7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
1/38
Proprietary Information
Proprietary Information
easYgen-3200 TrainingSection 9 - Synchronization and Breaker Logic
marked
CERTIFICATE ofDesign Assessment
byABSAmerican Bureau of Shipping & Affiliated Companies
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
2/38
Proprietary Information
Proprietary Information
ContentsIntroduction
Synchronization
Breaker Logic
FAQExercises
Slide 3
4
9
3132
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
3/38
3
Proprietary Information
Synchronization
IntroductionThe easYgen-3200 is able to perform synchronization of the generator
across the generator circuit breaker to a common bus as well as
synchronizing the common bus to a utility across the mains circuit
breaker. It is possible to configure the easYgen-3200 for either slip or
phase matching synchronization and the acceptable breaker closurewindow.
By adding SPM-D/10 synchronizers to the system, up to four generator
common busses and three tie breakers may be operated.
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
4/38
4
Proprietary Information
SynchronizationThe easYgen-3200 has a synchroscope in the display
Bus/mains
voltages
Bus/mains
frequencies
Voltage/frequency
differentialPhase
angle L1
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
5/38
5
Proprietary Information
Slip synchronization
Configurable frequency window
Configurable voltage window
Configurable synch. frequency differential Configurable breaker closing time
Used to calculate when breaker close pulse is issued
Formula for calculating phase angle at closing command
Phase angle = 360o* (Frequency differential) * (breaker closing time)
Example:
Phase angle = 360o* (0.3 Hz) * (0.2 sec) = 21.6
180o
-90o
+90o
0o
Synchronization
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
6/38
6
Proprietary Information
Slip synchronization
Define close pulse duration
Define stable timer Define maximum voltage differential
Synchronization
180o
-90o
+90o
0o
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
7/38
7
Proprietary Information
Select Configure MCB orGCB
Define stable timer
Define voltage differential window
Define positive and negative phase angle window limits
Define dwell time
180o
-90o
+90o
SynchronizationPhase matching
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
8/38
8
Proprietary Information
RUN Active synchronization is performed. Bias signals to the
governor and voltage regulator are active and breakerclose commands are issued.
PERMISSIVE Passive synchronization performed. Bias signals to the
governor and voltage regulator are not active but breakerclose commands are issued.
CHECK Active synchronization is simulated. Bias signals to the
governor and voltage regulator are active but breakerclose commands are not issued.
OFF The synchronization can be disabled
Synchronization
180o
-90o
+90o
Multiple synchronization modes
The synchronization modes can be changed via a LogicsManager output
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
9/38
9
Proprietary Information
Breaker logic
1 Parallel
Base load or import / export
Soft load / unload
2 Interchange
Parallel for a limited time
Soft load transfer
5 External
External breaker control (PLC)
Only open commands issued
4 Open transition
Break before make
Only dead busbar closing
3 Closed transition
Make before break
Block loading / unloading
The following MCB/GCB transition modes are available:
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
10/38
10
Proprietary Information
Breaker logic
Breaker logic may
be changed via the
LogicsManager
Only if application mode =
GCB/MCB
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
11/38
11
Proprietary Information
Breaker logic1. Parallel
Baseload Import / Export
Load
2
3
CT
CT
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
12/38
12
Proprietary Information
Breaker logic2. Interchange
Load
2
3
CT
220 kW
220 kW
1
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
13/38
13
Proprietary Information
Breaker logic2. Interchange
Load
2
3
CT
220 kW
0 kW
220 kW
Synchronize GCB
1
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
14/38
14
Proprietary Information
Breaker logic2. Interchange
Load
3
CT
220 kW
110 kW
110 kW
Generator soft
loads
1
2
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
15/38
15
Proprietary Information
Breaker logic2. Interchange
Load
2
3
CT
220 kW
110 kW
0 kW
Synchronize GCB
110 kW
1
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
16/38
16
Proprietary Information
Breaker logic2. Interchange
Load
1
2
3
CT
220 kW
110 kW
110 kW
Generator soft
loads
0 kW
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
17/38
17
Proprietary Information
Breaker logic2. Interchange
Load
1
2
3
CT
220 kW
110 kW
110 kW0 kW
Open MCB command issued
at zero power measurement
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
18/38
18
Proprietary Information
Breaker logic2. Interchange
Load
1
2
3
CT
220 kW
110 kW
110 kW
Plant load all on
generators
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
19/38
19
Proprietary Information
Breaker logic3. Closed transition
Load
1
2
3
220 kW
220 kW
Both breakers closed
for max 500 ms
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
20/38
20
Proprietary Information
Breaker logic3. Closed transition
Load
1
2
3
220 kW
220 kW
0 kWSynchronize GCB
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
21/38
21
Proprietary Information
Breaker logic3. Closed transition
Load
2
3
220 kW
220 kW
1
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
22/38
22
Proprietary Information
Breaker logic3. Closed transition
Load
1
2
3
220 kW
110 kW
110 kW
Synchronize GCB
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
23/38
23
Proprietary Information
Breaker logic3. Closed transition
Load
1
2
3
220 kW
110 kW
110 kW
Generator soft loads
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
24/38
24
Proprietary Information
Breaker logic
4. Open transition
Load
1
2
3
220 kW
220 kW
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
25/38
25
Proprietary Information
Breaker logic
4. Open transition
Load
1
2
3
220 kW
Transfer time GCBMCB
controls how long the load bus
is de-energized
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
26/38
26
Proprietary Information
Breaker logic
4. Open transition
Load
1
2
3
220 kW
220 kWDead bus closure
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
27/38
27
Proprietary Information
Breaker logic
4. Open transition
Load
1
2
3
220 kW
110 kW
0 kW
Synchronize GCB
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
28/38
28
Proprietary Information
Breaker logic
4. Open transition
Load
1
2
3
220 kW
110 kW
110 kW
Generator soft loads
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
29/38
29
Proprietary Information
Breaker logic
5. External
Breaker control performed externally (PLC)
Breaker open command depending on alarm class
Generator unloaded performed prior to open command
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
30/38
30
Proprietary Information
Breaker logic
The MCB operates only if Enable MCB = TRUE
The default configuration is as follows:
Closing of MCB stops
if alarm occurs
No closing if field
rotation is wrong
Synchronization
Breaker logic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
31/38
31
Proprietary Information
How do I define the operating ranges for synchronization ?The operating ranges are utilized for permitting breaker closures and defining when
an emergency mode should be initiated.
Generator Mains
FAQ
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
32/38
32
Proprietary Information
Exercise
Configure the following application:
1. You are commissioning an emergency standby generator for a manufacturing
plant. Select a breaker logic for the test run where the generator assumes the
entire plant load and then separates from the utility. The test mode must be
initiated via a discrete input.
2. A second breaker logic mode is desired where the generator assumes the
entire plant load but still remains paralleled with the utility.
Load
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
33/38
33
Proprietary Information
Solution
1) Test mode with the generator running isolated from mains
Configure the alarm class for DI 10 as controlSynchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
34/38
34
Proprietary Information
Solution
1) Test mode with the generator running isolated from mains
Select transition mode Interchange to open the breaker at zero power
Mains CT required!
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
35/38
35
Proprietary Information
Solution
1) Test mode with the generator running isolated from mains
Use discrete input 10 also as start command via Start in AutoSynchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
36/38
36
Proprietary Information
Solution
2) Test mode with the generator running parallel to mains
Select Parallel transition mode and configure the Load set point to Import 0 kWSynchronization
Breakerlogic
FAQ
Exercise
Introduction
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
37/38
37
Proprietary Information
Solution
2) Test mode with the generator running parallel to mains
Synchronization
Breakerlogic
FAQ
Exercise
Introduction
Use discrete input 10 also as start command via Start in Auto
7/22/2019 37397 a EG3200 Section 9 Synchronization and Breaker (NXPowerLite)
38/38
Note:
Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to update or otherwise revise any portion of this publication at any time. Technical data and
detailed information is available in Woodward product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or information otherwise expressly represented in
writing by Woodward as correct and accurate for the specific facts, circumstances and applications.
Other sections are :
1 Overview
2 Hardware and I/O
3 Operational Modes
4 Configuration and ToolKit
5 Communication
6 LogicsManager
7 Analog Manager
8 Controller
9 Synchronization and breaker
10 Application
11 Sequencing
End of this presentation
Thank you for your attention