Top Banner

of 34

2- Generator Maintenance

Jun 03, 2018

Download

Documents

Asantony Raj
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/12/2019 2- Generator Maintenance

    1/34

    GENERATORS

    MAINTENANCE

  • 8/12/2019 2- Generator Maintenance

    2/34

    Typical Generator Maintenance

  • 8/12/2019 2- Generator Maintenance

    3/34

  • 8/12/2019 2- Generator Maintenance

    4/34

    Generators

  • 8/12/2019 2- Generator Maintenance

    5/34

  • 8/12/2019 2- Generator Maintenance

    6/34

    System controls

  • 8/12/2019 2- Generator Maintenance

    7/34

  • 8/12/2019 2- Generator Maintenance

    8/34

  • 8/12/2019 2- Generator Maintenance

    9/34

  • 8/12/2019 2- Generator Maintenance

    10/34

  • 8/12/2019 2- Generator Maintenance

    11/34

  • 8/12/2019 2- Generator Maintenance

    12/34

  • 8/12/2019 2- Generator Maintenance

    13/34

  • 8/12/2019 2- Generator Maintenance

    14/34

  • 8/12/2019 2- Generator Maintenance

    15/34

  • 8/12/2019 2- Generator Maintenance

    16/34

  • 8/12/2019 2- Generator Maintenance

    17/34

  • 8/12/2019 2- Generator Maintenance

    18/34

  • 8/12/2019 2- Generator Maintenance

    19/34

  • 8/12/2019 2- Generator Maintenance

    20/34

    REASONS WHY GENERATORS FAIL

    FOREIGN OBJECT DAMAGE

    Problem: Objects can come from external sources or

    failure of internal components, they can pick up energy from the spinning rotor and do extensive damage

    Prevention: Inspect on a regular basis all internal parts

    that are prone to failure or can be dislodged.

    Inspection tests can be a combination of visual inspection along with ultrasonic or magnetic particle

    tests on rotating components

  • 8/12/2019 2- Generator Maintenance

    21/34

    STATOR WINDING VIBRATION

    Problem: Primarily a design related problem that

    affects large (>300Mw) generators which have

    insufficient end winding bracing to limit the

    movement of end turns. Prevention: Proper bracing of the end winding is

    required to limit motion caused by steady state and

    transient electromagnetic forces.

  • 8/12/2019 2- Generator Maintenance

    22/34

    ROTOR WINDING DISTORTION

    Problem: Rotor winding distortion caused by poor end

    turn blocking support design or by foreshortening of

    the rotor coils. Foreshortening is caused by thermal forces which compress rotor coils.

    Prevention: Proper design of rotor coils and bracing to

    support the coils under axial load is essential.

    Rotors should be tested for turn to turn shorts at operating speed.

  • 8/12/2019 2- Generator Maintenance

    23/34

    STATOR WINDING VIBRATION

    Problem: Primarily a design related problem that

    affects large (>300Mw) generators which have

    insufficient end winding bracing to limit the movement of end turns.

    Prevention: Proper bracing of the end winding is

    required to limit motion caused by steady state and

    transient electromagnetic forces.

  • 8/12/2019 2- Generator Maintenance

    24/34

    OVERHEATING

    Problem: Overheating of the rotor or stator can lead to

    insulation failure, shorting of turns and ground

    faults. Overheating can result from blocked

    ventilation passages caused by shifting insulation components or slot wedges.

    Prevention: Inspect on a regular basis to ensure all rotor

    wedges are "locked" in place preventing migration

    and thus blocking of cooling passages.

  • 8/12/2019 2- Generator Maintenance

    25/34

    CONTAMINATION

    Problem: For air cooled machines, dirt and dust cause

    tracking which can lead to electrical ground faults.

    Prevention: Inspect air filterson a regular basis , the filters must be checked and cleaned regularly.

    Polarization index (PI) tests give a good indication of

    overall cleanliness of the rotor winding.

  • 8/12/2019 2- Generator Maintenance

    26/34

    ROTOR VIBRATION

    Problem: There are many causes, turn-to-turn shorts,

    rotor coil foreshortening, electrical grounds,

    mechanical imbalances, overheating, etc.

    Prevention: Comprehensive vibration measuring iseffective

    combined with a regular maintenance program.

  • 8/12/2019 2- Generator Maintenance

    27/34

    STATOR WEDGE LOOSENESS

    Problem: When stator wedges become loose, coils can

    vibrate causing insulation wear leading to ground

    faults or turn-to-turn shorts. Prevention: Inspect on a regular basis tightness of

    wedge blocks.

  • 8/12/2019 2- Generator Maintenance

    28/34

    STATOR CORE DAMAGE

    Problem: Stator core looseness can occur over time as

    pre-tensioned through bolts relax. A loose core

    results in insulation wear to coils and laminations

    resulting in hot spots and core-to-coil failures. Prevention: Inspect bolt tightness on a regular basis.

  • 8/12/2019 2- Generator Maintenance

    29/34

    GENERATOR MAINTENANCE The following tests which should be carried

    out annuallyin addition to vendor recommended

    maintenance.

  • 8/12/2019 2- Generator Maintenance

    30/34

    A) INITIAL GENERATOR TEST Megger rotor winding

    Megger exciter armature winding

    Megger exciter field winding

    Complete polarization index (pi) on mainstator

    Check bearing insulation

  • 8/12/2019 2- Generator Maintenance

    31/34

    B) INSPECTION ON STATIC EXCITER Remove exciter end cover

    Examine condition of diode carrier

    Examine exciter armature/stator for contamination

    Examine exciter armature/stator for winding wear Check pmg magnets for contamination

  • 8/12/2019 2- Generator Maintenance

    32/34

    C) ELECTRICAL

    CONTROL/PROTECTION PANEL

    Visually inspect external surfaces of panel

    Complete insulation resistance checks of panelwiring

    Check function of all relays

    Check all fuses

    Check all lamps

    Check operation of all switches

    Check operation of panel heaters Run generator; recalibrate avr

    Secondary inject all protective relays

  • 8/12/2019 2- Generator Maintenance

    33/34

    E) ROTOR EARTH FAULT

    PROTECTOR

    Carry out static checks to confirm operation of

    detector

    Carry out functional check to confirm operation of

    detector

  • 8/12/2019 2- Generator Maintenance

    34/34

    F) SLIP-RINGS AND BRUSH-GEAR (IF

    FITTED)

    Check all brushes for grade and length

    Check condition of brush holders/mountings

    Check that spring tensions are correct

    Check conditions of slip-rings Check mechanical run-out of slip-rings

    Check cooler and leakage alarms