36 36 55 55 55 55 55 55 55 36 36 3632 36 36 36 36 55 55 55 55 55 55 36 36 3640 36 36 36 55 55 55 55 55 36 36 3650 36 36 55 55 55 55 36 36 3663 36 55 55 55 36 36 3680 55 55 36 36 36

100 55 36 36 36125 36 36160 3616 55 55 55 55 55 55 55 55 55 55 55 5520 55 55 55 55 55 55 55 55 55 55 5525 55 55 55 55 55 55 55 55 55 5532 55 55 55 55 55 55 55 55 5540 55 55 55 55 55 55 55 5550 55 55 55 55 55 55 5563 55 55 55 55 55 5580 55 55 55 55 55

100 55 55 55 55125 55 55160 5516 70 70 70 70 70 70 70 70 70 70 70 7020 70 70 70 70 70 70 70 70 70 70 7025 70 70 70 70 70 70 70 70 70 7032 70 70 70 70 70 70 70 70 7040 70 70 70 70 70 70 70 7050 70 70 70 70 70 70 7063 70 70 70 70 70 7080 70 70 70 70 70

100 70 70 70 70125 70 70160 70

Note: Independent of any Back-up value in this table, the maximum available current of the circuit where the upstream breaker is usedmay not exeed it's short circuit rating (Icu)

TM210 / TM220 / TM240

Line protection

Upstream molded case circuit breaker 3VA1

16 (B) / 25 (N) / 36 (S) 25 (N) / 36 (S) / 55 (M) / 70 (H)36 (S) /

55 (M) / 70 (H)

100 A 160 A 250 A

Siemens AGBack-up protection [kA]for 230 / 400 V ACacc. to IEC 60947-2

Edition 05/2017

160

A

36(S

)

Dow

nstre

am1-

pole

mol

ded

case

circ

uitb

reak

er3V

A1

25(N

)55

(M)

160

A

Dow

nstre

am1-

pole

mol

ded

case

circ

uitb

reak

er3V

A1

Lne

prot

ectio

n

TM21

0

160

A

Line

prot

ectio

n

TM21

0

Dow

nstre

am1-

pole

mol

ded

case

circ

uitb

reak

er3V

A1

Line

prot

ectio

n

TM21

0

Back-up-Schutztabellen_en_06102017.xlsx 2.1) 3VA1 - 3VA1 11 von 11 Druckdatum: 06.10.2017