This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Regenerative Turbine Pumps— Regenerative turbine pumps are used at cylinder docks, dispensing stations, and in other applications that require capacities of up to 25 gallons per minute.
At the pump inlet, the distance between the rotor and the pump liner widens and centrifugal force propels the vanes out from the center of the rotor.
As the rotor continues rotating toward the outlet, the oval shape of the liner results in less space between the rotor and the liner wall, acting to compress the liquid and increase its pressure at the pump’s outlet.
NFPA 58 requires that qualified persons must operate & main-tain bulk plants and industrial installations in accordance with the company’s written operating and maintenance procedures.
Before starting any bulk plant or industrial installation mainten-ance procedure, be sure to review your company’s maintenance procedures and equipment manufacturer’s instructions.
Lubrication Vane and gear-type pump bearings should be lubricated every three (3) months with a light Number 2 Lithium-base type of grease. Apply grease slowly with a hand gun to the grease fittings on each bearing cover until excess grease begins to come from the relief fittings. Do not use a high-pressure grease gun, and stop applying new grease when excess grease appears.
Belt-driven pumps should be examined for proper alignment and condition of the drive belts when lubrication is scheduled.
Shaft coupling-driven pumps should be checked for proper alignment of the couplings and wear of the spacing bushings.
Gear Reduction driven pumps must be checked for proper alignment and wear of their universal joints or couplings as applicable. The gearbox and U-joints should be lubricated according to manufacturer instructions and maintenance recommendations.
At all times during the maintenance of pumps and their drive components, electrical controls should be locked out and tagged according to company procedures.
If the drive belt and pulley guards or coupling guards are removed during inspection or maintenance operations, they must be properly installed and secured before lock out and tag out devices are removed and the equipment is placed back into service.
• Most manufacturers recommend that the installed strainer be at least one pipe size larger than the inlet piping.
• They also recommend a strainer with as large a screen area as possible, and to locate it at least ten pipe diameters upstream from the pump inlet, whenever possible.
Strainer Maintenance
• The strainer must be isolated from the rest of the transfer system by closing liquid piping valves upstream and downstream of the strainer.
• Propane trapped in the strainer must be bled off safely.
• The cover must be removed from the bottom of the strainer body or casing and be cleaned using a brass bristle brush and a solvent if necessary.
Flexible Connectors— Pumps are usually connected to the inlet and outlet piping with flexible connectors to avoid serious damage from vibration, expansion and contraction of the piping with heat and cold, and sags or other forces
transmitted to the pump through the plant transfer piping.
Selecting and Maintaining Hydrostatic Relief Valves —Hydrostatic relief valves must be designed to open at a pressure of not less than 400 psig and not more than 500 psig when selecting new or replacement valves.
Figure 8. Hydrostatic Relief Valves With Rain Caps
Hydrostatic relief valves should be fitted with rain caps to prevent moisture and debris from accumulating inside the valve.
The bypass valve should be set at least 15 to 20 psi below the pump’s internal relief valve setting. Qualified personnel using properly selected liquid-filled pressure gauges (rated for 0-400 psig service) can adjust the valve’s opening setting if the automatic bypass is not opening at the proper pressure to protect the pump.
To determine the automatic bypass opening setting or to adjust the setting, follow your company’s written maintenance procedures and equipment manufacturer instructions.