Top Banner
Bay Protection Solutions from Distribution to EHV application The art of Protection Bay
16
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 1KHA001079 BPS600_series_2006

Bay Protection Solutions

from Distribution to EHV application

The artofProtection

Bay

Page 2: 1KHA001079 BPS600_series_2006

2 ABB

Everything you need

The Highlights of ABB’s BPS 600 Series

■ Optimized, pre-designed protection solutions

from Distribution to EHV

■ Flexible realization of your protection philosophy and schemes

■ Scalable hardware and functionality

■ Fully modeled schemes according IEC 61850 and

efficient integration into IEC 61850-compliant systems

■ Convenient selection, simple

ordering and fast delivery

is already prepared

ordering and fast delivery

Page 3: 1KHA001079 BPS600_series_2006

3

The BPS600 Series of modular bay protection

solutions offers you a smart way of easily

realizing reliable protection schemes for all applications in new and retrofit substations.

ABB’s long experience and deep know-how as global protection systems supplier, field-proven

functionality and hardware as well as innovative technologies are all part of the package.

Short project implementation times, reduced risks and life-cycle cost as well as easy intro-

duction of IEC 61850 into your substations are additional benefits.

The BPS 600 Series together with BCS 600 Series Bay Control

Solutions and SAS 600 Series Substation Automation Solutions is

the perfect strategy to build Substation Automation Systems.

Page 4: 1KHA001079 BPS600_series_2006

Main 1 / Group1

BPS 673BPS 671 BPS 671 BPS 671 BPS 673BPS 670BPS 674

Main 2 / Group 2

Busbar

QB1 QB2

QA1

BI1BI2BI3BI4

QB1 QB2

QA1

BI1BI2BI3BI4

LongLine

BI1

QB1 QB2

QA1

BI1BI2BI3BI4

BI1

MediumLine

QB1 QB2

QA1

BI1BI2BI3BI4

ShortLine

BI1

QB1 QB2

QA1

BI1BI2BI3BI4

BI6

BI5

BI7

QB1 QB2

QA1

BI1BI2BI3BI4

BI6

BI7

Bay Protection Solutions

Cable feeder

Line Feeder

Busbar / Breaker-failure

TransformerCoupler / Section / DiameterShunt

MotorT-Zone

Distribution

Sub-transmission Main Backup

Main 1Main 2

Main

Main 1Main 2

Transmission

Protection

concept

BPS504

BPS503

BPS502

BPS501

BPS634

BPS533

BPS532

BPS531

BPS630

BPS654

BPS653

BPS552

BPS651

BPS650

BPS674

BPS

BPS

BPS671

BPS684

BPS

BPS682

BPS506

BPS685

BPS687

BPS681

BPS

BPS

673

670

672

683

680

BPS modular scalable

protection solutions

protects your entire

substation

4

built-inABB expertise

With

Page 5: 1KHA001079 BPS600_series_2006

Main 1 / Group1

BPS 673BPS 671 BPS 671 BPS 671 BPS 673BPS 670BPS 674

Main 2 / Group 2

Busbar

QB1 QB2

QA1

BI1BI2BI3BI4

QB1 QB2

QA1

BI1BI2BI3BI4

LongLine

BI1

QB1 QB2

QA1

BI1BI2BI3BI4

BI1

MediumLine

QB1 QB2

QA1

BI1BI2BI3BI4

ShortLine

BI1

QB1 QB2

QA1

BI1BI2BI3BI4

BI6

BI5

BI7

QB1 QB2

QA1

BI1BI2BI3BI4

BI6

BI7

Bay Protection Solutions

Cable feeder

Line Feeder

Busbar / Breaker-failure

TransformerCoupler / Section / DiameterShunt

MotorT-Zone

Distribution

Sub-transmission Main Backup

Main 1Main 2

Main

Main 1Main 2

Transmission

Protection

concept

BPS504

BPS503

BPS502

BPS501

BPS634

BPS533

BPS532

BPS531

BPS630

BPS654

BPS653

BPS552

BPS651

BPS650

BPS674

BPS

BPS

BPS671

BPS684

BPS

BPS682

BPS506

BPS685

BPS687

BPS681

BPS

BPS

673

670

672

683

680

5

Reliable solutions for efficient system integration

Page 6: 1KHA001079 BPS600_series_2006

beyondprotection

Far

Busbar Protection

BPS 6x0

■ For single to quadruple busbars incl. transfer bus■ For one and a half breaker systems■ Decentralized and centralized installation for up to 60 bays■ Breaker-failure protection■ Event- and disturbance recording

Busbar Protection Add-ons■ IEC 61850-8-1 interface■ Endfault protection■ Test switches

Line and Cable Protection

BPS 6x1 / 6x2

Line Differential protection■ Phase-segregated differential protection■ Direct fiber-optic link between relays (3 to 100 km)■ With / without transformers in the protected zone■ Redundant communi- cation possibility ■ GPS time synchroni- zation in route switched networks■ Associated functions ■ Long lines with charging current com- pensation ■ Non-directional E/F over-current protection ■ Disturbance recorder

Line Distance Protection■ Full scheme distance protection■ Up to 5 Zones, phase- selective, quadrilateral characteristics■ Wide range of commu- nication schemes■ Line distance protection can be an integrated part of the station pro- tection bay unit■ Associated functions ■ Non-directional E/F over-current protection ■ Directional E/F protection ■ Power-swing blocking ■ Fuse-failure super- vision ■ Switch-onto-fault ■ Disturbance recorder

Line and cable protection Add-ons ■ IEC 61850-8-1 Interface■ 1 and/or 3-phase auto- reclosure ■ Synchrocheck / voltage check ■ Bay unit with busbar / breaker- failure and endfault protection■ Trip circuit supervision ■ DTT Lockout relays■ Test switches

Transformer Protection

BPS 6x3

Transformer Differential Protection■ Biased differential protection for transfor- mers /autotransformers■ Phase-segregated high- impedance protection■ High-impedance/low- impedance restricted earth fault (REF) protect- ions on the primary and/or secondary side■ Tertiary earth fault protection■ Transformer differential protection can be an integrated part of the station protection bay unit

■ Associated functions ■ Non-directional E/F over-current protection ■ Phase over-current protection ■ Thermal overload ■ Overfluxing protection ■ Over-voltage protection ■ Logic for Buchholz, winding, oil tempera- ture etc. ■ Transformer guard units for eight mecha- nical protection signals like Buchholz ■ Disturbance recorder

Transformer Protection Add-ons ■ IEC 61850-8-1 interface■ Transformer guard unit for eight mechanical protections like Buch- holz, temperature and overpressure devices including necessary auxiliary relays for signaling / tripping■ Bay unit with busbar / breaker-failure and endfault protection■ Trip-circuit supervision ■ DTT Lockout relays■ Test switches

BPS 6x0 Busbar & Breakerfailure

BPS 6x Distance protection

BPS 6x Transformer protection

BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection

BPS 6x3 Transformer protection

BPS

BPS Motor protection

M

BPS 6x0 Busbar & Breakerfailure

BPS 6x Distance protection

BPS 6x Transformer protection

BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection

BPS 6x3 Transformer protection

BPS

BPS Motor protection

M

BPS 6x0 Busbar & Breakerfailure

BPS 6x Distance protection

BPS 6x Transformer protection

BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection

BPS 6x3 Transformer protection

BPS

BPS Motor protection

M

6

Page 7: 1KHA001079 BPS600_series_2006

Coupler / Section / Diameter Protection

BPS 6x4

■ Busbar protection bay unit■ Definite time overcurrent protection for the coupler / sectionalizer ■ Breaker-failure protection ■ Disturbance recorder ■ This solution is mostly combined with the central unit of a BPS6x0 in a decentralized arrangement

Coupler / Section / Diameter Protection Add-ons ■ IEC 61850-8-1 interface■ Trip circuit supervision ■ Test switches

Line Shunt Reactor Protection

BPS 6x5

■ Biased low-impedance or high-impedance differential protection■ Restricted earth fault, low or high- impedance ■ Non-directional over- current protection ■ Thermal overload ■ Overfluxing ■ Disturbance recorder

Line Shunt Reactor Protection Add-ons ■ IEC 61850-8-1 Interface■ Bay unit with busbar / breaker- failure and endfault protection■ Trip-circuit supervision■ DTT Lockout relays■ Test switches

BPS 6x0 Busbar & Breakerfailure

BPS 6x Distance protection

BPS 6x Transformer protection

BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection

BPS 6x3 Transformer protection

BPS

BPS Motor protection

M

BPS 6x0 Busbar & Breakerfailure

BPS 6x Distance protection

BPS 6x Transformer protection

BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection

BPS 6x3 Transformer protection

BPS

BPS Motor protection

M

T-Zone Protection

BPS 6x7

■ Biased differential protection or per-phase high-impedance protection■ Non-directional over- current protection■ Disturbance recorder

T-Zone Protection Add-ons ■ IEC 61850-8-1 Interface■ Lockout relays■ Test switches

BPS 6x0 Busbar & Breakerfailure

BPS 6x Distance protection

BPS 6x Transformer protection

BPS 6x1 Line protection & BPS 6x2 Cable protection BPS 6x Shunt protection

BPS 6x3 Transformer protection

BPS

BPS Motor protection

M

Sequence of events

■ Event list■ Historical events■ Filtering function■ Export facilities

Disturbance record upload

■ Manual upload■ Cyclic upload■ Event-driven upload

Disturbance record analysis

■ Waveform visualiza- tions, signal vectors■ Fault location, advan- ced calculation■ Frequency deviation, apparent and reactive power calculation■ Automatic analysis

Trip counter tableIED parameterization

Automatic sequences

Trends

Dynamic busbarcoloring

Measurements reports

External alarming

Advanced functionalities

Disturbance record upload

Disturbance record analysis

Public PagingSystems Faxe-mail

TelephoneFixed

AlarmBelx,eoidihjkjklkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never again

Alarm Belx,eoidihjkjk

lkdlkjdlkul lkj never again

Station Computer

TelephoneMobile ShortMessages(SMS)

AlarmBelx,eoidihjkjklkdlkjdlkul lkj never Quare sibi habeant.Belx,eoidihjkjklkdlkjdlkul lkj never again. Quare sibi habeant. Belx

Trip counter tableIED parameterization

Automatic sequences

Trends

Dynamic busbarcoloring

Measurements reports

External alarming

Advanced functionalities

Disturbance record upload

Disturbance record analysis

Public PagingSystems Faxe-mail

TelephoneFixed

AlarmBelx,eoidihjkjklkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never again

Alarm Belx,eoidihjkjk

lkdlkjdlkul lkj never again

Station Computer

TelephoneMobile ShortMessages(SMS)

AlarmBelx,eoidihjkjklkdlkjdlkul lkj never Quare sibi habeant.Belx,eoidihjkjklkdlkjdlkul lkj never again. Quare sibi habeant. Belx

IED parameterization

■ Configuration/para- meter upload from IED■ Change of individual parameters or para- meter sets■ Access to all IED para- meters

Trip counter tableIED parameterization

Automatic sequences

Trends

Dynamic busbarcoloring

Measurements reports

External alarming

Advanced functionalities

Disturbance record upload

Disturbance record analysis

Public PagingSystems Faxe-mail

TelephoneFixed

AlarmBelx,eoidihjkjklkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never againQuare sibi habeant.Belx,eoidihjkjk

lkdlkjdlkul lkj never again

Alarm Belx,eoidihjkjk

lkdlkjdlkul lkj never again

Station Computer

TelephoneMobile ShortMessages(SMS)

AlarmBelx,eoidihjkjklkdlkjdlkul lkj never Quare sibi habeant.Belx,eoidihjkjklkdlkjdlkul lkj never again. Quare sibi habeant. Belx

Various back-up protection functions are available in the used devices and can be applied as a customization■ Definite time over- and undercurrent protection

■ Three- phase current plausibility check■ Three- phase voltage plausibility check■ Direct. sensitive EF prot. for grounded systems■ Directional over-current inverse time protection

Back-up Protection

■ Inverse time over- current protection■ Definite time over- and undervoltage protection■ Inverse time earth fault over-current protection■ Directional overcurrent definite time protection

7

Page 8: 1KHA001079 BPS600_series_2006

BPS 6x1 / BPS 6x2 Line and cable protectionThe modular basic packages are

designed for cables, overhead lines

and multi-terminal lines of various

lengths. These can be complemen-

ted by a choice of options to meet

your specific requirements and

philosophy

Typical applications for BPS6x1

■ Short lines ■ Medium lines■ Long lines■ Multi-terminal lines with / without transformers■ Tapped lines with / without transformers

Typical applications for BPS6x2

■ Cables

Available line and cable protection solutions

Short lines

Medium lines

Long lines

Multi-terminal lines

V15

V25

V35

V11V14

V21V24

V11 V11 V11

IED 1Main 1

IED 2 Main 2 / Back-up BPS 651 BPS 671 BPS 681

IED 1 IED 2 BPS 652 BPS 672 BPS 682

Cables

V31

V41

V31

V21

V11

Mainprotection functions

Sub-transmission

Transmissionone and a

half breaker

Transmissionsingle /

double bus

PDIF PDIF

PDIF PDIS

PDIF PDIF

PDIF PDIS* PDIS

PDIF PDIS*

PDIF PDIS*

* used as a back-up in the same device

8 ABB

BB – I

Line Bay Single / Double Bus

BB – II

QB1

QA1

BI1

BI2

BI3

BU1

IEC 61850-8-1

General options

2769

TCSLatch

Busbar &Breaker Failure

Protection

PDIFRBRFPTOCRDREPTRC

87B50/62BF51EFP95DR

94

Main 1Protection

IEC ANSI

PDISPTOCPTOCPIOCPTOVRPSBPSOFPTTRPTRCRDREGGIO

21,8551/67N51/67

50/50N59/59N

78SOTF

4994

95DRDTT

Main 2Protection

IEC ANSI

Add-onPackage

IEC ANSI

RSYNRREC

2579

Add-onPackage

IEC ANSI

PDIFPDISPTOCPTOCPIOCPTOVRPSBPSOFPTRCRDREGGIO

87L21

51/67N51/67

50/50N59/59N

78SOTF

9495DRDTT

RSYNRREC

2579

IEC ANSI

IEC ANSI

Page 9: 1KHA001079 BPS600_series_2006

BPS 6x1 / BPS 6x2 Line and cable protection

9ABB

BB – I

Line Bay Single / Double Bus

BB – II

QB1

QA1

BI1

BI2

BI3

BU1

IEC 61850-8-1

General options

2769

TCSLatch

Busbar &Breaker Failure

Protection

PDIFRBRFPTOCRDREPTRC

87B50/62BF51EFP95DR

94

Main 1Protection

IEC ANSI

PDISPTOCPTOCPIOCPTOVRPSBPSOFPTTRPTRCRDREGGIO

21,8551/67N51/67

50/50N59/59N

78SOTF

4994

95DRDTT

Main 2Protection

IEC ANSI

Add-onPackage

IEC ANSI

RSYNRREC

2579

Add-onPackage

IEC ANSI

PDIFPDISPTOCPTOCPIOCPTOVRPSBPSOFPTRCRDREGGIO

87L21

51/67N51/67

50/50N59/59N

78SOTF

9495DRDTT

RSYNRREC

2579

IEC ANSI

IEC ANSI

Features■ Comprehensive functionality

for Main1 + Main 2 / Back-up■ LAN connectivity to IEDs for

configuration and monitoring

Options■ IEC 61850-8-1 communication

interface■ Autoreclosure and synchrocheck■ Busbar and breaker failure

protection■ Trip circuit supervision■ DTT Lock-out relays■ Test switches

Page 10: 1KHA001079 BPS600_series_2006

BPS 6x3 Transformer protectionThe scaleable solutions provide

reliable protection for all types and

sizes of transformers. Their field-

proven protection and monitoring

functionality helps to prolong the

service-life of the most expensive

pieces of equipment in your sub-

station.

Typical applications for BPS6x3

■ Two and three Winding-transformers■ Autotransformers

Available versions

IED 1Main 1

IED 2 Group 2 / Back-up

BPS 653 BPS 673 BPS 683

V12V12V15Two or three Winding-transformer

V22Autotransformer

Mainprotection functions

Sub-transmission

Transmissionone and a

half breaker

Transmissionsingle /

double bus

PDIF PTOCPDIF

PTOCPTTR

PTOVPVPH

PDIF PTOCPDIF

PTOCPTTR

PTOVPVPH

BB – I

Transformer Bay Single / Double Bus

BB – II

QB1 QB2

QA1

BI1

BI2

BI3

BI4

BI7

BI5

BI6

IEC 61850-8-1

Group 1Protection

PDIFPTOC PIOCPTTRPTRCRDREGGIO

87T51/67

50/50N4994

95DRDTT

IEC ANSI

PTOCPTOCPIOCPVPHPTOVPTRCRDREGGIO

51/67N51/67

50245994

95DRDTT

Group 2Protection

IEC ANSI

Add-onPackage

GGIO GuardIEC ANSI

PDIF HVPDIF MV

GGIO

87N87N

Guard

IEC ANSI

Add-onPackage

27 TCS

Busbar &Breaker Failure

Protection

PDIFRBRFPTOCRDREPTRC

87B50/62BF51EFP95DR

94

General optionsIEC ANSI

IEC ANSI

10

Page 11: 1KHA001079 BPS600_series_2006

BB – I

Transformer Bay Single / Double Bus

BB – II

QB1 QB2

QA1

BI1

BI2

BI3

BI4

BI7

BI5

BI6

IEC 61850-8-1

Group 1Protection

PDIFPTOC PIOCPTTRPTRCRDREGGIO

87T51/67

50/50N4994

95DRDTT

IEC ANSI

PTOCPTOCPIOCPVPHPTOVPTRCRDREGGIO

51/67N51/67

50245994

95DRDTT

Group 2Protection

IEC ANSI

Add-onPackage

GGIO GuardIEC ANSI

PDIF HVPDIF MV

GGIO

87N87N

Guard

IEC ANSI

Add-onPackage

27 TCS

Busbar &Breaker Failure

Protection

PDIFRBRFPTOCRDREPTRC

87B50/62BF51EFP95DR

94

General optionsIEC ANSI

IEC ANSI

IEC 61850-8-1

11ABB

Features■ Comprehensive functionality

for Group 1 + Group 2 / Back-up■ LAN connectivity to IED’s

for configuration and monitoring

Options■ IEC 61850-8-1 communication

interface■ Busbar and breaker-failure

protection■ Trip circuit supervision■ DTT Lock-out relays■ Test switches

Page 12: 1KHA001079 BPS600_series_2006

BPS6x0 / BPS 6x4 Busbar and Breakerfailure protectionThe solutions ensure highest

availability of busbars of any type,

configuration and size. Centralized

and cable-saving decentralized

solutions cater for new and retro-

fit substations and offer additional

backup protection in the bays.

For a more integrated, space and

cost-efficient solution, a station

protection system covering busbars,

line and transformers feeders is

available as well.

Typical applications for BPS6x0

■ Single to quadruple busbars incl. transfer bus

■ One and a half breaker systems

■ AIS / GIS installations with up to 60 bays

Typical applications for BPS6x4

■ Buscoupler■ Sections■ Diameters

Available versions

IEC 61850-8-1

Bay level

Bayunit

FOlink

Central unit

Bayunit

Station level

IEC ANSIBuscoupler

RBRFPTOCPTOCPDREPTRC

50/62BF51EFP

5195DR

94

27 TCS

Add-onIEC ANSI

PDIF 87B

Central unitBPS 670

IEC ANSIQ

B1

QB

2

QA

1

BI1

BI2

BI3

BI4

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI1

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI1

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI1

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI6

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI6

V11V12V13V14V15V16

V11V12V13V14V15V16

V11V12V13V14V15V16

Decentral

V21V34

V21V33V21

Central

BPS 650 BPS 670 BPS 680

V11V21

V11V12

V11Coupler /Section /Diameter

PDIF RBRF

PDIF RBRF

RBRFPTOC

Mainprotection functions

Sub-transmission

Transmissionone and a

half breaker

Transmissionsingle /

double bus

12

Page 13: 1KHA001079 BPS600_series_2006

BPS6x0 / BPS 6x4 Busbar and Breakerfailure protection

Features■ Highly selective and fast

busbar protection■ Breaker failure protection■ LAN connectivity to IED’s

for configuration and monitoring

Options■ IEC61850-8-1 communication

interface■ Back-up protection functions

in bay units■ Trip circuit supervision■ End fault protection■ Test switches

IEC 61850-8-1

Bay level

Bayunit

FOlink

Central unit

Bayunit

Station level

IEC ANSIBuscoupler

RBRFPTOCPTOCPDREPTRC

50/62BF51EFP

5195DR

94

27 TCS

Add-onIEC ANSI

PDIF 87B

Central unitBPS 670

IEC ANSI

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI1

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI1

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI1

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI6

QB

1Q

B2

QA

1

BI1

BI2

BI3

BI4

BI6

Page 14: 1KHA001079 BPS600_series_2006

Protection solutionsIEC 61850

Trans-mission

level

Sub-trans-

missionlevel

Hardcopyprinter

SAS 650

Eventprinter

Additionalworkstation

GPSRedundant station HMI

Stationalarmdevice

Remoteaccessrouter

Telecommuni-cation link

Masterclock

Bay Protection and Bay Control Solutions

Bay Protection and Bay Control Solutions

Substation Automation System

Typical ABB Substation Automation Solution

Stationlevel

BPS 670BPS 674

BPS 673 BPS 671

BPS 650BPS 654

BPS 653 BPS 651 BCS 680

BCS 670 BCS 670 BCS 670

Station server

Gateway

14 ABB

based on

Page 15: 1KHA001079 BPS600_series_2006

Protection solutionsIEC 61850

LD “Distance Protection”

“Circuit Breaker”

LD “Recloser”

PDIS 1 PTRC

XCBR

STR

TR

“Retrip” “Close”

Pos

Op

Op

STR STR TrMod

MaxCycl

MaxTmms

Rec i Tmms

TrBeh

RecCyc

OP

Op

Status Settings

Status

ProgrammableCombination

of Inputs

Op

STR

RREC

PDIS 2

PDIS n

15ABB

in a substation automation environmentin a substation in a substation

environment

How to use IEC 61850 for time-critical

information exchange

There are several automated functions in the substa-

tion automation system, which require a time-critical

exchange of binary information between functions

located within the same bay or in different bays.

Examples:■ Exchange between line protection and auto-recloser

■ Exchange between bays for breaker-failure protection

■ Exchange between bays for station interlocking

■ DR triggering by protection functions

Generic Object Oriented Substation Event

For the exchange of this type of (binary) information

over serial communication, IEC 61850 introduces a

specific information exchange service called GOOSE

(Generic Object Oriented Substation Event) based on

the publisher-subscriber concept. The content of a

GOOSE message is defined with a dataset (similar

as for the report model described above). The

GOOSE message is sent as a multicast message

over the communication network. This means that

various devices can receive the message and retrieve

the information required from the message. The

communication service is not confirmed; instead,

the message is repeated several times.

Exchange of information within the bay

A typical example is the exchange of information be-

tween Logical Device “Distance Protection” containing

instances of LN PDIS per zone and the LN PTRC

and the Logical Device “Recloser” containing the LN

RREC in case these both functions are installed in

separate devices.

Page 16: 1KHA001079 BPS600_series_2006

Bay Protection Solutions

Cable feeder

Line Feeder

Busbar / Breaker-failure

TransformerCoupler / Section / DiameterShunt

MotorT-Zone

Distribution

Sub-transmission Main Backup

Main 1Main 2

Main

Main 1Main 2

Transmission

Protection

concept

BPS504

BPS503

BPS502

BPS501

BPS634

BPS533

BPS532

BPS531

BPS630

BPS654

BPS653

BPS552

BPS651

BPS650

BPS674

BPS

BPS

BPS671

BPS684

BPS

BPS682

BPS506

BPS685

BPS687

BPS681

BPS

BPS

673

670

672

683

680

Perfect packages with the

Right functionality

Optimal hardware

Open communication

BPS 600 Series overview

Designed for your convenience

BPS 600—the smart choice

The BPS 600 Series together with BCS 600 Series Bay Control Solutions

and SAS 600 Series Substation Automation Solutions is the ultimate and

efficient strategy to build Substation Automation Systems.

© C

opyr

ight

200

6 A

BB

. A

ll rig

hts

rese

rved

.

1KH

A -

001

079

- S

EN

- P

DF

- 9.

06 -

Prin

ted

in S

witz

erla

nd.

ABB Schweiz LtdPower SystemsBruggerstrasse 72CH-5400 Baden/SwitzerlandPhone +41- 58 585 77 44Fax +41- 58 585 55 77E-mail [email protected]

www.abb.com/substationautomation