    Typical installations o the NPS modularoutdoor switch disconnector

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    2/382 NPS

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    3/38NPS 3

    Index

    Introduction .................. ................... ................... .................. .............. 4

    Technology review ................ ................... ................... ................... .... 5

    NPS technology ................ ................... ................... ................... .... 5

    Control cabinets ................ ................... ................... ................... .... 7

    Relays ................. .................. ................... ................... ................... . 8

    Product review ................... ................... ................... ................... ....... 9

    Benets .................. ................... .................. ................... ................. 9

    Technical data ................ ................... ................... ................... ..... 10

    NPS ordering guide........ ................... ................... ................... ..... 11

    Examples o pole installation .......................................................18

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    4/384 NPS

    The NPS design is based on many years o experience with

    installations around the world. With the NPS, ABB delivers reliable

    operation in all climatic conditions and congurations. In addition,

    the NPS can be either manually or remotely controlled, with the

    option o incorporation into automated networks as a sectionalizer.

    Thanks to its modular construction and important design eatures,

    the NPS is a key component in creating uture smart grids.

    NPS

    Current breaking solutions rom 25 A 630 A.

    Manual or remote motor controlled congurations available.

    Capability to install additional pole equipment or dierentdistribution network needs.

    Features

    Mechanically stable structure to suit dierent climatic conditions.

    Flexible mounting and installation options.

    Modular NPS design minimizes on site assembly and installation

    time.

    Wide range o breaking current parameters.

    Compact packaging reduces transportation and storage costs.

    Introduction

    Insulators available in porcelain, epoxy and silicon.

    Special metal surace treatment durable and resistant to high

    corrosion environments.

    No oil used in breaking chambers environmental protection

    and reduced maintenance.

    Designed to be tted with a wide range o optional modular

    accessories:

    earthing switches rom both sides o main switch,

    separate earthing switch solutions,

    current transormers and surge arresters on same supporting

    structure,

    current limiting uses, manual or motor operating mechanisms,

    wide range o control cabinets to allow installation o

    communication equipment.

    1. Wide range o operating mechanisms | 2. and 3. Remote controlled NPS | 4. Various breaking current solutions | 5. Pole mounted transormer

    substations

    51

    43

    2

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    5/38NPS 5

    The modular NPS design allows or a wide range o

    accessories or various applications or outdoor air-insulated

    switches. The NPS can be expanded and adapted to

    changing distribution network needs, even ater installation.

    The NPS oers three types o insulators - porcelain, epoxy

    (cycloaliphatic) and silicone.

    The epoxy and silicon insulators provide reduced weight,

    resistance to mechanical shock and good perormance in heavy

    polluted areas. In order to heavily polluted achieve high creepage

    perormance, the NPS oers a wide range o insulators.

    The NPS is provided with breaking whips as standard. I higher

    interrupting ratings are required, breaking chambers are provided.

    Technology reviewNPS technology

    1. Wide range o various equipment (third insulator, use bases, earthing switch rom the rocking side, use base integrated with NPS, UEKO3A1 &

    UEKO3B1 manual operating mechanism | 2. Various types o insulators

    The main current carrying path is electrolytic copper, silver plated

    to ensure a suitably low level o contact resistance. The design

    o the main contacts consists o copper contact tips xed by

    stainless steel springs. This design ensures sel positioning o

    the main contacts in the closed position. In addition, this design

    requires a lower amount o orce or closing and opening the

    disconnector. The short circuit withstand o the NPS is increased

    as a result o the eect o electrodynamic orces during short

    circuit current fow through the main current path. In addition,

    the tips may be reversed by 180 which extends the lie o the

    contacts. This is a simple operation using ordinary pliers.

    1

    2

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    6/386 NPS

    All steel components are coated with zinc galvanizing which

    provides a high level o corrosion resistance All copper

    components are silver-plated with the exception o terminals,

    which are coated with tin to allow line terminals, aluminium and

    copper, to be connected to the NPS without degrading their

    perormance. Flexible copper parts o the NPS are coated with

    tin, aluminum components are made o special aluminum alloy to

    ensure high resistance to extreme ambient conditions. For special

    customer requirements, acetal resin insulators are available or

    disconnectors rated up to 24 kV, or composite insulators or up to

    36 kV used in connection rods between the operating mechanism

    and switch.

    All standardized asteners are zinc galvanized or stainless steel.

    This allows the NPS switch disconnector to provide long-term

    operation even in the harshest environments.

    Technology reviewNPS technology

    Breaking chambers

    There are our dierent rated current breaking versions used in

    the NPS. Using one o the 2 types o chambers it is possible to

    achieve signicant values o breaking rated currents:

    standard fexible breaking whips or switching-o small currents

    (up to 25 A or 24 kV, up to 40 A or 12 kV),

    special (K1) breaking whips or switching o higher currents

    (up to 50 A at 24 kV, up to 80 A or 12 kV),

    air type breaking chamber (K4) with breaking capacity up to

    250 A (24 kV),

    air type breaking chamber (K5) with breaking capacity up to

    630 A (24 kV).

    1. Dierent rated current breaking versions | 2. Stainless or zinc galvanized or high anti-corrosion resistance

    1 2

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    7/38NPS 7

    Control cabinets

    The NPS control cabinets are designed or remote control and

    local automation applications o NPS switch disconnectors and

    other similar types with up/down operating movement.

    Together with the ABB REC601/603 or REC 523 monitoring and

    control units both simple applications such as remote open/close

    operations and more sophisticated auto sectionalizing schemes

    and measurements can be realized.

    Basic unction o REC601/603:

    1. Controls: one (REC601) or three (REC603) drives,

    2. GPRS communication3. Module o battery charging with temperature compensation,

    deep discharge protection, battery monitoring and testing

    4. Motor overload protection

    Technology reviewControl cabinetes

    Basic unctions o REC523:

    1. Control: max our switches, charging battery system and

    temperature.

    2. Measurement: continuous network parameters, the internal

    temperature and battery voltage level.

    3. Registration and identication: short-circuit currents and

    voltages in special application unctions.

    4. Monitoring: the level o battery charging, protection against

    excessive battery discharge, the operations counting, internal

    control o the relay status.

    5. Protection unctions and automation: auto-reclosing, phase

    discontinuity, overcurrent, earth-ault, under-voltage, transormerand motors inrush current.

    6. Communication protocols: SPA, LON, IEC 870-5-101, Modus,

    DNP 3.0.

    Analog inputs available or standard CTs and VTs.

    1. Motor operating mechanism | 2. Motor operating mechanism with REC523

    1 2

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    8/388 NPS

    Control cabinets can also be used without the integrated motor

    mechanism. These can be used in applications such as master

    terminal or monitoring and controlling existing motor devices

    or indoor and outdoor switch disconnectors and other motor

    operated apparatus. It is also applicable or switching devices with

    an integrated actuator.

    Control cabinet eatures:

    The product range includes master and slave units.

    Can be equipped with third party electronics/IED.

    Two dierent cabinet sizes.

    Terminals or installing dierent IEDs. Cabinets available with dierent options or batteries, battery

    chargers etc.

    Up/down tube operation o disconnectors.

    Stainless steel cabinet and mechanism.

    Dust tight (IP55) to ensure long lietime o critical electrical

    components.

    High torque, choice o 1.2 sec or 3 sec operating time.

    Optimum materials used.

    Over 30 years experience.

    Operating voltages: 24, 48, 110, 220 VDC 110, 230 V AC.

    1. 2. Control cabinet with REC523 | 3. Control unit REC603 with GPRS communications | 4. REC523 control unit

    Technology reviewNPS technology

    1

    3 4

    2

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    9/38NPS 9

    NPS can operate in all climatic conditions, and can be installed

    in a variety o dierent positions, with either manual or remote

    control.

    Disconnectors equipped with electric drives can be used in

    system automation solutions or distribution networks using the

    remote control or auto-closing unctions. In this case, in addition

    to the motor operating mechanism the NPS will also be equipped

    with the latest automation systems. So in this application, the

    NPS switch disconnectors will become an integral part o the

    development o Smart Grids.

    Benefts Modular design:

    allows or easy or installation reducing signicantly reducing

    site time and costs and improving saety,

    reduced transportation and storage size reduces associated

    costs,

    easily upgradeable,

    simple changing o current breaking devices, pole distances

    and manual to motor drive,

    Product reviewBeneits

    easy to accommodate various overhead line connections and

    operations third insulator version, rocking terminals,

    extended lie cycle reversible main current path parts,

    capability to oer specic solutions/unctions to suit local

    installation needs both side earthing switches, current

    limiting uses, surge arresters, instrument transormers.

    High quality materials and coating surace:

    increased perormance over the lie o the switch,

    terminals can be connected to both aluminium and copper

    lines without degradation in perormance.

    Feeder Automation Solutions:

    can be applied to remote control applications optimizingoverhead network,

    can be applied to auto-reclosing applications sectionalizer

    unction,

    ailure detection and localization support unctions,

    communication with local Scada systems.

    Modular design and high quality materials makes it sae and easy during the installation

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    10/3810 NPS

    Product reviewTechnical data

    Type NPS

    Rated maximum voltage [kV] 24 24 36 36

    Rated current [A] 630 630 630 630

    Rated requency [Hz] 50/60 50/60 50/60 50/60

    Rated lighting impulse withstand voltage: [kV]

    - across the insulating distance 145 165 2204) 2204)

    - to earth and between phases 125 150 2004) 2004)

    Rated power requency withstand voltage in wet conditions: [kV]

    - across the insulating distance 75 75 884) 884)

    - to earth and between phases 55 55 804) 804)

    Creepage distance [mm] 7401) 7602) 12052) 13652)

    Minimum distance between phases [mm] 260 350 430 430

    Minimum insulating distance [mm] 200 230 350 350

    Rated short-time withstand current - 1 s [kA] 16 20 21 21

    Rated short-time withstand current - 3 s [kA] 12.5 16 16 16

    Rated peak withstand current [kA] 40 50 52 52

    Making current [kA/no. operations] 5/7 5/7 - -

    Rated breaking current

    Standard breaking whip

    Special breaking whip

    Chamber NPAK4

    Chamber NPAK5

    A/no. operations

    A/no. operations

    A/no. operations

    A/no. operations

    25/1003)

    50/30

    250/100

    400/100

    25/1003)

    50/30

    250/100

    400/100

    -

    -

    -

    -

    -

    -

    -

    -

    Cable and overhead line charging current - 20 CO operations [A] 15 15 10 10

    Mechanical endurance [no. CO operations] 2000 2000 2000 2000

    Ambitne temperature limits [C] -50 to +40 -40 to +40 -40 to +40 -40 to +40

    Centilever strenght [kN] [kN] 2 9 6.2 6.2

    1) Epoxy insulators version.2) Silicon insulators version.3) 40 A or 12 kV version.4) Version with earthing switch got lower ratings.

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    11/38NPS 11

    Style Code NPS 2 3 E 1 G Q N B N N N K K 1

    Style Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

    Product reviewNPS ordering guide

    The guide above shows the specication o: 3 phase NPS, 24 kV,

    25 A breaking current (version with standard breaking whips and

    epoxy insulators), set o third insulator, hand operating mechanism

    type UEKO1A1 with operating rods 2x4m or horizontal installation

    on the single wooden pole.

    Digits 16, 17 and 18 are used to dene the version o the

    selected accessories. There are 999 dierent options or selecting

    accessories. Specic accessories should be selected and noted

    according to the selection guide below. I urther options are

    required please contact your local ABB representative.

    Selections Style code Style digit

    Sample Actual

    NPS switch NPS NPS 1

    Rated Maximum Voltage:

    1 - 12 kV

    2 - 24 kV

    3 - 36 kV* 3 2 2

    Poles number:

    1 - one pole solution

    3 - three pole solution

    1

    3

    3

    Insulators type:E - epoxy (this version available up to 24 kV only)

    P - porcelain

    S - silicon S E 4

    Creepage distance solution:

    1 - increased

    increased means: 740 mm or epoxy insulators - 24 kV, 760 mm or silicon insulators - 24 kV,

    1365 mm or silicon insulators - 36 kV;

    2 - normal

    normal means: 530 mm or porcelain insulators 24kV, 950mm or porcelain insulators 36kV, 1205 mm

    or silicon insulators - 36 kV1 1 5

    Breaking current solution:

    F - disconnector without breaking capacity

    G - standard breaking whips - up to 16 A (36 kV), up to 25 A (24 kV), up to 40 A (12 kV)

    H - K1 breaking whips - up to 50 A (24 kV), up to 80 A (12 kV)

    K - K4 breaking chamber - 250 A (24 kV)

    L - K5 breaking chamber - 630 A (24 kV) F G 6

    NPS equipment installed at the rocking insulator site:

    P - sel aligning terminal

    Q - third insulator set

    R - surge arrester

    S - current transormer type KOHU

    U - lexible dropping set or cable connection

    V - bar or line connection to transormer

    N - no equipment

    P

    Q

    7

    * see remarks on page 20.

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    12/3812 NPS

    Product reviewNPS ordering guide

    Selections Style code Style digit

    Sample Actual

    NPS equipment installed at the ixed insulator site:

    A - bars set or cable connection

    B - surge arrester

    C - current transormer type KOHU

    E - lexible dropping set or cable connection

    G-use base integrated with NPS or OFCD uses

    N - no equipment A N 8

    Hand operating mechanism type or NPS switch:

    1 B 9

    A - UEKE5A1 type hook stick operation

    B - UEKO1A1 type - one hand operation or low end switches

    C - UEME3A1 type or all NPS types

    D - UEKE3B1 type or all NPS types with rod length regulation device

    E - UEKE2/1 or all NPS types with auxiliary contacts 6NO/6NC

    G - UEMC50L5-24 VDC/21

    H - UEMC50H5-24 VDC/21

    J - UEMC50L1-24 VDC/1

    K - UEMC50H1-24 VDC/1

    N - no hand operation mechanism

    Earthing switch:

    A - integrated with NPS switch - rocking insulator side - close, open-earthed positions (do not needs

    additional operating mechanism)

    B - integrated with NPS switch - ixed insulator side (needs additional operating mechanism)

    C - both sides earthing switches (operated with separate operating mechanisms)

    D - integrated with NPS switch - rocking insulator side (needs additional operating mechanism)

    N - No earthing switch A N 10

    Hand operating mechanism type or earthing switch - rocking insulator side:

    B - UEKO1A1 type - one hand operation or low end switches

    C - UEME3A1 type or all NPS types

    D - UEKE3B1 type or all NPS types with rod length regulation device

    E - UEKE2/1 or all NPS types with auxiliary contacts 6NO/6NC

    N - no hand operation mechanism 1 N 11

    Hand operating mechanism type or earthing switch - ixed insulator side:

    B - UEKO1A1 type - one hand operating or low end switches

    C - UEME3A1 type or all NPS types

    D - UEKE3B1 type or all NPS types with rod length regulation device

    E - UEKE2/1 or all NPS types with auxiliary contacts 6NO/6NC

    N - no hand operating mechanism 1 N 12

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    13/38NPS 13

    Product reviewNPS ordering guide

    Selections Style code Style digit

    sample actual

    Operating rod L

    K - 2 x 4 m or installation up to 9 m above the ground level

    L - 3 x 3 m or installation up to 10 m above the ground level

    M - 2 x 4 m + 3 m or installation up to 12 m above the ground level

    N - without operating rod K K 13

    Type o the pole and pole dimmensions at NPS/operating mechanism level

    A - concrete pole, rectangular cross-section, dimensions 200 - 235 mm

    B - concrete pole, rectangular cross-section, dimensions 210 x 210 - 280 mm

    C - concrete pole, rectangular cross-section, dimensions 240 x 240 - 300 mm

    D - concrete pole, circular cross-section, dimensions 170 mm to 235 mm

    E - concrete pole, circular cross-section, dimensions 220 mm to 270 mm

    F - concrete pole, circular cross-section, dimensions 270 mm to 400 mm

    G - ZN type

    H - BSW type

    J - EPV12/12; 13.5/12 or 15/12 types

    K - wooden pole

    N - other type o supporting structure A K 14

    Method o NPS installation under the line:

    1 - one pole horizontal installation

    2 - one pole vertical installation

    3 - two pole horizontal installation

    4 - two pole vertical installation

    5 - on the top o single pole

    6 - on the top o two poles

    N - not deined 1 1 15

    Additional equipment

    A - separating insulator in connection rod up to 24 kV i additional

    needed.

    B - separating insulator in connection rod up to 36 kV i additional

    needed..

    C - crossarm set or NPS installation between 2 wooden poles

    1900mm i additional needed.

    D - crossarm and xing arms set or NPS installation on the topo wooden pole (epoxy and silicon insulators solutions) i

    additional needed.

    E - crossarm and xing arms set or NPS installation on the top

    o wooden pole (porcelain insulators solutions) i additional

    needed.

    G - terminals or copper line connection 16mmkw OJUZLL 1/3.

    H - terminals or aluminum line connection 16 mm2

    2 x 70 mm2 OJUZLL 3/3.

    J - terminals or aluminum line connection 62 mm2 99 mm2

    NPTL24/3.

    K - terminals or aluminum line connection 95 mm2

    240 mm2 OJUZLL 4/3.L - terminals or aluminum line connection 99 mm2 and copper

    16 mm2. NPTLA24/3.

    M - earthing switch or separate installation i additional needed.

    N - sel aligning terminal - Ag plated.

    Additional equipment dedicated to MV uses

    1 - use link OFCD24/6,3 type - 3 pcs.

    2 - use link OFCD24/16 type - 3 pcs.

    3 - use link OFCD24/25 type - 3 pcs.

    4 - use elements - 12 pcs. in one package.

    5 - operating rod or uses installation.

    6 - operating rod or UEKO5A1 operation.7 - operating rod or uses installation and UEKO5A1 operation.

    8 - use base or separate installation o or OFCD uses.

    9 - use base or separate installation or DIN type uses 442

    mm.

    10 - use base or separate installation or DIN type uses 537 mm.

    11 - tube support or melting uses acc to Swedish building

    standard.

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    14/3814 NPS

    Additional equipment dedicated to motor operating

    mechanism

    Batteries G2 and G3:

    A - UEZGP 17AH-24 V - Battery - 17 AH, 2 PCS -YUA NP17-

    12 (YUA ..TYPES) (all UEMC types).

    B - UEZGL 24AH-24 V - Battery - 24 AH, 2 PCS-YUA NPL24-

    12, long lie (YUA ..TYPES)

    (not or UEMC50H1 and L1).

    C - UEZGL 38AH-24 V - Battery - 38 AH, 2 PS -YUA NPL24-

    12, long lie (YUA ..TYPES)

    (only or UEMC50 H5/21 and L5/21).

    Battery chargers G1:

    D - UEZGC 24 V/3 A/230 VAC - installed charged, supply

    170..260 VAC (GYC RUN TYPE).

    E - UEZGC 24 V/3 A/110 VAC - installed charged, supply

    87..132 VAC (GYC RUN TYPE).

    Other alternative accessories:

    F - UEZS2/S10 - 3 NC/NO additional aux. contacts or

    UEMC50L...

    G - UEZS3/S10 - 3 NC/NO additional aux. contacts or

    UEMC50H...

    H - UEZS2/S11 - 6 NC/NO additional aux. contacts orUEMC50L...

    J - UEZS3/S11 - 6 NC/NO additional aux. contacts or

    UEMC50H...

    K - UEZS2/S12 - 4NC/NO+1NC/C+1NO/D additional aux.

    contacts or UEMC50H...

    L - UEZS3/S12 - 4NC/NO+1NC/C+1NO/D additional aux.

    contacts or UEMC50H...

    M - UEMZ 199 - heater switch.

    P - UEMZ 200 - charger and heater switch.

    Q - UEMZ 318 - thermostat, not adjustable. Disconnect at

    +30oC.

    R - UEMZ 319 - M.C.B. or charging and heater circ. 1 A.S - UEMZ1191/24 VDC - service light rom 24 VDC batteries.

    T - UEMZ1066 - xing bracket or rectangular pole.

    U - UEMZ1146 - xing bracket or rectangular bigger pole.

    W - UEMZ938 - door switch.

    X - UEMZ1276 - door retainer.

    Product reviewNPS ordering guide

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    15/38NPS 15

    Remarks:

    1. Standard short circuit withstand is 16/40 kA or 24 kV, version with

    silicon insulators (increased creepage distance) provides 20/50 kA.

    2. When using 3rd insulator, SAs or CTs it is not possible to use

    an integrated earthing switch at the same site o the NPS unit.

    In this case, reer to column 14 and select loose installation

    earthing switches i necessary.

    3. Fuse bases or separate installation or OFCD type uses are

    available only with epoxy insulators version.

    4. Selection o KOHU CTs electrical parameters should be dened

    according to the separate KOHU CT catalogue.

    Product reviewNPS ordering guide

    5. ABB recommends SAs POLIM D and POLIM K type.

    6. When selecting any style code then just one choice is available

    or the specic switch solution. Only the additional equipment

    has multi-choice options.

    7. Please note that 36 kV versions have limited versions o additi-

    onal equipment such as: earthing switches, dierent pole

    installation methods, SAs, uses, insulator types. Thereore,

    especially when selecting 36 kV versions we recommend dis-

    cussion o the required solution with your local ABB

    representative.

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    16/3816 NPS

    Product reviewNPS ordering guide

    Various equipment installed on both sides o 24kV NPS switch

    Earthing switch or the

    fxed insulator side

    Flexible dropping set

    or cable connection

    equipped with surge

    arrester

    Third insulator version

    Version 250A

    Version 25 A

    Version 630A

    Version 50 A

    Fuse base integrated with

    NPS switch (OFCD uselinks)

    Earthing switch

    integrated with NPS

    switch rocking

    insulator site close,

    open-earthed positions

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    17/38NPS 17

    Product reviewNPS ordering guide

    Selected accessories

    1 2 3

    45

    6

    7

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    18/3818 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 630 A o nominal current, installed on the top o circular pole

    Set o NPS23E2LPNCNNNKF5 + 2xOJUZLL4/3

    1

    2

    3

    45

    6

    7

    8

    9

    ~750

    ~1200

    ~10m

    10

    11

    12

    13

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    19/38NPS 19

    Part number Part name quantities

    1 1YMN000001M0001 One phase element with 630A breaking chamber 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Earthing terminal NPTMS8 111 1YMNOJUZLLM4/31 Line xing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNOJUPZLM9/32 Selaligning terminals set 1

    14 1YMN000114M0001 Crossarm ixing to the pole top 1

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FPNCNNNKF5 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2GPNCNNNKF5 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2HPNCNNNKF5 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2KPNCNNNKF5 +

    2xOJUZLL4/3

    Min 360 Min 260 Min 260

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    20/3820 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 630 A o nominal current, installed under the line, horizontal position, circular pole

    set o NPS23E2LPNCNNNKF1 + 2xOJUZLL4/3

    1

    2

    12

    3

    4

    5

    6

    7

    8

    9

    10

    ~750

    ~1200

    ~

    10m

    11

    13

    14

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    21/38NPS 21

    Part number Part name quantities

    1 1YMN000001M0001 One phase element with 630 A breaking chamber 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Earthing terminal NPTMS8 1

    11 1YMNOJUZLLM4/31 Line xing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNNPAZM3M1101 Crossarm ixing NPAZM31 1

    14 1YMNOJUPZLM9/32 Selaligning terminals set 1

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FPNCNNNKF1 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2GPNCNNNKF1+

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2HPNCNNNKF1 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2KPNCNNNKF1 +

    2xOJUZLL4/3

    Min 260 Min 260

    750

    Min 360

    2000

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    22/3822 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 630 A o nominal current, installed under the line, vertical position, circular pole with cable

    connection

    set o NPS23E2LQNCNNNKF2 + 2xOJUZLL4/3

    12

    2

    4

    5

    6

    7

    8

    9

    10

    14

    ~10m

    ~750

    ~1200

    1

    13

    3

    11

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    23/38NPS 23

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FQNCNNNKF2 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2GQNCNNNKF2+

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2HQNCNNNKF2 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2KQNCNNNKF2 +

    2xOJUZLL4/3

    Part number Part name quantities

    1 1YMN000001M0001 One phase element with 630 A breaking chamber 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Earthing terminal NPTMS8 1

    11 1YMNOJUZLLM4/31 Line xing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNNPAZM3M1101 Crossarm ixing NPAZM31 1

    14 1YMNNPAC9-MJ231 Third insulator set NPAC9-J2/3 1

    Min 260Min 260

    750

    Min 460

    2000

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    24/3824 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 25 A o nominal current, two circular poles installation at the top

    Set o NPS23E2GPNCNNNKF6 + 2xOJUZLL4/3

    ~1200

    ~10m

    ~750

    1 5

    9

    144

    6

    8

    7

    2 12

    3

    1011 13

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    25/38NPS 25

    Part number Part name quantities

    1 1YMN000004M0001 One phase element with 25 A breaking whips 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Earthing terminal NPTMS8 1

    11 1YMNOJUZLLM4/31 Line xing terminal OJUZLL4/3 212 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNOJUPZLM9/32 Selaligning terminals set 1

    14 1YMNNPAZL4M0001 Operating shat support NPAZL4 1

    15 1YMN000114M0001 Crossarm ixing to the pole top 2

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FPNCNNNKF6 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2HPNCNNNKF6 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2KPNCNNNKF6 +

    2xOJUZLL4/3

    Load break switch24 kV, 250 A

    breaking current

    NPS23E2LPNCNNNKF6 +2xOJUZLL4/3

    Min 260Min 300 Min 300

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    26/3826 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 25 A o nominal current, two circular poles installation below the line

    Set o NPS23E2GPNCNNNKF3 + 2xOJUZLL4/3

    ~750

    ~1200

    ~10m

    1

    10 3

    9

    5

    15

    12

    4

    11

    13

    14

    8

    6

    7

    2

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    27/38NPS 27

    Part number Part name quantities

    1 1YMN000004M0001 One phase element with 25 A breaking whips 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9* 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Earthing terminal NPTMS8 1

    11 1YMNOJUZLLM4/31 Line xing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNOJUPZLM9/32 Selaligning terminals set 1

    14 1YMNNPAZM3M1101 Crossarm ixing NPAZM31 2

    15 1YMNNPAZL4M0001 Operating shat support NPAZL4 1

    * 2,85 m crossarm is available as well 1YMNJ40146M4001.

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FPNCNNNKF3 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2HPNCNNNKF3 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2KPNCNNNKF3 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2LPNCNNNKF3 +

    2xOJUZLL4/3

    Min 260 Min 260Min 300 Min 300

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    28/3828 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 25 A o nominal current, installation below the line on pole mounted transormer substation,

    switch in horizontal position

    Set o NPS23E2GQNCNNNKF1 + 2xOJUZLL4/3

    ~

    10m

    ~750

    ~1200

    11

    13

    2

    12

    7

    8

    6

    10

    5

    9

    4

    3

    14

    1

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    29/38NPS 29

    Part number Part name quantities

    1 11YMN000004m0001 One phase element with 25 A breaking whips 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Fixing crossarm 2 m 1

    11 1YMNOJUZLLM4/31 Line ixing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNNPAZM3M1101 Crossarm ixing NPAZM31 1

    14 1YMNNPAC9-MJ231 Third insulator set NPAC9-J2/3 1

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FQNCNNNKF1 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2HQNCNNNKF1 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2KQNCNNNKF1 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2LQNCNNNKF1 +

    2xOJUZLL4/3

    Min 400 Min 260

    Min 260

    Min 260

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    30/3830 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 25 A o nominal current, installation below the line on pole mounted transormer substation,

    switch in vertical position

    Set o NPS23E2GQNCNNNKF2 + 2xOJUZLL4/3

    ~1200

    ~750

    ~10

    m

    2

    6

    8

    7

    13

    11

    12

    31

    9

    4

    14

    10

    5

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    31/38NPS 31

    Part number Part name quantities

    1 11YMN000004m0001 One phase element with 25 A breaking whips 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Fixing crossarm 2 m 1

    11 1YMNOJUZLLM4/31 Line ixing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNNPAZM3M1101 Crossarm ixing NPAZM31 1

    14 1YMNNPAC9-MJ231 Third insulator set NPAC9-J2/3 1

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FQNCNNNKF2 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2HQNCNNNKF2 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2KQNCNNNKF2 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2LQNCNNNKF2 +

    2xOJUZLL4/3

    Min 260Min260Min 400

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    32/3832 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 25 A o nominal current, installation below the line on end line pole mounted transormer

    substation, switch in horizontal position

    Set o NPS23E2GQNCNNNKF1 + 2xOJUZLL4/3

    ~10m

    ~750

    ~1200

    11

    13

    14

    3

    9

    4

    5

    10

    1

    12

    2

    6

    8

    7

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    33/38NPS 33

    Part number Part name quantities

    1 1YMN000004m0001 One phase element with 25 A breaking whips 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Fixing crossarm 2 m 111 1YMNOJUZLLM4/31 Line ixing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNNPAZM3M1101 Crossarm ixing NPAZM31 1

    14 1YMNNPAC9-MJ231 Third insulator set NPAC9-J2/3 1

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FQNCNNNKF1 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2HQNCNNNKF1 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2KQNCNNNKF1 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2LQNCNNNKF1 +

    2xOJUZLL4/3

    Min 400 Min 260

    Min 260

    Min 260

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    34/3834 NPS

    Samples o the pole installationsDimensional drawings

    24 kV NPS load-break switch or 630 A o nominal current, installation at the top o end line pole, overhead line to cable

    connection

    Set o NPS23E2LQNCNNNKF5 + 2xOJUZLL4/3

    ~10m

    ~750

    ~1200

    11 1

    3

    4 913

    12

    8

    6

    7

    2

    5

    10

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    35/38NPS 35

    Part number Part name quantities

    1 1YMN000001M0001 One phase element with 630 A breaking chamber 3

    2 1YMNUEKE3AM1001 UEKE3A1 manual operating mechanism 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 1

    4 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Fixing crossarm 2 m 1

    11 1YMNOJUZLLM4/31 Line ixing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 Operating mechanism xing elements round pole up to 400 mm 1

    13 1YMNNPAC9-MJ231 Third insulator set NPAC9-J2/3 1

    14 1YMN000114M0001 Crossarm ixing to the pole top 1

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector

    24 kV

    NPS23E2FQNCNNNKF5 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2GQNCNNNKF5+

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2HQNCNNNKF5 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2KQNCNNNKF5+

    2xOJUZLL4/3

    Min 260Min 260Min 460

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    36/3836 NPS

    Samples o the pole installationsDimensional drawings

    Remote controlled 24 kV NPS load break switch, 630 A, at the top o circular pole

    Set o NPS23E2LQNGNNNKF5 + 2xOJUZLL4/3

    ~10m

    ~750

    ~1400

    A

    B

    C

    1

    11

    2

    6

    8

    7

    9 4 5

    10

    12

    13

    3

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    37/38NPS 37

    Part number Part name quantities

    1 1YMN000001M0001 One phase element with 630 A breaking chamber 3

    2 1YMU000020M0001 Motor operating mechanism UEMC50L5-24VDC 1

    3 1YMNNPAM1/M3001 ixing clamps NPAM1/3 14 1YMNNPAZL7M0001 operating shat NPAZL7 1

    5 1YMNNPAZL2M0001 Operating lever NPAZL2 1

    6 1YMNNPAZL1M9/E1 Tube support NPAZL19/E1 2

    7 1YMNNPTOT3M8301 connecting tubes 2 x 4 m 1

    8 1YMNNPSZJ3M0002 Separating insulator NPSZJ30 1

    9 1YMNNPTRN1MT6S1 Fixing crossarm 2 m 1

    10 1YMNNPTMS8M0001 Earthing terminal NPTMS8 1

    11 1YMNOJUZLLM4/31 Line ixing terminal OJUZLL4/3 2

    12 1YMNNPAZM3M2001 UEMC50 ixing set to circular pole up to 400 mm 1

    13 1YMN000114M0001 Crossarm ixing to the pole top 1

    14 1YMNNPAC9-MJ231 Third insulator set NPAC9-J2/3 1

    Additional equipmentA 1YMS000050M0001 TDO VTs supporting structure or circular pole 1

    B 1YMV105111R0066 Auxiliary power supply VT TDO 6 21000//230 V 1

    C POLIM-D 24-07 POLIM-D 24-07 Surge arresters 3

    Complete set description according to

    style guide, alternative solutions

    NPS type Style code

    Disconnector24 kV

    NPS23E2FQNGNNNKF5 +2xOJUZLL4/3

    Load break switch

    24 kV, 25 A

    breaking current

    NPS23E2GQNHNNNKF5+

    2xOJUZLL4/3

    Load break switch

    24 kV, 50 A

    breaking current

    NPS23E2HQNHNNNKF5 +

    2xOJUZLL4/3

    Load break switch

    24 kV, 250 A

    breaking current

    NPS23E2KQNHNNNKF5 +

    2xOJUZLL4/3

    Min 320

    Min 460 Min 260 Min 360

    Min 360

  • 7/29/2019 3405PL733-W1-En Typical Installation of NPS

    38/38

    3405PL733-W1-en.

    Edition11.2

    012

    Contact us

    We reserve the right to make technical changes or

    modiy the contents o this document without prior

    notice. With regard to purchase orders, the agreed

    particulars shall prevail. ABB Sp. z o.o. does not

    accept any responsibility whatsoever or potential

    errors or possible lack o inormation in this document.

    We reserve all rights in this document and in the

    subject matter and illustrations contained therein.

    Any reproduction, disclosure to third parties

    or utilization o its contents in whole or

    in parts is orbidden without prior written

    consent o ABB Sp. z o.o.

    Copyright 2012 ABB

    All rights reserved