DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
A106 FINISH PLANS - TOILET ROOMS, BREAK ROOM, AND GYM
A401 INTERIOR ELEVATIONS, DETAILS AND SCHEDULES
FIRE PROTECTION
FAD101 FIRE ALARM 2ND FLOOR DEMO PLAN
FAD102 FIRE ALARM 2ND FLOOR DEMO PLAN
FA101 FIRE ALARM 2ND FLOOR FLOOR PLAN
FA102 FIRE ALARM 2ND FLOOR FLOOR PLAN
FP101 FIRE PROTECTION 2ND FLOOR PLAN
FP102 FIRE PROTECTION 2ND FLOOR PLAN
PLUMBING
P000 PLUMBING NOTES, LEGEND, AND ABBREVIATIONS
PD101 PLUMBING 2ND FLOOR DEMO PLAN
PD102 PLUMBING 2ND FLOOR DEMO PLAN
P101 PLUMBING 2ND FLOOR FLOOR PLAN
P102 PLUMBING 2ND FLOOR FLOOR PLAN
MECHANICAL
M000 MECHANICAL NOTES, LEGEND, AND ABBREVIATIONS
MD101 MECHANICAL 2ND FLOOR DEMO PLAN
MD102 MECHANICAL 2ND FLOOR DEMO PLAN
M101 MECHANICAL 2ND FLOOR FLOOR PLAN
M102 MECHANICAL 2ND FLOOR FLOOR PLAN
M103 MECHANICAL SCHEDULES
ELECTRICAL
E000 ELECTRICAL NOTES, LEGEND, AND ABBREVIATIONS
E001 ELECTRICAL PANEL SCHEDULES
ED101 ELECTRICAL 2ND FLOOR DEMO POWER PLAN
ED102 ELECTRICAL 2ND FLOOR DEMO POWER PLAN
ED103 ELECTRICAL 2ND FLOOR DEMO LIGHTING PLAN
ED104 ELECTRICAL 2ND FLOOR DEMO LIGHTING PLAN
E101 ELECTRICAL 2ND FLOOR POWER PLANS
E102 ELECTRICAL 2ND FLOOR POWER PLANS
E103 ELECTRICAL 2ND FLOOR LIGHTING PLANS
E104 ELECTRICAL 2ND FLOOR LIGHTING PLANS
PROJECT LOCATION
AT
FOR THE
PRICKETT BUILDING
THE DELAWARE DEPARTMENT OF HEALTH AND SOCIAL SERVICESDIVISION OF PUBLIC HEALTH - EMERGENCY MEDICAL SERVICES AND
PREPAREDNESS SECTION
STATE OF DELAWAREDEPARTMENT OF HEALTH AND SOCIAL SERVICES
CONTRACT # CSD20001-ARCH-ENG
DRAWING INDEX
Location Map Area Map Site Map
DIVISION OF PUBLIC HEALTH
DHSS STATE HEALTH OPERATIONS CENTER
SMYRNA, DE
N
TRUE
N
TRUE
N
TRUE
N
PLAN
PROJECT LOCATION
Mark Date Description
1 09.16.2020 ISSUED FOR AABREVIEW
2 10.23.2020 DFM 90% REVIEW
3 10.19.2021 ISSUED FOR BID
A101
1SIM
SF-1
1i
Name
101
1
A101
SIM
101
1
A101
SIM
0STRUCTURAL GRID LINES
SECTION ELEVATION
DETAILS IN PLAN, SECTION
WALL TYPE, SEE A001
ROOM NAME AND NUMBER
WINDOW TAG
DOOR TAG
EXISTING WALL TO REMAIN
EXISTING WALL TO BE REMOVED
NEW WALL
BRICK
CAST STONE
CONCRETE
CONCRETE MASONRY UNITS
SHINGLES
EARTH
PARTICLE BOARD
RIGID INSULATION
STEEL-LARGE SCALE
GLASS-LARGE SCALE
BATT INSULATION
STUD PARTITION
WOOD-FINISH
ACOUSTIC C.M.U. SMALL SCALE
ACOUSTIC C.M.U. LARGE SCALE
GLAZED C.M.U.
WOOD BLOCKING
SOLID CONCRETE MASONRY UNITS
ALL METALS-SMALL SCALE
1. CODES: ALL WORK ON THIS PROJECT SHALL BE DONE IN ACCORDANCE WITH ALL APPLICABLE BUILDING CODES, ORDINANCES, REGULATIONS, STANDARDS, AND ANY ADDITIONAL REQUIREMENT STATED IN ANY LAW, ORDINANCE, OR REGULATION PERTAINING TO CONSTRUCTION WITHIN THE LIMITS OF THE AUTHORITY HAVING JURISDICTION OVER THE PROPOSED WORK (INCLUDING BUT NOT LIMITED TO: FIRE, ACCESSIBILITY, ZONING, WATER, WASTEWATER, ENVIRONMENTAL, STRUCTURAL, ARCHITECTURAL, HEALTH, FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL, AND ENERGY CONSERVATION). CONFORMITY TO ALL CODES APPLICABLE TO THIS PROJECT SHALL BE THE CONTRACTORS RESPONSIBILITY.
2. EGRESS: ALL MEANS OF EGRESS SHALL BE CONTROLLED BY THE AUTHORITY HAVING JURISDICTION, INCLUDING EXITS, EXIT ACCESS, EXIT DISCHARGE, OTHER EGRESS PATHS, OCCUPANTS LOADS, SPRINKLER PROTECTION, ETC..
3. ACCESSIBILITY: ALL BUILDING COMPONENTS, FIXTURES, ACCESSORIES, ETC. SHALL BE INSTALLED WITH MANEUVERING AND OPERATING CLEARANCES, MOUNTING HEIGHTS, ETC. IN ACCORDANCE WITH AMERICANS WITH DISABILITIES ACT STANDARDS, ICC/ANSI A117.1, AND STATE ACCESSIBILITY CODE.
4. FIELD VERIFICATION: THE CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS AND PROPOSED BUILDING DIMENSIONS PRIOR TO CONSTRUCTION, ANY VARIATIONS, DISCREPANCIES, OR FIELD ALTERATIONS TO THESE DESIGN DRAWINGS SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION PRIOR TO CONSTRUCTION. IF CONTRACTOR COMMENCES CONSTRUCTION WITHOUT NOTIFYING ARCHITECT OF VARIATIONS, DISCREPENCIES, OR FIELD ALTERATIONS, THAT SHALL CONSTITUTE WAIVER TO ANY CLAIM BY CONTRACTOR FOR ADDITIONAL EXPENSES NECESSARY TO PERFORM WORK ASSOCIATED WITH THOSE CONDITIONS.
5. SUBMITTALS: CONTRACTOR SHALL SUBMIT ALL NECESSARY BUILDING COMPONENTS, SYSTEMS, EQUIPMENT, MATERIALS, FINISHES, ETC. FOR REVIEW BY ARCHITECT/OWNER PRIOR TO PROCUREMENT, FABRICATION, AND/OR INSTALLATION.
6. INSTALLATION: PROPER ASSEMBLY, INSTALLATION, AND OPERATION OF ALL MATERIALS, COMPONENTS, SYSTEMS, AND FINISHES IS THE CONTRACTOR'S RESPONSIBILITY AND SHALL BE IN ACCORDANCE WITH MANUFACTURES INSTRUCTIONS AND ALL APPLICABLE CODES.
7. INCIDENTAL WORK: ANY ITEMS NOT SPECIFICALLY SHOWN ON THE DRAWINGS, BUT WHICH ARE REASONABLY INCIDENTAL TO AND NECESSARY FOR THE SATISFACTORY COMPLETION OF THE PROJECT IN ACCORDANCE WITH APPLICABLE CODES, ORDINANCES, REGULATIONS, AND STANDARDS, ARE INCLUDED WITHIN THE INTENT OF THESE DESIGN DRAWINGS.
8. OWNER-PROVIDED WORK: LOCATION OF ALL OWNER-PROVIDED FIXTURES, EQUIPMENT, ETC. SHALL BE COORDINATED TO ENSURE PROPER ALIGNMENT FOR INSTALLATION AND OPERATION, BLOCKING, ETC.
9. SAFETY: COMPONENTS FOR CONSTRUCTION SAFETY ARE NOT INDICATED IN THESE DRAWINGS. THE CONTRACTOR IS RESPONSIBLE TO COMPLY WITH ALL RULES AND OTHER REQUIREMENTS OF THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA), AND APPLICABLE STATE AND LOCAL SAFETY REQUIREMENTS DURING ALL CONSTRUCTION ACTIVITIES.
10. INSPECTIONS: CONTRACTOR IS RESPONSIBLE FOR SCHEDULING ALL ON-SITE INSPECTIONS REQUIRED PRIOR TO OCCUPANCY APPROVAL.
11. DIMENSIONS: UNLESS OTHERWISE INDICATED: WALLS ARE TO FACE OF STUD FRAMING AND TO FACE OF MASONRY; WINDOWS AND DOORS ARE TO CENTERLINE OF OPENING IN STUD FRAMING AND TO FACE OF MASONRY OPENING IN MASONRY; PLUMBING FIXTURES ARE TO CENTERLINE OF FIXTURE.
12. BLOCKING: PROVIDE BLOCKING AS REQUIRED FOR INSTALLATION OF ALL PORTIONS OF THE WORK AND PER MANUFACTURER'S WRITTEN RECOMMENDATIONS, WHETHER OR NOT SPECIFICALLY INDICATED IN THESE DRAWINGS.
13. METAL PROTECTION AT TREATED WOOD: METAL CONNECTORS THAT COME IN CONTACT WITH TREATED LUMBER SHALL BE STAINLESS STEEL OR "ZMAX" CORROSION RESISTANT MATERIALS TO HELP PROTECT AGAINST ACCELERATED CORROSION. CONTRACTOR SHALL COORDINATE COMPATIBILITY OF ALL METALS USED WITH TREATMENT PRODUCT(S) MANUFACTURER(S)'S WRITTEN RECOMMENDATIONS.
14. HURRICANE TIES: CONTRCATOR SHALL PROVIDE HURRICANE TIES AND CONSTRUCTION CONNECTORS PER CODE AND AS REQUIRED BY AUTHORITY HAVING JURISDICTION.
15. WINDOWS AND DOORS: WINDOWS AND DOORS ARE INDICATED USING NOMINAL DIMENSIONS. MATERIALS AND INSTALLATION SHALL COMPLY WITH DESIGN PRESSURE (DP) RATINGS, WATER INFILTRATION RATING, IMPACT/SAFETY GLAZING, WIND REQUIREMENTS, EGRESS HARDWARE, U-FACTOR / R-VALUE, ETC.. ALL EXTERIOR UNITS SHALL HAVE CORROSION-RESISTANT HARDWARE.
16. LIFE SAFETY COMPONENTS: FINAL LOCATION OF FIRE EXTINGUISHERS, EMERGENCY LIGHTING, AND EXIT SIGNS TO BE AS DIRECTED BY LOCAL FIRE MARSHAL, AND ARE SUBJECT TO FINAL ON-SITE INSPECTION AND EVALUATION. CONTRACTOR SHALL MAKE REVISIONS AND/OR ADDITIONS IN ACCORDANCE WITH FIRE MARSHAL'S INSPECTION..
17. FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL WORK: ALL FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL WORK SHALL BE PERFROMED BY QUALIFIED, LICENSED (SUB)CONTRACTORS, AND BE IN ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, STANDARDS, ETC.. ALL COMPONENTS SHALL BE INSTALLED ABOVE THE FLOOD ELEVATION AS REQUIRED BY FEMA, LOCAL A.H.J., AND ALL APPLICABLE CODES
18. PIPE INSULATION: CONTRACTOR SHALL INSULATE AND PROTECT PIPES AS REQUIRED BY CODE, AND AS REQURIED TO PROTECT PIPING EXPOSED TO EXTERIOR CONDITIONS.
19. GRADING: CONTRACTOR SHALL COORDINATE SITE GRADING TO COMPLY WITH CODES AND ORDINANCES, AND TO MAINTAIN POSITIVE DRAINAGE AWAY FROM BUILDING.
FACING TILES.H. SHOWER HEADSHT. SHEETSIM. SIMILARS.M. SURFACE MOUNTEDS.P. STAND PIPES.S. SERVICE SINKS/S STAINLESS STEELSTL. STEELSTOR. STORAGESTRUCT. STRUCTURALSUSP. SUSPENDEDSYN.FL. SYNTHETIC FLOORTB, T.B. TACKBOARDTEL. TELEPHONET.& G. TONGUE AND GROOVETHRESH. THRESHOLDT.O.B. TOP OF BEARINGT.O.M. TOP OF MASONRY PARAPETT.P. TOILET PAPER HOLDERT.S. TACK STRIP,
LIFE SAFETY PLAN NOTES1. PROVIDE NEW FIRE EXTINGUISHERS IN CABINETS (FEC)
AND FIRE EXTINGUISHERS AS SHOWN ON FLOOR PLANS. 2. FIRE EXTINGUISHER SHALL BE MINIMUM 3A-40BC RATING.3. MARK ALL RATED WALLS AND PARTITIONS PER 2018 IBC
703.7 AND AS DETAILED.
MIN. EGRESS WIDTHREQ'D (INCHES)
MAX. OCC. ALLOWED
ACTUAL EGRESS WIDTHPROVIDED (INCHES)
ACTUALOCCUPANTS
EXIT CAPACITY
CLASSROOM
119ROOM NAME & NUMBER
786 SF39 OCC.
ROOM AREA
TRAVEL PATH #50' - 0"
EXIT ACCESS TRAVEL DISTANCE
OCCUPANCY LOAD(*AC* = ACCESSORY SPACE)
EXTERIOR WALL
FIRE WALL/PARTY WALL
FIRE BARRIER
FIRE PARTITION
SMOKE BARRIER
SMOKE PARTITION
NON-RATED PARTITION
TYPE OF WALL/PARTITION 1/2
ASSEMBLY RATING, IN HOURS)
0 1 2 3 4
RATED WALL/PARTITION LEGEND
PROPERTY LINE / IMAGINARY LOT LINE
AREA N.I.C.
TRAVEL PATH B
OFFICE
234C
OFFICE
234B
LARGEOFFICE
234
LARGECONF.ROOM
232
LARGEOPEN
OFFICE
230 RECEPTION/SECURITY
225
LARGEOFFICE
227
OFFICE
229
OFFICE
231
OFFICE
233
WOMENS
239
BREAKROOM
253
CONF.ROOM
253B
OFFICE
242C
OFFICE
242B
OFFICE
242A
OFFICE
240
LARGEOFFICE
249
OFFICE
251
ITCLOSET
247
EXGJAN
243
COPYROOM
236
OPENOFFICE
251A
WOMENS
278
MENS
285
BREAKROOM
271B
MENS
247
WOMENS
248 UNISEXTOILET
255
GYM
263
260
CORR.
ELEVATORLOBBY
260A
R 75' - 0"
R 75' - 0"
R 75' - 0"
FEC-1
FEC-1
FEC-1
148 SF2 OCC
28 SF1 OCC
BUSINESS SUITE5,851 SF59 OCC
122 SF2 OCC
125 SF2 OCC
143 SF2 OCC
237 SF3 OCC
268 SF3 OCC
TR
AV
EL P
AT
H A
CODE SUMMARY
1. NEW WORK DOES NOT ALTER EXISTING USE GROUP, CONSTRUCTION TYPE, BUILDING FIRE AREAS, OR OCCUPANCY CLASSIFICATION / COUNT.
2. ALL NEW WORK SHALL COMPLY WITH LEVEL 2 ALTERATIONS PER IEBC.
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
FINISH FLOOR (SEE FIN. SCHED.FOR FLOOR FIN. & WALL BASE)
WALL TYPES 2B
CE
ILIN
G H
EIG
HT
- S
EE
RE
FL
EC
TE
D C
EIL
ING
PLA
N
1. SEE CODE SHEET, G101, FOR REQUIRED FIRE RATINGS OF ALL WALL ASSEMBLIES. MULTIPLE LAYERS OF GWB MAY BE REQUIRED AT RATED PARTITIONS.
2. PROVIDE SOUND-ATTENUATING FIRE BATT INSULATION IN RATED STUD-FRAMED PARTITIONS AND FIBERGLASS SOUND BATT INSULATION IN NON-RATED STUD PARTITIONS.
3. PROVIDE MOLD AND MOISTURE RESISTANT GWB AT ALL STUD-FRAMED PARTITIONS IN WET LOCATIONS, INCLUDING TOILET ROOMS, AND AT SINKS AND LAVATORIES. EXTEND TO END OF CASEWORK RUN, INCLUDING SIDEWALLS WHERE ADJACENT TO SINKS.
4. BRACE NON-STRUCTURAL METAL STUD PARTITIONS WHERE NOT ATTACHED TO STRUCTURE ABOVE OR WHERE HEIGHT OF STRUCTURE EXCEEDS MANUFACTURER'S LIMITING HEIGHT FOR 5PSF @ 16" O.C., OR PROVIDE COLD-FORM FRAMING. SEE SPECIFICATIONS.
5. PROVIDE ACOUSTICAL SEALANT AT PARTITIONS IN THE FOLLOWING LOCATIONS: MECHANICAL ROOMS / MEZZANINES / PENTHOUSES / EQUIPMENT PLATFORMS, AND ELEVATOR MACHINE ROOM. SEE SPECIFICATIONS.
WALL TYPE GENERAL NOTES
WALL TYPE GENERAL NOTES
2B5/8" GWB ON ONE SIDE OF WALL ONLY UP TO UNDERSIDE OF DECK / STRUCTURESTUD
2 1/2" 5/8"
UNDERSIDE OF BEAMOR STRUCTURAL DECK
ACCOUSTIC SEALANT TYPICAL ORFIRE SEALANT AT FIRE RATEDWALL TYPES, TYP.
ATTACH GWB TO STUDS ASREQUIRED OR AS DIRECTEDBY ASSEMBLY INSTRUCTIONSWITH EXCEPTION: MAKE NO ATTACHMENTS CLOSER THEN1 1/2" FROM TOP OF WALL ENSURING NO FASTERNERSATTACH INTO THE TOP RUNNER
MTL STUDS TO BE CUT A MINIMUM OF 3/8" (MAX. 1/2")SHORTER THAN UNDERSIDEOF DECK - GWB TO BE CUTA MINIMUM OF 1/2" (MAX. 5/8")SHORTER THAN UNDERSIDEOF DECK
NOTE: DO NOT ATTACH STEELSTUDS TO TOP RUNNERS
METAL STUD TOP RUNNER
TYPICAL STUD WALL DETAILSCALE : 1 1/2" = 1'-0"
TYPICAL CHASE DETAILSSCALE : 1 1/2" = 1'-0"
CONTINUE CHASE TO 8" ABOVE CEILING
PIPE(S), ETC. - SEE MECH.
A. TYPICAL CHASE IN CORNER B. TYPICAL FREE STANDING CHASE
NOTE: COORDINATE CHASE SIZES WITH MECHANICAL/PLUMBING & STRUCTURAL REQUIREMENTSAND WITH DIMENSIONS INDICATED ON FLOOR PLANS. ALIGN CHASE WITH ADJACENT WALLSAS INDICATED ON PLANS.
2B
2B
TYPICAL RATED PARTITION DETAILSN.T.S.
TYPICAL SIGNAGE DETAILS
5 6
7 8 SCALE: 1-1/2" = 1'-0"
NOTE:TYPICAL HORIZONTAL TRANSITIONS WHERE CMU BLOCK AND GYPSUM DRYWALL ALIGN
JOINT COMPOUND
5/8" GWB REVEAL
PROVIDE SMALL BEAD OF PAINTERSCAULK AT TRIM/BLOCK INTERFACE
GPDW
CMU
METAL
STUD
TYPICAL REVEAL DETAILSCALE : N.T.S.1
1-HR FIRE BARRIER - PROTECT ALL OPENINGS
30' - 0" O.C. MAX. HORIZONTALLY
1" H RED LETTERING, STENCILOR PERMANENTLY AFFIXED SIGNS
C. MARKING OF RATED PARTITIONS AND WALLS AT FINISH CEILING
12"
TY
P.
1" H RED LETTERING, STENCIL OR PERMANENTLY AFFIXED SIGNS
BOTTOM OF STRUCTURE
B. MARKING OF RATED PARTITIONS AND WALLS AT EXPOSED STRUCTURE
FINISH CEILING SEE FINISHSCHEDULE AND RCP
NOTES: 1. MARK BOTH SIDES OF RATED WALLS AND PARTITIONS.2. WHERE WALL OR PARTITION CHANGES DIRECTION, MARK EACH SEGMENT INDIVIDUALLY.3. LOCATE MARKINGS SO AS TO NOT BE OBSTRUCTED BY WIRES, CONDUIT, PIPES, EQUIPMENT, ETC..4. LETTERING SHALL READ AS FOLLOWS:
A. SMOKE PARTITION: " SMOKE PARTITION - PROTECT ALL OPENINGS "B. 1-HR FIRE BARRIER: " 1-HR FIRE BARRIER - PROTECT ALL OPENINGS "C. 2-HR FIRE WALL: " 2-HR FIRE WALL - PROTECT ALL OPENINGS "
1-HR FIRE BARRIER - PROTECT ALL OPENINGS
1-HR FIRE BARRIER - PROTECT ALL OPENINGS
30' - 0" O.C. MAX. HORIZONTALLY
1-HR FIRE BARRIER - PROTECT ALL OPENINGS
12"
TY
P.
NON-RATEDPARTITION
FIRE RATED PARTITION
INSULATION, TYP., SEE WALL TYPE AND SPECIFICATION
A. TYPICAL FIRE RATED PARTITION INTERSECTION DETAILS
NOTE: SEE PLANS AND WALL TYPESFOR PARTITIONS TYPES AND CONFIGURATION, AND SURROUNDING ELEMENTS.
18-GAUGE HANGER WIRE ATTACHED TO CEILING GRID AND DECK ABOVE
18-GUAGE HANGER WIRE
SUSPENDED CEILING GRID -SEE CEILING PLAN FOR GRID LAYOUT
2 X 2 ACT, TYP.
SUSPENSION WALL ANGLE
SUSPENSION TEE
CEILING TYPE 1 N.T.S.
CEILING TYPE 2 2 3 CEILING TYPE 3
SCALE: 1 1/2" = 1' 0"4
EXG CONSTRUCTION
18-GAUGE HANGER WIRE ATTACHED TO CEILING GRID AND DECK ABOVE
18-GUAGE HANGER WIRE
SUSPENDED CEILING GRID -SEE CEILING PLAN FOR GRID LAYOUT
2 X 2 ACT, TYP.
6" ONE PIECE AXIOM TRIM
SUSPENSION TEE
AXTBC
5 7
/8"
SCALE: 1 1/2" = 1' 0"
UNDERSIDE OF BEAMOR STRUCTURAL DECK
FINISH FLOOR (SEE FIN. SCHED.FOR FLOOR FIN. & WALL BASE)
WALL TYPES
2C
5/8" GWB ON 3/4" METAL HAT CHANNEL FURRING ON ONE SIDE OF EXG MASONRY TO CONTINUE TO UNDERSIDE OF DECK / STRUCTURE
2C
CE
ILIN
G H
EIG
HT
- S
EE
RE
FL
EC
TE
D C
EIL
ING
PLA
N
F.V.
VARIES
5/8" GWB ON ONE SIDE OF EXG MASONRY TO CONTINUE
TO UNDERSIDE OF DECK / STRUCTURE
F.V.
VARIES
2D
3/4"5/8"
2D
5/8"
F.V.
VARIES
5/8"
STUD
2 1/2"
STUD
2 1/2" 5/8"
A. TYPICAL ROOM SIGN B. TYPICAL TOILET ROOM SIGN D. ROOM NUMBER SIGN
MIN. 1 1/4" H TACTILE TEXT
GRADE 2 BRAILLE, TYP.
MIN. 5/8" H TACTILE TEXT
3/4" RADIUS - TYPICAL
MIN. 1 1/4" H TACTILE TEXT
(USED ONLY WHERE INDICATED AND AS DIRECTED DURING SHOP DRAWING REVIEW )
TRAINING
TOILET
FO
R R
OO
M T
EX
T
8"
INC
RE
AS
E A
S R
EQ
'D
FO
R R
OO
M T
EX
T
6"
INC
RE
AS
E A
S R
EQ
'D
6" MIN.
3"
MIN
.
6" MIN.
MIN
. 6
" P
ICT
OG
RA
M F
IEL
D
6" MIN.
108
3/4" RADIUS, TYP.
PICTOGRAM TO MATCH ROOM SERVED - SEE SIGNAGE NOTE 14.
MIN. 5/8" CAP. H TACTILE TEXT
GRADE 2 BRAILLE
108
C. EXIT SIGN
3 1
/2"
6"
EXITMIN. 1 1/2" H TACTILE TEXT
1/2
"3
/8"
1' - 1"
9"
B. DIRECTIONAL EXIT SIGNP
ICT
OG
RA
M F
IEL
D
6"
PICTOGRAM RAISED 1/32"
GRAPHIC PLAN
NORTHEAST STAIR FLOOR
31ST TO 3RD FLOOR NO ROOF ACCESS
DOWN TO 1ST FLOORFOR EXIT DISCHARGE
60
" A
FF
MIN
.1
8"
MIN
.
84
" A
FF
MA
X.
1" HIGH TEXT
5" HIGH TEXT MIN.
1" HIGH TEXT
SIGNAGE NOTES:1. PROVIDE SIGN AT EACH FLOOR LANDING IN INTERIOR EXIT STAIRWAYS AND RAMPS CONNECTING 3 OR MORE STORIES.2. SIGN SHALL BE VISIBLE IF DOOR IS OPEN OR CLOSED.3. BASEMENT AND MEZZANINE LEVELS SHALL BE NUMBERED WITH PRECEDING "B" AND "M" (E.G., B1 AND M1).4. STAIR WITH ROOF ACCESS SHALL OMIT "NO ROOF ACCESS".5. SIGN SHALL COMPLY WITH NFPA 101 FIGURE A.7.2.2.5.4 AND IBC 1023.9.6. PROVIDE WALL-MOUNTED TACTILE SIGN CONTAINING SAME INFORMATION MOUNTED AT THE DOOR FROM THE STAIRWAY/RAMP INTO THE CORRIDOR. 7. SIGNAGE SHALL COMPLY WITH 2010 ADA STANDARDS, ICC/ANSI A117.1-2017, IBC, AND NFPA 101. 8. COORDINATE SIGN MESSAGES WITH APPROVED ROOM NAMES AND NUMBERS. 9. TEXT COLOR SHALL CONTRAST WITH BACKGROUND COLOR. BRAILLE COLOR SHALL MATCH BACKGROUND COLOR.10. REFER TO ELECTRICAL FOR ILLUMINATED AREA OF REFUGE AND EXTERIOR AREA FOR RESCUE ASSISTANCE SIGNS. 11. PROVIDE INSTRUCTION SIGN AT AREAS OF REFUGE FOR USE OF THE AREA UNDER EMERGENCY CONDITIONS. 12. WHERE LUMINOUS EGRESS PATH MARKINGS ARE REQUIRED, SPECIAL EXIT SIGNS AND STAIR LANDING SIGNS SHALL BE OF SAME LUMINOUS MATERIALS.13. TACTILE TEXT SHALL BE RAISED 1/32".14. WHERE TOILET ROOM DOES NOT INCLUDE COMPLIANT FACILITIES ADDITIONAL PLAQUE SHALL DIRECT OCCUPANTS TO THE NEAREST COMPLIANT FACILITY.
FIN. FLOOR
C. STAIR LANDING SIGN
PROVIDE SIGN AT EACH DOOR LEADING INTO AN AREA OF REFUGE, EXIT STAIRWAY, EXTERIOR AREA FOR RESCUE ASSISTANCE, EXIT PASSAGEWAY, AND EXIT DISCHARGE.
BACKGROUND COLOR 1
BACKGROUND COLOR 2
BACKGROUND COLOR 2
BACKGROUND COLOR 1
A. SPECIAL EXIT SIGNS
AREA OF REFUGE
9"
INC
RE
AS
E A
S R
EQ
'D F
OR
TE
XT
PIC
TO
GR
AM
FIE
LD
MIN
. 6
"
6" MIN. 3/4" RADIUS, TYP.
WHITE PICTOGRAM ON 1/8" THICK BACKGROUND,FIELD MIN. 6" HIGH, AS SHOWN
MIN. 5/8" CAP. HEIGHT TACTILETEXT, RAISED 1/32", WHITE -FULL CAPS
GRADE 2 BRAILLE
BACKGROUND COLOR 2
BACKGROUND COLOR 1
PROVIDE SIGNS FOR "AREA OF REFUGE" AND "EXTERIOR AREA FOR ASSISTED RESCUE".
PROVIDE DIRECTIONAL EXIT SIGN AT ELEVATOR LANDINGS, WITHIN AREAS OF REFUGE, AND AT EXITS SERVING ACCESSIBLE SPACES BUT NOT PROVDING APPROVED ACCESSIBLE MEANS OF EGRESS.
12" MIN.
A. TYPICAL SINGLE LEAF DOOR
18'' x 18'' CLR AREA, TYP.
C. RECESSED SINGLE LEAF DOOR
18'' x 18'' CLR AREA, TYP.
B. TYPICAL PAIR DOOR
D. RECESSED PAIR DOOR
18'' x 18'' CLR AREA, TYP.
E. PAIR DOOR WITH INOPERABLE LEAF
18'' x 18'' CLR AREA, TYP.
OPERABLE LEAF
FIXED LEAF
18'' x 18'' CLR AREA, TYP.
SIGN, TYP.
SIGN, TYP.
SIGN, TYP. SIGN, TYP.
SIGN, TYP.
F. TYPICAL SIGN ELEVATIONS
WHERE SIGN IS MOUNTED ON GLASS, PROVIDE "BLANK" OF SAME SIZE AND FINISH OF SIGN ON OPPOSITE SIDE OF GLASS. ALIGN "BLANK" WITH SIGN TO CONCEAL ALL MOUNTING ADHESIVES AND BACK OF SIGN FROM VIEW.
HINGE SIDE OF DOOR
STRIKE SIDE OF DOOR
ROOM SIGN, TYP.8" MIN.
4' -
0"
MIN
.
5' -
0"
MA
X.
BOT OF HIGHEST TACTILE CHARACTER
BOT OF LOWEST TACTILE CHARACTER
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
REMOVED EXISTING INTERIOR PARTITION IN ITS ENTIRETY. PARTITIONS DENOTED WITH THIS SOLID HATCH SHALL BE REMOVED BY THE ABATEMENT CONTRACTOR VIA SEPARATE CONTRACT. GENERAL CONTRACTOR TO COORDINATE WITH ABATEMENT CONTRACTOR.
CUT AND REMOVE PORTION OF EXISTING INTERIOR PARTITION TO ACCOMMODATE NEW OPENING.PARTITIONS DENOTED WITH THIS SOLID HATCH SHALL BE REMOVED BY THE ABATEMENT CONTRACTOR VIA SEPARATE CONTRACT. GENERAL CONTRACTOR TO COORDINATE WITH ABATEMENT CONTRACTOR.
REMOVE EXISTING WALL FINISH AND SUBSTRATE DOWN TO FACE OF STUD OR MASONRY.
REMOVAL OF EXISTING FLOOR FINISH TO SLAB IN THESE AREAS, INCLUDING BUT NOT LIMITED TO WALL BASE, PADDING, MASTIC, GROUT, ETC. SHALL BE PERFORMED BY THE ABATEMENT CONTRACTOR VIA SEPARATE CONTRACT. GENERAL CONTRACTOR TO COORDINATE WITH ABATEMENT CONTRACTOR.
DEMOLITION KEY NOTES X
1
2
3
4
REMOVE EXISTING FLOOR FINISH TO SLAB, INCLUDING BUT NOT LIMITED TO WALL BASE, PADDING, MASTIC, GROUT, ETC.
5
REMOVE EXISTING WALL TILE AND PREPARE SUBSTRATE TO RECEIVE NEW FINISH.6
REMOVE EXISTING DOOR/INTERIOR VISION PANEL, FRAME, AND ASSOCIATED HARDWARE.7
REMOVE EXISTING PLUMBING FIXTURE AND PIPING AS REQUIRED TO ACCOMMODATE NEW WORK. CAP AND ABANDON LINES BELOW SLAB OR IN WALL. COORDINATE WITH PLUMBING DRAWINGS.
8
REMOVE EXISTING TOILET PARTITIONS AND ALL ASSOCIATED COMPONENTS.9
REMOVE/MODIFY EXISTING RECESSED MECHANICAL UNIT. COORDINATE WITH MECHANICAL DRAWINGS. PROVIDE BATT INSULATION AS REQUIRED. PATCH AND FINISH TO MATCH AND ALIGN WITH ADJACENT WALL SURFACE
10
REMOVE EXISTING CASEWORK AND COUNTERTOP IN ITS ENTIRETY.11
REMOVE CEILING GRIDS, TILES, HANGERS, HARDWARE, LIGHTS,G.R.D.'S, AND ACCESSORIES.
12
GENERAL DEMOLITION NOTES1. FIELD VERIFY ALL EXISTING CONDITIONS.2. COORDINATE EXTENT OF REQUIRED DEMOLITION WITH NEW WORK, OWNER, AND OTHER TRADES.3. ALL KNOWN HAZARDOUS MATERIALS SHALL BE REMOVED BY THE OWNER VIA SEPARATE
CONTRACT PRIOR TO COMMENCEMENT OF DEMOLITION ACTIVITY. SEE SPECIFICATION PROCEDURE FOR HAZARDOUS MATERIALS ENCOUNTERED DURING DEMOLITION.
4. IN ALL AREAS OF CONSTRUCTION, REMOVE ALL EXISTING WALL MOUNTED ITEMS INCLUDING BUT NOT LIMITED TO TACKBOARDS, PHOTOGRAPHS, FRAMED ITEMS, SIGNAGE, SAFETY EQUIPMENT, TOILET ACCESSORIES AND ALL ASSOCIATED HANGERS AND SUPPORTS. TURN OVER TO OWNER OR CAREFULLY STORE FOR REUSE/REINSTALLATION AS DIRECTED BY OWNER.
5. IN ALL AREAS OF CONSTRUCTION, REMOVE ALL EXISTING. EQUIPMENT AS REQUIRED FOR DEMOLITION; STORE AND PROTECT FOR REINSTALLATION AS DIRECTED BY OWNER.
6. EXISTING WORK OR EQUIPMENT TO REMAIN SHALL BE PROTECTED FROM DEMOLITION OPERATIONS.
7. CONTRACTOR TO PROVIDE TEMPORARY BRACING AND SHORING AS REQUIRED TO ACCOMPLISH DEMOLITION ACTIVITIES AND TO MAINTAIN STRUCTURAL STABILITY UNTIL NEW WORK IS INSTALLED.
8. AT AREAS OF FIRST FLOOR BELOW AREA OF WORK - REMOVE EXISTING ACOUSTIC CEILING TILES AS REQUIRED TO ACCOMMODATE NEW WORK; STORE AND PROTECT FOR REINSTALLATION.
9. CUT AND REMOVE PORTIONS OF EXISTING GWB BULKHEADS AS REQUIRED TO ACCOMMODATE NEW WORK. PATCH AND PAINT TO MATCH ADJACENT.
10. CONTRACTOR SHALL DOCUMENT ALL EXISTING CONDITIONS PRIOR TO BEGINNING OF DEMOLITION TO ASSIST AND ENSURE REINSTALLATION IS CONSISTENT WITH AND MATCHING EXISTING CONDITIONS.
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
SCALE: 1/4" = 1'-0"1DEMOLITION PLAN - OFFICEAREA A
SCALE: 1/4" = 1'-0"2DEMOLITION PLAN - OFFICEAREA B
SCALE: 1/4" = 1'-0"
0' 2' 4' 8'
PLA
N
NO
RT
H
N
Mark Date Description
1 09.16.2020 ISSUED FOR AABREVIEW
2 10.23.2020 DFM 90% REVIEW
3 10.19.2021 ISSUED FOR BID
EXG. EQUIPMENT TO REMAIN (SEE ELEC.)
263
GYM
12
EXG. SHELVING TO BE REMOVED BY OWNER PRIOR TO START OF WORK
8
8
5
6
255
UNISEXTOILET
12
9
5
6
5
68
8
8
8
9
9
98
8
8
8
247
MENS
248
WOMENS 11
271B
BREAKROOM
12
278
TOILETROOM
5
6
9
8
8
8
1
7
12
286
WOMENS285
MENS5
6
5
61
11
88
8
8
7
7
12
12
REMOVED EXISTING INTERIOR PARTITION IN ITS ENTIRETY. PARTITIONS DENOTED WITH THIS SOLID HATCH SHALL BE REMOVED BY THE ABATEMENT CONTRACTOR VIA SEPARATE CONTRACT. GENERAL CONTRACTOR TO COORDINATE WITH ABATEMENT CONTRACTOR.
CUT AND REMOVE PORTION OF EXISTING INTERIOR PARTITION TO ACCOMMODATE NEW OPENING.PARTITIONS DENOTED WITH THIS SOLID HATCH SHALL BE REMOVED BY THE ABATEMENT CONTRACTOR VIA SEPARATE CONTRACT. GENERAL CONTRACTOR TO COORDINATE WITH ABATEMENT CONTRACTOR.
REMOVE EXISTING WALL FINISH AND SUBSTRATE DOWN TO FACE OF STUD OR MASONRY.
REMOVAL OF EXISTING FLOOR FINISH TO SLAB IN THESE AREAS, INCLUDING BUT NOT LIMITED TO WALL BASE, PADDING, MASTIC, GROUT, ETC. SHALL BE PERFORMED BY THE ABATEMENT CONTRACTOR VIA SEPARATE CONTRACT. GENERAL CONTRACTOR TO COORDINATE WITH ABATEMENT CONTRACTOR.
DEMOLITION KEY NOTES X
1
2
3
4
REMOVE EXISTING FLOOR FINISH TO SLAB, INCLUDING BUT NOT LIMITED TO WALL BASE, PADDING, MASTIC, GROUT, ETC.
5
REMOVE EXISTING WALL TILE AND PREPARE SUBSTRATE TO RECEIVE NEW FINISH.6
REMOVE EXISTING DOOR/INTERIOR VISION PANEL, FRAME, AND ASSOCIATED HARDWARE.7
REMOVE EXISTING PLUMBING FIXTURE AND PIPING AS REQUIRED TO ACCOMMODATE NEW WORK. CAP AND ABANDON LINES BELOW SLAB OR IN WALL. COORDINATE WITH PLUMBING DRAWINGS.
8
REMOVE EXISTING TOILET PARTITIONS AND ALL ASSOCIATED COMPONENTS.9
REMOVE/MODIFY EXISTING RECESSED MECHANICAL UNIT. COORDINATE WITH MECHANICAL DRAWINGS. PROVIDE BATT INSULATION AS REQUIRED. PATCH AND FINISH TO MATCH AND ALIGN WITH ADJACENT WALL SURFACE
10
REMOVE EXISTING CASEWORK AND COUNTERTOP IN ITS ENTIRETY.11
REMOVE CEILING GRIDS, TILES, HANGERS, HARDWARE, LIGHTS,G.R.D.'S, AND ACCESSORIES.
12
GENERAL DEMOLITION NOTES1. FIELD VERIFY ALL EXISTING CONDITIONS.2. COORDINATE EXTENT OF REQUIRED DEMOLITION WITH NEW WORK, OWNER, AND OTHER TRADES.3. ALL KNOWN HAZARDOUS MATERIALS SHALL BE REMOVED BY THE OWNER VIA SEPARATE
CONTRACT PRIOR TO COMMENCEMENT OF DEMOLITION ACTIVITY. SEE SPECIFICATION PROCEDURE FOR HAZARDOUS MATERIALS ENCOUNTERED DURING DEMOLITION.
4. IN ALL AREAS OF CONSTRUCTION, REMOVE ALL EXISTING WALL MOUNTED ITEMS INCLUDING BUT NOT LIMITED TO TACKBOARDS, PHOTOGRAPHS, FRAMED ITEMS, SIGNAGE, SAFETY EQUIPMENT, TOILET ACCESSORIES AND ALL ASSOCIATED HANGERS AND SUPPORTS. TURN OVER TO OWNER OR CAREFULLY STORE FOR REUSE/REINSTALLATION AS DIRECTED BY OWNER.
5. IN ALL AREAS OF CONSTRUCTION, REMOVE ALL EXISTING. EQUIPMENT AS REQUIRED FOR DEMOLITION; STORE AND PROTECT FOR REINSTALLATION AS DIRECTED BY OWNER.
6. EXISTING WORK OR EQUIPMENT TO REMAIN SHALL BE PROTECTED FROM DEMOLITION OPERATIONS.
7. CONTRACTOR TO PROVIDE TEMPORARY BRACING AND SHORING AS REQUIRED TO ACCOMPLISH DEMOLITION ACTIVITIES AND TO MAINTAIN STRUCTURAL STABILITY UNTIL NEW WORK IS INSTALLED.
8. AT AREAS OF FIRST FLOOR BELOW AREA OF WORK - REMOVE EXISTING ACOUSTIC CEILING TILES AS REQUIRED TO ACCOMMODATE NEW WORK; STORE AND PROTECT FOR REINSTALLATION.
9. CUT AND REMOVE PORTIONS OF EXISTING GWB BULKHEADS AS REQUIRED TO ACCOMMODATE NEW WORK. PATCH AND PAINT TO MATCH ADJACENT.
10. CONTRACTOR SHALL DOCUMENT ALL EXISTING CONDITIONS PRIOR TO BEGINNING OF DEMOLITION TO ASSIST AND ENSURE REINSTALLATION IS CONSISTENT WITH AND MATCHING EXISTING CONDITIONS.
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
KEY ACCESSORY DESCRIPTION BASIS OF DESIGN MANUFACTURERBASIS OF DESIGN MFR'S
PRODUCT NO.
A SOAP DISPENSER Bobrick Washroom Equipment, Inc. B-2112
B1 42" GRAB BAR Bobrick Washroom Equipment, Inc. B-6806.99x42
B2 36" GRAB BAR Bobrick Washroom Equipment, Inc. B-6806.99x36
B3 18" VERTICAL GRAB BAR Bobrick Washroom Equipment, Inc. B-6806.99x18
C TOILET PAPER DISPENSER Bobrick Washroom Equipment, Inc. B-2888
D SANITARY NAPKIN DISPOSAL Bobrick Washroom Equipment, Inc. B-270
E UNDER-LAV SHIELD TRUEBRO Model #20181
F1 FRAMED MIRROR 18" x 36" Bobrick Washroom Equipment, Inc. B-165 Series
F2 FRAMELESS MIRROR Bobrick Washroom Equipment, Inc. B-165 Series
G PAPER TOWEL DISPENSER AND WASTE RECEPTACLE Bobrick Washroom Equipment, Inc. B-3699 ClassicSeries
H ROBE HOOK Bobrick Washroom Equipment, Inc. B-672
K SHOWER CURTAIN AND HOOKS Bobrick Washroom Equipment, Inc. B-204-3
L SHOWER CURTAIN ROD Bobrick Washroom Equipment, Inc. B-6047x60
M SOAP DISH American Specialties, Inc. 7410-S
SCALE: 1/4" = 1'-0"1 FLOOR PLAN - WOMENS 239SCALE: 1/4" = 1'-0"2 FLOOR PLAN - WOMENS 278
PLA
N
NO
RT
H
N
SCALE: 1/4" = 1'-0"
0' 2' 4' 8'
Mark Date Description
1 09.16.2020 ISSUED FOR AABREVIEW
2 10.23.2020 DFM 90% REVIEW
3 10.19.2021 ISSUED FOR BID
CEILING LEGEND
NEW 2x2 ACT CEILING
INTERIOR - GWB CEILINGS /BULKHEADS
X EXPOSED
EXG PLASTER - PATCH AND PAINT AS NEEDED
EXISTING 2x2 ACT CEILING TO REMAIN
1. SEE FINISH SCHEDULE FOR ACT TYPES.
2. SEE MECHANICAL DRAWINGS FOR G.R.D. TYPES, LOCATIONS, AND ADDITIONAL WORK.
3. SEE ELECTRICAL DRAWINGS FOR LIGHT FIXTURE TYPES AND LOCATIONS
4. CEILING HEIGHTS INDICATED ARE FROM FINISH FLOOR. CEILINGS AT LANDINGS, RAMPS ETC., REFER TO NEAREST FLOOR LEVEL. COORDINATE WITH EXG. WINDOW MULLION LOCATIONS.
5. ALL EXPOSED LINTELS SHALL BE PAINTED.
CEILING NOTES
2X2 RECESSED LIGHT (SEE ELEC.)
2X4 RECESSED LIGHT (SEE ELEC.)
RECESSED DOWN LIGHT (SEE ELEC.)
SUSPENDED OR SURFACE MOUNTED LINEAR PENDANT (SEE ELEC.)
LED EXIT SIGN (SEE ELEC.)
SUPPLY DIFFUSER(SEE MECH.)
RETURN GRILLE(SEE MECH.)
CASSETTE UNIT(SEE MECH.)
EXHAUST(SEE MECH.)
OPENOFFICE
251A
OFFICE
240
OFFICE
242A
OFFICE
242B
OFFICE
242C CONF. ROOM
253B
BREAKROOM
253
EXG JAN
243
LARGEOFFICE
249 IT CLOSET
247
OFFICE
251
OFFICE
234B
LARGEOFFICE
234
CORRIDOR
260
8' - 9"
7' - 10" 7' - 10" 7' - 10"
7' - 10"
8' - 9"
7' - 10"
7' - 10"
7' - 10"
7' - 10"
7' - 10"
7' - 10"
7' - 10"
7' - 10"
A104
1
CLOSET
241
OFFICE
233
WOMENS
239
OFFICE
234C
7' - 10"
COPY ROOM
236
7' - 10"
7' - 10"
MATCHLINE - SEE 1 / A103
7
A401
LARGE OPENOFFICE
230
LARGECONF. ROOM
232
OFFICE
231
OFFICE
229
LARGEOFFICE
227
RECEPTION/SECURITY
225
CORRIDOR
260
ELEVATORLOBBY
260A
7' - 10"
7' - 10"
8' - 9"
7' - 10"
7' - 10"
7' - 10"
7' - 10"
CLOSET
230A
7' - 10"
N.I.C.
MATCHLINE - SEE 2 / A103
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
SCALE: 1/4" = 1'-0"2REFLECTED CEILING PLAN -OFFICE AREA B
SCALE: 1/4" = 1'-0"1REFLECTED CEILING PLAN -OFFICE AREA A
SCALE: 1/4" = 1'-0"
0' 2' 4' 8'
PLA
N
NO
RT
H
N
Mark Date Description
1 09.16.2020 ISSUED FOR AABREVIEW
2 10.23.2020 DFM 90% REVIEW
3 10.19.2021 ISSUED FOR BID
GYM
263
7' - 10"
MENS
247
WOMENS
248
7' - 10"
7' - 10"
MENS
285
7' - 10"
WOMENS
239
7' - 10"
UNISEXTOILET
255
7' - 10"
CEILING LEGEND
NEW 2x2 ACT CEILING
INTERIOR - GWB CEILINGS /BULKHEADS
X EXPOSED
EXG PLASTER - PATCH AND PAINT AS NEEDED
EXISTING 2x2 ACT CEILING TO REMAIN
1. SEE FINISH SCHEDULE FOR ACT TYPES.
2. SEE MECHANICAL DRAWINGS FOR G.R.D. TYPES, LOCATIONS, AND ADDITIONAL WORK.
3. SEE ELECTRICAL DRAWINGS FOR LIGHT FIXTURE TYPES AND LOCATIONS
4. CEILING HEIGHTS INDICATED ARE FROM FINISH FLOOR. CEILINGS AT LANDINGS, RAMPS ETC., REFER TO NEAREST FLOOR LEVEL. COORDINATE WITH EXG. WINDOW MULLION LOCATIONS.
5. ALL EXPOSED LINTELS SHALL BE PAINTED.
CEILING NOTES
2X2 RECESSED LIGHT (SEE ELEC.)
2X4 RECESSED LIGHT (SEE ELEC.)
RECESSED DOWN LIGHT (SEE ELEC.)
SUSPENDED OR SURFACE MOUNTED LINEAR PENDANT (SEE ELEC.)
LED EXIT SIGN (SEE ELEC.)
SUPPLY DIFFUSER(SEE MECH.)
RETURN GRILLE(SEE MECH.)
CASSETTE UNIT(SEE MECH.)
EXHAUST(SEE MECH.)
7' - 3"
WOMENS
278
7' - 10"
BREAKROOM
271B
7' - 10"
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
REFLECTED CEILINGPLANS - TOILETROOMS, BREAKROOM, AND GYM
BVVJMK
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATEHEALTHOPERATIONSCENTER
SCALE: 1/4" = 1'-0"6REFLECTED CEILING PLAN -GYM 263
SCALE: 1/4" = 1'-0"4REFLECTED CEILING PLAN -MENS 247 AND WOMENS 248
SCALE: 1/4" = 1'-0"3REFLECTED CEILING PLAN -MENS 285
SCALE: 1/4" = 1'-0"1REFLECTED CEILING PLAN -WOMENS 239
SCALE: 1/4" = 1'-0"5REFLECTED CEILING PLAN -UNISEX TOILET 255
SCALE: 1/4" = 1'-0"2REFLECTED CEILING PLAN -WOMENS 278
PLA
N
NO
RT
H
N
SCALE: 1/4" = 1'-0"
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"7REFLECTED CEILING PLAN -BREAK ROOM 271B
NOTE: SEE MECHANICAL DRAWINGS FOR RELOCATION OF EXISTING DIFFUSERS TO REMAIN.
NOTE: SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION ON EXISTING EXHAUST TO REMAIN.
NOTE: SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION ON EXISTING EXHAUST TO REMAIN.
Mark Date Description
1 09.16.2020 ISSUED FOR AABREVIEW
2 10.23.2020 DFM 90% REVIEW
3 10.19.2021 ISSUED FOR BID
CPT-1
RB-1
ACT-1
PT-1
LARGE
CONF.ROOM
232
CPT-1
RB-1
ACT-1
PT-1
RECEPTION/
SECURITY
225
CPT-1
RB-1
ACT-1
PT-1
LARGE
OFFICE
227
CPT-1
RB-1
ACT-1
PT-1
OFFICE
229
CPT-1
RB-1
ACT-1
PT-1
OFFICE
231
CPT-1
RB-1
ACT-1
PT-1
LARGE
OPENOFFICE
230
ELEVATORLOBBY
260A
CPT-1
RB-1
ACT-1
VWC-1/VWC-2
CORRIDOR
260
CPT-1
RB-1
PT-1
PT-1
CLOSET
230A
MATCHLINE - SEE 1 / A101
EX
GC
PT
EX
GC
PT
CPT-1
RB-1
ACT-1
PT-1
OFFICE
240
CPT-1
RB-1
ACT-1
PT-1
OFFICE
242A
CPT-1
RB-1
ACT-1
PT-1
OFFICE
242B
CPT-1
RB-1
ACT-1
PT-1
OFFICE
242C
CPT-1
RB-1
ACT-1
PT-1
OFFICE
251
CPT-1
RB-1
ACT-1
PT-1
LARGE
OFFICE
249
CPT-1
RB-1
ACT-1
PT-1
CONF.
ROOM
253B
VCT-1
RB-2
ACT-1 PT-1
PT-1
BREAK
ROOM
253
CPT-1
RB-1
ACT-1
PT-1
LARGE
OFFICE
234
CPT-1
RB-1
ACT-1
PT-1
OFFICE
234B
VCT-1
RB-2
PT-1
PT-1
EXG
JAN
243
CPT-1
RB-1
ACT-1
PT-1
OPEN
OFFICE
251A
CPT-1
RB-1
ACT-1
VWC-1/VWC-2
CORRIDOR
260
CPT-1
RB-1
PT-1
PT-1
COPY
ROOM
236
CPT-1
RB-1
ACT-1
PT-1
OFFICE
233
CT-1
CT-2
ACT-1
CT-2, CT-3, PT-1
WOMENS
239
CPT-1
RB-1
ACT-1
PT-1
OFFICE
234C
MATCHLINE - SEE 1 / A101
VCT-1
RB-2
PT-1
PT-1
IT
CLOSET
247
CPT-1
RB-1
PT-1
PT-1
CLOSET
241
A401
5
CTCPT
VCTCPT
VC
TC
PT
VC
TC
PT
STAIR
EXG.
EXGCPT
CP
TE
XG
FRAME OPENING WITH WOOD TRIM AND TERMINATE VWC
A106
1
FINISH PLAN LEGEND
FINISH PLAN NOTES
1. WALLS AND CEILINGS MAY CONTAIN MORE THAN ONE MATERIAL OR FINISH AS INDICATED. COORDINATE WITH CONSTRUCTION TYPE AND FINISH SIMILAR TO ADJACENT MATERIALS, U.N.O.
2. REFER TO ELEVATIONS, REFLECTED CEILING PLANS AND DETAILS FOR ADDITIONAL INFORMATION REGARDING HEIGHTS, BULKHEADS/SOFFITS, FINISHES, PATTERNS, ORIENTATIONS AND TRANSITIONS.
3. PLAN WALL TYPES TAKE PRECEDENCE OVER SCHEDULED WALL FINISH. PROVIDE APPROPRIATE WALL FINISH TO CORRESPOND TO WALL TYPES.
4. MOLD AND MOISTURE RESISTANT GYPSUM BOARD SHALL BE USED AT ALL KITCHEN AREAS, TOILET ROOMS, AND CUSTODIAN SERVICE CLOSETS SCHEDULED TO HAVE GYPSUM BOARD FINISHES.
5. PROVIDE SEALANT/CAULK AT INTERSECTIONS OF DISSIMILAR MATERIALS AND AS RECOMMENDED BY MANUFACTURERS' GUIDELINES.
6. WALL AND CEILING FINISHES SHALL INCLUDE ALL PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, MATERIAL CHANGES, OR OTHER ENCLOSURES. REFER TO REFLECTED CEILING PLANS.
7. ALL EXISTING AND NEW PARTITIONS AND WALLS WITHIN SCOPE SHALL BE PAINTED.
8. REVIEW ALL FIELD CONDITIONS AND PLANNED WORK. RESOLVE ALL DISCREPANCIES IN A MANNER APPROVED BY THE ARCHITECT THAT COULD AFFECT THE FINISHES OR TRANSITIONS PRIOR TO PROCEEDING WITH WORK AFFECTED BY DISCREPANCIES.
9. LOCATE FLOOR FINISH TRANSITIONS AT CENTERLINE OF DOOR, UNLESS NOTED OTHRWISE.
10. PAINT AND FINISH EXPOSED SURFACES UNLESS NOTED OTHERWISE. PAINT SURFACES BEHIND REMOVABLE EQUIPMENT/FURNITURE. PAINT BEHIND NON-REMOVABLE ITEMS WITH PRIME COAT ONLY.
11. GRILLES, PLATES, DIFFUSERS AND OTHER ITEMS OCCURRING IN WALLS OR CEILING SHALL BE FACTORY FINISHED IN PAINT OF COLOR AND SHEEN TO MATCH SURFACES ON WHICH THEY OCCUR UNLESS NOTED OTHERWISE.
12. SEALANT TO BE APPLIED BETWEEN BASE OF ALL DOOR FRAMES AND TILE FLOORING. SEALANT TO MATCH COLOR OF DOOR FRAMES.
ROOM FINISH TAG:
FINISH TAG:
FINISH SYMBOL:
XX-1
XX-1
XX-1
XX-1
CEILING FINISH
WALL FINISH (FIELD)
WALL BASE FINISH
FLOOR FINISH
ACCENT WALL LOCATION (XX-1)
CPT-1
HATCH INDICATES AREA NOT IN CONTRACT (N.I.C.)
GENERAL LEGEND
CT-1 VCT-1
CPT METAL SCHLUTER TRANSITION STRIP; RENO-RAMP - ENSURE ADA COMPLIANCECT
CPT TARKETT JOHNSONITE RUBBER TRANSITION STRIP - COORDINATE WITH FINISH MATERIAL THICKNESS
VCT
CPT TARKETT JOHNSONITE RUBBER TRANSITION STRIP - COORDINATE WITH FINISH MATERIAL THICKNESS
EXG
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
SS-1 SOLID SURFACE WILSONART SOLID SURFACE WHITE STONE 9208CS
Mark Date Description
1 09.16.2020 ISSUED FOR AABREVIEW
2 10.23.2020 DFM 90% REVIEW
3 10.19.2021 ISSUED FOR BID
EXG
EXG
EXG
PT-1
BREAK
ROOM
271B
2' -
0"
6"
EXG
EXG
EXG
PT-1
GYM
263
CT-1
CT-2
PT-1
CT-2,CT-3, PT-1
MENS
247
CT-1
CT-2
PT-1
CT-2,CT-3, PT-1
WOMENS
248
EX
GC
TE
XG
CT
CT-1
CT-2
ACT-1
CT-2,CT-3, PT-1
MENS
285
CTEXG
CT-1
CT-2
ACT-1
CT-2,CT-3, PT-1
UNISEX
TOILET
255
EXGCT
CT-1
CT-2
ACT-1
CT-2, CT-3, PT-1
WOMENS
239
CTEXG
CT-1
CT-2
ACT-1
CT-2, CT-3, PT-1
WOMENS
278
A4016
EX
GC
T
FINISH PLAN LEGEND
FINISH PLAN NOTES
1. WALLS AND CEILINGS MAY CONTAIN MORE THAN ONE MATERIAL OR FINISH AS INDICATED. COORDINATE WITH CONSTRUCTION TYPE AND FINISH SIMILAR TO ADJACENT MATERIALS, U.N.O.
2. REFER TO ELEVATIONS, REFLECTED CEILING PLANS AND DETAILS FOR ADDITIONAL INFORMATION REGARDING HEIGHTS, BULKHEADS/SOFFITS, FINISHES, PATTERNS, ORIENTATIONS AND TRANSITIONS.
3. PLAN WALL TYPES TAKE PRECEDENCE OVER SCHEDULED WALL FINISH. PROVIDE APPROPRIATE WALL FINISH TO CORRESPOND TO WALL TYPES.
4. MOLD AND MOISTURE RESISTANT GYPSUM BOARD SHALL BE USED AT ALL KITCHEN AREAS, TOILET ROOMS, AND CUSTODIAN SERVICE CLOSETS SCHEDULED TO HAVE GYPSUM BOARD FINISHES.
5. PROVIDE SEALANT/CAULK AT INTERSECTIONS OF DISSIMILAR MATERIALS AND AS RECOMMENDED BY MANUFACTURERS' GUIDELINES.
6. WALL AND CEILING FINISHES SHALL INCLUDE ALL PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, MATERIAL CHANGES, OR OTHER ENCLOSURES. REFER TO REFLECTED CEILING PLANS.
7. ALL EXISTING AND NEW PARTITIONS AND WALLS WITHIN SCOPE SHALL BE PAINTED.
8. REVIEW ALL FIELD CONDITIONS AND PLANNED WORK. RESOLVE ALL DISCREPANCIES IN A MANNER APPROVED BY THE ARCHITECT THAT COULD AFFECT THE FINISHES OR TRANSITIONS PRIOR TO PROCEEDING WITH WORK AFFECTED BY DISCREPANCIES.
9. LOCATE FLOOR FINISH TRANSITIONS AT CENTERLINE OF DOOR, UNLESS NOTED OTHRWISE.
10. PAINT AND FINISH EXPOSED SURFACES UNLESS NOTED OTHERWISE. PAINT SURFACES BEHIND REMOVABLE EQUIPMENT/FURNITURE. PAINT BEHIND NON-REMOVABLE ITEMS WITH PRIME COAT ONLY.
11. GRILLES, PLATES, DIFFUSERS AND OTHER ITEMS OCCURRING IN WALLS OR CEILING SHALL BE FACTORY FINISHED IN PAINT OF COLOR AND SHEEN TO MATCH SURFACES ON WHICH THEY OCCUR UNLESS NOTED OTHERWISE.
12. SEALANT TO BE APPLIED BETWEEN BASE OF ALL DOOR FRAMES AND TILE FLOORING. SEALANT TO MATCH COLOR OF DOOR FRAMES.
ROOM FINISH TAG:
FINISH TAG:
FINISH SYMBOL:
XX-1
XX-1
XX-1
XX-1
CEILING FINISH
WALL FINISH (FIELD)
WALL BASE FINISH
FLOOR FINISH
ACCENT WALL LOCATION (XX-1)
CPT-1
HATCH INDICATES AREA NOT IN CONTRACT (N.I.C.)
GENERAL LEGEND
CT-1 VCT-1
CPT METAL SCHLUTER TRANSITION STRIP; RENO-RAMP - ENSURE ADA COMPLIANCECT
CPT TARKETT JOHNSONITE RUBBER TRANSITION STRIP - COORDINATE WITH FINISH MATERIAL THICKNESS
VCT
CPT TARKETT JOHNSONITE RUBBER TRANSITION STRIP - COORDINATE WITH FINISH MATERIAL THICKNESS
EXG
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
FAD101
FIRE ALARM
2ND FLOOR
DEMO PLAN
FIRE ALARM WORK:
1. FIRE ALARM CONTRACTOR SHALL REMOVE ALL EXISTING FIRE ALARM DEVICES (SMOKE DETECTORS,
PULL STATIONS, STROBES, ETC.) AS REQUIRED FOR NEW BATHROOMS & OFFICE SPACE LAYOUTS
FIRE ALARM CONTRACTOR SHALL REINSTALL EXISTING DEVICES AND SHALL INSTALL NEW DEVICES
AS REQUIRED. REFER TO DRAWINGS FA101 & FA102 FOR LOCATIONS OF NEW FIRE ALARM DEVICES.
2. ALL FIRE ALARM WORK SHALL BE HANDLED BY A DHSS APPROVED FIRE ALARM CONTRACTOR. ALL
FIRE ALARM WORK SHALL BE COORDINATED BY THE GENERAL CONTRACTOR OF THIS PROJECT.
3. REINSTALL EXISTING FIRE ALARM DEVICE IN NEW CEILING OR NEW WALLS AS REQUIRED.
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
FAD101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - DEMO PLAN
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
WP
AutoCAD SHX Text
F
AutoCAD SHX Text
FIRE ALARM SYSTEM MANUAL PULL STATION FIRE ALARM SYSTEM STROBE DEVICE - STANDARD, WEATHERPROOF - WALL MOUNTED FIRE ALARM SYSTEM HORN/STROBE DEVICE - WALL MOUNTED SMOKE DETECTOR
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
FAD102
FIRE ALARM
2ND FLOOR
DEMO PLAN
FIRE ALARM WORK:
1. FIRE ALARM CONTRACTOR SHALL REMOVE ALL EXISTING FIRE ALARM DEVICES (SMOKE DETECTORS,
PULL STATIONS, STROBES, ETC.) AS REQUIRED FOR NEW BATHROOMS & OFFICE SPACE LAYOUTS
FIRE ALARM CONTRACTOR SHALL REINSTALL EXISTING DEVICES AND SHALL INSTALL NEW DEVICES
AS REQUIRED. REFER TO DRAWINGS FA101 & FA102 FOR LOCATIONS OF NEW FIRE ALARM DEVICES.
2. ALL FIRE ALARM WORK SHALL BE HANDLED BY A DHSS APPROVED FIRE ALARM CONTRACTOR. ALL
FIRE ALARM WORK SHALL BE COORDINATED BY THE GENERAL CONTRACTOR OF THIS PROJECT.
3. REINSTALL EXISTING FIRE ALARM DEVICE IN NEW CEILING OR NEW WALLS AS REQUIRED.
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
SD
AutoCAD SHX Text
F
AutoCAD SHX Text
WP
AutoCAD SHX Text
F
AutoCAD SHX Text
FIRE ALARM SYSTEM MANUAL PULL STATION FIRE ALARM SYSTEM STROBE DEVICE - STANDARD, WEATHERPROOF - WALL MOUNTED FIRE ALARM SYSTEM HORN/STROBE DEVICE - WALL MOUNTED SMOKE DETECTOR
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
FP101
FIRE PROTECTION
2ND FLOOR PLAN
1
2
SHEET NOTES : _1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGEND &
SPECIFICATIONS
2. ALL EQUIPMENT SHALL BE COORDINATE WITH ALL OTHERTRADES AND UTILITIES.
3. COORDINATE WITH ARCHITECTURAL PLANS AND OTHERTRADES FOR MOUNTED HEIGHTS OF MATERIAL ANDEQUIPMENT.
.
ALL WORK SHALL BE
FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF
NEW HEAD LOCATIONS WITH ALL OTHER TRADES INVOLVED IN SPACE
RENOVATION.
THE SPRINKLER CONTRACTOR SHALL SEEK THE APPROVAL OF THE LOCAL
FIRE MARSHALL AND ROHM AND HAAS PRIOR TO INSTALLATION AND
MODIFICATION OF THE EXISTING SPRINKLER SYSTEM.
ALL RELOCATED SPRINKLER HEADS TO BE INSTALLED IN THE CENTER OF
THE CEILING TILES.
3.
1.
2.
4.
FIRE PROTECTION:
5.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
FP101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - FP PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
FP101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS B - FP PLAN
AutoCAD SHX Text
KEYED NOTES:
AutoCAD SHX Text
CONTRACTOR SHALL PROVIDE NEW FIRE PROTECTION CONCEALED SPRINKLER HEADS IN NEW CEILING. DURING CONSTRUCTION, THE ENTIRE FIRE PROTECTIONS SYSTEM FOR THE REMAINDER OF THE BUILDING SHALL REMAIN OPERATIONAL. FIRE WATCH OR AN AHJ AGREED UPON FIRE SAFETY PLAN SHALL BE ENFORCED DURING FIRE PROTECTION SHUT-DOWNS. CONTRACTOR SHALL RELOCATE EXISTING SPRINKLER HEADS TO NEW CEILING, COORDINATE EXACT LOCATION IN THE FIELD.
AutoCAD SHX Text
THE EXISTING SPRINKLER SYSTEM SHALL BE MODIFIED TO SUIT THE NEW SPACE CONFIGURATION AND CEILING LAYOUT. INSTALLED IN ACCORDANCE WITH NFPA 13 AND SHALL 13 AND SHALL BE CLASSIFIED FOR ORDINARY HAZARD.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
FP102
FIRE PROTECTION
2ND FLOOR PLAN
SHEET NOTES : _1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGEND &
SPECIFICATIONS
2. ALL EQUIPMENT SHALL BE COORDINATE WITH ALL OTHERTRADES AND UTILITIES.
3. COORDINATE WITH ARCHITECTURAL PLANS AND OTHERTRADES FOR MOUNTED HEIGHTS OF MATERIAL ANDEQUIPMENT.
1
2
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
FP102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uGYM 263 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
FP102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMENS TOILET ROOM 285 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
FP102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMEN'S 247 & WOMEN'S 248 DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
FP102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uBREAK ROOM 271B - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
FP102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 255 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
FP102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 278 - DEMO PLAN
AutoCAD SHX Text
(E)MAIN
AutoCAD SHX Text
FP LINE
AutoCAD SHX Text
PENDENT SPRINKLER
AutoCAD SHX Text
NEW 1" FP LINE
AutoCAD SHX Text
(E)MAIN
AutoCAD SHX Text
FP LINE
AutoCAD SHX Text
EXTEND TO NEW CONCEALED
AutoCAD SHX Text
CONNECT 1" FP TO EXISTING &
AutoCAD SHX Text
DEMOLITION
AutoCAD SHX Text
RELOCATION
AutoCAD SHX Text
REMOVE EXIST PIPE
AutoCAD SHX Text
& UPRIGHT SPRINKLER
AutoCAD SHX Text
NEW CONCEALED
AutoCAD SHX Text
PENDENT SPRINKLER
AutoCAD SHX Text
DISCONNECT FROM EXISTING 1"FP
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
7
AutoCAD SHX Text
FP102
AutoCAD SHX Text
NTS
AutoCAD SHX Text
%%uTYPICAL SPRINKLER DEMOLITION/RELOCATION
AutoCAD SHX Text
KEYED NOTES:
AutoCAD SHX Text
CONTRACTOR SHALL PROVIDE NEW FIRE PROTECTION CONCEALED SPRINKLER HEADS IN NEW CEILING. DURING CONSTRUCTION, THE ENTIRE FIRE PROTECTIONS SYSTEM FOR THE REMAINDER OF THE BUILDING SHALL REMAIN OPERATIONAL. FIRE WATCH OR AN AHJ AGREED UPON FIRE SAFETY PLAN SHALL BE ENFORCED DURING FIRE PROTECTION SHUT-DOWNS. CONTRACTOR SHALL RELOCATE EXISTING SPRINKLER HEADS TO NEW CEILING, COORDINATE EXACT LOCATION IN THE FIELD.
WHITE FINISH, FLOOR MOUNTED TOP SPUD FLUSHOMETER TOILET. PROVIDE MODEL 5901.11T.020 TOILET SEAT. PROVIDE 10 YEAR BATTERY SENSOR OPERATED FLUSH VALVE RATED FOR 1.28 GPF. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL PLANS.
AutoCAD SHX Text
AMERICAN STANDARD 6066.121.002
AutoCAD SHX Text
2"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
-
AutoCAD SHX Text
AMERICAN STANDARD 6064.013.002
AutoCAD SHX Text
WHITE FINISH, WALL MOUNTED. PROVIDE WALL HANGER. PROVIDE AUTOMATIC FLUSH VALVE RATED FOR .125 TO 1 GPF. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL PLANS. PROVIDE 10 YEAR BATTERY SENSOR OPERATED FLUSH VALVE.
AutoCAD SHX Text
MODEL# 6590.001EC.020
AutoCAD SHX Text
AMERICAN STANDARD
AutoCAD SHX Text
MODEL# K-2214
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
1-1/4"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
MODEL# K-13468
AutoCAD SHX Text
WHITE FINISH, UNDERMOUNT, SINGLE HOLE AND GRID STRAINER. PROVIDE SENSOR OPERATED 0.5 GPM FAUCET. FAUCET REQUIRES 120V AC POWER SOURCE. PROVIDE PROFLO PF200 SERIES PIPE COVERS FOR EXPOSED PIPING BELOW FIXTURE.
AutoCAD SHX Text
AMERICAN STANDARD
AutoCAD SHX Text
1-1/2"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
AMERICAN STANDARD
AutoCAD SHX Text
MODEL# 7074.000.002
AutoCAD SHX Text
25"X22"X8" SINGLE BOWL STAINLESS STEEL SELF-RIMMING SINK. PROVIDE COLONY PRO SINGLE CONTROL KITCHEN FAUCET - 1.5 GPM. ADA COMPLIANT
AutoCAD SHX Text
MODEL# 20SB.8252283S.075
AutoCAD SHX Text
-
AutoCAD SHX Text
ZURN
AutoCAD SHX Text
MODEL# Z7121-SS-LH-DV2P-HW
AutoCAD SHX Text
3"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
PROVIDE ADA COMPLIANT SHOWER HEAD. DRAIN SHALL BE EQUAL TO SCHLUTER-KERDI DRAIN WITH 6" STAINLESS STEEL GRATE. COORDINATE WITH ARCHITECTURAL PLANS FOR SHOWER CONSTRUCTION.
AutoCAD SHX Text
LAV-2
AutoCAD SHX Text
MODEL# K-2084
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
1-1/4"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
WHITE FINISH, WALL MOUNTED, SINGLE HOLE AND GRID STRAINER. PROVIDE SENSOR OPERATED 0.5 GPM FAUCET. FAUCET REQUIRES 120V AC POWER SOURCE. PROVIDE PROFLO PF200 SERIES PIPE COVERS FOR EXPOSED PIPING BELOW FIXTURE.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
PD101
PLUMBING
2ND FLOOR
DEMO PLAN
1
2
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
PD101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
PD101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS B - DEMO PLAN
AutoCAD SHX Text
KEYED NOTES:
AutoCAD SHX Text
DEMO EXISTING LAVATORY. DEMO HOT AND COLD DOMESTIC WATER, AND SAN PIPING BACK TO EXISTING RISER. CAP IN CHASE. DEMO EXISTING FIXTURE. REROUTE EXISTING HOT AND COLD DOMESTIC WATER, SANITARY, AND VENT PIPING FOR EXISTING 3RD FLOOR FIXTURES. TIE NEW REROUTED HOT AND COLD DOMESTIC WATER, SANITARY, AND VENT PIPING TO EXISTING PIPING ON FIRST FLOOR.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
PD102
PLUMBING
2ND FLOOR
DEMO PLAN
1
2
3
4
5
6
7
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
PD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uGYM 263 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
PD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMENS TOILET ROOM 285 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
PD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMEN'S 247 & WOMEN'S 248 DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
PD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uBREAK ROOM 271B - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
PD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 255 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
PD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 278 - DEMO PLAN
AutoCAD SHX Text
KEYED NOTES:
AutoCAD SHX Text
DEMO EXISTING FIXTURE. DISCONNECT EXISTING HOT AND COLD DOMESTIC WATER, SANITARY, AND VENT PIPING ABOVE 2ND FLOOR CEILING. REROUTE ALL SYSTEMS TO NEW CHASE ON 2ND FLOOR. RECONNECT NEW SYSTEMS TO EXISTING RISER ON 1ST FLOOR ABOVE THE CEILING. DEMO EXISTING SINK. REUSE EXISTING HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING FOR NEW SINK. EXTEND PIPING AS REQUIRED. DEMO EXISTING LAVATORY. REUSE EXISTING HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING FOR NEW LAVATORY. EXTEND PIPING AS REQUIRED. DEMO EXISTING TOILET. REUSE EXISTING COLD DOMESTIC WATER, SANITARY AND VENT PIPING FOR NEW TOILET. EXTEND PIPING AS REQUIRED. DEMO EXISTING MOP SINK. REUSE EXISTING HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING FOR NEW SHOWER. EXTEND PIPING AS REQUIRED. DEMO EXISTING TOILET. DEMO COLD DOMESTIC WATER, AND SAN PIPING BACK TO EXISTING RISER. CAP IN CHASE. DEMO EXISTING FIXTURE. REUSE EXISTING HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING FOR NEW BATHROOM FIXTURE LAYOUT. EXTEND PIPING TO NEW FIXTURES AS REQUIRED.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
P101
PLUMBING
2ND FLOOR
FLOOR PLAN
1
2
3
4
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
P101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
P101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS B - FLOOR PLAN
AutoCAD SHX Text
KEYED NOTES:
AutoCAD SHX Text
FURNISH AND INSTALL NEW SINK. RUN NEW HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING TO FIXTURES AS REQUIRED FROM EXISTING PIPING CHASE. PROVIDE NEW 4" FLOOR DRAIN FOR ICE MACHINE. ROUTE ICE MACHINE DRAIN TO NEW FLOOR DRAIN. PROVIDE NEW 1/2" CW SUPPLY WITH INLINE CARTRIDGE FILTER. COORDINATE FILTER MANUFACTURER WITH OWNER. FURNISH AND INSTALL NEW TOILET. RUN NEW COLD WATER, SANITARY AND VENT PIPING TO NEW FIXTURE AS REQUIRED FOR A COMPLETE INSTALLATION. FURNISH AND INSTALL NEW LAVATORY. RUN NEW HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING TO NEW FIXTURE AS REQUIRED FOR A COMPLETE INSTALLATION.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
P102
PLUMBING
2ND FLOOR
FLOOR PLAN
1
2
3
4
5
6
7
NOTE:
1. VERTICAL DROP MAY NOT BE IN THE SAME PLANE AS THE
CLEANOUT.
2. H = ABSOLUTE VALUE OF THE DESIGN STATIC PRESSURE INSIDE
AIR HANDLING UNIT OR COIL SECTION. (H=+H=-H)
3. SIZE PIPE TO MATCH PAN FITTING.
ROUTE TO EXTERIOR
NOTE:
PIPE (TYP.)
12" (MAX.)
METAL JACKET
NATIONAL GALVANIZED
INSULATION SHIELD FIG. 300
NATIONAL CONTINUOUS
THREADED ROD FIG. 755
NATIONAL ADJUSTABLE
CLEVIS HANGER WITH
WELDED SHIELD FIG. 220.
SIZE PER PIPE.
FIRE STOP
SEALENT
CONTINUOUS PIPE
SLEEVE AROUND PIPE.
ANCHOR PIPE SLEEVE
TO WALL.
NOTE:
4' MAXIMUM CLEVIS HANGER SPACING UNLESS OTHERWISE NOTED
FOR PIPING 2" & GREATER PIPE HANGERS SHALL BE:
NATIONAL ADJUSTABLE CLEVIS HANGER WITH WELDED SHIELD FIG. 220
----OR----
NATIONAL ADJUSTABLE CLEVIS HANGER FIG. 200 WITH PIPE COVERING
PROTECTION SHIELD FIG. 300
CONTRACTOR SHALL INSURE BUILDING FIRE RATINGS ARE MAINTAINED BY
PROVIDING INTUMESCENT CAULK AT ALL LOCATIONS WHERE PIPING
PENETRATES FIRE-RATED WALLS AND FLOORS.
1
4
"
INSULATION (TYP.)
INSULATION IF
REQUIRED (TYP.)
METAL STUD WALL
NEW OR EXISTING DRYWALL
℄
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
P102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UGYM 263 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
P102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UMENS TOILET ROOM 285 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
P102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UMEN'S 247 & WOMEN'S 248 FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
P102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UBREAK ROOM 271B - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
P102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UTOILET ROOM 255 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
P102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UTOILET ROOM 278 - FLOOR PLAN
AutoCAD SHX Text
KEYED NOTES:
AutoCAD SHX Text
RECONNECT NEW SINK TO EXISTING HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING. EXTEND PIPING AS REQUIRED. RECONNECT NEW TOILET TO EXISTING HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING. EXTEND PIPING AS REQUIRED. FURNISH AND INSTALL NEW TOILET. RUN NEW COLD WATER, SANITARY AND VENT PIPING TO NEW FIXTURE AS REQUIRED FOR A COMPLETE INSTALLATION. FURNISH AND INSTALL TO NEW INTEGRAL SURFACE BOWL NEW FAUCET, ETC. RUN NEW HOT AND COLD DOMESTIC WATER, SANITARY AND VENT PIPING TO NEW FIXTURE AS REQUIRED FOR A COMPLETE INSTALLATION. FURNISH AND INSTALL NEW URINAL. RUN NEW COLD WATER, SANITARY AND VENT PIPING TO NEW FIXTURE AS REQUIRED FOR A COMPLETE INSTALLATION. FURNISH AND INSTALL NEW SHOWER. SHOWER SHALL BE FULL SOLID SURFACE SURROUND. COORDINATE DIMENSIONS WITH ARCHITECT PRIOR TO PURCHASING AND INSTALLING. RUN NEW HOT AND COLD WATER, SANITARY AND VENT PIPING TO NEW SHOWER AS REQUIRED FOR A COMPLETE INSTALLATION. PROVIDE NEW 4" FLOOR DRAIN FOR ICE MACHINE. ROUTE ICE MACHINE DRAIN TO NEW FLOOR DRAIN. PROVIDE NEW 1/2" CW SUPPLY WITH INLINE CARTRIDGE FILTER. COORDINATE FILTER MANUFACTURER WITH OWNER.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
7
AutoCAD SHX Text
P102
AutoCAD SHX Text
NONE
AutoCAD SHX Text
%%UCONDENSATE TRAP DETAIL
AutoCAD SHX Text
(1.5H)
AutoCAD SHX Text
PLUG
AutoCAD SHX Text
NEGATIVE PRESSURE (H)
AutoCAD SHX Text
IF H<0, H+1 MIN. DROP
AutoCAD SHX Text
IF H>0, 2" MIN. DROP
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
PVC DWV PIPING & FITTINGS
AutoCAD SHX Text
DRAIN PAN
AutoCAD SHX Text
(1.5H)
AutoCAD SHX Text
PLUG
AutoCAD SHX Text
NEGATIVE PRESSURE (H)
AutoCAD SHX Text
IF H<0, H+1 MIN. DROP
AutoCAD SHX Text
IF H>0, 2" MIN. DROP
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
PVC DWV PIPING & FITTINGS
AutoCAD SHX Text
DRAIN PAN
AutoCAD SHX Text
LOCATE FLOOR DRAIN WHERE SHOWN ON PLUMBING PLAN.
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
DEEP-SEAL P-TRAP
AutoCAD SHX Text
PIPE INCREASER FOR COMBINATION WASTE & VENT
AutoCAD SHX Text
FLOOR DRAIN BODY WITH 3" OUTLET (CAULK OR PUSH-ON), MEMBRANE CLAMPING COLLAR, AND SEDIMENT BUCKET
AutoCAD SHX Text
SET TOP OF DRAIN GRATE FLUSH WITH FINISHED FLOOR. VERIFY FLOOR FINISH MATERIAL.
AutoCAD SHX Text
REF ARCHITECTURAL DRAWINGS FOR FLOOR SLOPE AND ELEVATION
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
MD101
MECHANICAL
2ND FLOOR
DEMO PLAN
1
2
3
SHEET NOTES : _1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGEND &
SPECIFICATIONS
2. ALL EQUIPMENT SHALL BE COORDINATE WITH ALL OTHERTRADES AND UTILITIES.
3. COORDINATE WITH ARCHITECTURAL PLANS AND OTHERTRADES FOR MOUNTED HEIGHTS OF MATERIAL ANDEQUIPMENT.
4
AutoCAD SHX Text
SS
AutoCAD SHX Text
1
AutoCAD SHX Text
SS
AutoCAD SHX Text
1A
AutoCAD SHX Text
SS
AutoCAD SHX Text
1B
AutoCAD SHX Text
SS
AutoCAD SHX Text
2
AutoCAD SHX Text
SS
AutoCAD SHX Text
2B
AutoCAD SHX Text
SS
AutoCAD SHX Text
2A
AutoCAD SHX Text
SS
AutoCAD SHX Text
3A
AutoCAD SHX Text
SS
AutoCAD SHX Text
8
AutoCAD SHX Text
SS
AutoCAD SHX Text
8A
AutoCAD SHX Text
SS
AutoCAD SHX Text
8B
AutoCAD SHX Text
SS
AutoCAD SHX Text
9
AutoCAD SHX Text
SS
AutoCAD SHX Text
9A
AutoCAD SHX Text
(3 CIRCUITS)
AutoCAD SHX Text
SS
AutoCAD SHX Text
8A
AutoCAD SHX Text
(E)RAD.
AutoCAD SHX Text
SS
AutoCAD SHX Text
2
AutoCAD SHX Text
SS
AutoCAD SHX Text
2B
AutoCAD SHX Text
SS
AutoCAD SHX Text
8
AutoCAD SHX Text
SS
AutoCAD SHX Text
8A
AutoCAD SHX Text
(3 CIRCUITS)
AutoCAD SHX Text
SS
AutoCAD SHX Text
3
AutoCAD SHX Text
SS
AutoCAD SHX Text
3C
AutoCAD SHX Text
SS
AutoCAD SHX Text
3B
AutoCAD SHX Text
SS
AutoCAD SHX Text
4
AutoCAD SHX Text
SS
AutoCAD SHX Text
4A
AutoCAD SHX Text
SS
AutoCAD SHX Text
4B
AutoCAD SHX Text
SS
AutoCAD SHX Text
5
AutoCAD SHX Text
SS
AutoCAD SHX Text
5A
AutoCAD SHX Text
SS
AutoCAD SHX Text
5B
AutoCAD SHX Text
SS
AutoCAD SHX Text
6
AutoCAD SHX Text
SS
AutoCAD SHX Text
6A
AutoCAD SHX Text
SS
AutoCAD SHX Text
7A
AutoCAD SHX Text
SS
AutoCAD SHX Text
7
AutoCAD SHX Text
SS
AutoCAD SHX Text
7B
AutoCAD SHX Text
SS
AutoCAD SHX Text
7C
AutoCAD SHX Text
SS
AutoCAD SHX Text
8A
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
MD101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
MD101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS B - DEMO PLAN
AutoCAD SHX Text
KEYED NOTES:
AutoCAD SHX Text
CONTRACTOR SHALL DEMOLISH AND REMOVE EXISTING STEAM/HOT WATER WALL MOUNTED RADIATORS. CONTRACTOR SHALL CUT AND CAP ALL PIPING ASSOCIATED WITH RADIATOR AND SHALL PREPARE SPACE FOR INFILL. CONTRACTOR SHALL ENSURE CONTINUITY OF HEATING SYSTEM IN OTHER AREAS OF THE BUILDING UTILIZING THE SAME SYSTEM. CONTRACTOR SHALL DEMOLISH AND REMOVE EXISTING SPLIT SYSTEMS AS INDICATED. ALL APPURTENANCES SHALL BE REMOVED. CONTRACTOR SHALL MAINTAIN EXISTING CONDENSATE FOR CONNECTION WITH NEW CONDENSATE FROM NEW UNITS AS REQUIRED. CONTRACTOR SHALL MAINTAIN THE EXISTING UNITS AS SHOWN AND SHALL ENSURE UNITS THAT REMAIN ARE IN GOOD WORKING ORDER. CONTRACTOR SHALL VERIFY CONTROLS FOR A SINGLE INDOOR UNIT ARE FUNCTIONING WHERE ONE UNIT IS REMOVE FROM A MULTIPLE INDOOR UNIT SYSTEM. CONTRACTOR SHALL DEMOLISH DUCTWORK BELOW FLOOR. CAP DUCT. COORDINATE AHU SHUTDOWN WITH OWNER.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
MD102
MECHANICAL
2ND FLOOR
DEMO PLAN
1
2
3
4
5
SHEET NOTES : _1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGEND &
SPECIFICATIONS
2. ALL EQUIPMENT SHALL BE COORDINATE WITH ALL OTHERTRADES AND UTILITIES.
3. COORDINATE WITH ARCHITECTURAL PLANS AND OTHERTRADES FOR MOUNTED HEIGHTS OF MATERIAL ANDEQUIPMENT.
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
(E)RAD.
AutoCAD SHX Text
T
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
(E)RAD.
AutoCAD SHX Text
T
AutoCAD SHX Text
SP
AutoCAD SHX Text
(E)RAD.
AutoCAD SHX Text
SP
AutoCAD SHX Text
(E)ELEC. BB
AutoCAD SHX Text
(E)RAD.
AutoCAD SHX Text
T
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
T
AutoCAD SHX Text
T
AutoCAD SHX Text
(E)RAD.
AutoCAD SHX Text
(E)RAD.
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
T
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
MD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uGYM 263 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
MD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMENS TOILET ROOM 285 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
MD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMEN'S 247 & WOMEN'S 248 DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
MD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uBREAK ROOM 271B - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
MD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 255 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
MD102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 278 - DEMO PLAN
AutoCAD SHX Text
KEYED NOTES:
AutoCAD SHX Text
EXISTING MECHANICAL SYSTEM TO REMAIN. CONTRACTOR SHALL CLEAN EXISTING UNIT/GRD, ETC. AND PREPARE FOR NEW FINISHES. COORDINATE WITH ARCHITECT AND GENERAL CONTRACTOR. EXISTING DIFFUSER TO BE RELOCATED. DISCONNECT EXISTING DUCTWORK. NEW LOCATION FOR RELOCATED DIFFUSER. PROVIDE NEW DUCTWORK FROM DIFFUSER TO MAIN DUCT. CONTRACTOR SHALL DEMOLISH AND REMOVE EXISTING EXHAUST GRILLE AND SHALL REPLACE GRILLE IN-KIND INTO NEW CEILING. CUT BACK OR EXTEND DUCTWORK TO INSTALL NEW GRILLE IN THE CENTER OF A NEW CEILING TILE. CONTRACTOR SHALL DEMOLISH AND REMOVE EXHAUST GRILLE. REMOVE AND DEMOLISH ALL EXHAUST DUCT BACK TO MAIN AND CAP.
1
OU
CD,10"Ø155CFM
CD,10"Ø155CFM
10"Ø
10"Ø
12
x1
21
2x1
2
0184
IU
T
T
MATCHLINE - SEE 1/M101
LARGE
CONF. ROOM
232
RECEPTION/SECURITY
225
LARGE
OFFICE
227
OFFICE
229
OFFICE
231
LARGE OPEN
OFFICE
230
ELEVATOR
LOBBY
260A
LARGE
OFFICE
234
IT CLOSET
230A
PROVIDE AND INSTALLNEW 4" DEEPCONCRETEHOUSEKEEPING PAD.PAD SHALL EXTEND MIN4" AROUND UNIT.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
M102
MECHANICAL
2ND FLOOR
FLOOR PLAN
SHEET NOTES : _1. REFER TO DRAWING M000 FOR GENERAL NOTES, LEGEND &
SPECIFICATIONS
2. REFER TO DRAWING M103 FOR ALL DETAILS.
3. ALL EQUIPMENT SHALL BE COORDINATE WITH ALL OTHERTRADES AND UTILITIES.
4. COORDINATE WITH ARCHITECTURAL PLANS AND OTHERTRADES FOR MOUNTED HEIGHTS OF MATERIAL ANDEQUIPMENT.
NOTE:NOTE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
M102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UGYM 263 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
M102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UMENS TOILET ROOM 285 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
M102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UMEN'S 247 & WOMEN'S 248 FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
M102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UBREAK ROOM 271B - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
M102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UTOILET ROOM 255 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
M102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UTOILET ROOM 278 - FLOOR PLAN
AutoCAD SHX Text
DUCTWORK
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
FLEXIBLE DUCTWORK
AutoCAD SHX Text
INSULATED
AutoCAD SHX Text
BALANCING DAMPER
AutoCAD SHX Text
SPIN COLLAR W/
AutoCAD SHX Text
DUCTWORK
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
FLEXIBLE DUCTWORK
AutoCAD SHX Text
INSULATED
AutoCAD SHX Text
HEEL TAKEOFF W/ TRANSITION TO ROUND
AutoCAD SHX Text
SPIN COLLAR W/ BALANCING DAMPER
AutoCAD SHX Text
PLUS BALANCING DAMPER.
AutoCAD SHX Text
ROUND DUCTWORK
AutoCAD SHX Text
LENGTH AS REQUIRED
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
1. FLEXIBLE DUCT BENDS SHALL NOT HAVE A RADIUS FLEXIBLE DUCT BENDS SHALL NOT HAVE A RADIUS GREATER THAN 90°. 2. MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 6'-0". MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 6'-0".
AutoCAD SHX Text
DUCTWORK
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
FLEXIBLE DUCTWORK
AutoCAD SHX Text
INSULATED
AutoCAD SHX Text
BALANCING DAMPER
AutoCAD SHX Text
SPIN COLLAR W/
AutoCAD SHX Text
DUCTWORK
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
FLEXIBLE DUCTWORK
AutoCAD SHX Text
INSULATED
AutoCAD SHX Text
HEEL TAKEOFF W/ TRANSITION TO ROUND
AutoCAD SHX Text
SPIN COLLAR W/ BALANCING DAMPER
AutoCAD SHX Text
PLUS BALANCING DAMPER.
AutoCAD SHX Text
ROUND DUCTWORK
AutoCAD SHX Text
LENGTH AS REQUIRED
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
1. FLEXIBLE DUCT BENDS SHALL NOT HAVE A RADIUS FLEXIBLE DUCT BENDS SHALL NOT HAVE A RADIUS GREATER THAN 90°. 2. MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 6'-0". MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 6'-0".
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
E000
ELECTRICAL
NOTES, LEGEND, AND
ABBREVIATIONS
FIRE ALARM SYSTEM MODIFICATION NOTES:
LUMINAIRE SCHEDULE
AutoCAD SHX Text
+
AutoCAD SHX Text
CIRCUIT BREAKER. "#A" AND "3P" IDENTIFY CIRCUIT BREAKER AMPACITY AND 3 POLES UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
GROUND TO EARTH
AutoCAD SHX Text
TRANSFORMER.
AutoCAD SHX Text
FEEDER REFERENCE TAG, REFER TO FEEDER LEGEND.
AutoCAD SHX Text
+
AutoCAD SHX Text
+
AutoCAD SHX Text
+
AutoCAD SHX Text
WP
AutoCAD SHX Text
SINGLE-POLE OR TWO-POLE (AS REQUIRED), 250V AC, 1 HP RATED, TOGGLE TYPE MANUAL MOTOR STARTED UNIT WITH MELTING ALLOY TYPE THERMAL OVERLOAD RELAY, APPROPRIATELY SIZED THERMAL UNITS, NEMA TYPE 1 OR 4 (AS REQUIRED) ENCLOSURE, AND HANDLE GUARD/LOCK-OFF. SQUARE D CLASS 2510 FG OR FW TYPES (AS REQUIRED) OR APPROVED EQUAL. THREE-POLE, 250V AC, 1 OR 2 HP RATED (AS REQUIRED), TOGGLE TYPE MANUAL MOTOR STARTER UNIT WITH MELTING ALLOY TYPE THERMAL OVERLOAD RELAY, APPROPRIATELY SIZED THERMAL UNITS, NEMA TYPE 1 ENCLOSURE AND HANDLE GUARD/LOCK-OFF. SQUARE D CLASS 2510 K TYPE OR APPROVED EQUAL.
AutoCAD SHX Text
20A, 120-277V AC, THREE-WAY TOGGLE SWITCH. SWITCH MOUNTING HEIGHT = 48" A.F.F. TO CENTER OF DEVICE BOX, U.O.N..
AutoCAD SHX Text
20A, 120-277V AC, SINGLE TOGGLE SWITCH. SWITCH MOUNTING HEIGHT = 48" A.F.F. TO CENTER OF DEVICE BOX, U.O.N..
AutoCAD SHX Text
JUNCTION BOX OR EQUIPMENT CONNECTION.
AutoCAD SHX Text
20A, 120V AC, NEMA 5-20R, GROUND FAULT CIRCUIT INTERRUPTER (GFCI) DUPLEX RECEPTACLE WITH WEATHERPROOF COVER. 18" AFF TO CENTER OF DEVICE BOX U.O.N.
AutoCAD SHX Text
20A, 120V AC, NEMA 5-20R, GROUND FAULT CIRCUIT INTERRUPTER (GFCI) TYPE DUPLEX RECEPTACLE. MOUNTING HEIGHT TO CENTER OF DEVICE = 18" A.F.F., + = ABOVE COUNTER HEIGHT MOUNT (COORDINATE WITH MILLWORK).
AutoCAD SHX Text
20A, 120V AC, NEMA 5-20R, DOUBLE DUPLEX RECEPTACLE. MOUNTING HEIGHT TO CENTER OF DEVICE = 18" A.F.F., + = ABOVE COUNTER HEIGHT MOUNT (COORDINATE WITH MILLWORK).
AutoCAD SHX Text
20A, 120V AC, NEMA 5-20R, DUPLEX RECEPTACLE. MOUNTING HEIGHT TO CENTER OF DEVICE = 18" AFF TO CENTER OF DEVICE BOX U.O.N., + = ABOVE COUNTER HEIGHT MOUNT (COORDINATE WITH MILLWORK).
AutoCAD SHX Text
#
AutoCAD SHX Text
WATER HEATER. PROVIDED BY MECHANICAL CONTRACTOR
AutoCAD SHX Text
#
AutoCAD SHX Text
FUSIBLE DISCONNECT SWITCH. "#A" IDENTIFIES DISCONNECT SWITCH AMPACITY RATING. "#AF", IF PRESENT, IDENTIFIES APPROXIMATE FUSE RATING. UNLESS OTHERWISE NOTED, ALL FUSIBLE DISCONNECT SWITCHES SHALL BE COMPLETE WITH APPROPRIATELY SIZED DE, TD, CL, CLASS RK5 FUSES.
AutoCAD SHX Text
CIRCUIT BREAKER TYPE COMBINATION STARTER UNIT WITH DOOR MOUNTED H-O-A SWITCH AND RED "MOTOR RUNNING" LED TYPE PILOT LIGHT. PROVIDE AUXILIARY CONTACT. "#A" IDENTIFIES DISCONNECT SWITCH AMPACITY RATING. NEMA SIZE AS INDICATED.
AutoCAD SHX Text
FUSIBLE SWITCH TYPE COMBINATION STARTER UNIT WITH DOOR MOUNTED H-O-A SWITCH AND RED "MOTOR RUNNING" LED TYPE PILOT LIGHT. PROVIDE AUXILIARY CONTACT. NEMA SIZE AS INDICATED. "#A" IDENTIFIES DISCONNECT SWITCH AMPACITY RATING. "#A", IF PRESENT, IDENTIFIES APPROXIMATE FUSE RATING. UNLESS OTHERWISE NOTED, ALL FUSIBLE DISCONNECT SWITCHES SHALL BE COMPLETE WITH APPROPRIATELY SIZED DE, TD, CL, CLASS RK5 FUSES.
AutoCAD SHX Text
EXHAUST FAN. PROVIDED BY MECHANICAL CONTRACTOR
AutoCAD SHX Text
AIR HANDLING UNIT. PROVIDED BY MECHANICAL CONTRACTOR
AutoCAD SHX Text
S
AutoCAD SHX Text
M
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
S
AutoCAD SHX Text
J
AutoCAD SHX Text
SPECIAL PURPOSE ELECTRICAL RECEPTACLE. NEMA CONFIGURATION AS SHOWN NEXT TO RECEPTACLE.
AutoCAD SHX Text
MOTORIZED EQUIPMENT. "#" IF PRESENT INSIDE SYMBOL IDENTIFIES MOTOR HORSEPOWER.
AutoCAD SHX Text
WH
AutoCAD SHX Text
#
AutoCAD SHX Text
EF
AutoCAD SHX Text
#
AutoCAD SHX Text
AHU
AutoCAD SHX Text
#
AutoCAD SHX Text
TV
AutoCAD SHX Text
FUTURE TELEVISION OUTLET. PROVIDE STANDARD SQUARE DEVICE BOX, TILE RING (DEPTH AS REQUIRED), DEVICE PLATE (COLOR AS SPECIFIED BY ARCHITECT/ENGINEER AND/OR OWNER), STUB-UP 3/4" CONDUIT TO NEAREST ACCESSIBLE SPACE. MOUNTING HEIGHT = 18" A.F.F. TO CENTER OF DEVICE.
AutoCAD SHX Text
20A, 120V AC, NEMA 5-20R, HALF-SWITCHED DUPLEX RECEPTACLE. MOUNTING HEIGHT TO CENTER OF DEVICE = 18" A.F.F., + = ABOVE COUNTER HEIGHT MOUNT (COORDINATE WITH MILLWORK).
BASIC ELECTRICAL REQUIREMENTS: 1. GENERAL: ALL ELECTRICAL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE 2017 NATIONAL ELECTRICAL CODE (NEC) GENERAL: ALL ELECTRICAL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE 2017 NATIONAL ELECTRICAL CODE (NEC) AND NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) STANDARDS UNLESS MORE STRINGENT REQUIREMENTS ARE INDICATED. ALL ELECTRICAL WORK SHALL COMPLY WITH ADA RECOMMENDATIONS. ALL ELECTRICAL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER BY A LICENSED ELECTRICIAN, OR A CERTIFIED APPRENTICE WORKING UNDER THE DIRECT SUPERVISION OF A LICENSED ELECTRICIAN, USING THE BEST METHODS KNOWN TO THE TRADE AND SHALL PRESENT A NEAT AND PROFESSIONAL APPEARANCE WHEN COMPLETED. THE OWNER RESERVES THE RIGHT TO CHANGE, WITHOUT ADDITIONAL COST, THE LOCATION OF ANY APPARATUS OR OUTLET, PROVIDED SUCH CHANGE DOES NOT ADD MORE THAN 10 FT TO THE FEEDER AND IS ORDERED BEFORE INSTALLATION OF THE AFFECTED PORTION OF THE WORK IS COMMENCED. CONTRACTOR SHALL BRING ALL CONFLICTS ON THE DRAWINGS TO THE OWNERS ATTENTION FOR HIS RESOLUTION. SUCH RESOLUTION SHALL BE IMPLEMENTED WITH OUT COST TO THE OWNER. 2. THE CONTRACTOR SHALL SURVEY THE PROJECT SITE PRIOR TO THE BID TO ASSESS ACTUAL FIELD CONDITIONS. FAILURE TO THE CONTRACTOR SHALL SURVEY THE PROJECT SITE PRIOR TO THE BID TO ASSESS ACTUAL FIELD CONDITIONS. FAILURE TO PERFORM THIS INSPECTION BINDS THE CONTRACTOR TO PERFORM THE WORK WITH OUT EXTRA CHARGES DESPITE THE IGNORANCE OF REASONABLY ANTICIPATED CONDITIONS. 4. ROUGH-INS: THE CONTRACTOR SHALL VERIFY AND COORDINATE THE ROUGH-IN REQUIREMENTS OF EACH ITEM OF EQUIPMENT ROUGH-INS: THE CONTRACTOR SHALL VERIFY AND COORDINATE THE ROUGH-IN REQUIREMENTS OF EACH ITEM OF EQUIPMENT WITH THE CONTRACTOR SUPPLYING THE EQUIPMENT. 5. INSTALLATION: THE ELECTRICAL DRAWINGS INDICATE THE EXTENT AND GENERAL LOCATION AND ARRANGEMENT OF EQUIPMENT INSTALLATION: THE ELECTRICAL DRAWINGS INDICATE THE EXTENT AND GENERAL LOCATION AND ARRANGEMENT OF EQUIPMENT AND MATERIALS. THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL DETAILS OF THE WORK AND VERIFY ALL DIMENSIONS IN THE FIELD SO THAT EQUIPMENT AND MATERIALS WILL BE PROPERLY LOCATED AND READILY ACCESSIBLE. THE CONTRACTOR SHALL SEQUENCE, COORDINATE, AND INTEGRATE THE VARIOUS ELEMENTS OF ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS. COMPLY WITH THE FOLLOWING REQUIREMENTS: A. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS. B. COORDINATE ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS INSTALLATION WITH OTHER BUILDING COMPONENTS AND COORDINATE ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS INSTALLATION WITH OTHER BUILDING COMPONENTS AND TRADES. C. ARRANGE FOR CHASES, SLOTS, AND OPENINGS IN OTHER BUILDING COMPONENTS DURING PROGRESS OF CONSTRUCTION, ARRANGE FOR CHASES, SLOTS, AND OPENINGS IN OTHER BUILDING COMPONENTS DURING PROGRESS OF CONSTRUCTION, TO ALLOW FOR INSTALLATION OF ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS. D. SEQUENCE, COORDINATE, AND INTEGRATE INSTALLATION OF ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS FOR SEQUENCE, COORDINATE, AND INTEGRATE INSTALLATION OF ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS FOR EFFICIENT FLOW OF THE WORK. E. WHERE MOUNTING HEIGHTS ARE NOT INDICATED, INSTALL ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS TO PROVIDE WHERE MOUNTING HEIGHTS ARE NOT INDICATED, INSTALL ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS TO PROVIDE MAXIMUM HEADROOM POSSIBLE. F. INSTALL ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS TO CONFORM WITH APPROVED SUBMITTAL DATA TO THE INSTALL ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS TO CONFORM WITH APPROVED SUBMITTAL DATA TO THE GREATEST EXTENT POSSIBLE. CONFORM TO THE ARRANGEMENTS INDICATED ON THE ELECTRICAL DRAWINGS, RECOGNIZING THAT PORTIONS OF THE WORK ARE SHOWN ONLY IN DIAGRAMATIC FORM. WHERE COORDINATION REQUIREMENTS CONFLICT WITH INDIVIDUAL SYSTEM REQUIREMENTS, REFER CONFLICT TO THE ARCHITECT/ENGINEER OR OWNER'S REPRESENTATIVE FOR RESOLUTION. G. IN GENERAL, INSTALL ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS LEVEL AND PLUMB, PARALLEL AND IN GENERAL, INSTALL ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO BUILDING LINES AND/OR FEATURES AND/OR OTHER BUILDING SYSTEMS. H. INSTALL ELECTRICAL EQUIPMENT TO FACILITATE SERVICING, MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT INSTALL ELECTRICAL EQUIPMENT TO FACILITATE SERVICING, MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT AND COMPONENT PARTS. AS MUCH AS PRACTICAL, CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, WITH MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS. I. INSTALL ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS GIVING RIGHT-OF-WAY PRIORITY TO SYSTEMS REQUIRED TO INSTALL ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS GIVING RIGHT-OF-WAY PRIORITY TO SYSTEMS REQUIRED TO BE INSTALLED AT A SPECIFIC SLOPE(INCL. SPRINKLER SYSTEMS). 6. CUTTING AND PATCHING: ALL ELECTRICAL WORK SHALL BE CAREFULLY LAID OUT IN ADVANCE, AND WHERE CUTTING, CUTTING AND PATCHING: ALL ELECTRICAL WORK SHALL BE CAREFULLY LAID OUT IN ADVANCE, AND WHERE CUTTING, CHANNELING, CHASING, OR DRILLING OF FLOORS, WALLS, PARTITIONS, CEILINGS, OR OTHER SURFACES IS NECESSARY FOR THE PROPER INSTALLATION, SUPPORT, OR ANCHORAGE OF CONDUIT OR OTHER ELECTRICAL WORK, THIS WORK SHALL BE CAREFULLY DONE. ANY RESULTING DAMAGE TO THE BUILDING OR OTHER SYSTEMS, EQUIPMENT, OR MATERIALS SHALL BE REPAIRED BY SKILLED MECHANICS OF THE TRADES INVOLVED, AT NO ADDITIONAL COST TO THE OWNER. 7. PRODUCTS: SYSTEMS, EQUIPMENT, AND MATERIALS DESCRIBED ON THE ELECTRICAL DRAWINGS ESTABLISH THE MINIMUM PRODUCTS: SYSTEMS, EQUIPMENT, AND MATERIALS DESCRIBED ON THE ELECTRICAL DRAWINGS ESTABLISH THE MINIMUM STANDARDS FOR QUALITY AND STYLE AND SHALL BE THE BASIS OF THE BID. ALL SYSTEMS, EQUIPMENT, AND MATERIALS SHALL BE NEW AND SHALL BEAR THE UL LABEL OR BE UL LISTED, WHERE APPLICABLE, AND SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC AND NEMA STANDARDS. 8. SUBSTITUTIONS: WHERE SYSTEMS, EQUIPMENT, OR MATERIALS ARE SPECIFIED BY MANUFACTURER OR BRAND NAME AND CATALOG SUBSTITUTIONS: WHERE SYSTEMS, EQUIPMENT, OR MATERIALS ARE SPECIFIED BY MANUFACTURER OR BRAND NAME AND CATALOG NUMBER, SUCH SPECIFICATION SHALL ESTABLISH THE MINIMUM STANDARDS FOR QUALITY AND STYLE AND SHALL BE THE BASIS OF THE BID. SYSTEMS, EQUIPMENT, AND MATERIALS SO SPECIFIED SHALL BE FURNISHED UNDER THE CONTRACT UNLESS CHANGED BY WRITTEN AGREEMENT. SHOULD THE CONTRACTOR PROPOSE TO FURNISH PRODUCTS OTHER THAN THOSE SPECIFIED, AS PERMITTED BY "OR APPROVED EQUAL" CLAUSES, HE SHALL SUBMIT A WRITTEN REQUEST FOR SAID SUBSTITUTIONS THROUGH APPROPRIATE CHANNELS TO THE ARCHITECT/ENGINEER FOR HIS REVIEW. SUCH REQUEST SHALL BE ACCOMPANIED WITH COMPLETE DESCRIPTIVE LITERATURE INCLUDING, BUT NOT LIMITED TO, CATALOG CUT SHEETS, BROCHURES, CIRCULARS, SPECIFICATIONS, PERFORMANCE DATA, INSTALLATION INSTRUCTIONS, SHOP DRAWINGS, AND OTHER PRINTED INFORMATION IN SUFFICIENT DETAIL AND SCOPE TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF THE CONTRACT. DESCRIPTIVE LITERATURE ON PROPOSED SUBSTITUTIONS SHALL BE CLEAR, CONCISE, AND LOGICALLY ARRANGED. ALL DATA WHICH IS, AND IS NOT, APPLICABLE SHALL BE CLEARLY IDENTIFIED AS SUCH. IF REQUESTED, THE CONTRACTOR SHALL SUBMIT SAMPLES OF BOTH SPECIFIED AND PROPOSED ITEMS FOR INSPECTION. DESCRIPTIVE LITERATURE ON PROPOSED SUBSTITUTIONS SHALL BE RETURNED WITHOUT REVIEW IF NOT PROPERLY PREPARED. ACCEPTANCE OR REJECTION OF PROPOSED SUBSTITUTIONS SHALL BE UP TO THE DISCRETION OF THE ARCHITECT/ENGINEER AND/OR THE OWNER. 9. SUBMITTALS: THE CONTRACTOR SHALL FOLLOW THE GENERAL PROVISIONS OF THE CONTRACT AND ESTABLISHED PROCEDURES. SUBMITTALS: THE CONTRACTOR SHALL FOLLOW THE GENERAL PROVISIONS OF THE CONTRACT AND ESTABLISHED PROCEDURES. SUBMITTALS SHALL CONSIST OF COMPLETE DESCRIPTIVE LITERATURE INCLUDING, BUT NOT LIMITED TO, CATALOG CUT SHEETS, BROCHURES, CIRCULARS, SPECIFICATIONS, PERFORMANCE DATA, INSTALLATION INSTRUCTIONS, SHOP DRAWINGS, AND OTHER PRINTED INFORMATION IN SUFFICIENT DETAIL AND SCOPE TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF THE CONTRACT. DESCRIPTIVE LITERATURE SHALL BE CLEAR, CONCISE, AND LOGICALLY ARRANGED. ALL DATA WHICH IS, AND IS NOT, APPLICABLE SHALL BE CLEARLY IDENTIFIED AS SUCH. IF REQUESTED, THE CONTRACTOR SHALL SUBMIT SAMPLES OF SPECIFIED ITEMS FOR INSPECTION. DESCRIPTIVE LITERATURE SHALL BE RETURNED WITHOUT REVIEW IF NOT PROPERLY PREPARED. THE FOLLOWING SYSTEMS, EQUIPMENT, AND MATERIALS, AS A MINIMUM, REQUIRE SUBMITTALS: A. ANY PROPOSED SUBSTITUTIONS. ANY PROPOSED SUBSTITUTIONS. B. WIRING DEVICES. WIRING DEVICES. C. PANELBOARDS. PANELBOARDS. D. DISCONNECT SWITCHES. DISCONNECT SWITCHES. E. CIRCUIT BREAKERS. CIRCUIT BREAKERS. F. LIGHTING FIXTURES INCLUDING BALLASTS. LIGHTING FIXTURES INCLUDING BALLASTS. 10. RECORD DRAWINGS: THE CONTRACTOR SHALL MAINTAIN AT THE SITE A CLEAN, UNDAMAGED SET OF BLUE- OR BLACK-LINE RECORD DRAWINGS: THE CONTRACTOR SHALL MAINTAIN AT THE SITE A CLEAN, UNDAMAGED SET OF BLUE- OR BLACK-LINE WHITE PRINTS OF CONTRACT DRAWINGS. THIS RECORD SET OF CONTRACT DRAWINGS SHALL BE MARKED TO SHOW THE ACTUAL INSTALLATION AND WHERE THE ACTUAL INSTALLATION VARIES SUBSTANTIALLY FROM THE ELECTRICAL WORK AS ORIGINALLY SHOWN. MARK WHICHEVER DRAWINGS ARE MOST CAPABLE OF SHOWING CONDITIONS FULLY AND ACCURATELY. GIVE PARTICULAR ATTENTION TO CONCEALED ELEMENTS THAT WOULD BE DIFFICULT TO MEASURE AND RECORD AT A LATER DATE. MARK RECORD DRAWINGS WITH A RED ERASABLE PENCIL; USE OTHER COLORS TO DISTINGUISH BETWEEN VARIATIONS IN SEPARATE CATEGORIES OF THE ELECTRICAL WORK. NOTE CONTRACT MODIFICATIONS AND APPROVED SUBSTITUTIONS WHERE APPLICABLE. 11. PROTECTION OF INSTALLED SYSTEMS, EQUIPMENT, AND MATERIALS: PROTECT INSTALLED SYSTEMS, EQUIPMENT, AND MATERIALS PROTECTION OF INSTALLED SYSTEMS, EQUIPMENT, AND MATERIALS: PROTECT INSTALLED SYSTEMS, EQUIPMENT, AND MATERIALS FROM DAMAGE UNTIL FINAL ACCEPTANCE BY THE OWNER. REPAIR OR REPLACE, AT NO ADDITIONAL COST TO THE OWNER, DAMAGED SYSTEMS, EQUIPMENT, AND MATERIALS TO THE SATISFACTION OF THE ARCHITECT/ ENGINEER AND/OR OWNER. 12. CLEANING: UPON COMPLETION OF INSTALLATION, INSPECT INTERIOR AND EXTERIOR OF ALL ELECTRICAL EQUIPMENT. REMOVE CLEANING: UPON COMPLETION OF INSTALLATION, INSPECT INTERIOR AND EXTERIOR OF ALL ELECTRICAL EQUIPMENT. REMOVE PAINT SPLATTERS AND OTHER SPOTS, DIRT, AND DEBRIS. TOUCH-UP SCRATCHES AND MARS OF FINISH TO MATCH ORIGINAL FINISH. 13. CERTIFICATIONS: THE FOLLOWING SHALL BE OBTAINED AND SUBMITTED TO THE OWNER PRIOR TO FINAL PAYMENT: CERTIFICATIONS: THE FOLLOWING SHALL BE OBTAINED AND SUBMITTED TO THE OWNER PRIOR TO FINAL PAYMENT: A. ELECTRICAL SYSTEMS: A CERTIFICATE OF FINAL INSPECTION AND APPROVAL BY THE AUTHORITIES HAVING JURISDICTION. ELECTRICAL SYSTEMS: A CERTIFICATE OF FINAL INSPECTION AND APPROVAL BY THE AUTHORITIES HAVING JURISDICTION. 14. GUARANTEE: THE CONTRACTOR SHALL SUBMIT A WRITTEN GUARANTEE TO THE OWNER, PRIOR TO FINAL PAYMENT, THAT GUARANTEE: THE CONTRACTOR SHALL SUBMIT A WRITTEN GUARANTEE TO THE OWNER, PRIOR TO FINAL PAYMENT, THAT WARRANTS THE INSTALLATION SHALL REMAIN FREE OF DEFECTS FOR A PERIOD OF ONE YEAR AFTER FINAL ACCEPTANCE BY THE OWNER. THE GUARANTEE SHALL STATE THAT THE OWNER IS NOT LIABLE FOR PARTS AND LABOR COSTS INCURRED BY THE CONTRACTOR IN THE REPAIR OF ACTUAL PRODUCT OR INSTALLATION DEFECTS. THE GUARANTEE SHALL ALSO STATE THAT THE ON-SITE RESPONSE TIME TO REQUESTS FOR ASSISTANCE WILL BE 24 HOURS FOR NON-EMERGENCY CONDITIONS AND 2 HOURS FOR EMERGENCY CONDITIONS.
AutoCAD SHX Text
ELECTRICAL MATERIALS: 1. RACEWAYS: RACEWAYS: A. RIGID GALVANIZED STEEL (RGS) CONDUIT: ANSI C80.1 RIGID GALVANIZED STEEL (RGS) CONDUIT: ANSI C80.1 B. ELECTRICAL METALLIC TUBING (EMT) AND FITTINGS: ANSI C80.3 WITH COMPRESSION TYPE FITTINGS. ELECTRICAL METALLIC TUBING (EMT) AND FITTINGS: ANSI C80.3 WITH COMPRESSION TYPE FITTINGS. C. LIQUIDTIGHT FLEXIBLE METAL CONDUIT: UL 360. FLEXIBLE STEEL CONDUIT WITH PVC JACKET. LIQUIDTIGHT FLEXIBLE METAL CONDUIT: UL 360. FLEXIBLE STEEL CONDUIT WITH PVC JACKET. 2. BOXES: BOXES: A. SHEET METAL: NEMA OS 1. SHEET METAL: NEMA OS 1. B. CAST METAL: NEMA FB 1, TYPE FD, CAST FERALLOY BOX WITH GASKETED COVER. CAST METAL: NEMA FB 1, TYPE FD, CAST FERALLOY BOX WITH GASKETED COVER. C. HINGED COVER ENCLOSURES: NEMA 250, GALVANIZED STEEL ENCLOSURE WITH CONTINUOUS HINGE COVER, QUICK HINGED COVER ENCLOSURES: NEMA 250, GALVANIZED STEEL ENCLOSURE WITH CONTINUOUS HINGE COVER, QUICK RELEASE TYPE LATCHES, REMOVABLE INTERIOR PANEL, AND MANUFACTURER'S STANDARD GRAY ENAMEL INSIDE AND OUT. 3. WIRES AND CABLES: WIRES AND CABLES: A. CONDUCTOR MATERIAL: ANNEALED COPPER. CONDUCTOR MATERIAL: ANNEALED COPPER. B. INSULATION: THHN/THWN CONFORMING TO WC 5. INSULATION: THHN/THWN CONFORMING TO WC 5. C. CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED. MC CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLID; CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED. MC CABLE IS PERMITTED FOR BRANCH CIRCUITRY, AND SHALL UTILIZE SOLID CONDUCTORS. MC CABLE GROUND CONDUCTORS MUST BE INSULATED AND COPPER MATERIAL. MC QUICK OR EQUIVALENTS ARE NOT ACCEPTABLE. D. GROUND CONDUCTORS #10 AWG AND SMALLER SHALL HAVE GREEN THHN/THWN INSULATION. GROUND CONDUCTORS #10 AWG AND SMALLER SHALL HAVE GREEN THHN/THWN INSULATION. 4. WIRING DEVICES: WIRING DEVICES: A. GENERAL: GENERAL: a. RESIDENTIAL: RECEPTACLES SHALL LISTED TAMPER RESISTANT HUBBELL BR SERIES OR EQUAL. GFCI RESIDENTIAL: RECEPTACLES SHALL LISTED TAMPER RESISTANT HUBBELL BR SERIES OR EQUAL. GFCI RECEPTACLES SHALL BE LISTED TAMPER & WEATHER RESISTANT HUBBELL GF SERIES OR EQUAL. b. COMMERCIAL: HUBBELL CR SERIES OR EQUAL. COMMERCIAL: HUBBELL CR SERIES OR EQUAL. B. COLOR: WHITE, BLACK, GRAY, IVORY, OR BROWN TO BE AS SELECTED BY THE ARCHITECT/ ENGINEER AND/OR THE COLOR: WHITE, BLACK, GRAY, IVORY, OR BROWN TO BE AS SELECTED BY THE ARCHITECT/ ENGINEER AND/OR THE OWNER. C. RECEPTACLES: COMPLY WITH UL 498, "ELECTRICAL ATTACHMENT PLUGS AND RECEPTACLES, "HEAVY DUTY RECEPTACLES: COMPLY WITH UL 498, "ELECTRICAL ATTACHMENT PLUGS AND RECEPTACLES, "HEAVY DUTY SPECIFICATION GRADE EXCEPT AS OTHERWISE INDICATED. GROUND FAULT CIRCUIT INTERRUPTER (GFCI) TYPE RECEPTACLES SHALL COMPLY WITH UL 943, "GROUND FAULT CIRCUIT INTERRUPTERS," WITH INTEGRAL NEMA 5-20R DUPLEX RECEPTACLE DESIGNED FOR INSTALLATION IN A 2-3/4" DEEP DEVICE BOX WITHOUT ADAPTER. D. TOGGLE SWITCHES: 20A, 120-277V AC, QUIET TYPE, SPECIFICATION GRADE AND SHALL COMPLY WITH UL 20, TOGGLE SWITCHES: 20A, 120-277V AC, QUIET TYPE, SPECIFICATION GRADE AND SHALL COMPLY WITH UL 20, "GENERAL USE SNAP SWITCHES." SINGLE-POLE, TWO-POLE, THREE-WAY, AND FOUR-WAY AS INDICATED AND/OR REQUIRED. E. DEVICE PLATES: SINGLE AND COMBINATION TYPES WHICH MATE AND MATCH WITH CORRESPONDING WIRING DEVICES. DEVICE PLATES: SINGLE AND COMBINATION TYPES WHICH MATE AND MATCH WITH CORRESPONDING WIRING DEVICES. SMOOTH MATCHING NYLON IN ALL AREAS. F. MANUFACTURER: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS AS MANUFACTURED BY HUBBEL MANUFACTURER: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS AS MANUFACTURED BY HUBBEL INC., OR APPROVED EQUAL BY COOPER WIRING DEVICES. 5. GROUNDING: GROUNDING: A. GROUNDING AND BONDING PRODUCTS: OF TYPES INDICATED AND/OR OF SIZES AND RATINGS TO COMPLY WITH THE GROUNDING AND BONDING PRODUCTS: OF TYPES INDICATED AND/OR OF SIZES AND RATINGS TO COMPLY WITH THE NEC. WHERE TYPES, SIZES, RATINGS, AND QUANTITIES ARE IN EXCESS OF NEC REQUIREMENTS, THE MORE STRINGENT REQUIREMENTS AND THE GREATER SIZE, RATING, AND QUANTITY INDICATIONS SHALL GOVERN. B. CONDUCTOR MATERIAL: COPPER. CONDUCTOR MATERIAL: COPPER. C. WIRE AND CABLE CONDUCTORS: CONFORM TO NEC TABLE 8, EXCEPT AS OTHERWISE INDICATED, FOR CONDUCTOR WIRE AND CABLE CONDUCTORS: CONFORM TO NEC TABLE 8, EXCEPT AS OTHERWISE INDICATED, FOR CONDUCTOR PROPERTIES, INCLUDING STRANDING. D. CONNECTOR PRODUCTS: UL LISTED AND LABELED AS GROUNDING CONNECTORS FOR THE MATERIALS USED. CONNECTOR PRODUCTS: UL LISTED AND LABELED AS GROUNDING CONNECTORS FOR THE MATERIALS USED. 6. PANELBOARDS: PANELBOARDS: A. CIRCUIT BREAKERS: PROVIDE TYPE, RATING, AND FEATURES INDICATED. BOLT-ON EXCEPT WHERE PLUG-IN FOR USE CIRCUIT BREAKERS: PROVIDE TYPE, RATING, AND FEATURES INDICATED. BOLT-ON EXCEPT WHERE PLUG-IN FOR USE ON EXISTING PANELBOARDS(NOT BEING UPGRADED) TANDEM CIRCUIT BREAKERS SHALL NOT BE USED. MULTIPOLE CIRCUIT BREAKERS SHALL HAVE AN INTERNAL COMMON TRIP AND A SINGLE HANDLE. B. ENCLOSURES: NEMA TYPE 1, UNLESS OTHERWISE INDICATED. ENCLOSURES: NEMA TYPE 1, UNLESS OTHERWISE INDICATED. C. FRONT: SECURED TO BOX WITH CONCEALED TRIM CLAMPS EXCEPT AS INDICATED. FRONT FOR SURFACE MOUNTED FRONT: SECURED TO BOX WITH CONCEALED TRIM CLAMPS EXCEPT AS INDICATED. FRONT FOR SURFACE MOUNTED PANELBOARDS SHALL BE SAME DIMENSIONS AS BOX. D. DIRECTORY FRAME: METAL WITH CLEAR PLASTIC COVER MOUNTED ON INSIDE OF PANELBOARD DOOR. DIRECTORY FRAME: METAL WITH CLEAR PLASTIC COVER MOUNTED ON INSIDE OF PANELBOARD DOOR. E. BUS WORK: HARD DRAWN COPPER OF 98% CONDUCTIVITY. BUS WORK: HARD DRAWN COPPER OF 98% CONDUCTIVITY. F. MAIN AND NEUTRAL LUGS: COMPRESSION TYPE. MAIN AND NEUTRAL LUGS: COMPRESSION TYPE. G. EQUIPMENT GROUND BUS: ADEQUATE FOR FEEDER AND BRANCH CIRCUIT EQUIPMENT GROUND CONDUCTORS. BONDED EQUIPMENT GROUND BUS: ADEQUATE FOR FEEDER AND BRANCH CIRCUIT EQUIPMENT GROUND CONDUCTORS. BONDED TO BOX. H. PROVISIONS FOR FUTURE DEVICES: EQUIP WITH MOUNTING BRACKETS, BUS CONNECTION, AND NECESSARY PROVISIONS FOR FUTURE DEVICES: EQUIP WITH MOUNTING BRACKETS, BUS CONNECTION, AND NECESSARY APPURTENANCES, FOR THE CIRCUIT BREAKER AMPERE RATINGS INDICATED FOR FUTURE INSTALLATION OF DEVICES. I. MAIN AND SUBFEED LUGS: PROVIDE WHERE INDICATED. MAIN AND SUBFEED LUGS: PROVIDE WHERE INDICATED. J. NAMEPLATE: CUSTOM ENGRAVED PLASTIC LAMINATE, WHITE LETTERS ON BLACK FIELD, FOR EACH PANELBOARD NAMEPLATE: CUSTOM ENGRAVED PLASTIC LAMINATE, WHITE LETTERS ON BLACK FIELD, FOR EACH PANELBOARD MOUNTED WITH EPOXY OR INDUSTRIAL CEMENT OR ADHESIVE. K. MANUFACTURER: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS AS MANUFACTURED BY MANUFACTURER: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS AS MANUFACTURED BY SQUARE-D, CUTLER HAMMER CO., OR GENERAL ELECTRIC. 7. DISCONNECTS AND CIRCUIT BREAKERS: DISCONNECTS AND CIRCUIT BREAKERS: A. FUSIBLE SWITCH, 800A AND SMALLER: NEMA KS 1, TYPE HD, CLIPS TO ACCOMODATE SPECIFIED FUSES, ENCLOSURE FUSIBLE SWITCH, 800A AND SMALLER: NEMA KS 1, TYPE HD, CLIPS TO ACCOMODATE SPECIFIED FUSES, ENCLOSURE SUITABLE FOR THE ENVIRONMENT WHERE INSTALLED, HANDLE LOCKABLE WITH TWO (2) PAD LOCKS, AND INTERLOCKED WITH COVER IN "CLOSED" POSITION. ENCLOSURES SHALL COMPLY WITH NEMA KS 1; TYPE 1 INDOOR DRY LOCATIONS; B. MOLDED CASE CIRCUIT BREAKER: NEMA AB 1, HANDLE LOCKABLE WITH TWO (2) PADLOCKS. FRAME SIZE, TRIP RATING, MOLDED CASE CIRCUIT BREAKER: NEMA AB 1, HANDLE LOCKABLE WITH TWO (2) PADLOCKS. FRAME SIZE, TRIP RATING, NUMBER OF POLES, AND AUXILLARY DEVICES AS INDICATED. ENCLOSURES SHALL COMPLY WITH NEMA AB 1; TYPE 1. INDOOR DRY LOCATIONS. CIRCUIT BREAKERS SHALL HAVE A MINIMUM INTERRUPTING CAPACITY OF 10KAIC. C. MANUFACTURER: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS AS MANUFACTURED BY SQUARE-D, MANUFACTURER: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS AS MANUFACTURED BY SQUARE-D, CUTLER HAMMER CO., OR GENERAL ELECTRIC. 8. LIGHT FIXTURES (REFER TO FIXTURE SCHEDULE ON DRAWING E-101.)LIGHT FIXTURES (REFER TO FIXTURE SCHEDULE ON DRAWING E-101.)
AutoCAD SHX Text
ELECTRICAL METHODS: 1. WIRING METHODS: UNLESS OTHERWISE INDICATED, WIRING SHALL CONSIST OF CABLES AND WIRES INSTALLED IN RGS CONDUIT, WIRING METHODS: UNLESS OTHERWISE INDICATED, WIRING SHALL CONSIST OF CABLES AND WIRES INSTALLED IN RGS CONDUIT, EMT, LIQUIDTIGHT FLEXIBLE METAL CONDUIT AND MC CABLES. RACEWAYS SHALL BE CONCEALED WITHIN FINISHED WALLS AND CEILINGS UNLESS OTHERWISE INDICATED. OTHER THAN ROOF PENETRATIONS REQUIRED TO FEED ROOF MOUNTED EQUIPMENT, RACEWAYS WILL NOT BE ROUTED EXPOSED OUTSIDE OF THE BUILDING. 2. RACEWAYS: RACEWAYS SHALL BE PROVIDED WHERE INDICATED AND REQUIRED AND SHALL BE INSTALLED AS SPECIFIED BELOW, RACEWAYS: RACEWAYS SHALL BE PROVIDED WHERE INDICATED AND REQUIRED AND SHALL BE INSTALLED AS SPECIFIED BELOW, UNLESS OTHERWISE INDICATED. MINIMUM RACEWAY SIZE SHALL BE 3/4 IN. RGS CONDUIT SHALL BE USED FOR ALL OUTDOOR INSTALLATIONS. EMT SHALL BE USED FOR ALL INDOOR INSTALLATIONS. LIQUIDTIGHT FLEXIBLE METAL CONDUIT, 6 FT MAXIMUM LENGTH, SHALL BE USED FOR ALL CONDUIT TERMINATIONS AT EQUIPMENT SUBJECT TO VIBRATION. BUSHINGS, MANUFACTURED FITTINGS, OR BOXES PROVIDING EQUIVALENT MEANS OF PROTECTION SHALL BE INSTALLED ON THE ENDS OF ALL CONDUITS AND SHALL BE OF THE INSULATING TYPE WHERE REQUIRED BY THE N.E.C. ONLY LISTED ADAPTERS SHALL BE USED TO CONNECT EMT TO RGS CONDUIT AND CAST METAL BOXES AND CONDUIT BODIES. PENETRATIONS OF SLABS AND FIRE RATED WALLS SHALL BE FIRESTOPPED. KEEP RACEWAYS AT LEAST 6 IN. AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT WATER PIPING. INSTALL HORIZONTAL RACEWAY RUNS HIGHER THAN WATER AND STEAM PIPING. RACEWAYS CROSSING STRUCTURAL EXPANSION JOINTS SHALL BE PROVIDED WITH SUITABLE EXPANSION FITTINGS OR OTHER SUITABLE MEANS TO COMPENSATE FOR THE BUILDING EXPANSION AND CONTRACTION. RACEWAYS SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS AND FEATURES, MECHANICAL DUCT AND PIPING SYSTEMS, OR INTERSECTIONS OF VERTICAL PLANES AND CEILINGS. CHANGES IN DIRECTION OF RUNS SHALL BE ACCOMPLISHED WITH SYMMETRICAL BENDS OR CAST METAL FITTINGS. FIELD-MADE ELBOWS AND OFFSETS SHALL BE MADE WITH AN APPROVED HICKEY OR CONDUIT BENDING MACHINE. CRUSHED OR DEFORMED RACEWAY SHALL NOT BE INSTALLED. CARE SHALL BE TAKEN TO PREVENT THE LODGMENT OF DIRT, AND CONSTRUCTION MATERIALS AND DEBRIS IN RACEWAYS DURING THE COURSE OF CONSTRUCTION. CLOGGED RACEWAYS SHALL BE ENTIRELY FREED OF OBSTRUCTIONS OR SHALL BE REPLACED. RGS CONDUIT AND EMT SHALL BE SECURELY AND RIGIDLY FASTENED IN PLACE AT INTERVALS OF NOT MORE THAN 10 FT AND WITHIN 3 FT OF FITTINGS AND BOXES WITH APPROVED PIPE STRAPS, WALL BRACKETS, CONDUIT CLAMPS, CONDUIT HANGERS, THREADED C-CLAMPS, OR CEILING TRAPEZE. C-CLAMPS OR BEAM CLAMPS SHALL HAVE STRAP OR ROD TYPE RETAINERS. LOADS AN SUPPORTS SHALL BE COORDINATED WITH SUPPORTING STRUCTURES TO PREVENT DEFORMATION OR DAMAGE TO STRUCTURES, BUT NO LOAD SHALL BE APPLIED TO JOIST BRIDGING. FASTENINGS SHALL BE BY WOOD SCREWS OR SCREW TYPE NAILS TO WOOD; BY TOGGLE BOLTS ON HOLLOW CMU; BY EXPANSION BOLTS ON CONCRETE OR BRICK; AND BY MACHINE SCREWS, WELDED THREADED STUDS, HEAT TREATED OR SPRING STEEL TENSION CLAMPS ON STEEL WORK. NAIL TYPE NYLON ANCHORS OR THREADED STUDS DRIVEN IN BY A POWDER CHARGE AND PROVIDED WITH LOCK WASHERS AND NUTS MAY BE USED IN LIEU OF EXPANSION BOLTS OR MACHINE SCREWS. RACEWAYS OR PIPE STRAPS SHALL NOT BE WELDED TO STEEL STRUCTURES. IN PARTITIONS OF LIGHT STEEL CONSTRUCTION, SHEET METAL SCREWS MAY BE USED. CONDUIT SHALL NOT BE SUPPORTED USING WIRE OR NYLON TIES. RACEWAYS SHALL BE INSTALLED AS A COMPLETE SYSTEM AND BE INDEPENDENTLY SUPPORTED FROM THE STRUCTURE. UPPER RACEWAYS SHALL NOT BE THE SUPPORT OF LOWER RACEWAYS. SUPPORTING MEANS WILL NOT BE SHARED BETWEEN ELECTRICAL RACEWAYS AND MECHANICAL DUCTS OR PIPING. MOUNTING HARDWARE SHALL NOT PRESENT SHARP EDGES WHERE PERSONNEL CONTACT IS POSSIBLE. IN MECHANICAL SPACES, "MINERALAC" SUPPORTS SHALL NOT BE USED BELOW 10' A.F.F. 3. BOXES: BOXES SHALL BE PROVIDE IN RACEWAY SYSTEMS WHEREVER REQUIRED FOR PULLING OF WIRES, MAKING BOXES: BOXES SHALL BE PROVIDE IN RACEWAY SYSTEMS WHEREVER REQUIRED FOR PULLING OF WIRES, MAKING CONNECTIONS, AND MOUNTING OF DEVICES OR LIGHTING FIXTURES. IN GENERAL, BOXES SHALL BE CONSTRUCTED OF HOT-DIPPED GALVANIZED FINISHED SHEET STEEL. BOXES FOR METALLIC RACEWAYS, 4 IN. BY 4 IN. NOMINAL SIZE AND SMALLER, SHALL BE OF THE CAST METAL HUB TYPE AND GASKETED WHEN LOCATED OUTSIDE OF THE BUILDING. BOXES SHALL BE LISTED AS SUITABLE FOR THE ENVIRONMENTAL CONDITIONS OF THE LOCATION THEY ARE INSTALLED. BOXES FOR MOUNTING OF LIGHTING FIXTURES SHALL BE NOT LESS THAN 4 IN. SQUARE EXCEPT SMALLER BOXES SHALL BE INSTALLED WHERE REQUIRED BY FIXTURE CONFIGURATION. UNLESS OTHERWISE INDICATED, DEVICE BOXES FOR RECEPTACLES SHALL BE MOUNTED WITH THE CENTER OF THE DEVICE BOX APPROXIMATELY 18 IN. AFF. INDICATED, DEVICE BOXES FOR TOGGLE SWITCHES SHALL BE MOUNTED WITH THE CENTER OF THE DEVICE BOX APPROXIMATELY 48 IN. AFF. BOXES AND BOX SUPPORTS SHALL BE FASTENED TO WOOD WITH WOOD SCREWS OR SCREW TYPE NAILS OF EQUAL HOLDING STRENGTH, WITH BOLTS AND METAL EXPANSION SHIELDS ON CONCRETE AND BRICK, WITH TOGGLE BOLTS ON HOLLOW CMU, AND WITH MACHINE SCREWS OR WELDED STUDS ON STEEL WORK. THREADED STUDS DRIVEN IN BY POWDER CHARGE AND PROVIDED WITH LOCKWASHERS AND NUTS, OR NAIL TYPE NYLON ANCHORS MAY BE USED IN LIEU OF EXPANSION SHIELDS OR MACHINE SCREWS. HANGERS SHALL NOT BE FASTENED OR SUPPORTED FROM JOIST BRIDGING. 4. WIRES AND CABLES: EXAMINE RACEWAYS AND BUILDING FINISHES TO RECEIVE WIRES AND CABLES FOR COMPLIANCE WITH WIRES AND CABLES: EXAMINE RACEWAYS AND BUILDING FINISHES TO RECEIVE WIRES AND CABLES FOR COMPLIANCE WITH INSTALLATION TOLERANCES AND OTHER CONDITIONS. DO NOT PROCEED WITH INSTALLATION UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED. PULL WIRES AND CABLES INTO RACEWAY SIMULTANEOUSLY WHERE MORE THAN ONE IS BEING INSTALLED IN THE SAME RACEWAY. USE PULLING COMPOUND OR LUBRICANT WHERE NECESSARY; COMPOUND USED MUST NOT DETERIORATE CONDUCTORS OR INSULATION. USE PULLING MEANS, INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE WIRE/CABLE GRIPS THAT WILL NOT DAMAGE WIRES/CABLES OR RACEWAY. INSTALL EXPOSED CABLE, PARALLEL AND PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS AND FEATURES, MECHANICAL DUCT AND PIPING SYSTEMS, OR INTERSECTIONS OF VERTICAL PLANES AND CEILINGS. HORIZONTAL RUNS OF MC CABLE SHALL BE SUPPORTED ON 3 FT MAXIMUM CENTERS. VERTICAL RUNS OF MC CABLES SHALL BE SUPPORTED ON 6 FT MAXIMUM CENTERS. EXPOSED PLENUM CABLE SHALL BE SUPPORTED ON 3 FT MAXIMUM CENTERS. THE NUMBER OF SPLICES SHALL BE KEPT TO AN ABSOLUTE MINIMUM. WIRING AT EACH OUTLET SHALL BE INSTALLED WITH AT LEAST 8 IN. SLACK. BRANCH CIRCUIT CONDUCTORS SHALL BE A MINIMUM OF #12 AWG. FOR 120/208V CIRCUITS, WHERE THE DISTANCE EXCEEDS ONE HUNDRED FEET TO THE FIRST DEVICE, THE SIZE OF THE WIRES SHALL BE INCREASED FROM THAT SPECIFIED BY THE FOLLOWING AMOUNTS: LENGTH HOMERUN REMAINDER OF CIRCUIT HOMERUN REMAINDER OF CIRCUIT REMAINDER OF CIRCUIT 0 TO 100 FT. AS SPECIFIED AS SPECIFIED AS SPECIFIED AS SPECIFIED AS SPECIFIED 101 TO 175 FT. ONE STANDARD SIZE AS SPECIFIED ONE STANDARD SIZE AS SPECIFIED AS SPECIFIED 176 TO 300 FT. TWO STANDARD SIZES ONE STANDARD SIZE TWO STANDARD SIZES ONE STANDARD SIZE ONE STANDARD SIZE 301 TO 450FT. THREE STANDARD SIZES TWO STANDARD SIZES THREE STANDARD SIZES TWO STANDARD SIZES TWO STANDARD SIZES 5. WIRING DEVICES: INSTALL WIRING DEVICES WHERE INDICATED IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTALLATION WIRING DEVICES: INSTALL WIRING DEVICES WHERE INDICATED IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTION, APPLICABLE REQUIREMENTS OF THE NEC, AND RECOGNIZED INDUSTRY PRACTICES. INSTALL WIRING DEVICES IN DEVICE BOXES WHICH ARE CLEAN AND FREE FROM DIRT AND CONSTRUCTION MATERIALS AND DEBRIS. INSTALL WIRING DEVICES AFTER WIRING WORK IS COMPLETE. INSTALL DEVICE PLATES AFTER PAINTING WORK IS COMPLETE. TIGHTEN CONNECTORS AND TERMINALS, INCLUDING SCREWS AND BOLTS, IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. PRIOR TO ENERGIZING CIRCUITS, TEST WIRING FOR ELECTRICAL CONTINUITY AND SHORTS. ENSURE PROPER POLARITY OF CONNECTIONS IS MAINTAINED. SUBSEQUENT TO ENERGIZING, TEST WIRING DEVICES AND DEMONSTRATE COMPLIANCE WITH REQUIREMENTS. 6. GROUNDING: ELECTRICAL SYSTEMS AND EQUIPMENT, METALLIC RACEWAYS AND BOXES, CABLE SHIELDS, METALLIC CABLE GROUNDING: ELECTRICAL SYSTEMS AND EQUIPMENT, METALLIC RACEWAYS AND BOXES, CABLE SHIELDS, METALLIC CABLE SHEATHS AND ARMOR, AND OTHER NON-CURRENT CARRYING METALLIC PARTS OF EQUIPMENT SHALL BE GROUNDED IN CONFORMANCE WITH THE NEC. EQUIPMENT GROUND CONDUCTORS SHALL COMPLY WITH NEC ARTICLE 250 FOR SIZES AND QUANTITIES, EXCEPT WHERE LARGER SIZES AND/OR MORE CONDUCTORS ARE INDICATED. PROVIDE SEPARATE INSULATED GROUND CONDUCTOR IN ALL RACEWAYS, REGARDLESS OF RACEWAY TYPE. SEPARATELY DERIVED SYSTEMS AS DEFINED BY THE NEC SHALL BE GROUNDED IN CONFORMANCE WITH NEC ARTICLE 250 PARA. 26. TERMINATE EQUIPMENT GROUND WIRES FOR FEEDERS AND BRANCH CIRCUITS WITH PRESSURE TYPE GROUND LUGS. WHERE METALLIC CONDUITS TERMINATE AT METALLIC HOUSINGS WITHOUT MECHANICAL AND ELECTRICAL CONNECTION TO HOUSING, TERMINATE EACH CONDUIT WITH A GROUNDING BUSHING. CONNECT GROUNDING BUSHINGS WITH A GROUND WIRE TO THE GROUND BUS IN THE HOUSING. BOND ELECTRICALLY NONCONTINUOUS CONDUITS AT BOTH ENTRANCES AND EXITS WITH GROUNDING BUSHINGS AND GROUND WIRES. TIGHTEN GROUNDING AND BONDING CONNECTORS AND TERMINALS, INCLUDING SCREWS AND BOLTS, IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. 7. PANELBOARDS: INSTALL PANELBOARDS AND ACCESSORY ITEMS IN ACCORDANCE WITH NEMA PB 1.1, "GENERAL INSTRUCTIONS PANELBOARDS: INSTALL PANELBOARDS AND ACCESSORY ITEMS IN ACCORDANCE WITH NEMA PB 1.1, "GENERAL INSTRUCTIONS FOR PROPER INSTALLATION, OPERATION, AND MAINTENANCE OF PANELBOARDS RATED 600 VOLTS OR LESS," AND MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS. MOUNT PANELBOARDS PLUMB AND RIGID WITHOUT DISTORTION OF BOX AND WITH THE TOP OF THE TRIM AT 78 IN. AFF UNLESS OTHERWISE INDICATED. PROVIDE NEATLY TYPED AND ACCURATE CIRCUIT DIRECTORIES IN EACH PANELBOARD, REFLECTIVE OF FINAL CIRCUIT CONFIGURATION. PROVIDE FILLER PLATES IN ALL UNUSED SPACES. TRAIN WIRES IN PANELBOARDS GUTTERS NEATLY IN GROUPS, BUNDLE, AND WRAP WITH WIRE TIES. GROUND PANELBOARD IN CONFORMANCE WITH THE NEC. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, INCLUDING GROUNDING CONNECTIONS, IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. PERFORM INSULATION RESISTANCE TESTS OF PANELBOARD BUSES, COMPONENTS, AND FEEDER AND BRANCH CIRCUIT WIRING; INSULATION RESISTANCE LESS THAN 100 MEGOHM IS UNACCEPTABLE. 8. DISCONNECTS AND CIRCUIT BREAKERS: PROVIDE DISCONNECTS AND CIRCUIT BREAKERS WHERE INDICATED ON THE ELECTRICAL DISCONNECTS AND CIRCUIT BREAKERS: PROVIDE DISCONNECTS AND CIRCUIT BREAKERS WHERE INDICATED ON THE ELECTRICAL DRAWINGS AND/OR WHERE REQUIRED BY THE NEC, WHETHER INDICATED ON THE ELECTRICAL DRAWINGS OR NOT. INSTALL DISCONNECTS AND CIRCUIT BREAKERS PLUMB AND LEVEL AND IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS. UPON COMPLETION OF INSTALLATION OF DISCONNECTS AND CIRCUIT BREAKERS, ENERGIZE CIRCUITS AND DEMONSTRATE CAPABILITY AND COMPLIANCE WITH REQUIREMENTS. EXCEPT AS OTHERWISE INDICATED, DO NOT DEMONSTRATE DISCONNECTS AND CIRCUIT BREAKERS BY OPERATING THEM UNDER LOAD; HOWEVER, DEMONSTRATE DISCONNECT AND CIRCUIT BREAKER OPERATION THROUGH SIX OPENING/CLOSING CYCLES WITH CIRCUIT UNLOADED. OPEN DISCONNECT AND CIRCUIT BREAKER ENCLOSURES FOR INSPECTION OF INTERIOR, MECHANICAL AND ELECTRICAL CONNECTIONS, FUSE INSTALLATION IF APPLICABLE, AND FOR VERIFICATION OF TYPE AND RATING OF FUSES INSTALLED IF APPLICABLE. CORRECT DEFICIENCIES THEN RETEST TO DEMONSTRATE COMPLIANCE WITH REQUIREMENTS. REMOVE AND REPLACE DEFECTIVE UNITS WITH NEW UNITS AND RETEST. 9. LIGHTING FIXTURES: INSTALL FIXTURES WHERE, AND AT HEIGHTS, INDICATED IN ACCORDANCE WITH FIXTURE MANUFACTURER'S LIGHTING FIXTURES: INSTALL FIXTURES WHERE, AND AT HEIGHTS, INDICATED IN ACCORDANCE WITH FIXTURE MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS, REQUIREMENTS OF THE NEC, AND RECOGNIZED INDUSTRY PRACTICES. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, INCLUDING GROUND CONNECTIONS, IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. RECESSED OR SEMIRECESSED FIXTURES MAY BE SUPPORTED BY CEILING SUPPORT SYSTEM. INSTALL CEILING SUPPORT SYSTEM RODS OR WIRES AT A MINIMUM OF FOUR (4) RODS OR WIRES PER FIXTURE LOCATED NOT MORE THAN 6 IN. FROM FIXTURE CORNERS. FIXTURES WHICH ARE SMALLER THAN CEILING GRID SHALL BE CENTERED IN ACOUSTICAL CEILING PANEL AND SUPPORTED BY AT LEAST TWO (2) 3/4 IN. METAL CHANNELS SPANNING AND SECURED TO CEILING SYSTEM GRID TEE'S. FIXTURES WHICH LAY-IN CEILING GRID SYSTEM SHALL BE SECURED IN PLACE BY INSTALLATION OF CLIPS WHICH SECURELY FASTEN FIXTURE TO CEILING GRID TEE'S. SUPPORT SURFACE MOUNT FIXTURES GREATER THAN 2 FT IN LENGTH AT A POINT IN ADDITION TO THE OUTLET BOX FIXTURE STUD. UPON COMPLETION OF INSTALLATION AND JUST PRIOR TO DEMONSTRATION, CLEAN AND RELAMP FIXTURES. LAMP FIXTURES WITH SPECIFIED LAMPS IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTRUCTIONS. UPON COMPLETION OF INSTALLATION, DEMONSTRATE CAPABILITY AND COMPLIANCE WITH REQUIREMENTS. WHERE POSSIBLE, CORRECT MALFUNCTIONING FIXTURES AT THE SITE, THEN RETEST TO DEMONSTRATE COMPLIANCE; OTHERWISE, REMOVE MALFUNCTIONING UNITS AND REPLACE WITH NEW UNITS AND PROCEED WITH RETESTING. PRIOR TO FINAL ACCEPTANCE, ADJUST AIMABLE FIXTURES AS DIRECTED BY THE ARCHITECT/ENGINEER AND/OR OWNER.
AutoCAD SHX Text
TYPICAL BRANCH CIRCUITING HOME RUN SYMBOL. GENERALLY 15A BRANCH CIRCUITS CONSISTS OF (2) #14 AWG CU. AND (1) #14 AWG CU. GND. IN 3/4" CONDUIT AND 20A BRANCH CIRCUITS CONSISTS OF (2) #12 AWG CU. AND (1) #12 AWG CU. GND. IN 3/4" CONDUIT, UNLESS OTHERWISE NOTED. "#" IDENTIFIES PANEL BOARD CIRCUIT NUMBER. REFER TO CIRCUITING NOTES FOR SPECIFIC PANEL DESIGNATION.
AutoCAD SHX Text
ELECTRICAL POWER PANEL
AutoCAD SHX Text
M
AutoCAD SHX Text
ELECTROMAGNETIC DOOR HOLDER
AutoCAD SHX Text
20A, 120/277V AC, WALL MOUNTED OCCUPANCY SWITCH, SWITCH MOUNTING HEIGHT = 48" A.F.F. TO CENTER OF DEVICE BOX, U.O.N. SWITCH SHALL BE MODEL NUMBER AT1277W AS MANUFACTURED BY HUBBELL.
AutoCAD SHX Text
S
AutoCAD SHX Text
OC
AutoCAD SHX Text
COMBINATION TELE/DATA OUTLET CONSISTING OF ONE 4" SQUARE BOX, TILE RING (DEPTH AS REQUIRED), DEVICE PLATE (COLOR AS SPECIFIED BY ARCHITECT/ENGINEER AND/OR OWNER), AND 3/4" CONDUIT STUBBED UP INTO THE NEAREST ACCESSIBLE CEILING. MOUNTING HEIGHT=18" AFF TO THE CENTER OF DEVICE BOX UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
LOW VOLTAGE
AutoCAD SHX Text
HIGH VOLTAGE
AutoCAD SHX Text
KILOVOLT AMPERES
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
KILOWATTS
AutoCAD SHX Text
KILOVOLTS
AutoCAD SHX Text
HERTZ
AutoCAD SHX Text
HORSE POWER
AutoCAD SHX Text
HAND-OFF-AUTOMATIC
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
LV
AutoCAD SHX Text
KW
AutoCAD SHX Text
KV
AutoCAD SHX Text
KVA
AutoCAD SHX Text
JB
AutoCAD SHX Text
HZ
AutoCAD SHX Text
HV
AutoCAD SHX Text
HOA
AutoCAD SHX Text
HP
AutoCAD SHX Text
GRD
AutoCAD SHX Text
ABB.
AutoCAD SHX Text
DEFINITION
AutoCAD SHX Text
ABB.
AutoCAD SHX Text
DEFINITION
AutoCAD SHX Text
ABB.
AutoCAD SHX Text
DEFINITION
AutoCAD SHX Text
ABB.
AutoCAD SHX Text
DEFINITION
AutoCAD SHX Text
ABB.
AutoCAD SHX Text
DEFINITION
AutoCAD SHX Text
ABB.
AutoCAD SHX Text
DEFINITION
AutoCAD SHX Text
NC
AutoCAD SHX Text
NF
AutoCAD SHX Text
NIC
AutoCAD SHX Text
MTD
AutoCAD SHX Text
NEUT
AutoCAD SHX Text
DEFINITION
AutoCAD SHX Text
NO
AutoCAD SHX Text
NTS
AutoCAD SHX Text
OH
AutoCAD SHX Text
PB
AutoCAD SHX Text
PL
AutoCAD SHX Text
OHD
AutoCAD SHX Text
SS
AutoCAD SHX Text
ST
AutoCAD SHX Text
RMS
AutoCAD SHX Text
S/N
AutoCAD SHX Text
PVC
AutoCAD SHX Text
PNL
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
A
AutoCAD SHX Text
C
AutoCAD SHX Text
ABB.
AutoCAD SHX Text
A.F.F.
AutoCAD SHX Text
CAB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CKT
AutoCAD SHX Text
CL
AutoCAD SHX Text
DN
AutoCAD SHX Text
DT
AutoCAD SHX Text
DWG
AutoCAD SHX Text
E.C.
AutoCAD SHX Text
F
AutoCAD SHX Text
EWC
AutoCAD SHX Text
EX
AutoCAD SHX Text
EQUIP
AutoCAD SHX Text
FAS
AutoCAD SHX Text
EF
AutoCAD SHX Text
AMPERES
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
CABINET
AutoCAD SHX Text
CIRCUIT
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DRAWING
AutoCAD SHX Text
CURRENT LIMITING
AutoCAD SHX Text
DOUBLE THROW
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
FUSED
AutoCAD SHX Text
EXHAUST FAN
AutoCAD SHX Text
FIRE ALARM SYSTEM
AutoCAD SHX Text
ELECTRIC WATER COOLER
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
MOUNTED
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
OVERHEAD
AutoCAD SHX Text
NON-FUSED
AutoCAD SHX Text
PUSH BUTTON
AutoCAD SHX Text
NORMALLY CLOSED
AutoCAD SHX Text
NOT IN CONTRACT
AutoCAD SHX Text
NORMALLY OPEN
AutoCAD SHX Text
OVERHEAD DOOR
AutoCAD SHX Text
SAFETY SWITCH
AutoCAD SHX Text
SINGLE THROW
AutoCAD SHX Text
POLYVINYL CHLORIDE
AutoCAD SHX Text
ROOT MEAN SQUARE
AutoCAD SHX Text
SOLID NEUTRAL
AutoCAD SHX Text
PILOT LIGHT
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
SYS
AutoCAD SHX Text
TYP
AutoCAD SHX Text
TEL
AutoCAD SHX Text
UG
AutoCAD SHX Text
SWBD
AutoCAD SHX Text
SWGR
AutoCAD SHX Text
VOLTS
AutoCAD SHX Text
WIRE
AutoCAD SHX Text
UH
AutoCAD SHX Text
V
AutoCAD SHX Text
W
AutoCAD SHX Text
WP
AutoCAD SHX Text
U.O.N.
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
1P
AutoCAD SHX Text
2P
AutoCAD SHX Text
3P
AutoCAD SHX Text
AutoCAD SHX Text
FR
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
MCC
AutoCAD SHX Text
MH
AutoCAD SHX Text
MCM
AutoCAD SHX Text
MLO
AutoCAD SHX Text
MB
AutoCAD SHX Text
FRAME
AutoCAD SHX Text
MAIN BREAKER
AutoCAD SHX Text
MOUNTING HEIGHT
AutoCAD SHX Text
MAIN LUGS ONLY
AutoCAD SHX Text
THOUSAND CIRCULAR MILLS
AutoCAD SHX Text
MOTOR CONTROL CENTER
AutoCAD SHX Text
SWITCHBOARD
AutoCAD SHX Text
SWITCHGEAR
AutoCAD SHX Text
SYMMETRICAL
AutoCAD SHX Text
TELEPHONE
AutoCAD SHX Text
UNIT HEATER
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
ONE POLE
AutoCAD SHX Text
TWO POLE
AutoCAD SHX Text
THREE POLE
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
UNDERGROUND
AutoCAD SHX Text
SW
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
FBO
AutoCAD SHX Text
FURNISHED BY OTHERS
AutoCAD SHX Text
GROUND FAULT CURRENT INTERRUPTER
AutoCAD SHX Text
(R)
AutoCAD SHX Text
RELOCATED EQUIPMENT
AutoCAD SHX Text
ELECTRICAL ABBREVIATIONS:
AutoCAD SHX Text
S
AutoCAD SHX Text
T
AutoCAD SHX Text
120V-277V AC, BATH FAN / LIGHT SWITCH/ DELAY AND VENTILATION CONTROLLER. SWITCH MOUNTING HEIGHT = 48" A.F.F. TO CENTER OF DEVICE BOX, U.O.N. SWITCH MODEL SHALL BE SMARTEXHAUST AS MANUFACTURED BY AIRCYCLER.
AutoCAD SHX Text
1000 SQ. FT. COVERAGE CEILING MOUNTED OCCUPANCY SENSOR., 24V DC, DUAL TECHNOLOGY (ULTRASONIC AND PASSIVE INFRARED). SENSOR SHALL BE MODEL NUMBER LMDC-100 AS MANUFACTURED BY WATTSTOPPER OR EQUAL. FINISH SHALL BE SELECTED BY OWNER/ARCHITECT. OCCUPANCY SENSOR SHALL BE FED FROM DIGITAL ROOM CONTROLLER. CABLING BETWEEN CONTROLLER AND OCCUPANCY SENSOR SHALL BE CAT-5E CABLE WITH RJ45 CONNECTORS.
AutoCAD SHX Text
RC1
AutoCAD SHX Text
20A, 120V AC, 60HZ, DIGITAL ROOM CONTROLLER, SINGLE RELAY, UL LISTED, U.O.N. SWITCH SHALL BE MODEL NUMBER LMRC-101 AS MANUFACTURED BY WATTSTOPPER OR EQUAL. CABLING BETWEEN LOW VOLTAGE DEVICES AND DIGITAL ROOM CONTROLLER SHALL BE CAT-5E CABLE WITH RJ45 CONNECTORS. E.C. SHALL MOUNT DIGITAL ROOM CONTROLLER SECURELY ABOVE DROP CEILING IN ACCESSIBLE SPACE. ROOM CONTROLLER'S FED FROM EMERGENCY CIRCUITS SHALL BE PROVIDED WITH AN EMERGENCY BYPASS CONTROLLER. EMERGENCY BYPASS CONTROLLER SHALL BE MANUFACTURED BY WATTSTOPPER, MODEL ELCU-200. E.C. SHALL PROVIDE (1) ONE DIGITAL WIRELESS CONFIGURATION TOOL AS MANUFACTURED BY WATTSTOPPER, MODEL LMCT-100. THE DIGITAL CONFIGURATION TOOL SHALL BE USED TO PROGRAM THE DIGITAL ROOM CONTROLLERS.
AutoCAD SHX Text
OS
AutoCAD SHX Text
S
AutoCAD SHX Text
D
AutoCAD SHX Text
20A, 120-277V AC, DIGITAL SINGLE BUTTON WALL SWITCH. SWITCH MOUNTING HEIGHT = 48" A.F.F. TO CENTER OF DEVICE BOX, U.O.N. OCCUPANCY SWITCH SHALL BE #LMSW-100 AS MANUFACTURED BY WATTSTOPPER.
AutoCAD SHX Text
FLOOR BOX PROVIDE WITH (2)DUPLEX RECEPTACLES AND (2)ETHERNET CONNECTIONS. E.C. TO COORDINAE EXACT LOCATION IN FIELD. LEGRAND EVOLUTION SERIES EFBG-OG WITH METAL COVER TYPE SELECTED BY ARCHITECT ARCHITECT. PROVIDE POWER AND DATA CONDUITS TO WALL AND UP WALL TO AN ACCESSIBLE CEILING. DATA JACK AND CABLING BY OTHERS. PROVIDE RECEPTACLES AND BRANCH CIRCUIT WIRING.
AutoCAD SHX Text
F1
AutoCAD SHX Text
F2
AutoCAD SHX Text
FLOOR BOX FOR FURNITURE FEED. E.C. TO COORDINAE EXACT LOCATION IN FIELD. LEGRAND EVOLUTION SERIES EFB6 WITH FURNITURE FEED COVER METAL COLOR SELECTED BY ARCHITECT ARCHITECT. PROVIDE POWER AND DATA CONDUITS TO WALL AND UP WALL TO AN ACCESSIBLE CEILING. DATA JACK AND CABLING BY OTHERS. PROVIDE LIQUID TIGHT CONDUIT FOR CONNECTION TO FURNITURE.
AutoCAD SHX Text
F3
AutoCAD SHX Text
FLOOR BOX FOR A/V FURNITURE FEED. E.C. TO COORDINAE EXACT LOCATION IN FIELD. LEGRAND EVOLUTION SERIES EFB8 WITH FURNITURE FEED COVER, METAL COLOR SELECTED BY ARCHITECT ARCHITECT. PROVIDE POWER AND DATA CONDUITS TO WALL AND UP WALL TO AN ACCESSIBLE CEILING. DATA JACK AND CABLING BY OTHERS. PROVIDE LIQUID TIGHT CONDUIT FOR CONNECTION TO FURNITURE.
AutoCAD SHX Text
THE ELECTRICAL CONTRACTOR SHALL SECURE THE SERVICES OF AN OWNER-APPROVED LICENSED FIRE ALARM SYSTEMS CONTRACTOR TO MODIFY THE EXISTING BUILDING FIRE ALARM SYSTEM AS INDICATED HEREIN. ALL MODIFICATIONS TO THE EXISTING SYSTEM SHALL BE COORDINATED WITH THE OWNER'S FIRE OWNER'S FIRE ALARM SYSTEM VENDOR AND MONITORING STATION. MODIFICATIONS SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: 1. PROVISION OF NEW ADDRESSABLE DUCT SMOKE DETECTORS AS INDICATED. NEW DETECTORS SHALL BE PROVISION OF NEW ADDRESSABLE DUCT SMOKE DETECTORS AS INDICATED. NEW DETECTORS SHALL BE CONNECTED TO THE EXISTING BUILDING FIRE ALARM SYSTEM AND SHALL SHUT DOWN ASSOCIATED HVAC EQUIPMENT UPON ACTIVATION. 2. MODIFICATIONS TO THE EXISTING SYSTEM SHALL BE DOCUMENTED ON FULL SIZE DRAWINGS AND MODIFICATIONS TO THE EXISTING SYSTEM SHALL BE DOCUMENTED ON FULL SIZE DRAWINGS AND SUBMITTED ALONG WITH CUT SHEETS OF EQUIPMENT, DEVICES AND OTHER DESCRIPTIVE DATA TO THE AUTHORITY HAVING JURISDICTION FOR APPROVAL AS REQUIRED BY STATE AND LOCAL FIRE REGULATIONS PRIOR TO BEGINNING WORK. 3. PROGRAMMING OF NEW AND EXISTING SYSTEM COMPONENTS SHALL BE PROVIDED AS REQUIRED BY PROGRAMMING OF NEW AND EXISTING SYSTEM COMPONENTS SHALL BE PROVIDED AS REQUIRED BY FIRE ALARM CONTRACTOR.
AutoCAD SHX Text
RC2
AutoCAD SHX Text
20A, 120V AC, 60HZ, DIGITAL ROOM CONTROLLER, DUAL RELAY, UL LISTED, U.O.N. SWITCH SHALL BE MODEL NUMBER LMRC-101 AS MANUFACTURED BY WATTSTOPPER OR EQUAL. CABLING BETWEEN LOW VOLTAGE DEVICES AND DIGITAL ROOM CONTROLLER SHALL BE CAT-5E CABLE WITH RJ45 CONNECTORS. E.C. SHALL MOUNT DIGITAL ROOM CONTROLLER SECURELY ABOVE DROP CEILING IN ACCESSIBLE SPACE. ROOM CONTROLLER'S FED FROM EMERGENCY CIRCUITS SHALL BE PROVIDED WITH AN EMERGENCY BYPASS CONTROLLER. EMERGENCY BYPASS CONTROLLER SHALL BE MANUFACTURED BY WATTSTOPPER, MODEL ELCU-200. E.C. SHALL PROVIDE (1) ONE DIGITAL WIRELESS CONFIGURATION TOOL AS MANUFACTURED BY WATTSTOPPER, MODEL LMCT-100. THE DIGITAL CONFIGURATION TOOL SHALL BE USED TO PROGRAM THE DIGITAL ROOM CONTROLLERS.
AutoCAD SHX Text
A
AutoCAD SHX Text
FIXTURE TYPE
AutoCAD SHX Text
MANUFACTURER MODEL NO.
AutoCAD SHX Text
BALLASTS/DRIVERS
AutoCAD SHX Text
QTY.
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
INPUT VOLTS
AutoCAD SHX Text
INPUT VA
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
INPUT WATTS
AutoCAD SHX Text
1
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
2'x4' RECESSED LED ARCHITECTURAL TROFFER LUMINAIRE WITH EXTRUDED ALUMINUM FRAME AND WHITE FINISH. EM FIXTURES, INSTALL EMERGENCY LED BATTERY PACK.
AutoCAD SHX Text
30
AutoCAD SHX Text
COLUMBIA LIGHTING LCAT24-3500XWHEG-EDU-ELL14 (OR APPROVED EQUAL BY PHILIPS DAY-BRITE OR LITHONIA)
AutoCAD SHX Text
LED ARRAY 2650 LUMENS 3500K 80 CRI
AutoCAD SHX Text
HIGH POWER FACTOR LED DRIVER (0-10V DIMMING)
AutoCAD SHX Text
LIGHT SOURCE
AutoCAD SHX Text
D
AutoCAD SHX Text
1
AutoCAD SHX Text
-
AutoCAD SHX Text
6" DOWNLIGHT. EM FIXTURES, INSTALL EMERGENCY LED BATTERY PACK.
AutoCAD SHX Text
28
AutoCAD SHX Text
PRESCOLITE LTR-6RD-HL25L-DM1EM-LTR- GRD-T-HL35K8WD-SS (OR APPROVED EQUAL BY PHILIPS DAY-BRITE OR LITHONIA)
AutoCAD SHX Text
LED 2500 LUMENS 3500K 80 CRI
AutoCAD SHX Text
120
AutoCAD SHX Text
HIGH POWER FACTOR LED DRIVER (0-10V DIMMING)
AutoCAD SHX Text
UNIVERSALLY-MOUNTED SINGLE/DOUBLE FACE LED EXIT SIGN WITH WHITE THERMOPLASTIC HOUSING, RED STENCILED LETTERS, UNIVERSAL SNAP-IN CHEVRON ARROWS, MAINTENANCE-FREE NICKEL-CADMIUM BATTERY, TEST SWITCH AND SELF-TESTING DIAGNOSTICS. WHERE WALL MOUNTED, MOUNT BOTTOM OF SIGN 7'-6" A.F.F.
AutoCAD SHX Text
DUAL-LITE LXURWEI (OR APPROVED EQUAL BY PHILIPS CHLORIDE OR LITHONIA)
AutoCAD SHX Text
-
AutoCAD SHX Text
120
AutoCAD SHX Text
5
AutoCAD SHX Text
4
AutoCAD SHX Text
LED
AutoCAD SHX Text
-
AutoCAD SHX Text
X
AutoCAD SHX Text
SHOWER LIGHT
AutoCAD SHX Text
1
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
20
AutoCAD SHX Text
LED
AutoCAD SHX Text
B
AutoCAD SHX Text
HIGH POWER FACTOR LED DRIVER (0-10V DIMMING)
AutoCAD SHX Text
SHOWER LIGHT
AutoCAD SHX Text
A1
AutoCAD SHX Text
1
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
2'x2' RECESSED LED ARCHITECTURAL TROFFER LUMINAIRE WITH EXTRUDED ALUMINUM FRAME AND WHITE FINISH. EM FIXTURES, INSTALL EMERGENCY LED BATTERY PACK.
AutoCAD SHX Text
-
AutoCAD SHX Text
COLUMBIA LIGHTING LCAT22-3500XWHEG-EDU-ELL14 (OR APPROVED EQUAL BY PHILIPS DAY-BRITE OR LITHONIA)
AutoCAD SHX Text
LED ARRAY - LUMENS 3500K 80 CRI
AutoCAD SHX Text
HIGH POWER FACTOR LED DRIVER (0-10V DIMMING)
AutoCAD SHX Text
SCONCE
AutoCAD SHX Text
1
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
14
AutoCAD SHX Text
LED
AutoCAD SHX Text
F
AutoCAD SHX Text
HIGH POWER FACTOR LED DRIVER (0-10V DIMMING)
AutoCAD SHX Text
WALL SCONCE
AutoCAD SHX Text
INDUSTRIAL STRIP LIGHT
AutoCAD SHX Text
1
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
20
AutoCAD SHX Text
LED
AutoCAD SHX Text
C
AutoCAD SHX Text
HIGH POWER FACTOR LED DRIVER
AutoCAD SHX Text
CHAIN HUNG OR SURFACE MOUNTED INDUSTRIAL STRIP LIGHT, 12X48.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
ED101
ELECTRICAL
2ND FLOOR
DEMO POWER PLAN
GENERAL SHEET NOTES :
NEW KEYED SHEET NOTES :
1
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
ED101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
ED101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS B - DEMO PLAN
AutoCAD SHX Text
1. SEE SHEET E000 FOR ELECTRICAL LEGEND AND SEE SHEET E000 FOR ELECTRICAL LEGEND AND ABBREVIATIONS. 2. ELECTRICAL DESIGN IS BASED ON INFORMATION ELECTRICAL DESIGN IS BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS AND EXISTING DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-VERIFICATION OF EXISTING CONDITIONS PRIOR TO BEGINNING WORK, AND SHALL CONTACT DEDC, LLC IF FIELD CONDITIONS ARE FOUND TO DIFFER FROM THOSE INDICATED ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-IDENTIFICATION OF EXISTING CIRCUITS WHERE SOURCES ARE UNKNOWN. 3. SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS THAT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
E.C. SHALL REFER TO ARCHITECTURAL DRAWINGS FOR EXACT EXTENT OF SCOPE OF WORK.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
ED102
ELECTRICAL
2ND FLOOR
DEMO POWER PLAN
GENERAL SHEET NOTES :
NEW KEYED SHEET NOTES :
1
2
3
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
ED102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uGYM 263 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
ED102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMENS TOILET ROOM 285 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
ED102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMEN'S 247 & WOMEN'S 248 DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
ED102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uBREAK ROOM 271B - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
ED102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 255 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
ED102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 278 - DEMO PLAN
AutoCAD SHX Text
1. SEE SHEET E000 FOR ELECTRICAL LEGEND AND SEE SHEET E000 FOR ELECTRICAL LEGEND AND ABBREVIATIONS. 2. ELECTRICAL DESIGN IS BASED ON INFORMATION ELECTRICAL DESIGN IS BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS AND EXISTING DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-VERIFICATION OF EXISTING CONDITIONS PRIOR TO BEGINNING WORK, AND SHALL CONTACT DEDC, LLC IF FIELD CONDITIONS ARE FOUND TO DIFFER FROM THOSE INDICATED ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-IDENTIFICATION OF EXISTING CIRCUITS WHERE SOURCES ARE UNKNOWN. 3. SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS THAT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
E.C. SHALL REFER TO ARCHITECTURAL DRAWINGS FOR EXACT EXTENT OF SCOPE OF WORK. E.C. SHALL DEMOLISH AND REMOVE ALL EXISTING ELECTRICAL DEVICES. RECEPTACLE AND LIGHTING CIRCUIT SHALL BE REUSED FOR NEW WORK SCOPE. REFER TO NEW WORK PLANS FOR MORE INFORMATION. EXISTING LIGHTING CONTROLS TO REMAIN.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
ED103
ELECTRICAL
2ND FLOOR
DEMO LIGHTING PLAN
GENERAL SHEET NOTES :
NEW KEYED SHEET NOTES :
1
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
ED103
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
ED103
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS B - DEMO PLAN
AutoCAD SHX Text
1. SEE SHEET E000 FOR ELECTRICAL LEGEND AND SEE SHEET E000 FOR ELECTRICAL LEGEND AND ABBREVIATIONS. 2. ELECTRICAL DESIGN IS BASED ON INFORMATION ELECTRICAL DESIGN IS BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS AND EXISTING DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-VERIFICATION OF EXISTING CONDITIONS PRIOR TO BEGINNING WORK, AND SHALL CONTACT DEDC, LLC IF FIELD CONDITIONS ARE FOUND TO DIFFER FROM THOSE INDICATED ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-IDENTIFICATION OF EXISTING CIRCUITS WHERE SOURCES ARE UNKNOWN. 3. SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS THAT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
E.C. SHALL REFER TO ARCHITECTURAL DRAWINGS FOR EXACT EXTENT OF SCOPE OF WORK.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
ED104
ELECTRICAL
2ND FLOOR
DEMO LIGHTING PLAN
GENERAL SHEET NOTES :
1
2
NEW KEYED SHEET NOTES :
3
AutoCAD SHX Text
S
AutoCAD SHX Text
NC
AutoCAD SHX Text
A
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
DEMO RADIANT PANEL
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
NC
AutoCAD SHX Text
W
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
ED104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uGYM 263 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
ED104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMENS TOILET ROOM 285 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
ED104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uMEN'S 247 & WOMEN'S 248 DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
ED104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uBREAK ROOM 271B - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
ED104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 255 - DEMO PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
ED104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uTOILET ROOM 278 - DEMO PLAN
AutoCAD SHX Text
1. SEE SHEET E000 FOR ELECTRICAL LEGEND AND SEE SHEET E000 FOR ELECTRICAL LEGEND AND ABBREVIATIONS. 2. ELECTRICAL DESIGN IS BASED ON INFORMATION ELECTRICAL DESIGN IS BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS AND EXISTING DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-VERIFICATION OF EXISTING CONDITIONS PRIOR TO BEGINNING WORK, AND SHALL CONTACT DEDC, LLC IF FIELD CONDITIONS ARE FOUND TO DIFFER FROM THOSE INDICATED ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-IDENTIFICATION OF EXISTING CIRCUITS WHERE SOURCES ARE UNKNOWN. 3. SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS THAT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
E.C. SHALL REFER TO ARCHITECTURAL DRAWINGS FOR EXACT EXTENT OF SCOPE OF WORK. E.C. SHALL DEMOLISH AND REMOVE EXISTING LIGHTING. EXISTING LIGHTING CIRCUIT SHALL BE REUSED FOR NEW LIGHTING IN THIS AREA. REFER TO NEW WORK PLANS FOR MORE INFORMATION. EXISTING WALL PHONE TO REMAIN.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
E101
ELECTRICAL
2ND FLOOR
POWER PLANS
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
F1
AutoCAD SHX Text
TV
AutoCAD SHX Text
+72
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
F2
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
TV
AutoCAD SHX Text
+72
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
F1
AutoCAD SHX Text
TV
AutoCAD SHX Text
+72
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
+78
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
E101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
E101
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS B - FLOOR PLAN
AutoCAD SHX Text
GENERAL SHEET NOTES : 1. SEE SHEET E000 FOR ELECTRICAL LEGEND AND SEE SHEET E000 FOR ELECTRICAL LEGEND AND ABBREVIATIONS. 2. ELECTRICAL DESIGN IS BASED ON INFORMATION ELECTRICAL DESIGN IS BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS AND EXISTING DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-VERIFICATION OF EXISTING CONDITIONS PRIOR TO BEGINNING WORK, AND SHALL CONTACT DEDC, LLC IF FIELD CONDITIONS ARE FOUND TO DIFFER FROM THOSE INDICATED ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-IDENTIFICATION OF EXISTING CIRCUITS WHERE SOURCES ARE UNKNOWN. 3. SYMBOLS WITH LIGHT LINEWEIGHTS REPRESENT ITEMS SYMBOLS WITH LIGHT LINEWEIGHTS REPRESENT ITEMS THAT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
E102
ELECTRICAL
2ND FLOOR
POWER PLANS
AutoCAD SHX Text
2
AutoCAD SHX Text
OU
AutoCAD SHX Text
009S
AutoCAD SHX Text
IU
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+42
AutoCAD SHX Text
+78
AutoCAD SHX Text
+42
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
E102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UGYM 263 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
E102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UMENS TOILET ROOM 285 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
E102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UMEN'S 247 & WOMEN'S 248 FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
E102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UBREAK ROOM 271B - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
E102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UTOILET ROOM 255 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
E102
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UTOILET ROOM 278 - FLOOR PLAN
AutoCAD SHX Text
GENERAL SHEET NOTES : 1. SEE SHEET E000 FOR ELECTRICAL LEGEND AND SEE SHEET E000 FOR ELECTRICAL LEGEND AND ABBREVIATIONS. 2. ELECTRICAL DESIGN IS BASED ON INFORMATION ELECTRICAL DESIGN IS BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS AND EXISTING DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-VERIFICATION OF EXISTING CONDITIONS PRIOR TO BEGINNING WORK, AND SHALL CONTACT DEDC, LLC IF FIELD CONDITIONS ARE FOUND TO DIFFER FROM THOSE INDICATED ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-IDENTIFICATION OF EXISTING CIRCUITS WHERE SOURCES ARE UNKNOWN. 3. SYMBOLS WITH LIGHT LINEWEIGHTS REPRESENT ITEMS SYMBOLS WITH LIGHT LINEWEIGHTS REPRESENT ITEMS THAT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
E103
ELECTRICAL
2ND FLOOR
LIGHTING PLANS
GENERAL SHEET NOTES :
AutoCAD SHX Text
C
AutoCAD SHX Text
X
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
F
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
RC1
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
E103
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS A - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
E103
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%uOFFICE RENOVATIONS B - FLOOR PLAN
AutoCAD SHX Text
1. SEE SHEET E000 FOR ELECTRICAL LEGEND AND SEE SHEET E000 FOR ELECTRICAL LEGEND AND ABBREVIATIONS. 2. ELECTRICAL DESIGN IS BASED ON INFORMATION ELECTRICAL DESIGN IS BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS AND EXISTING DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-VERIFICATION OF EXISTING CONDITIONS PRIOR TO BEGINNING WORK, AND SHALL CONTACT DEDC, LLC IF FIELD CONDITIONS ARE FOUND TO DIFFER FROM THOSE INDICATED ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-IDENTIFICATION OF EXISTING CIRCUITS WHERE SOURCES ARE UNKNOWN. 3. SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS THAT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
Rittenhouse Station250 South Main Street, Suite 109
Newark, DE 19711302.369.3700
7/2
0/2
02
0 9
:3
2:1
3 A
MB
IM
3
60
://D
HS
S - S
myrn
a R
en
ova
tio
n/2
02
01
41
00
_R
20
.rvt
DBCDEDC
10.19.2021
2020141.00
SMYRNA, DE
DHSS STATE
HEALTH
OPERATIONS
CENTER
Mark Date Description
Dan B. Cordle, P.E.
DE # 25081
07/09/21
AS NOTED
1 09.16.2020 ISSUED FOR AAB
REVIEW
2 10.23.2020 DFM 90% REVIEW
Dan B. Cordle, P.E.
DE # 25081
07/09/21
3 10.19.2021 ISSUED FOR BID
E104
ELECTRICAL
2ND FLOOR
LIGHTING PLANS
GENERAL SHEET NOTES :
NEW KEYED SHEET NOTES :
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
1
AutoCAD SHX Text
A1
AutoCAD SHX Text
S
AutoCAD SHX Text
1
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
1
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
1
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
1
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
1
AutoCAD SHX Text
LVD
AutoCAD SHX Text
S
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
RC1
AutoCAD SHX Text
OS
AutoCAD SHX Text
1
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
1
AutoCAD SHX Text
E104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UGYM 263 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
2
AutoCAD SHX Text
E104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UMENS TOILET ROOM 285 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
3
AutoCAD SHX Text
E104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UMEN'S 247 & WOMEN'S 248 FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
4
AutoCAD SHX Text
E104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UBREAK ROOM 271B - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
5
AutoCAD SHX Text
E104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UTOILET ROOM 255 - FLOOR PLAN
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
6
AutoCAD SHX Text
E104
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
%%UTOILET ROOM 278 - FLOOR PLAN
AutoCAD SHX Text
1. SEE SHEET E000 FOR ELECTRICAL LEGEND AND SEE SHEET E000 FOR ELECTRICAL LEGEND AND ABBREVIATIONS. 2. ELECTRICAL DESIGN IS BASED ON INFORMATION ELECTRICAL DESIGN IS BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS AND EXISTING DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-VERIFICATION OF EXISTING CONDITIONS PRIOR TO BEGINNING WORK, AND SHALL CONTACT DEDC, LLC IF FIELD CONDITIONS ARE FOUND TO DIFFER FROM THOSE INDICATED ON DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD-IDENTIFICATION OF EXISTING CIRCUITS WHERE SOURCES ARE UNKNOWN. 3. SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS SYMBOLS WITH LIGHT LINE WEIGHTS REPRESENT ITEMS THAT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
NEW LIGHTING FIXTURES SHALL BE POWERED UTILIZING EXISTING LIGHTING CIRCUIT.