2012 IFGC Design, Installation and Inspection Principles 12/11/2017 Copyright 2011 International Code Council 1 2012 International Fuel Gas Code ® Design, Installation and Inspection Principles 2012 International Fuel Gas Code ® Design, Installation and Inspection Principles Based on the 2012 International Fuel Gas Code ® Overview Overview Administration Definitions General regulations Gas piping installations Chimneys and vents Specific appliances 2012 IFGC Design, Installation and Inspection Principles 2 Seminar Goal Seminar Goal The goal of this is for you to apply the 2012 International Fuel Gas Code to the design, plan review, installation and inspection of all fuel-gas- related construction. 2012 IFGC Design, Installation and Inspection Principles 3 Page 1 Objectives Objectives Upon completion, participants will be better able to: Locate general topics in the 2012 IFGC. Locate applicable tables in the 2012 IFGC for specific situations. Apply code requirements to clear-cut real world situations. Explain the intent behind a given code requirement. Use judgment to identify borderline scenarios as compliant or noncompliant. 2012 IFGC Design, Installation and Inspection Principles 4 Page 1
57

2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

Sep 24, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 1

2012 International Fuel Gas Code® Design, Installation and Inspection Principles

2012 International Fuel Gas Code® Design, Installation and Inspection Principles

Based on the 2012 International Fuel Gas Code®

OverviewOverview Administration Definitions General regulations Gas piping installations Chimneys and vents Specific appliances

2012 IFGC Design, Installation and Inspection Principles 2

Seminar GoalSeminar Goal The goal of this is for you to apply the 2012

International Fuel Gas Code to the design, plan review, installation and inspection of all fuel-gas-related construction.

2012 IFGC Design, Installation and Inspection Principles 3Page 1

ObjectivesObjectives Upon completion, participants will be better able

to: Locate general topics in the 2012 IFGC. Locate applicable tables in the 2012 IFGC for specific

situations. Apply code requirements to clear-cut real world

situations. Explain the intent behind a given code requirement. Use judgment to identify borderline scenarios as

compliant or noncompliant.

2012 IFGC Design, Installation and Inspection Principles 4Page 1

Page 2: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 2

Chapter 1Scope and Administration Chapter 1Scope and Administration

Module 1

AdministrationAdministration

“Due Process of Law” The responsibilities of

the various professionals are also established:

The code official reviews the proposed work for code compliance.

As a public servant, the code official enforces the code in an unbiased, proper manner.

The design professional designs a safe, operational fuel gas system.

The contractor installs the system in strict accordance with the plans and/or manufacturer’s installation requirements.

2012 IFGC Design, Installation and Inspection Principles 6Page 5

Applicability - 102Applicability - 102 Codes and standards referenced in

Chapter 8 shall be considered part of the requirements of this code. Provisions of this code shall apply, where

conflicts occur between the provisions of this code and the referenced standards.

2012 IFGC Design, Installation and Inspection Principles 7Page 6

Chapter 2DefinitionsChapter 2Definitions

Module 2

Page 3: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 3

DefinitionsDefinitions APPLIANCE. Any

apparatus or device that utilizes a fuel or raw material to produce light, heat, power, refrigeration or air conditioning.

2012 IFGC Design, Installation and Inspection Principles 9Page 9

DefinitionsDefinitions

COMBUSTIBLE ASSEMBLY. Wall, floor, ceiling or other assembly constructed of one or more component materials that are not defined as noncombustible.

COMBUSTIBLE MATERIAL. Any material not defined as noncombustible.

2012 IFGC Design, Installation and Inspection Principles 10Page 9

DefinitionsDefinitions

EXCESS FLOW VALVE (EFV). A valve designed to activate when the fuel gas passing through it exceeds a prescribed flow rate.

2012 IFGC Design, Installation and Inspection Principles 11Page 10

DefinitionsDefinitions

FLASHBACK ARRESTOR CHECK VALVE. A device that will prevent the backflow of one gas into the supply system of another gas and prevent the passage of flame into the gas supply system.

2012 IFGC Design, Installation and Inspection Principles 12Page 10

Page 4: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 4

DefinitionsDefinitions NONCOMBUSTIBLE MATERIALS. Materials

tested in accordance with ASTM E 136, have at least three of four specimens tested meeting the following criteria:

2012 IFGC Design, Installation and Inspection Principles 13

1. The recorded temperature of the surface and interior thermocouples shall not at any time during the test rise more than 54ºF (30ºC) above the furnace temperature at the beginning of the test.

2. Shall not be flaming from the specimen after the first 30 seconds.

3. If the weight loss of the specimen during testing exceeds 50 percent, the recorded temperature of the surface and interior thermocouples shall not at any time during the test rise above the furnace air temperature at the beginning of the test, and there shall not be flaming of the specimen.

Page 11

DefinitionsDefinitions REGULATOR, PRESSURE. A device placed in

a gas line for reducing, controlling and maintaining the pressure in that portion of the piping system downstream of the device.

2012 IFGC Design, Installation and Inspection Principles 14Page 11

DefinitionsDefinitions REGULATOR, SERVICE PRESSURE. For

natural gas systems, a device installed by the serving gas supplier to reduce and limit the service line pressure to delivery pressure.

2012 IFGC Design, Installation and Inspection Principles 15Page 11

DefinitionsDefinitions THIRD-PARTY

CERTIFICATION AGENCY. An approved agency operating a product or material certification system that incorporates initial product testing, assessment and surveillance of a manufacturer's quality control system.

2012 IFGC Design, Installation and Inspection Principles 16Page 11

Page 5: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 5

DefinitionsDefinitions THIRD-PARTY CERTIFIED. Certification

obtained by the manufacturer indicating that the function and performance characteristics of a product or material have been determined by testing and ongoing surveillance by an approved third-party certification agency.

2012 IFGC Design, Installation and Inspection Principles 17Page 11

DefinitionsDefinitions THIRD-PARTY TESTED.

Procedure by which an approved testing laboratory provides documentation that a product, material or system conforms to specified requirements.

2012 IFGC Design, Installation and Inspection Principles 18Page 12

DefinitionsDefinitions1. ____ Third-Party

Certified

2. ____ Regulator Service Pressure

3. ____ Excess Flow Valve (EFV)

2012 IFGC Design, Installation and Inspection Principles 19

4. ____ Third-Party Tested

5. ____ Flashback Arrestor Check Valve

6. ____ Third-Party Certification Agency

E.

F.

A.

B.

D.

C.

Page 13

Chapter 3General RegulationsChapter 3General Regulations

Module 3

Page 6: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 6

General Regulations Chapter 3General Regulations Chapter 3 Governs the approval

and installation of equipment and appliances.

2012 IFGC Design, Installation and Inspection Principles 21Page 15

General Regulations/RequirementsGeneral Regulations/Requirements In accordance with other codes Labeling Structural safety Combustion, ventilation, dilution air Clearance reduction for required clearances

2012 IFGC Design, Installation and Inspection Principles 22Page 15

ConsistencyConsistency

International Building Code (IBC) International Mechanical Code (IMC) International Energy Conservation Code

(IECC) International Plumbing Code (IPC) Listed Appliances Manufacturer’s Instructions

2012 IFGC Design, Installation and Inspection Principles 23Page 15

Listed and labeled – 301.3Listed and labeled – 301.3 The code intends that appliances be installed

and used in a manner consistent with the nature of their listing. This will prevent an appliance from being used in an application other than for what it was listed.

2012 IFGC Design, Installation and Inspection Principles 24Page 15

Page 7: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 7

Appliance Labeling and Listing -301.5Appliance Labeling and Listing -301.5 Required information Manufacturer’s name or

trademark Model number Serial number Hourly rating in Btu/h (W) Type of fuel Seal or mark of testing

agency Minimum clearance

requirements

2012 IFGC Design, Installation and Inspection Principles 25Page 15-16

Label and ListingLabel and Listing

2012 IFGC Design, Installation and Inspection Principles 26

Trane Co.

TUE 080 A936KZ

N315TK1ZG

80,000

Natural Gas

AGA

ANSI Z21.47-2003

Page 17

Manufacturer: ___________________________ Model number: __________________________ Serial number: __________________________ Hourly rating in Btu/hr (W): ________________ Type of fuel: ____________________________ Testing agency:__________________________ Test Standard: ________________________

Flood Hazard – 301.11Flood Hazard – 301.11 Section 1612 of the IBC for utilities and

attendant equipment. For structures located in flood hazard areas,

the appliance, equipment and system installations shall be located at or above the elevation required.

2012 IFGC Design, Installation and Inspection Principles 27Page 18

Structural Integrity – 302 Structural Integrity – 302 Installation of fuel gas piping systems and

appliances must not affect: Structural integrity of building components Fire-resistive integrity of building components

Cutting, notching and drilling of structural members and penetration of assemblies must be regulated.

2012 IFGC Design, Installation and Inspection Principles 28Page 18

Page 8: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 8

Cutting and Notches in Wood StudsCutting and Notches in Wood Studs

2012 IFGC Design, Installation and Inspection Principles 29Page 18

Bored Hole RequirementsBored Hole Requirements

2012 IFGC Design, Installation and Inspection Principles 30Page 18

Structural IntegrityStructural Integrity

Identify what is wrong

2012 IFGC Design, Installation and Inspection Principles 31Page 20

Structural IntegrityStructural Integrity

Identify what is wrong.

2012 IFGC Design, Installation and Inspection Principles 32Page 20

Page 9: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 9

Structural IntegrityStructural Integrity

Identify what is wrong.

2012 IFGC Design, Installation and Inspection Principles 33Page 20

Appliance Location Appliance Location

Hazardous locations(Section 303.2)

Appliances shall not be located in hazardous locations unless listed and approved for such use.

Closets and alcoves(Sections 303.5)

Furnaces and boilers installed in closets and alcoves must be listed for such installation

Outdoor installations(Section 303.6)

.Appliances installed outdoors must be listed for such installation

2012 IFGC Design, Installation and Inspection Principles 34Page 21

Prohibited Locations – 303.3 Prohibited Locations – 303.3

Fuel-fired appliance shall not be located in: Sleeping rooms Bathrooms Toilet rooms Storage closets Surgical rooms

2012 IFGC Design, Installation and Inspection Principles 35Page 21

Prohibited LocationsProhibited Locations Five exceptions

1. Direct-vent appliances.2. Vented room heaters, wall furnaces, vented

decorative appliances or decorative appliances.

3. A single wall-mounted, unvented room heater with an input rating 6000 Btu/hr installed in a bathroom.

2012 IFGC Design, Installation and Inspection Principles 36Page 21

Page 10: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 10

Prohibited LocationsProhibited Locations

Five exceptions (cont.)4. A single-listed, wall-mounted, unvented room

heater with an input rating 10,000 Btu/hr. 5. Appliances in a dedicated enclosure in which

all combustion air is taken directly from the outdoors.

2012 IFGC Design, Installation and Inspection Principles 37Page 21

Prohibited Locations – 303.3Prohibited Locations – 303.3

2012 IFGC Design, Installation and Inspection Principles 38Page 22

Appliance locations

Protection from Vehicle Impact –303.4Protection from Vehicle Impact –303.4

2012 IFGC Design, Installation and Inspection Principles 39Page 22

Appliance Protected from Vehicle Impact

Appliance LocationAppliance Location1. A water heater is located in a closet that

is accessed through a bathroom. All combustion air is taken from the building interior in full compliance with Section 304.5.

2012 IFGC Design, Installation and Inspection Principles 40Page 23

YES or NO

Page 11: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 11

Appliance LocationAppliance Location2. A wall-mounted, unvented room heater is

installed in a bedroom with exterior walls. The heater has a oxygen depletion safety shutoff device and the bedroom has the volume required by Section 304.5. The input rating of the heater is 11,000 Btu/hr.

2012 IFGC Design, Installation and Inspection Principles 41Page 23

YES or NO

Combustion, Ventilation, and Dilution Air – 304 Combustion, Ventilation, and Dilution Air – 304 Gas utilization equipment requires air for

combustion, ventilation and dilution of flue gases

Requirements assure: Proper air supply for the combustion and venting

process Ventilation cooling for appliances

2012 IFGC Design, Installation and Inspection Principles 42Page 24

Reliability of Air Supply –304.4Reliability of Air Supply –304.4

Maintenance of appropriate relationships Choice of appliance

location / contaminated atmospheres Advantages of direct-

vent appliances

2012 IFGC Design, Installation and Inspection Principles 43Page 24

Free Area of an Opening –304.10 Free Area of an Opening –

304.10

2012 IFGC Design, Installation and Inspection Principles 44Page 25

Page 12: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 12

Decision Tree for Combustion AirDecision Tree for Combustion Air

2012 IFGC Design, Installation and Inspection Principles 45Page 26

Indoor Combustion Air –304.5Indoor Combustion Air –304.5

To determine if volume of spaces meets combustion air demand of appliances:1. Determine type (s) of appliance (s)2. Determine input rating for appliances3. Determine if air change rate (ACR) is known4. Determine volume calculation method to use5. Calculate the required volume for each

appliance.

2012 IFGC Design, Installation and Inspection Principles 46Page 27

Indoor Combustion Air –304.5Indoor Combustion Air –304.5

To determine if volume of spaces meets combustion air demand:6. Find available volume of room or rooms. 7. Determine if makeup air required for exhaust

systems, clothes dryers, etc.. 8. Add the calculated volumes and compare the

total required volume to the available volume. 9. Determine if available volume is sufficient.

Determine if spaces need to be combined to increase available volume.

2012 IFGC Design, Installation and Inspection Principles 47Page 27

Indoor Combustion Air CalculationIndoor Combustion Air Calculation

2012 IFGC Design, Installation and Inspection Principles 48Page 28

Page 13: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 13

Indoor Combustion Air CalculationIndoor Combustion Air Calculation

1. Calculate required volume for each boiler (Equation 3-2).

2. Calculate required volume for each water heater (Equation 3-1).

3. Total volumes required for all appliancesBoiler 1 5,350Boiler 2 5,350Water heater 1 4,500

+ Water heater 2 4,500Total: 19,700 ft.3

2006 IFGC Design, Installation and Inspection Principles 49Page 28

Indoor Combustion Air CalculationIndoor Combustion Air Calculation

4. Determine available (actual) volume in building Basement volume 48ft. X 25ft. X 9ft. = 10,800 ft3

Grade-floor volume 48ft. X 25ft. X 9ft. = 10,800 ft3

5. Louvered door opening area adequate? Determine actual louvered opening. Section 304.10

30 in. x 72 in. = 2,160 in2 x .25 = 540 in2

Determine required area. Section 304.5.2 (400,000 Btu/h / 1,000) x 2 = 800 in.

2006 IFGC Design, Installation and Inspection Principles 50Page 29

Indoor Combustion Air CalculationIndoor Combustion Air Calculation

Combined volume (both stories) > Required Louvered door opening area: Inadequate Possible Solutions?

2006 IFGC Design, Installation and Inspection Principles 51Page 29

Adding outdoor openings in accordance with Section 304.7 or providing metal louvers in

the door instead of wood.

Mechanical Combustion Air CalculationMechanical Combustion Air Calculation

Calculate required airflow rate for combustion air fan (304.9)

2012 IFGC Design, Installation and Inspection Principles 52Page 30

Page 14: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 14

Mechanical Combustion Air CalculationMechanical Combustion Air Calculation

1. Total appliance input rating:

2. Total input Btu/h / 1000 Btu/h x 0.35 CFM

2012 IFGC Design, Installation and Inspection Principles 53Page 30

= 750,000 Btu/h

= 262.5 CFM

Combined Indoor/Outdoor Air – 304.7Combined Indoor/Outdoor Air – 304.7

2006 IFGC Design, Installation and Inspection Principles 54Page 31

Combined Indoor/Outdoor Air – 304.7Combined Indoor/Outdoor Air – 304.7

Required volume of room = 9,000 ft.3

Actual room volume = 8,000 ft.3

Ratio of available to required = 0.89 Outdoor size reduction factor = 0.11 Area of boiler vent connector = 56.5 in2

Actual required size = 6.6 in2

Minimum area must be = 9 in2

2006 IFGC Design, Installation and Inspection Principles 55Pages 31-32

Combustion Air Ducts – 304.11 Combustion Air Ducts – 304.11

In general, combustion air ducts must: Be composed of corrosion-resistant material. Terminate in an unobstructed space. Serve a single appliance enclosure. Not serve both upper / lower combustion

openings.

2012 IFGC Design, Installation and Inspection Principles 56Page 32

Page 15: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 15

Combustion Air Ducts – 304.11 Combustion Air Ducts – 304.11

In general, combustion air ducts must: (cont.) Maintain separation between openings at air

source. Not be screened where terminating in attic. Not be sloped. Duct openings to outdoors are at least 12

inches above grade.

2012 IFGC Design, Installation and Inspection Principles 57Page 32

Contaminated Atmospheres –304.12 Contaminated Atmospheres –304.12 If Indoor combustion air

is contaminated or, Contamination of

occupancy is anticipated

Then Outdoor combustion

air must be provided

2012 IFGC Design, Installation and Inspection Principles 58Page 32

Installation – 305.1 Installation – 305.1 Installation instructions must be available: On site At time of inspection

If the code and manufacturer’s instructions disagree: the most restrictive provision must prevail

2012 IFGC Design, Installation and Inspection Principles 59Page 33

Elevation of Ignition Source –305.3 Elevation of Ignition Source –305.3

Elevate appliances so that the ignition source is no less than 18 inches above floor in:

Hazardous locations. Public garages. Private garages. Repair garages. Motor fuel-dispensing

facilities. Parking garages.

2012 IFGC Design, Installation and Inspection Principles 60Page 33

Page 16: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 16

Installation in Residential Garages – 305.3.1Installation in Residential Garages – 305.3.1

2012 IFGC Design, Installation and Inspection Principles 61Page 34

Elevation of Appliances Not Required

Garage InstallationGarage InstallationPublic Garages(Section 305.4)

Private Garages(Section 305.5)

8 feet (2438 mm) above floor 6 feet (1829 mm) above floor

Where the motor vehicles are capable of passing under an appliance, the

appliance must be installed at the clearance required by the manufacture

and not less than 1 foot (305 mm) higher than the tallest vehicle garage

door opening.If appliances are protected from motor

vehicle impact, are installed in accordance with NFPA 30A, and the

ignition source elevation requirements of this code are met, the 8-foot (2438 mm)

height requirement does not apply.

If appliances are protected from motorvehicle impact and the ignition sourceelevation requirements of this code are

met, the 6-foot (1829 mm) height requirement does not apply.

2012 IFGC Design, Installation and Inspection Principles 62Page 34

Garage InstallationsGarage Installations

2012 IFGC Design, Installation and Inspection Principles 63Page 35

Public Garages

Garage InstallationsGarage Installations

2012 IFGC Design, Installation and Inspection Principles 64Page 35

Garage Space vs. Living Space

Page 17: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 17

Equipment and appliances on roof or elevated structures – 306.5Equipment and appliances on roof or elevated structures – 306.5

2012 IFGC Design, Installation and Inspection Principles 65Page 36

Guards – 306.6Guards – 306.6

2012 IFGC Design, Installation and Inspection Principles 66Page 37

Guards

Guards – 306.6 Guards – 306.6

2012 IFGC Design, Installation and Inspection Principles 67

Roof Plan View

Page 37

Scope - 308.1 Scope - 308.1 For the purposes of this code, gypsum

board is identified as a combustible material, as it is in the IMC.

2012 IFGC Design, Installation and Inspection Principles 68Page 38

Page 18: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 18

Clearance Reduction - Table 308.2 Clearance Reduction - Table 308.2

2012 IFGC Design, Installation and Inspection Principles 69Page 38-39

Clearance ReductionClearance Reduction

Rooms considered large in comparison with size of equipment Assemblies listed for such appliances are also

permitted. Linear interpolation is permitted between distances in

Table 308.2. Reduced clearances below range of the table are not

permitted. Clearances shall not be reduced where reduction is

specifically prohibited by the terms of the appliance or equipment listing.

2012 IFGC Design, Installation and Inspection Principles 70Page 38

Electrical Bonding – 310 Electrical Bonding – 310

2012 IFGC Design, Installation and Inspection Principles 71Page 40

Gas Pipe Bonding by Appliance Branch Circuit

Corrugated Stainless Steel Tubing (CSST) – 310.1.1 Corrugated Stainless Steel Tubing (CSST) – 310.1.1

2012 IFGC Design, Installation and Inspection Principles 72Page 41

CSST Bonding

Page 19: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 19

Corrugated Stainless Steel Tubing (CSST) – 310.1.1 Corrugated Stainless Steel Tubing (CSST) – 310.1.1

2012 IFGC Design, Installation and Inspection Principles 73Page 42

Alternate Location for Bonding Clamp

Chapter 4Gas Piping InstallationsChapter 4Gas Piping Installations

Module 4

Scope IncludesScope Includes

Design Materials Components Installation Fabrication

Assembly Testing Inspection Operation

2012 IFGC Design, Installation and Inspection Principles 75Pages 43-45

Gas Piping InstallationGas Piping Installation Addresses the intent to minimize hazards

associated with the use and distribution of highly flammable fuel gas.

2012 IFGC Design, Installation and Inspection Principles 76Page 45

Page 20: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 20

Identification - 401.9Identification - 401.9 Each length of pipe or

tubing and each pipe fitting must have the manufacturer's identification.

2012 IFGC Design, Installation and Inspection Principles 77Page 46

Third-party testing and certification - 401.10Third-party testing and certification - 401.10 All piping, tubing and fittings shall comply with

the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9.

Piping, tubing and fittings shall either be tested by an approved third-party testing agency or certified by an approved third-party certification agency.

2012 IFGC Design, Installation and Inspection Principles 78Page 46

Plan ReviewPlan Review

Sized to accommodate full utilization of all the gas utilization equipment in the plan simultaneously.

2012 IFGC Design, Installation and Inspection Principles 79Page 46-48

Five Step Review ProcessFive Step Review Process

1. Determine maximum gas demand2. Determine length to most remote outlet3. Select correct table4. Locate gas demand figures5. Locate nominal size of pipe required

2012 IFGC Design, Installation and Inspection Principles 80Page 47

Page 21: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 21

What You Need to KnowWhat You Need to Know To determine compliance: Allowable loss in pressure from point of

delivery to gas utilization equipment Maximum gas demand Length of piping and number of fittings Labeled pipe sizes Specific gravity of the gas Diversity factor

2012 IFGC Design, Installation and Inspection Principles 81Page 47

Gas Piping System Gas Piping System

• Tables in Chapter 4 determine sizing of gas piping.

• Variables to take into account1. Type of fuel gas2. Specific gravity of gas3. Gas supply pressure4. Pressure drop indicated5. Piping material used

2012 IFGC Design, Installation and Inspection Principles 82

Page 31-66

Page 48-49

Gas Piping System Gas Piping System

Table A.2.4 lists multipliers Used with Tables 402.4(1) through

402.4(22) where specific gravity of gas is other than 0.60.

Several tables are used to determine sizing between First- and second-stage regulators Single- or second-stage regulators and

appliances

2012 IFGC Design, Installation and Inspection Principles 83

Page 142

Page 48

Tables 402.4(1) through 402.4(35)Tables 402.4(1) through 402.4(35)

Which table would you use? A gas piping system using Schedule 40

steel piping with an identified pressure drop of 0.5 in wc; with a gas pressure of < 0.5 psi (< 3.4 kPa) and conveying a gas of 0.6 specific gravity.

Table 402.4(2)

2012 IFGC Design, Installation and Inspection Principles 84Page 49

Page 22: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 22

Tables 402.4(1) through 402.4(35)Tables 402.4(1) through 402.4(35)

Which table would you use? A gas piping system using Schedule 40

steel piping with an identified pressure drop of 1.0 psi (6.9 kPa), gas pressure of 2 psi(14 kPa) and conveying a gas of 0.7 specific gravity.

Table 402.4(3) and Appendix Table A.2.4

2012 IFGC Design, Installation and Inspection Principles 85Page 49

Gas System Sizing ProblemGas System Sizing Problem

2012 IFGC Design, Installation and Inspection Principles 86Page 51

Gas System Sizing ProblemGas System Sizing Problem

1. Determine maximum gas demand:Outlet A: 20 cfh (ft3/h)Outlet B: 45 cfh (ft3/h)Outlet C: 73 cfh (ft3/h)Outlet D: 133 cfh (ft3/h)Maximum gas demand: 271 cfh (ft3/h)

2012 IFGC Design, Installation and Inspection Principles 87Page 52

Gas System Sizing ProblemGas System Sizing Problem

2. Determine length to the most remote outlet:Section 1: 15 ft.Section 2: 25 ft.Section 3:Section 4:Section 5:Total pipe length to most remote outlet: 80 ft.

2012 IFGC Design, Installation and Inspection Principles 88Page 52

5 ft.5 ft.30 ft.

Page 23: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 23

Gas System Sizing ProblemGas System Sizing Problem

3. Select applicable table:Specific gravity:Gas pressure:Pressure drop:Type of material:Special conditions:Table Used:

2012 IFGC Design, Installation and Inspection Principles 89

0.6010 IN WC0.5 IN WCSteel PipeNA402.4(2)

Page 52

Gas System Sizing ProblemGas System Sizing Problem

4. Locate gas demand figures: Horizontal row showing length of piping Indicates length from point of delivery to most

remote outlet If not exact, use next longer distance Use this row for all gas demand figures

2012 IFGC Design, Installation and Inspection Principles 90Page 53

Gas System Sizing ProblemGas System Sizing Problem

5. Locate nominal size of pipe required: Outlet C: 73 ft3/h requires 3/4 inch pipe

Outlet D: 133 ft3/h requires 1 inch pipe

Pipe Section 4 (A,B,C): 138 ft3/h requires 1 inch pipe

Pipe Section 5 (A,B,C,D): 271 ft3/h requires 1 ¼ inch pipe

2012 IFGC Design, Installation and Inspection Principles 91Page 54

Branch Length Method Branch Length Method Determine the size of gas piping sections

2012 IFGC Design, Installation and Inspection Principles 92Page 54

Page 24: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 24

Branch Length MethodBranch Length Method Determine the size of trunkline sections Determine load for each section of pipe A = 230 MBH B = 170 MBH C = 135 MBH D = 95 MBH E = 20 MBH

Determine the table to use Because longest run length of pipe is between

rows, use next higher row. 2012 IFGC Design, Installation and Inspection Principles 93Page 56

= 402.4(2)

Branch Length MethodBranch Length Method Determine the size of trunk line sections Determine size for each section of pipe A = 1 ¼ inch B = 1 inch C = 1 inch D = ¾ inch E = 3/8 inch

2012 IFGC Design, Installation and Inspection Principles 94Page 57

Branch Length MethodBranch Length Method Determine the load for the following

branch sections Section F: Section G: Section H: Section I: Section J:

2012 IFGC Design, Installation and Inspection Principles 95Page 58

20 ft3/h60 ft3/h35 ft3/h40 ft3/h75 ft3/h

Branch Length MethodBranch Length Method Determine the length for each branch Section F: Section G: Section H: Section I: Section J:

Determine the table to use Table 402.4(13)

2012 IFGC Design, Installation and Inspection Principles 96Page 58-59

85 ft.25 ft.40 ft.60 ft.75 ft.

Page 25: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 25

Branch Length MethodBranch Length Method Determine the size for each section of gas pipe.

2012 IFGC Design, Installation and Inspection Principles 97

Pipe Section Length (ft.) Load (MBH) Size

A 85 20 18

B 25 60 19

C 40 35 18

D 60 40 23

E 75 75 30

Page 53

Hybrid Pressure System Sizing –402.4.3Hybrid Pressure System Sizing –402.4.3

2012 IFGC Design, Installation and Inspection Principles 98Page 59

Parallel System – 6” WCParallel System – 6” WC

2012 IFGC Design, Installation and Inspection Principles 99Page 62

Parallel System – 6” WCParallel System – 6” WC Required Size (CSST) A B C D E F G

2012 IFGC Design, Installation and Inspection Principles 100Page 62-64

37251923231818

Page 26: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 26

MP RegulatorMP Regulator

2012 IFGC Design, Installation and Inspection Principles 101Page 65

Medium Pressure SystemMedium Pressure System

2012 IFGC Design, Installation and Inspection Principles 102Page 67

Medium Pressure SystemMedium Pressure System Required Size (CSST) A B C D E F G

2012 IFGC Design, Installation and Inspection Principles 103Page 67-70

18151313151313

Branch Length MethodBranch Length Method

2012 IFGC Design, Installation and Inspection Principles 104Page 71-72

Page 27: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 27

Branch Length MethodBranch Length Method

Required Size 40” Steel Pipe A B C D E F G

2012 IFGC Design, Installation and Inspection Principles 105

Required Size (CSST) H I J K L M N

Page 71-72

1 ¼”1 ¼” 1”1”¾”¾”3/8”

13231518151813

Piping Materials - 403Piping Materials - 403 Corrugated Stainless Steel Tubing Plastic Piping Copper Tubing Number and Length of Threads

2012 IFGC Design, Installation and Inspection Principles 106Page 743-75

Piping Material Piping Material

Identify any code violations apparent in the installation

20126 IFGC Design, Installation and Inspection Principles 107Page 74

Tubing joints – 403.10.2Tubing joints – 403.10.2

2012 IFGC Design, Installation and Inspection Principles 108

Press Copper Fitting

Page 75-76

Page 28: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 28

Piping System Installation - 404 Piping System Installation - 404

Prohibited locations Piping in concealed locations Underground penetration prohibited Protection against physical damage Piping in solid floors Conduit with both ends terminating indoors Minimum burial depth Individual outdoor appliances

2012 IFGC Design, Installation and Inspection Principles 109Pages 76-79

404.2 CSST Piping Systems404.2 CSST Piping Systems CSST piping systems shall be installed in

accordance with their listing and the manufacturer’s installation instructions.

Significant Changes to the International Mechanical and Fuel Gas Codes, 2012 Edition 110

Sample installation instructions for CSST gas pipingSample installation instructions for CSST gas piping

Significant Changes to the International Mechanical and Fuel Gas Codes, 2012 Edition 111

Underground penetration prohibited – 404.6Underground penetration prohibited – 404.6

2012 IFGC Design, Installation and Inspection Principles 112

Above Grade Entrance/Exit

Pages 77\

Page 29: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 29

Piping in Solid Floors – 404.8Piping in Solid Floors – 404.8

2012 IFGC Design, Installation and Inspection Principles 113Pages 77

Conduit with both ends terminating indoors – 404.8.2 & 404.14.2Conduit with both ends terminating indoors – 404.8.2 & 404.14.2

2012 IFGC Design, Installation and Inspection Principles 114Pages 78

Piping Under Slab Between Interior Points

Protective coatings and wrapping - 404.11.2Protective coatings and wrapping - 404.11.2 Field application is only permitted where the factory-applied material may

have been damaged during transit or installation where the applied coating was removed

for pipe welding or threading of the pipe; for short sections (nipples) of pipe used

in the installation.

2012 IFGC Design, Installation and Inspection Principles 115Pages 78

Minimum burial depth – 404.11.2Minimum burial depth – 404.11.2

To avoid possible harm to the pipe from the use of hand tools a depth of 12 inches is considered sufficient.

2012 IFGC Design, Installation and Inspection Principles 116Pages 78

Page 30: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 30

Prohibited devices -404.18Prohibited devices -404.18 Excess flow valves

and other devices are allowed to be installed in gas piping provided that the piping system has been designed for such restrictions.

2012 IFGC Design, Installation and Inspection Principles 117Pages 79

Inspection, Testing and Purging -406Inspection, Testing and Purging -406 All piping installation must be inspected and

pressure tested. Includes: Visual inspection Pressure test

Leakage test verifies connection to appliances are gas-tight.

2012 IFGC Design, Installation and Inspection Principles 118Page 79

Appliance isolation – 406.3.4Appliance isolation – 406.3.4 Since the minimum required test pressure

exceeds the maximum inlet pressure for most appliances, the appliance must not be connected to the piping system during pressure testing.

2012 IFGC Design, Installation and Inspection Principles 119Page 80

Purging – 406.7Purging – 406.7

2012 IFGC Design, Installation and Inspection Principles 120Page 80

Page 31: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 31

Combustible Gas Indicator Section 406.7.1.4Combustible Gas Indicator Section 406.7.1.4 Combustible gas

indicator shall be listed and calibrated in accordance with the manufacturer’s instruction and display a volume scale from zero to 100 percent in 1 percent or smaller increments.

2012 IFGC Design, Installation and Inspection Principles 121Page 81

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.1

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.11. Design operating

pressure greater than 2 psig.

2. Pipe being purged contains one or more sections of pipe or tubing meeting the size and length criteria of Table 406.7.1.1.

2012 IFGC Design, Installation and Inspection Principles 122Page 82-83

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.1

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.1

2012 IFGC Design, Installation and Inspection Principles 123Page 82-83

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.1

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.1PROCEDURERemoval from ServicePlacing in ServiceAppliance/Equipment Purge

2012 IFGC Design, Installation and Inspection Principles 124Page 82-83

Page 32: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 32

Piping support design and installation – 407.2 Piping support design and installation – 407.2 All materials and devices used to hang or

support gas piping must be constructed of metal. Piping is allowed to rest upon and be supported

by building structural components.

2012 IFGC Design, Installation and Inspection Principles 125Page 83

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.2.1

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.2.11. Design operating pressure is 2 psig or less.2. Piping being purged is constructed entirely of

pipe or tubing not meeting the size and length criteria of Table 406.7.1.1.

2012 IFGC Design, Installation and Inspection Principles 126Page 84

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.1

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.1

2012 IFGC Design, Installation and Inspection Principles 127Page 84

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.2.1

GAS LINE PURGING CHECKLISTFOR THE FOLLOWING TWO CONDITIONSBASED ON IFGC SECTION 406.7.2.1PROCEDUREAppliance/Equipment Purge

2012 IFGC Design, Installation and Inspection Principles 128Page 84

Page 33: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 33

Sediment Trap - 408.4Sediment Trap - 408.4

2012 IFGC Design, Installation and Inspection Principles 129Page 85

Shutoff Valves - 409Shutoff Valves - 409

2012 IFGC Design, Installation and Inspection Principles 130Page 86

Appliance shutoff valves located at manifold – 409.5 and 409.5.3Appliance shutoff valves located at manifold – 409.5 and 409.5.3 Appliance shutoff valves are now permitted to be

located within 50 feet (15 240 mm) of the appliance on a remote manifold.

2012 IFGC Design, Installation and Inspection Principles 131Page 86

Shutoff valve for laboratories –409.6Shutoff valve for laboratories –409.6

2012 IFGC Design, Installation and Inspection Principles 132

Master Shutoff Valve for Laboratories

Page 86

Page 34: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 34

Gas Flow Controls Gas Flow Controls Medium Pressure (MP) gas regulators

2012 IFGC Design, Installation and Inspection Principles 133Pages 87

Hybrid Pressure System

Gas Flow ControlsGas Flow Controls Medium Pressure (MP) gas regulators

2012 IFGC Design, Installation and Inspection Principles 134Pages 87

Low-pressure (Single) System

Venting of regulators – 410.3Venting of regulators – 410.3

2012 IFGC Design, Installation and Inspection Principles 135Page 88

Gas Pressure Regulator

Vent piping – 410.3.1Vent piping – 410.3.1 Regulator relief vents and breather vents must

be connected to vent piping constructed of the same materials as allowed for gas distribution.

The text addresses the practice of joining multiple vents to a manifold piping arrangement.

2012 IFGC Design, Installation and Inspection Principles 136Page 88

Page 35: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 35

Excess Flow Valves - 410.4Excess Flow Valves - 410.4

2012 IFGC Design, Installation and Inspection Principles 137Page 88

Flashback arrestor check valve -410.5Flashback arrestor check valve -410.5

2012 IFGC Design, Installation and Inspection Principles 138Page 89

Appliance Connections - 411Appliance Connections - 411

Choice of connection type to use must take into consideration: Appliance movement Vibration Ambient conditions Susceptibility to physical damage

2012 IFGC Design, Installation and Inspection Principles 139Page 90

Connecting appliances- 411.1Connecting appliances- 411.1

2012 IFGC Design, Installation and Inspection Principles 140Page 90

Page 36: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 36

Commercial cooking appliances – 411.1.1 Commercial cooking appliances – 411.1.1 Connectors listed to ANSI Z21.69 are required

for all commercial cooking appliances that are moved from cleaning/sanitation purposes.

Connectors are designed to tolerate repeated movement to allow for cleaning operations or relocation.

2012 IFGC Design, Installation and Inspection Principles 141Page 90

Connector Installation Connector Installation

2012 IFGC Design, Installation and Inspection Principles 142

Connector Installation

Page 91

Prohibited locations and penetrations – 411.1.3.3Prohibited locations and penetrations – 411.1.3.3

2012 IFGC Design, Installation and Inspection Principles 143

Connector Piping Downstream of Shutoff Valve

Page 91-92

Suspended low-intensity infrared tube heaters – 411.3Suspended low-intensity infrared tube heaters – 411.3

2012 IFGC Design, Installation and Inspection Principles 144Page 92

Connector Piping Downstream of Shutoff Valve

Page 37: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 37

Chapter 5Chimneys and VentsChapter 5Chimneys and Vents

Module 5

Chimneys and VentsChimneys and Vents

Code provides requirements for: InstallationMaintenance Repair Approval Of residential and commercial chimney and venting systems.

2012 IFGC Design, Installation and Inspection Principles 146Page 93

Purpose of VentingPurpose of Venting Venting Systems Convey products of combustion to the outdoors

2012 IFGC Design, Installation and Inspection Principles 147Page 93

General RequirementsGeneral Requirements Every fuel-burning appliance is required to be

vented except as allowed by Section 501.8 Venting method must be designed for particular

type of appliance Venting material and method of installation

depend on characteristics of gas utilization equipment

2012 IFGC Design, Installation and Inspection Principles 148Page 93

Page 38: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 38

Operating CharacteristicsOperating Characteristics Positive or non-positive pressure in the venting

system Temperature of vent gases and possibility of

condensation

2012 IFGC Design, Installation and Inspection Principles 149Page 93

Appliance CategoriesAppliance Categories

2012 IFGC Design, Installation and Inspection Principles 150Page 94

Venting SystemsVenting Systems Type B Gas Vent Type BW Gas Vent Type L Vent Chimney Single-Wall Metal Pipe Plastic Pipe and Stainless Steel special vents

2012 IFGC Design, Installation and Inspection Principles 151Page 94

ChimneysChimneys

Masonry chimneys Multiple solid fuel

prohibited Gas-fired appliances Decorative shrouds Existing chimneys

and vents

2012 IFGC Design, Installation and Inspection Principles 152Pages 96-98

Page 39: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 39

Chimney TerminationsChimney Terminations

2012 IFGC Design, Installation and Inspection Principles 153Page 96

Chimney TerminationsChimney Terminations

2012 IFGC Design, Installation and Inspection Principles 154Page 96

Gas-fired appliances – 501.11Gas-fired appliances – 501.11 Manufacturer’s instructions specify very limited

conditions under which the appliance is allowed to vent to a masonry chimney.

Conditions include: size; state or condition; location and construction of a chimney.

2012 IFGC Design, Installation and Inspection Principles 155Page 96

Decorative shrouds Decorative shrouds Decorative shrouds are

intended to conceal chimney and vent terminations to improve the appearance of a building.

Only specific listed/tested assemblies are allowed

2012 IFGC Design, Installation and Inspection Principles 156Page 98

Page 40: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 40

Existing Chimneys and Vents –501.15Existing Chimneys and Vents –501.15

2012 IFGC Design, Installation and Inspection Principles 157Page 98

Sizing Venting SystemsSizing Venting Systems Important to correctly size fuel gas

systems: Minimize condensation Maintain required draft in Category I and II Convey products of combustion to the

outdoors Prevent moisture damage Avoid overheating of equipment and building

materials

2012 IFGC Design, Installation and Inspection Principles 158Page 99

Vent System Performance FactorsVent System Performance Factors

2012 IFGC Design, Installation and Inspection Principles 159Page 99

Length of vent connector –503.10.8Length of vent connector –503.10.8 The connector length limits are applicable in all

cases except where part of an engineered system.

2012 IFGC Design, Installation and Inspection Principles 160Page 101

Page 41: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 41

Evaluation of a common vent system Evaluation of a common vent system

2012 IFGC Design, Installation and Inspection Principles 161

Common Vent System

Offset

Allsingle wallfittingsandpipe

Page 101

Passage through ceilings, floors or walls – 503.10.13Passage through ceilings, floors or walls – 503.10.13

2012 IFGC Design, Installation and Inspection Principles 162Page 101

Passage through ceilings, floors or walls – 503.10.13Passage through ceilings, floors or walls – 503.10.13

2012 IFGC Design, Installation and Inspection Principles 163Page 102

Combined connectors – 504.3.4Combined connectors – 504.3.4

2012 IFGC Design, Installation and Inspection Principles 164Page 103

Page 42: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 42

Connector Length LimitConnector Length Limit

2012 IFGC Design, Installation and Inspection Principles 165Page 104

Connector Length LimitConnector Length LimitA: Actual connector length

Max. allowedB: Actual connector length

Max. allowedC: Actual connector length

Max. allowed

2012 IFGC Design, Installation and Inspection Principles 166Page 104

= 2.5= 4.5= 4.5= 6.0= 9.5= 9.0

Length Alternative Length Alternative

2012 IFGC Design, Installation and Inspection Principles 167Page 106

Length Alternative Length Alternative 1. Determine maximum allowable vent

connector lengthUse Table 504.3.2 5 inch connector diameter

7 ½ feet.

2012 IFGC Design, Installation and Inspection Principles 168Page 106

225

Page 43: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 43

Length Alternative Length Alternative 2. Determine absolute maximum allowable

vent connector lengthUse Section 503.10.9 5 inch connector diameter

20 feet.

2012 IFGC Design, Installation and Inspection Principles 169Page 107

195

Length Alternative Length Alternative 3. Evaluate steps 1 and 2 Apply the more restrictive criteria, or Apply connector length alternative provisions

of Section 504.3.3

2012 IFGC Design, Installation and Inspection Principles 170Page 107

30

Maximum Allowable Vent Connector Length Maximum Allowable Vent Connector Length

4. Apply provisions of Section 504.3.3 Use Tables 504.3(2) and 504.3(1) Extend vent connector maximum length to 15 feet Apply 10 percent capacity reduction Maximum input capacity of 176,000 Btu/h

[176,000 x .90] = 158,400 Btu/h 158,400 Btu > 135,000 Btu/h Boiler exceeds minimum required input of

59,000 Btu/h in Table 504.2(1)

2012 IFGC Design, Installation and Inspection Principles 171Page 107-108

(A/B × C) + D(2.5/5 × 30) + 195(1/2 × 30) + 19515 + 195 = 210

Common Vent offsets – 504.3.5Common Vent offsets – 504.3.5

2012 IFGC Design, Installation and Inspection Principles 172

Offset in Attic to Avoid Streetside Roof Penetration

Page 110

Page 44: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 44

Common vertical vent offset –504.3.5 Common vertical vent offset –504.3.5

2012 IFGC Design, Installation and Inspection Principles 173Page 110

Seven Times Rule – 504.2.8 & 504.3.17 Seven Times Rule – 504.2.8 & 504.3.17 Flow area of vertical vent must not be larger

than seven times the area of the smallest appliance vent connection.

2012 IFGC Design, Installation and Inspection Principles 174Page 111

Category I AppliancesCategory I Appliances Central furnaces

(forced air types) Low pressure boilers Water heaters Duct furnaces Unit heaters Vented room heaters Floor furnaces Conversion burners

2012 IFGC Design, Installation and Inspection Principles 175Page 112

Vent offsets – 504.2.3Vent offsets – 504.2.3 To create a lateral (horizontal) run of vent or a

vent connector, one or two elbows are necessary.

Tables account for two 90-degree changes in direction.

2012 IFGC Design, Installation and Inspection Principles 176Page 113

Page 45: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 45

Height entries - 504.2.17 and 504.3.28Height entries - 504.2.17 and 504.3.28 Tables 504.2(1) through 504.2(6) Actual height of a vent falls between entries in the

height column Either interpolation shall be used or the lower

appliance input rating FAN MAX and NAT MAX column values and the

higher appliance input rating shall be used for the FAN MIN column values.

2012 IFGC Design, Installation and Inspection Principles 177Page 115

Height entries - 504.2.17 and 504.3.28Height entries - 504.2.17 and 504.3.28

Consider a single, Category I appliance with an 8 inch B-vent height of 18 feet. The lateral offset is 5 feet and the B-vent

is directly connected to the appliance. What are the values for FAN MAX, NAT

MAX and FAN MIN?

2012 IFGC Design, Installation and Inspection Principles 178Page 115-116

Table InterpolationTable Interpolation

2012 IFGC Design, Installation and Inspection Principles 179Page 117

Table InterpolationTable Interpolation

2012 IFGC Design, Installation and Inspection Principles 180Page 118

Page 46: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 46

Table InterpolationTable Interpolation Step 1: Find the maximum vent capacity

(MAX) at the first height entry greater than 121/2 feet, [i.e., 15 feet ].

Step 2: Find the maximum vent capacity (MAX) at the next height entry lower than 121/2 feet, [i.e., 10 feet ].

2012 IFGC Design, Installation and Inspection Principles 181Page 117-118

Table InterpolationTable Interpolation Step 3: Determine the difference between

the two maximum vent capacities. Step 4: Determine the maximum vent

capacity for a 121/2-foot-high (3810 mm) vent.

2012 IFGC Design, Installation and Inspection Principles 182Page 118

Sizing Venting System: Two or More Appliances – 504.3Sizing Venting System: Two or More Appliances – 504.3 A common vent is a vent for two or more

appliances on the same floor level Must be designed to vent products of

combustion when: Any one Any combination, and All of the connected appliances operate

2012 IFGC Design, Installation and Inspection Principles 183Page 118-119

Sizing Venting System: Two or More AppliancesSizing Venting System: Two or More Appliances Connector, for purposes of designing a common

vent Is that part of the vent piping between the

appliance outlet and its junction with the rest of the system For each connector the correct size must be

found

2012 IFGC Design, Installation and Inspection Principles 184Page 118-119

Page 47: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 47

Vent fitting – 504.3.9 Vent fitting – 504.3.9

2012 IFGC Design, Installation and Inspection Principles 185Page 119

Common Vent Fittings

Tee and wye fittings – 504.3.9.1Tee and wye fittings – 504.3.9.1

This code section requires tees and wyes used in common vent systems to be constructed of the same materials as the common vent.

2012 IFGC Design, Installation and Inspection Principles 186Page 119

Height and Rise Measurements –504.3.11 & 504.3.12Height and Rise Measurements –504.3.11 & 504.3.12 Least total height Vertical distance from highest appliance outlet

to lowest discharge opening of vent cap Least total height is used for vent sizing for all

connected appliances on one floor level.

2012 IFGC Design, Installation and Inspection Principles 187Page 120

Size B vent systemSize B vent system

Rise Measurement - Rise (R) Vertical distance from the draft hood outlet or

flue collar to the level where the vent gas streams merge

2012 IFGC Design, Installation and Inspection Principles 188Page 120

Page 48: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 48

Size B vent systemSize B vent system

2012 IFGC Design, Installation and Inspection Principles 189Page 121

FANNAT

Size B vent systemSize B vent system

Find each connector size Correct Table: Least total height and vent rise Vent height: Water heater rise: Furnace rise:

Vent connector size Water heater: Furnace:

2012 IFGC Design, Installation and Inspection Principles 190Page 121

Table 504.3(1)

15 feet1 foot3 feet

4 inch 5 inch

Size B vent systemSize B vent system

Find common vent size Total Btu/h input: Combined input rating: Size of common vent:

2012 IFGC Design, Installation and Inspection Principles 191Page 121

164,000 Btu/h5 inch

Flue gases must leave the structure – 503.6.4Flue gases must leave the structure – 503.6.4

2012 IFGC Design, Installation and Inspection Principles 192

Top Location Rules

Page 123

Page 49: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 49

Gas Vent TerminationGas Vent Termination

Determine which diagram shows correct vent termination requirement

2012 IFGC Design, Installation and Inspection Principles 193Page 124

Venting SystemVenting System Given the following

information, size the entire venting system. Water heater 40,000 Btu/h Natural draft 3-inch draft hood Furnace 80,000 Btu/h Fan assisted 4 inch flue collar

2012 IFGC Design, Installation and Inspection Principles 194Page 125

Sizing of Venting Systems for Two or More AppliancesSizing of Venting Systems for Two or More Appliances

A. Diameter for the water heater connector.4 inches

B. Diameter for the furnace connector.4 inches

C. Percent capacity reduction for common vent.20 percent, Sections 504.3.5 and 505.3.6

2012 IFGC Design, Installation and Inspection Principles 195Page 114

Sizing of Venting Systems for Two or More AppliancesSizing of Venting Systems for Two or More Appliances

D. Diameter of common vent.5 inches, (159,000 Btu/h ´ 0.80 =

127,200 Btu/h)E. Maximum allowable horizontal connector

length.6 feet or in accordance with Sections 504.3.2 and 503.10.9 the MAX Length allowed is 12.75' (75% ´ 17' = 12.75)

2012 IFGC Design, Installation and Inspection Principles 196Page 128

Page 50: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 50

Sizing of Venting Systems for Two or More AppliancesSizing of Venting Systems for Two or More Appliances

F. Maximum allowable length of common vent offset.

7.5

G. Is interpolation necessary?No

2012 IFGC Design, Installation and Inspection Principles 197Page 128

Sizing of Venting Systems for Two or More AppliancesSizing of Venting Systems for Two or More Appliances

2012 IFGC Design, Installation and Inspection Principles 198Page 129

Sizing of Venting Systems for Two or More AppliancesSizing of Venting Systems for Two or More Appliances

2012 IFGC Design, Installation and Inspection Principles 199Page 131-132

Sizing of Venting Systems for Two or More AppliancesSizing of Venting Systems for Two or More Appliances

Determine the venting system sizing for the two appliances.

Find the size of the common vent based on least total height and the combination of connected appliances

2012 IFGC Design, Installation and Inspection Principles 200Page 114-115

Page 51: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 51

Sizing of Venting Systems for Two or More AppliancesSizing of Venting Systems for Two or More Appliances

A. Furnace Connector Material: Size:

B. Water Heater Connector Material:Size:

C. Common Vent Size:

2012 IFGC Design, Installation and Inspection Principles 201

Type B 4 inches, [Table 504.3(1)]

Single-wall 4 inches, [Table 504.3(2)]

4 inches (10% reduction for offset, 132,000 Btu/h ´0.9 = 118,800 Btu/h)

Page 130

Sizing of Venting Systems for Two or More AppliancesSizing of Venting Systems for Two or More Appliances

D. Interpolation Necessary? E. Any Noted Violations?

2012 IFGC Design, Installation and Inspection Principles 202Page 131-132

No

Direct-vent terminationsDirect-vent terminations

2012 IFGC Design, Installation and Inspection Principles 203Page 133

Direct Vent AppliancesDirect Vent Appliances

2012 IFGC Design, Installation and Inspection Principles 204Page 133

Page 52: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 52

Commercial cooking appliance vented by exhaust hoodsCommercial cooking appliance vented by exhaust hoods

2012 IFGC Design, Installation and Inspection Principles 205

Solenoid Valve Interlock Method

Page 134

Mechanical Draft Venting System TerminationsMechanical Draft Venting System Terminations

2012 IFGC Design, Installation and Inspection Principles 206Page 135

Chapter 6Specific AppliancesChapter 6Specific Appliances

Module 6

Specific AppliancesSpecific Appliances Provides requirements for all aspects of specific

appliances Special requirements for installation and location Assures for installation in accordance with

manufacturer’s installation instructions

2012 IFGC Design, Installation and Inspection Principles 208Page 137

Page 53: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 53

ScopeScope Approval Design Installation Construction Maintenance Alteration Repair

2012 IFGC Design, Installation and Inspection Principles 209Page 137

AppliancesAppliances Standards Typical Application Prohibited Installations Major code enforcement issues

2012 IFGC Design, Installation and Inspection Principles 210Page 137

AppliancesAppliances Decorative Gas-Fired Appliances for Installation

in Vented Fireplaces (Section 602) Gas Fireplaces (Section 604) Gas Fireplace Heaters (Section 605) Vented Wall Furnaces (Section 608)

2012 IFGC Design, Installation and Inspection Principles 211Page 137-140

AppliancesAppliances Floor Furnaces (Section 609) Non-recirculating Direct-Fired Industrial Air

Heaters (Section 611) Recirculating Direct-Fired Industrial Air Heaters

(Section 612) Cloths Dryers (Section 613) Clothes Dryer exhaust (Section 614)

2012 IFGC Design, Installation and Inspection Principles 212Page 140-143

Page 54: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 54

Projection required – 614.6.3Projection required – 614.6.3 Section 614.6.3

requires clothes dryer exhaust ducts to be protected from penetration by fasteners such as drywall screws and trim nails

2012 IFGC Design, Installation and Inspection Principles 213Page 144

Length identification – 614.6.6Length identification – 614.6.6 Requires a label or

tag to be placed by the point of connection to a concealed clothes dryer exhaust duct system.

2012 IFGC Design, Installation and Inspection Principles 214Page 144

Common exhaust systems for clothes dryers located in multistory structuresCommon exhaust systems for clothes dryers located in multistory structures

Provides 11 provisions for the construction of a multistory common exhaust shaft to serve clothes dryers on multiple floors. The shaft in which the duct is installed shall be

constructed and fire-resistant rated as required by the IBC.

Dampers shall be prohibited in the exhaust duct. Rigid metal ductwork shall be installed within the shaft

to convey the exhaust.

2012 IFGC Design, Installation and Inspection Principles 215Page 144

Common exhaust systems for clothes dryers located in multistory structuresCommon exhaust systems for clothes dryers located in multistory structures

Provides 11 provisions for the construction of a multistory common exhaust shaft to serve clothes dryers on multiple floors. The ductwork within the shaft shall be designed and

installed without offsets. The exhaust fan motor design shall be in accordance

with Section 503.2 of the IMC. The exhaust fan motor shall be located outside of the

airstream.

2012 IFGC Design, Installation and Inspection Principles 216Page 144

Page 55: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 55

Common exhaust systems for clothes dryers located in multistory structuresCommon exhaust systems for clothes dryers located in multistory structures

Provides 11 provisions for the construction of a multistory common exhaust shaft to serve clothes dryers on multiple floors. The exhaust fan shall run continuously, and shall be

connected to a standby power source. The exhaust fan operation shall be monitored in an

approved location and shall initiate an audible or visual signal when the fan is not in operation.

Makeup air shall be provided for the exhaust system.

2012 IFGC Design, Installation and Inspection Principles 217Page 144

Common exhaust systems for clothes dryers located in multistory structuresCommon exhaust systems for clothes dryers located in multistory structures

Provides 11 provisions for the construction of a multistory common exhaust shaft to serve clothes dryers on multiple floors. A cleanout opening shall be located at the base of the

shaft to provide access to the duct to allow for cleaning and inspection.

Screens shall not be installed at the termination.

2012 IFGC Design, Installation and Inspection Principles 218Page 144

AppliancesAppliances Forced-Air Warm-Air Furnaces (Section 618) Unit Heaters (Section 620) Unvented Room Heaters (Section 621) Cooking Appliances (Section 623)

2012 IFGC Design, Installation and Inspection Principles 219Pages 145-147

AppliancesAppliances Water Heaters

(Section 624) Air Conditioning

Equipment (Section 627)

Illuminating Appliances (Section 628)

Boilers (Section 631)

2012 IFGC Design, Installation and Inspection Principles 220Page 147-150

Page 56: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 56

Outdoor Decorative Appliances–636.1Outdoor Decorative Appliances–636.1 Permanently, fixed-in-

place outdoor decorative appliances must be tested in accordance with ANSI Z21.97 and installed in accordance with the manufacturer’s instructions.

2012 IFGC Design, Installation and Inspection Principles 221Page 151

Review and Final QuestionsReview and Final Questions

223

International Code Council is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of Completion for non-AIA members are available on request.

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

224

Copyright Materials

This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is

prohibited.

© International Code Council 2006

Page 57: 2012 IFGC Design Install Insp Princ - ccaps.umn.edu€¦ · 2012 IFGC Design, Installation and Inspection Principles 13 1. The recorded temperature of the surface and interior thermocouples

2012 IFGC Design, Installation and Inspection Principles 12/11/2017

Copyright 2011 International Code Council 57

Thank you for participating!Thank you for participating!

To schedule a seminar, contact:The Learning Center™

1‐888‐ICC‐SAFE (422‐7233) Ext. 33818or

E‐mail: [email protected]

2012 Template 225

000

Dark 1

255255255

Light 1

000

Dark 2

38866

Light 2

19200

Accent 1

255255153

Accent 2

2551920

Accent 3

105216255

Accent 4

15384204

Accent 5

0122112

Accent 6

0112192

Hyperlink

11248160

Followed Hyperlink

Custom Color 1 Custom Color 2 Custom Color 3 Custom Color 4 Custom Color 5 Custom Color 6

Custom Color 7 Custom Color 8 Custom Color 9 Custom Color 10Custom Color 11Custom Color 12

2_Office Theme