8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
1/14
LV C a pa c itor CLMD03 P ow er Module
Instruction manual
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
2/14
2 Ta ble of co ntents CLMD03 P ow er Module Instruction ma nual
Table of Contents
1 Safet y ....................................................................................................................... 32 Upon reception ....................................................................................................... 3
2.1 Inspe ction on reception ......................................................................................... 3 2.2 S torag e- tra nspo rtation hand ling ........................................................................ 3
3 Hardware Description ............................................................................................ 43.1 CLMD03 P ow er mod ule layo ut ............................................................................. 43.2 CLMD03 po w er mod ule dimensions ..................................................................... 5
4 Power module installat ion ..................................................................................... 64.1 Mecha nica l insta lla tion .......................................................................................... 64.2 Airflow a nd co oling requirement ........................................................................... 7 4.3 Elec trica l Insta lla tion .............................................................................................. 9
4.3.1 Elec trica l connec tion o verview ..................................................................... 94.3.2 Ca ble s izing ................................................................................................... 9 4.3.3 Contactor for capacitor switching............................................................... 104.3.4 Earthing ....................................................................................................... 104.3.5 Fuses ........................................................................................................... 10
5 Commissioning ..................................................................................................... 116 Operation ............................................................................................................... 117 Maintenance .......................................................................................................... 118 Detailed technic al specific ation .......................................................................... 12
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
3/14
CLMD03 P ow er Module Instruction manua l Safety Upon reception 3
B efore insta lla tion, rea d this notice c a refully a nd keep it a t dispos a l of peop le in cha rge
of installation, maintenance and operation.
1 Safety
For a s a fe use of C LMD ca pa citor units, pleas e ensure:
Installation and maintenance are undertaken only by authorized and qualified
personnel, in accordance with current local regulations;
Iso la te the e q uipment from the s upply b efore wo rking
Wa it 5 min. a fter iso la ting s upply before ha ndling.
After 5 min, s hort-circuit the ca pa citor termina ls w ith a piec e o f insula ted ca ble to
confirm discharge.
Failure to respect the safety rules may lead to bodily injury, premature
failure, or other material damage to installations.
2 Upon reception2.1 Inspection on reception Inspect the pac king a nd immediately report a ny da mag es
Unpac k the CLMD03 P OWER MODULE and c heck tha t:
data on the label correspond to those of your purchase order
CLMD03 POWER MODULE is not d am ag ed. Any loss or dama gesho uld b e notified immediately to your closes t ABB a gent.
2.2 Storage- t ransportation handling
Indoo r, in d ry, d ust free a nd no n-corros ive environments, protected fromvibrations or shoc ks.
S torag e in initial pa cking is reco mmended
S torag e temperature:
minimum: -40 C/-40 F.
ma ximum: 75 C/167 F.
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
4/14
4 Ha rdwa re des cription CLMD03 P ow er Module Instruction manua l
3 Hardware Description3.1 CLMD03 Power module layout
Two types of C LMD03 P OWER MODULES exist:
CLMD03 POWER MODULE to be connected with a reactor.
CLMD03 POWER MODULE to be connected without reactor.
CLMD03 P ow er Module to b e c onnected w ith a rea ctor
1. Contactor2. Ca bles from c ap a citor to co ntac tor (provided )3. Disc harge resisto r4. Fuses &fuse holder5. Capacitor
CLMD03 Pow er Module to be connec ted w ithout rea ctor
1. Contactor2. Ca bles from co ntac tor to fuse (provided )3. Ca bles from c ap ac itor to conta ctor (provided )4. Discharge Resistor5. Fuses &fuse holder6. Capacitor
Please refer to 4.3.1 for the electrical drawings that present the parts included or not for
both versions of the produc t.
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
5/14
CLMD03 Power Module Instruction manual Hardware description 5
3.2 CLMD03 power module dimensions
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
6/14
6 P ow er mod ule insta lla tion CLMD03 P ow er Module Instruction ma nual
4 Power module installation4.1 Mechanical installation
CLMD03 Power Module must be f ixed VERTICALLY so as to allow airf low
circulation (see blue arrows in the figure below).
C LMD03 POWER MODULE mus t be fixed o n a rigid pla te/frame w ith four M6 sc rew s ,
nuts and washers (not provided).
Make sure that the rigidity of the support and the screws are sufficient to bear the weight(a bo ut 9 kg ) of t he C LMD03 P OWER MODULE(s).
CLMD03 POWER MODULE can be mounted in 2 different positions: totally inside its
enclosure or partly external to the enclosure as illustrated at the next page.
Clearances : 25 mm to wa lls a nd fla nge to fla nge be twee n modules.
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
7/14
CLMD03 Power Module Instruction manual Power module installation 7
CLMD03 P ow er Mod ule to ta lly mounted inside its enc los ure
The ca pac itor of the power mod ule must b e locate d ina specific air duct (vertical row) with forced ventilation(refer to4.2 Airflow a nd co oling req uirement)withcylindrical links vertical.
The othe r co mpone nts of the CLMD03 POWER
MODULE (co ntac tor, fuses , discha rge resisto r andca bles) must b e co oled with forced a ir co oling a s w ell.
Rules of goo d prac tice:
When reactors are used they should be placed in sucha wa y that they do not rad iate heat d irectly on theca pa citors. A thermal barrier is recommend ed
CLMD03 P ow er Mod ule mo unted pa rtly outs ide its e nclosure
In such mo unting, C apa citor cylinders a re loca tedoutside the enc los ure.
Cylinders a re naturally a ir cooled a s they a re orientedoutside the enc los ure.
Cylinders must not be heated by external source ofheat.
A clearanc e d ista nce o f minimum 25 mm must berespected between the cylinders and the wall.
Inside the enc los ure, the other compo nents o f the
CLMD03 P OWER MODULE (co ntac tor, fuse, discha rgeresistor and cables) must also be cooled with forced aircooling (refer to4.2 Airflow a nd c oo ling req uirement)
4.2 Airflow and cooling requirementThe service conditions specified in the IEC 608311 4 are applicable.
As per IEC 60831-1 3.21, the ambient temperature for capacitors is the
temperature around t he capacitors itself and not around the cubicle.
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
8/14
8 P ow er mod ule insta lla tion CLMD03 P ow er Module Instruction ma nual
CLMD03 P ow er Mod ule to ta lly mounted inside its enc los ure
Internal ca pa citors rea r view
The cros s-se ction of air inlet a nd outlet must be a da pted to the a ir flow .
Air should flow from the bo ttom to the top of the c ubicle a s illustrated onthe oppo site picture.
One fan per 6 PMOD03 columns blowing a minimum air flow of 420 m/h isrequested.
Design guideline:
Difference be twe en a mbient temperature outs ide the c ubicle a ndmea sured temperature must be lower than 22.5 C. To meet tha treq uirement, the temperature probe must b e loca ted a t a bo ut 2/3 of the a irduct, a ttac hed to the ce ntra l cylinder of the CLMD03 POWER MODULE, asper (1) of present drawing.
CLMD03 P ow er Mod ule mo unted pa rtly outs ide its e nclosure
External ca pac itors left view
CLMD03 ca pac itor cylinders a re na tural a ir cooled.
Air must circulate freely around the c ylinders a t lea st one mete r below a ndabove them without any other source of heat around them.
Inside the c ubicle, an a ir forced ventila tion has to be ensured by a fan of170 m/h.
Note:The use of a n over temperature protec tion c a n be performed by the RVT
tempera ture probe in order to s witch the ba nk off in ca se of fan fa ilure or over
tempera ture due to other ca uses .
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
9/14
CLMD03 Power Module Instruction manual Power module installation 9
4.3 Electrical Installation4.3.1 Electrical connection overviewCLMD03 Pow er Module to be connec ted w ithoutreactor
CLMD03 P ow er Module to b e co nnectedwithout reactor
1. Capacitor2. Ca ble from c a pac itor to co ntac tor (provided )3. Contactor4. Ca ble from c onta ctor to fuse (provided )5. Fuse
1. Capacitor2. Ca ble from c a pac itor to co ntac tor (provided )3. Contactor4. Ca ble from c onta ctor to rea ctor (not provided )5. Reactor (not provided)6. Cable from reactor to fuse (not provided)7. Fuse
4.3.2 Cable sizingThe c a bles mus t be s ized for a c urrent o f 1.5 times nom ina l current (In) minimum.
The nominal current c a n be ca lculated w ith the follow ing formula :
=
3
Where:
Qn is the ca pa citor ra ted reac tive pow er
Vn is the capacitor rated voltage
The tempera ture a round the ca bles must also b e c onsidered a cc ording to c a ble
manufacturer.
Note: In case of CLMD03 POWER MODULE connected without reactor, it is necessary
to add additional inductance to attenuate the inrush peak current. A practical method for
making a dd itiona l inducta nce is s imply ma de by w inding the c a bles des igned to c onnect
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
10/14
10 P ow er mod ule insta llation CLMD03 Power Module Instruction manual
the P ow er Mod ule onto a c ylinder. For more de ta ils p lea s e refer to the Attenuation of
the Inrush P ea k cha pter of the ABB UA conta ctor ma nual.
4.3.3 Contactor for capacitor switchingCa pac itor sw itching lea ds to trans ient operating cond itions.
Therefore, the use o f standa rd contac tors is not a cc eptab le and c a n be da ngerous for
the sa fety of people a s well a s the insta lla tions.The ABB UA50 and UA75 contac tors a re s pecially d esigned to co ntrol capa citors w hose
inrus h current pea ks a re les s than o r eq ual to 100 times nomina l rms c urrent.
P lea se refer to the ABB conta ctors for ca pac itor sw itching a pplica tion g uide for the
co nductors dimensions a s well a s the a dditiona l inducta nce in ca se of inrush current
peak.
4.3.4 EarthingEarthing is a chieved throug h fixa tion p oints of the CLMD03 POWER MODULE.
An extra c a ble betw een the C LMD03 POWER MODULE enclos ure a nd the ea rthing
co ntac t of the insta lla tion is therefore req uired in ca se the C LMD03 P OWER MODULE
unit is fixed to an isolating material.
4.3.5 FusesThe fuses a re ma de with non-iso la ted g ripping lugs, double indica tor and co ntac t blades
comp lia nt to DIN VDE 0636 P a rt 201 and IEC 60269-2-1. The NH sys tem is c la s s ed
a mong plug-in fuse s ystems
M8 cable shoes are fixed with M8 screw and nuts (both not provided) on the fuse
terminal.
While tightening the bo lt, a ded ica ted torq ue must be a pplied for proper electrica lco nnection ac co rding to the applica ble sta nda rds .
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
11/14
CLMD03 Power Module Instruction manual Commissioning Operation - Maintenance 11
5 CommissioningWith the eq uipment isolate d from the supply, che ck:
Cabling is properly connected (including earth)
Ambient ventila tion is a deq uate
Correct tightness of the co nnections
6 OperationThe C LMD03 P OWER MODULE ca pa c itor unit is de livered w ith fac tory-ins ta lled
disc harge resistors to comply with IEC 60831 a nd a llow a dec rea se of the residua l
volta ge to less than 50V a fter 1 min. disc onnec tion from supply.
During o peration, ma ke sure the de la y be fore the CLMD03 is re-energized is not s horter
than 40 sec. Failure to follow this rule may cause damage and reduce the lifetime of the
capacitor.
Like other standard capacitor units, CLMD03 POWER MODULE discharge
devices are not suitable for use with rapid switc hing rates like thyristor
switc hed banks (minimum off time: 40 sec).
Additional external resistors are not a solution for such cases. Only specially designed
capacitors must be used in such applications. Please contact ABB.
Installation of capacitors on networks disturbed by harmonics may require special
preca utions e spec ia lly w hen there is a risk of resonanc e phenomena. P lea se ensure that
your installation is as per the over current rating as per IEC 60831 Standard. Please
co ntac t ABB for technica l support.
Harmonics
7 MaintenanceEnsure s a fety proced ures are co mpleted (see para graph S a fety)
Maintenance freq uency d epends on w orking cond itions.
At least a yearly maintenance should include:
Removal of dust d epos its, cleaning o f a ll parts;
Check of tightness of all electrical connections;
Check of ambient temperature;
Chec k condition of disc harge res istors.
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
12/14
12 Deta iled tec hnica l spe cifica tion CLMD03 P ow er Module Instruction ma nual
8 Detailed technical specificationVoltage range 400V and 415V at 50Hz
380V and 480V at 60Hz
For other values, pleas e co nsult us
Connection Three-phas e
Net output powe r QN 25 or 50 kvar
Disc harge resistors Included
Discharge: less than 50V in 1 minute
Terminals Fuse: M8 threa ded terminals
Co ntac tor: UA50 and UA75
Earth Earth connec tion on the enc los ure flang e
M6
Case material Aluminum
Color Raw aluminum
Fixing Four slots for M6 screws (12x7mm) on the upper flange
Execution Indoor
P rotection deg ree (a cc ording to IEC 60529) IP 00
Weight Approx. 9 kg
Maximum a mbient temperature Class D according to IEC60831:
Maximum averag e over 1 yea r: 35C
Maximum averag e over 24h: 45C
Maximum: 55C
Minimum ambient temperature -25C
Fuse ABB gG or gL 50, 63, 100 and 125 A
Contactor ABB UA50 for 25kvar
ABB UA75 for 50 kvar
Co ntrol voltag e:
230V at 50Hz
120V at 60Hz
Clearance 25 mm minimum to walls
Flange to flang e betw een pow er modules
Ca pac itor loss es Less tha n 0.5 W/kvar (disc ha rge res is tor los se s included )
Contactor and fuses loss es With UA50 co nta c tor: 0.53 W/kvar
With UA75 co nta c tor: 0.82 W/kvar
Tolerance on ca pac itanc e 0% + 10 %
Capacitor voltage test Between terminals:
2.15xUn for 10 sec onds
Betw een terminals a nd ea rth:
3kV for 10 sec : Un 450V
4kV for 10 sec: Un > 450V
Lightning impulse voltage :
8 kV: Un 690V
8/12/2019 2GCS204011A0030 - CLMD03 Power Module Manual
13/14
CLMD03 Power Module Instruction manual Detailed technical specification 13
Overload capability
(according to IEC 60831)
Overvoltage tolerance: 10% for maximum 8h in every 24ha nd 30% for ma ximum 1min
Maximum permiss ible c urrent: 1.3x In.
Altitude Up to 1000m
Compliance IEC 60831 part 1 &2
CE marked
Dimensions
Cooling If the ca pa citors are place d exte rnally: natural cooling for ca pa citorsand force d air cooling for internal pa rts
If the ca pa citors are place d internally: forced air cooling
Label