Top Banner
1 2009 Eaton Corporation. All rights reserved. Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors
14

2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

Dec 23, 2015

Download

Documents

Barry Moody
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

1

2009 Eaton Corporation. All rights reserved.

Measuring- and Communication Modulefor Molded Case Breakers and Switch Disconnectors

Page 2: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

2202.Jul.2009 2009 Eaton Corporation. All rights reserved.

Measuring- and Communication Module

Energy costs Under strict control

Page 3: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

3302.Jul.2009 2009 Eaton Corporation. All rights reserved.

Metering and Visualization

classic compact

+ all-purpose

- high amount of wiring

+ basic setup+ easy to install+ attractive price

Page 4: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

4402.Jul.2009 2009 Eaton Corporation. All rights reserved.

XMC Products

• Optional Display

• For Premium version

• 96x96 front mounting

• Viewing of all parameters

• Preconfigured

Page 5: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

5502.Jul.2009 2009 Eaton Corporation. All rights reserved.

Overview

XMC

Incorporated CTs

Dig S0 output

Voltage access

2 dig. I

2 dig. Q

Remote Control

Modbus

Display

Page 6: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

6602.Jul.2009 2009 Eaton Corporation. All rights reserved.

Metering Data of Premium Version

Data via Modbus and Display accessible:

Phase voltages L-N und L-L Phase currents L1,L2,L3Active power per phase and directionActive power totalReactive energy per phaseReactive energy totalReactive energy capacitive/inductiveApparent power per phaseApparent power totalPower factor Cos PhiFrequency3 configurable time windows6 configurable alarms

Page 7: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

7702.Jul.2009 2009 Eaton Corporation. All rights reserved.

Basics on Power

• Active power [Watt]• P=u*i cos phi

• Real power (billing)

• Reactive Power [var]• Q=u*i sin phi

• Unwanted, not unusable power; bouncing between generator and consumer

• Apparent Power [VA]• S=U*I

• Needed for wiring dimension

G M

G M

Page 8: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

8802.Jul.2009 2009 Eaton Corporation. All rights reserved.

Device versions

Standard Version Premium Version

1 dig S0 Pulse-Outputfor Active Energy

Ideal to incorporate energy data via SmartWireDarwin

2 S0 Pulse-Outputsfor Active Energy

Display interface

Fieldbus interface (Modbus)

Expandable with max 2 cards:

NZM-XMC-1AO 1 analog output

NZM-XMC-2DO-R 2 relais output

NZM-XMC-4DO-R 4 Relais output

NZM-XMC-4DI-4DO 4 dig. input + 4 dig. output

Page 9: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

9902.Jul.2009 2009 Eaton Corporation. All rights reserved.

Topology for PROFIBUS-DP or PROFINET

Metering BusModbus RTU

Typically 32 breakers

PROFIBUS-DPor

PROFINET

M S

M S

M S

Gatewayto PROFINET or PROFIBUS-DP

Scada

PLC

Page 10: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

1010

02.Jul.2009 2009 Eaton Corporation. All rights reserved.

S0-pulse output

Typical signal according EN 62053-31

requirements

Page 11: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

1111

02.Jul.2009 2009 Eaton Corporation. All rights reserved.

Assortment

NZM-XMC-COND3NZM-XMC-COND3NZM-XMC-KIT-630 3 630 Kit including conductors and terminalsNZM-XMC-KIT-TCP-630 3 630 Kit including conductors and terminals

and ModbusTCP Gateway

Page 12: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

1212

02.Jul.2009 2009 Eaton Corporation. All rights reserved.

630 A KIT

Page 13: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

1313

02.Jul.2009 2009 Eaton Corporation. All rights reserved.

• Voltage Measuring

• Range: 40...700V

• Error: 0.49% reading + 0,01%FS

• Current Measuring

• Range: 115% ... 1% Inom

• 300A: 350...3A

• 630A: 735...6.3A

• Error: 0.49% reading + 0,01% FS

• Power / Energy

• Error: 0.99% reading + 0,01% FS

Technical Data

Page 14: 2009 Eaton Corporation. All rights reserved. 1 Measuring- and Communication Module for Molded Case Breakers and Switch Disconnectors.

1414

02.Jul.2009 2009 Eaton Corporation. All rights reserved.