Top Banner
1 UNINTERRUPTIBLE POWER SUPPLIES JOHN LIGUORI CONSULTING ENGINEER MSEE, PE PRESENTED TO THE IEEE LONG ISLAND CONSULTANT’S NETWORK 9/6/06
43
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 2006 0906 Uninterruptible Power Supplies

1

UNINTERRUPTIBLE POWER SUPPLIES

JOHN LIGUORI

CONSULTING ENGINEER

MSEE, PE

PRESENTED TO THE IEEE LONG ISLAND CONSULTANT’S NETWORK

9/6/06

Page 2: 2006 0906 Uninterruptible Power Supplies

2

UNINTERRUPTIBLE POWER SUPPLIES

• THIS PRESENTATION IS FOR INFORMATIONAL AND EDUCATIONAL PURPOSES ONLY. IT DOES NOT CONTAIN ALL INFORMATION REQUIRED, AND IS NOT INTENDED TO BE USED FOR THE SPECIFICATION OR DESIGN OF UNINTERRUPTIBLE POWER SUPPLIES (UPS) OR UPS SYSTEMS.

Page 3: 2006 0906 Uninterruptible Power Supplies

3

UNINTERRUPTIBLE POWER SUPPLIESOUTLINE

• INTRODUCTION• POWER DISTURBANCES• UNINTERRUPTIBLE POWER SUPPLIES• GENERAL DISCUSSION• SUMMARY• REFERENCES• QUESTIONS

Page 4: 2006 0906 Uninterruptible Power Supplies

4

INTRODUCTION

• PURPOSE• WHAT IS AN UNINTERRUPTIBLE POWER SUPPLY?• WHY USE A UPS?

Page 5: 2006 0906 Uninterruptible Power Supplies

5

PURPOSE

• THE PURPOSE OF THIS PRESENTATION IS TO DISCUSS THE DIFFERENT TYPES OF UNINTERRUPTIBLE POWER SUPPLIES AVAILABLE, WHAT THE UPS PROTECTS AGAINST, THE COMPONENTS OF A UPS, AND ISSUES REGARDING SELECTION AND SIZING.

• THE DIFFERENT TYPES AND CAUSES OF POWER DISTURBANCES ARE DISCUSSED, AS WELL AS WHAT THE POWER UTILITY, THE ORIGINAL EQUIPMENT MANUFACTURER, AND YOU, CAN DO TO MINIMIZE THEIR EFFECT.

Page 6: 2006 0906 Uninterruptible Power Supplies

6

WHAT IS AN UNINTERRUPTIBLE POWER SUPPLY?

• AN UNINTERRUPTIBLE POWER SUPPLY (UPS) IS A DEVICE THAT HAS AN ALTERNATE SOURCE OF ENERGY THAT CAN PROVIDE POWER WHEN THE PRIMARY POWER SOURCE IS TEMPORARILY DISABLED

• THE SWITCHOVER TIME MUST BE SMALL ENOUGH TO NOT CAUSE A DISRUPTION IN THE OPERATION OF THE LOADS

Page 7: 2006 0906 Uninterruptible Power Supplies

7

WHY USE A UPS?

• PROTECTS AGAINST MULTIPLE TYPES OF POWER DISTURBANCES

• ONLY DEVICE THAT PROTECTS AGAINST AN OUTAGE• OFFERS PROTECTION AGAINST

EQUIPMENT NOT OPERATING PROPERLYCOMPUTER AND EQUIPMENT DAMAGEDATA LOSSTIME AND EXPENSE TO RECOVER BACK TO WHERE

YOU WERE, IF EVEN POSSIBLE

Page 8: 2006 0906 Uninterruptible Power Supplies

8

POWER DISTURBANCES

• CAUSES• TYPES• DURATION• RESULTING PROBLEMS• COMMENTS• WHAT THE POWER UTILITY CAN DO• WHAT THE ORIGINAL EQUIPMENT MANUFACTURER (OEM)

CAN DO• WHAT YOU CAN DO• PROTECTIVE DEVICES

Page 9: 2006 0906 Uninterruptible Power Supplies

9

CAUSES OF POWER DISTURBANCES

• STORM ACTIVITY – LIGHTNING, WIND, ICE• OBJECTS COMING IN CONTACT WITH POWER LINE AND

TRIPPING BREAKER – TREE BRANCHES, ANIMALS, OTHER• UTILITY FAULT CLEARING• CONSTRUCTION ACTIVITY• ACCIDENTS – MOTOR VEHICLE, OTHER• EQUIPMENT FAILURE• OVERLOADING• LOAD SWITCHING• NON-LINEAR LOADS• POOR GROUNDING• ESD

Page 10: 2006 0906 Uninterruptible Power Supplies

10

TYPES OF POWER DISTURBANCES

• INTERRUPTION• SAG, UNDER VOLTAGE• SURGE, OVER VOLTAGE• VOLTAGE FLUCTUATION• FREQUENCY VARIATION• SPIKES / TRANSIENTS

IMPULSIVE OSCILLATORY

• WAVEFORM DISTORTION DC OFFSET HARMONICS INTERHARMONICS NOTCHING NOISE

• VOLTAGE IMBALANCE

Page 11: 2006 0906 Uninterruptible Power Supplies

11

DURATION OF POWER DISTURBANCES

• INSTANTANEOUS - ½ CYCLE (8 1/3 ms) OR LESS• MOMENTARY - ½ CYCLE TO 3 SEC• TEMPORARY - 3 SEC TO 1 MIN• SUSTAINED - GREATER THAN 1 MINUTE

Page 12: 2006 0906 Uninterruptible Power Supplies

12

CLASSIFICATION OF PROBLEMS RESULTING FROMPOWER DISTURBANCES

• DISRUPTIVE EQUIPMENT DOES NOT OPERATE AS INTENDED

• DISSIPATIVE EQUIPMENT EXPERIENCES REPEATED STRESSES THAT LEAD TO

FAILURE LATER FOR NO APPARENT REASON

• DESTRUCTIVE EQUIPMENT FAILS AT THE INSTANT THE DISTURBANCE OCCURS

Page 13: 2006 0906 Uninterruptible Power Supplies

13

PROBLEMS RESULTING FROMPOWER DISTURBANCES

• DATA ERRORS• DATA LOSS• BLOWN FUSES• TRIPPED BREAKERS• INTERFERENCE WITH CONTROL OF LOADS• OVERLOADED NEUTRAL CONDUCTORS• MOTORS

HEATING SPEED VARIATION STALLING AUDIBLE NOISE VIBRATION

• TRANSFORMERS HEATING AUDIBLE NOISE VIBRATION

Page 14: 2006 0906 Uninterruptible Power Supplies

14

POWER DISTURBANCES - COMMENTS

• NOT ONLY IS MODERN EQUIPMENT MORE SUSCEPTIBLE TO POWER DISTURBANCES, BUT THE EQUIPMENT ITSELF GENERATES MORE DISTURBANCES

• ALL LOADS, FROM LARGE POWERFULL MOTORS AND INDUSTRIAL EQUIPMENT TO SMALL, SENSITIVE ELECTRONIC COMPONENTS, ARE CONNECTED TO THE SAME POWER GRID

Page 15: 2006 0906 Uninterruptible Power Supplies

15

WHAT THE POWER UTILITY CAN DO TO MINIMIZE THE EFFECT OF POWER DISTURBANCES

• INSTALL STORM RESISTANT WIRING• USE INFRA RED SCANNING TO DETECT WEAK SPOTS IN

POWER LINES• INSTALL REMOTE CONTROLLED RADIO SWITCHES TO

RESTORE POWER QUICKLY• CLEAR TREE LIMBS AWAY FROM POWER LINES

Page 16: 2006 0906 Uninterruptible Power Supplies

16

WHAT THE OEM CAN DO TO MINIMIZE THE EFFECT OF POWER DISTURBANCES

BUILD EQUIPMENT CONTAINING ONE OR MORE INTERNAL PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES LINE FILTERS ISOLATION TRANSFORMER BATTERY OR CAPACITOR BACK UP TO INCREASE RIDE THROUGH TIME

Page 17: 2006 0906 Uninterruptible Power Supplies

17

WHAT YOU CAN DO TO MINIMIZE THE EFFECT OF POWER DISTURBANCES

• BUY EQUIPMENT THAT HAS INTERNAL PROTECTIVE DEVICES FOR EXAMPLE, BATTERY BACK UP FOR ANY APPLIANCE THAT

CONTAINS A CLOCK

• USE ONE OR MORE EXTERNAL PROTECTIVE DEVICES SURGE PROTECTORS LINE FILTERS ISOLATION TRANSFORMER VOLTAGE REGULATING LINE CONDITIONER UPS

Page 18: 2006 0906 Uninterruptible Power Supplies

18

PROTECTIVE DEVICES OTHER THAN UPS

• SURGE PROTECTIVE DEVICES – SPD’SPROTECTS AGAINST SPIKES OF LIMITED ENERGY

METAL OXIDE VARISTORS – MOV DIODES GAS TUBES LCR FILTERS HYBRIDS

• LINE FILTERSFILTERS OUT HARMONICS, TRANSIENTS AND NOISE

• ISOLATION TRANSFORMERELIMINATES DC OFFSET AND NOISE

• VOLTAGE REGULATING LINE CONDITIONERAUTOMATICALLY ADJUSTS FOR UNDER AND OVER VOLTAGES

CONSTANT VOLTAGE TRANSFORMER - CVT MOTORIZED VARIAC

Page 19: 2006 0906 Uninterruptible Power Supplies

19

POWER DISTURBANCESAND

PROTECTIVE DEVICES

SURGE PROTECTOR

LINE FILTER ISOLATION TRANSFORMER

VOLTAGE REGULATING

LINE CONDITIONER

ON-LINE UPS

INTERRUPTION YESSAG, UNDER VOLTAGE YES YES

SURGE, OVER VOLTAGE YES YESVOLTAGE FLUCTUATION YES YESFREQUENCY VARIATION YES

IMPULSIVE YES YES YESOSCILLATORY YES YES YES

DC OFFSET YES YESHARMONICS YES YES

INTERHARMONICS YESNOTCHING YES YES

NOISE YES YES YESVOLTAGE IMBALANCE YES

PROTECTIVE DEVICE OFFER PROTECTION?

WAVEFORM DISTORTION

SPIKES / TRANSIENTS

POWER DISTURBANCE

Page 20: 2006 0906 Uninterruptible Power Supplies

20

UPS

• ARCHITECTURES• WAVEFORMS• INVERTER TECHNOLOGY• COMPONENTS• SWITCHOVER TIME• ADVANTAGES / DIS-ADVANTAGES• SIZING• BATTERY SAFETY

Page 21: 2006 0906 Uninterruptible Power Supplies

21

UPS ARCHITECTURES

• LINE INTERACTIVE• ON-LINE

Page 22: 2006 0906 Uninterruptible Power Supplies

22

BLOCK DIAGRAMLINE INTERACTIVE UPS

BATTERY CHARGER

AC SUPPLY

INVERTERDC TO AC

CRITICALLOAD

(AC)

BATTERY

AUTOMATIC SWITCH

AC FAIL

Page 23: 2006 0906 Uninterruptible Power Supplies

23

BLOCK DIAGRAMON-LINE UPS

CONVERTER AC TO DC

AC SUPPLY

INVERTERDC TO AC

CRITICALLOAD

(AC)

BATTERY

AUTOMATIC SWITCH

INVERTER FAIL

Page 24: 2006 0906 Uninterruptible Power Supplies

24

BLOCK DIAGRAMLAPTOP COMPUTER POWER SUPPLY

CONVERTER AC TO DC

AC SUPPLY

CONVERTERDC TO DC

BATTERY

CRITICALLOAD

(DC)

Page 25: 2006 0906 Uninterruptible Power Supplies

25

UPS WAVEFORMS

• TRUE SINEWAVE• MODIFIED SINEWAVE• SQUARE WAVE

Page 26: 2006 0906 Uninterruptible Power Supplies

26

UPS WAVEFORMS

-170

0

170

0 4 8 12 16 20

TIME (ms)

VO

LT

AG

E

TRUE SINEWAVEMODIFIED SINEWAVESQUARE WAVE

Page 27: 2006 0906 Uninterruptible Power Supplies

27

INVERTER TECHNOLOGY FOR TRUE SINEWAVE

• PULSE WIDTH MODULATION - PWM• LINEAR AMPLIFIER• RESONANT INVERTER

Page 28: 2006 0906 Uninterruptible Power Supplies

28

BLOCK DIAGRAMPWM INVERTER

HIGH FREQUENCY GENERATOR

PULSE WIDTH MODULATOR

BASE / GATE DRIVE

TRANSISTOR BRIDGE

TRANSFORMER FILTER

CRITICALLOAD

(AC)

REFERENCE SINEWAVE

GENERATORCOMPARISON

AMPLIFIER

DC POWER

Page 29: 2006 0906 Uninterruptible Power Supplies

29

BLOCK DIAGRAMLINEAR AMPLIFER INVERTER

OSCILLATORAMPLIFIER

SINEWAVE OSCILLATOR

TRANSFORMER

COMPARISONAMPLIFIER

POWERAMPLIFIER

CRITICALLOAD

(AC)

DC POWER

Page 30: 2006 0906 Uninterruptible Power Supplies

30

BLOCK DIAGRAMRESONANT INVERTER

SQUARE WAVE

GENERATOR

SWITCH DRIVE

TRANSISTOR SWITCHES

TRANSFORMERLC RESONANT TANK FILTER

CRITICALLOAD

(AC)

DC POWER

(OR FERRORESONANT)

Page 31: 2006 0906 Uninterruptible Power Supplies

31

UPS COMPONENTS

• CONVERTER - AC TO DC SPD - PROTECTS AGAINST SPIKES AND TRANSIENTS

• BATTERY STORED ENERGY DEVICE - PROTECTS AGAINST INTERRUPTIONS

• INVERTER – DC TO AC WAVEFORM SYNTHESIS – PROTECTS AGAINST DC OFFSET AND

INTERHARMONICS FILTER – PROTECTS AGAINST HARMONICS, NOTCHING AND NOISE VOLTAGE REGULATOR – PROTECTS AGAINST SAGS, SURGES AND

FLUCTUATIONS

• MONITOR AND CONTROL HARDWARE / SOFTWARE

Page 32: 2006 0906 Uninterruptible Power Supplies

32

SWITCHOVER TIME

• A TYPICAL SWITCHOVER TIME 2 – 4 ms

ONE QUARTER CYCLE OR LESS

FOR SOME EQUIPMENT THIS IS NOT TOLERABLE

Page 33: 2006 0906 Uninterruptible Power Supplies

33

ADVANTAGES / DIS-ADVANTAGES OF THE DIFFERENT UPS ARCHITECTURES

• LINE INTERACTIVE ADVANTAGES AC TO DC CONVERTER / BATTERY CHARGER DOES NOT HAVE TO

PROVIDE FULL LOAD POWER (POTENTIALLY CHEAPER) LESS STRESS ON DC TO AC INVERTER SINCE IT RUNS AT NO LOAD UNTIL

UPS SWITCHES TO BATTERY POWER (POTENTIALLY CHEAPER)

• ON-LINE ADVANTAGES ZERO SWITCHOVER TIME FROM MAIN LINE TO BATTERY POWER ALWAYS ISOLATED FROM POWER DISTURBANCES ON THE MAIN LINE

Page 34: 2006 0906 Uninterruptible Power Supplies

34

SIZING THE UPS

• EQUIPMENT RATINGS FOR LOADS OBTAIN RATINGS FROM NAMEPLATE OR SPEC SHEET ENERGY USAGE MAY BE SPECIFIED IN VOLT AMPS (VA) OR WATTS (W)

AND IN VALUES THAT ARE EITHER MAXIMUM OR NOMINAL (VA) AND (W) ARE RELATED VIA THE POWER FACTOR

• TOTAL UPS LOAD MUST NOT EXCEED THE UPS VOLT AMP (VA) RATING

• TOTAL UPS LOAD MUST NOT EXCEED THE UPS WATT (W) RATING

• OVERSIZE / DERATE TO ADD LIFE

• RUNTIME CHARTS

Page 35: 2006 0906 Uninterruptible Power Supplies

35

UPS SIZING – EXAMPLE SPREADSHEET

ITEM EQUIPMENT DESCRIPTION MANUFACTURER MODEL VOLT AMPSMAX

(va)

POWER

MAX

(w)

NOTES

1 PC2 MONITOR3 EXTERNAL HARD DRIVE 14 EXTERNAL HARD DRIVE 25 AUDIO SYSTEM6 PRINTER 17 PRINTER 28 CABLE MODEM9 LAPTOP / DOCKING STATION

10 PHONE AND ANSWER MACHINE11 LAMP12 CLOCK

TOTAL

Page 36: 2006 0906 Uninterruptible Power Supplies

36

BATTERY SAFETY

• MAINTENANCE INSPECT PERIODICALLY REPLACE AS NEEDED

• RISKS ACID ELECTRIC SHOCK BURN FLYING, MOLTEN METAL (EYES) INJURIES RESULTING FROM CARRYING HEAVY BATTERY PACKS

• DISPOSAL DISPOSE OF PROPERLY RECYCLE WHENEVER POSSIBLE

Page 37: 2006 0906 Uninterruptible Power Supplies

37

GENERAL DISCUSSION

• DOES A UPS OFFER COMPLETE PROTECTION?• DO YOU THINK “POWER DISTURBANCES WON’T HAPPEN TO

YOU” ?• MISCELLANEOUS

Page 38: 2006 0906 Uninterruptible Power Supplies

38

DOES A UPS OFFER COMPLETE PROTECTION?

• SOME POWER DISTURBANCES MAY EXCEED THE HANDLING CAPABILITY OF THE UPS

• UPS FAILURE

Page 39: 2006 0906 Uninterruptible Power Supplies

39

DO YOU THINK “POWER DISTURBANCES WON’T HAPPEN TO YOU” ?

• POWER DISTURBANCES OCCUR FREQUENTLY, THOUGH MANY ARE SMALL AND WITHOUT CONSEQUENCE

• AN ON-LINE UPS CAN PROTECT AGAINST MORE SIGNIFICANT POWER DISTURBANCES WHEN THEY DO OCCUR

• THE COST OF NOT HAVING A UPS CAN EASILY EXCEED THE COST OF A UPS

Page 40: 2006 0906 Uninterruptible Power Supplies

40

MISCELLANEOUS

• MANY RETAIL UPS FOR COMPUTER APPLICATIONS ARE LINE INTERACTIVE

• MANUFACTURERS AND BUILDING CODES DO NOT ALLOW EXTENSION CORDS OR SURGE SUPPRESSORS TO BE USED WITH A UPS

Page 41: 2006 0906 Uninterruptible Power Supplies

41

SUMMARYTHINGS TO CONSIDER WHEN SPECIFYING A UPS

• POWER QUALITY ARCHITECTURE - LINE INTERACTIVE OR ON-LINE WAVEFORM - SQUARE, MODIFIED SINE, TRUE SINE IMMUNITY TO DISTURBANCES OTHER THAN OUTAGE

• RUN TIME WITH AN OUTAGE• RELIABILITY• AUDIBLE NOISE• MONITOR AND CONTROL HARDWARE / SOFTWARE

LOCAL / REMOTE CONTROL

• INITIAL COST• MAINTENANCE COST• WARRANTY

Page 42: 2006 0906 Uninterruptible Power Supplies

42

REFERENCES

• IEEE STANDARD 1100-2005RECOMMENDED PRACTICE FOR POWERING AND GROUNDING SENSITIVE

ELECTRONIC EQUIPMENT

• IEEE STANDARD 1159-1995RECOMMENDED PRACTICE FOR MONITORING ELECTRICAL POWER QUALITY

Page 43: 2006 0906 Uninterruptible Power Supplies

43

QUESTIONS