Installation Guide 3RU Splice and Patch Panel Series
Installation Guide
3RU Splice and Patch Panel
Series
2 © AFL Hyperscale. All rights reservedSeries
Safety Precautions
Laser Precautions
Warning: The laser light used to transmit information over optical fiber cables can cause severe eye damage. Because this light is invisible, it will not cause the iris of the eye to contract involuntarily as when
viewing a bright visible light, and no pain is felt as the retina is burned.
Never look into the end of a fiber or connector which may have a laser coupled to it. Should accidental eye exposure to laser light be suspected, arrange for an eye examination immediately.
General Precautions
Personnel must be thoroughly familiarized with all applicable Occupational Health and Safety (OH&S) regulations, local regulations, and your company safety practices and policies.
Warning: To reduce the chance of accidental injury:
Before work begins, all personnel must be thoroughly familiar with the operation of all equipment and procedures to be used during the installation.
Before use, all equipment, especially safety gear, must be inspected and tested for proper operation. Replace and repair as necessary.
U-Series 3RU Splice and Patch Panel
Before installing or adjusting this product, please read these instructions carefully. Please keep this guide for future reference.
3
U-Series 3RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Component Overview
01
02
07
06
05
04
03
4 © AFL Hyperscale. All rights reservedSeries
In the Box
Item Number
ItemLC
QtySC
Qty
01U-Series 3RU Splice and
Patch Panel1 1
02U-Series Patch Adapter Plate
12 12
03 Patch Cable Management 1 1
04 Brush Strip 2 2
05 Rear Cover 1 1
06Internal Fiber Slack
Management1 1
07 Front Door Assembly 1 1
08 M6 Cage Nut + Screw 4 4
0912f Ribbon Splice
Protector24 12
10Cable Tie
Black 300mm x 4.5mm10 10
11500mm Length of Ø32mm
Conduit1 1
12 Ribbon Pigtail 12 12
13 Hose Clip Ø11-16mm 2 2
(01) U-Series 3RU Splice and Patch Panel
(04) Brush Strip
Cross-Head + Flat-Head Screwdriver
(07) Front Door Assembly
(10) Cable Tie Black 300mm x 4.5mm
(02) U-Series Patch Adapter Plate
(05) Rear Cover
(08) M6 Cage Nut + Screw
(11) 500mm Length of Ø32mm Conduit
(13) Hose Clip Ø11-16mm
(03) Patch Cable Management
(06) Internal Fiber Slack Management
(09) 12f Ribbon Splice Protector
(12) Ribbon Pigtail
What You Will Need Related Products
FVP Pre-Terminated Replacement Cassette
250 μm WTC with SWR®
One-Click® Cleaner
D-LC, Duplex LC
U-Series 3456f & 6912f
Breakout Box
5
U-Series 3RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Installation Procedure
Turn the quick release fasteners anti-clockwise to remove the rear cover (05).
4Attach the front door assembly (07) as shown.3
Insert the cage nut screws (08) with a screwdriver.
2Insert cage nuts (08) in the positions shown above on both the left- and right-hand sides of the rack.
1
3U
2U
6 © AFL Hyperscale. All rights reservedSeries
Route the conduit (11) into the panel and cable tie (10) it to the internal bracket as shown above.
8Push conduit (11) up and over the cable jacket and cable tie (10) the conduit to the bracket.
7
Remove the brush strip (14), tie off the cable using the hose clip (13) and flat head screwdriver - ensure the jacket strip point is as shown.
6
Installation Procedure
Slide the hose clip (13) and conduit (11) (cut to 150mm) over the cable, and strip 1m of cable jacket in accordance with the cable manufacturers’ guidelines.
5
1m
(ap
pro
x.)
150m
m (
ap
pro
x.) Jacket strip point
7
U-Series 3RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Inbound fiberPre-installed
ribbon pigtails
Ensure the fiber is routed around these managers before cutting to the maximum length
Installation Procedure
Re-fit the rear cover and secure with a quarter turn of the fasteners - they will click when they are closed.
12Re-dress the fiber into the panel, clipping the splice protectors into the holders. Use the dotted line route for re-spliced fibers.
11
Undress the fiber from all the managers and splice according to splice schedule and cable manufacturers’ guidelines (approx. 700mm of slack available).
10Dress the fiber into the panel as per the green route, cut both inbound and pre-installed fiber to length.
9
Inbound fiberPre-installed
ribbon pigtails
8 © AFL Hyperscale. All rights reservedSeries
LC Fiber Map
SC Fiber Map
Po
siti
on
Nu
mb
er
1
2
3
4
5
6
7
8
9
10
11
12
13
Po
sition
Nu
mb
er
14
15
16
17
18
19
20
21
22
23
24
PositionNumber
Fiber/Tubing Color
1 Blue
2 Orange
3 Green
4 Brown
5 Grey
6 White
7 Red
8 Black
9 Yellow
10 Purple
11 Pink
12 Aqua
Position Number
Fiber/Tubing Color
13 Orange
14 Blue
15 Brown
16 Green
17 White
18 Grey
19 Black
20 Red
21 Purple
22 Yellow
23 Aqua
24 Pink
1 2 3 4 5 6 7 8 9 10 11 12Adapter Plate Numbers
Adapter Plate Numbers
Adapter Keyway Up
Po
siti
on
Nu
mb
er
1
3
5
7
9
11
2
Po
sition
Nu
mb
er
4
6
8
10
12
Position Number Fiber/Tubing Color
1 Blue
2 Orange
3 Green
4 Brown
5 Grey
6 White
7 Red
8 Black
9 Yellow
10 Purple
11 Pink
12 Aqua
1 2 3 4 5 6 7 8 9 10 11 12
9
U-Series 3RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Notes
10 © AFL Hyperscale. All rights reservedSeries
Notes
11
U-Series 3RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Notes
Thank you for choosing AFL Hyperscale
AFLHS3RUSPP270820
www.aflhyperscale.com