This Datasheet is for the 1756-PB72 The Allen-Bradley / Rockwell Automation 1756-PB72 is a 24 V DC ControlLogix Standard Power Supply. Operating voltage of 1756PB72 is 18...32 V DC. The ControlLogix power supply is accompanied with the 1756 chassis to provide 1.2V, 3.3V, 5V, and 24V DC power to the chassis backplane (chassis standard series A and B). http://www.qualitrol.com/shop/p-15937-1756-pb72.aspx For further information, please contact Qualitrol Technical Support at 1-800-784-9385 [email protected]
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
This Datasheet is for the
1756-PB72
The Allen-Bradley / Rockwell Automation 1756-PB72 is a 24 V DC ControlLogix Standard
Power Supply. Operating voltage of 1756PB72 is 18...32 V DC. The ControlLogix power
supply is accompanied with the 1756 chassis to provide 1.2V, 3.3V, 5V, and 24V DC power
to the chassis backplane (chassis standard series A and B).
user memory CompactFlash CompactFlash CompactFlash CompactFlash None None CompactFlash
Built-in
communication
ports
1 port RS-232 serial 1 port RS-232 serial 1 port RS-232 serial • 1769-L31: 2 RS-232 ports • 1769-L32C, 1769-L35CR: 1 ControlNet port and 1 RS-232 serial port • 1769-L32E, 1769-L35E: 1 EtherNet/IP port
and 1 RS-232 serial port
• 1769-L23E-
QB1B: 1 EtherNet/IP port
and 1 RS-232 serial port • 1769-L23E-QBFC1B: 1 EtherNet/IP
port and 1 RS-232 serial
port • 1769-L23-
QBFC1B: 2 RS-232 serial
ports
Depends on
personal computer 1 port RS-232 serial
Communication
options • EtherNet/IP • ControlNet • DeviceNet • Data Highway Plus • Remote I/O • SynchLink
• EtherNet/IP (standard and
safety) • ControlNet (standard and
safety) • DeviceNet (standard and
safety) • Data Highway Plus • Remote I/O • SynchLink
SERCOS interface N/A N/A SERCOS interface Analog encoder
input
• 1 full servo • 1 feedback axis
Programming
languages • Relay ladder • Structured text • Function block • SFC
• Relay ladder • Structured text • Function block • SFC
• Relay ladder • Structured text • Function block • SFC
• Relay ladder • Structured text • Function block • SFC
• Relay ladder • Structured
text • Function block • SFC
• Relay ladder • Structured text • Function block • SFC • External routines (developed in
C/C++)
• Relay ladder • Structured text • Function block • SFC
Publication 1756-SG001M-EN-P - May 2009 5
Select a ControlLogix
System
Select a ControlLogix System
Publication 1756-SG001M-EN-P - May 2009 7
ControlLogix System
Overview
The ControlLogix system provides discrete, drives, motion, process, and safety
control together with communication and state-of-the-art I/O in a small, cost-
competitive package. The system is modular, so you can design, build, and
modify it efficiently with significant savings in training and engineering.
Example Configuration - ControlLogix System
A simple ControlLogix system consists of a standalone controller and I/O
modules in a single chassis. For a more comprehensive system, use:
• multiple controllers in a single chassis.
• multiple controllers joined across networks.
• I/O in multiple platforms that are distributed in
many locations and connected over multiple I/O
links.
4
Select a ControlLogix System
Publication 1756-SG001M-EN-P - May 2009
ControlLogix-XT System
The ControlLogix-XT controllers function in the same way as the traditional
ControlLogix controllers. The ControlLogix-XT products include control
and communication system components that, when used with FLEX I/O-
XT products, provide a complete control system solution that can be used in
environments where temperatures range from -20...70 °C (-4...158 °F).
When used independently, the ControlLogix-XT system can withstand
environments where the temperature ranges from -25...70 °C (-13...158 °F).
GuardLogix Safety System
A GuardLogix controller is a ControlLogix controller that also provides
safety control. The GuardLogix system is a dual controller solution — you
must use a 1756-L6xS primary controller and a 1756-LSP safety partner to
achieve SIL 3/CAT. 4. A major benefit of this system is that it’s still a single
project, safety and standard together. The safety partner controller is a part
of the system, is automatically configured, and requires no user setup.
Application Description
SIL 3 The GuardLogix controller system is type-approved and certified for use in safety applications up to and including SIL 3 according to IEC 61508, and applications up to and including category (CAT) 4, according to EN954-1. For more information, see:
• GuardLogix Controllers Systems Safety Reference Manual, publication 1756-
RM093.
• GuardLogix Controllers User Manual, publication 1756-UM020.
• GuardLogix Safety Application Instruction Set Reference Manual,
publication 1756-RM095.
SIL 2 Components of the ControlLogix system are type-approved and certified for use in SIL 2 applications, according to IEC 61508, and AK4 applications according to DIN V19250. For a list of ControlLogix system components that meet SIL 2 requirements, see Using ControlLogix in SIL 2 Applications Safety Reference Manual, publication 1756-
RM001.
Example Configuration - Redundant ControlLogix
System The ControlLogix controller supports controller
1786-RPFRXL ControlNet fiber ring repeater, extra long
1786-RPFS ControlNet fiber ring repeater, short
1786-RPFM ControlNet fiber ring repeater, medium
DeviceNet Communication Module
The DeviceNet network is an open, low-level network that provides
connections between simple industrial devices (such as sensors and actuators)
and higher-level devices (such as controllers and computers). The DeviceNet
network uses the proven Common Industrial Protocol (CIP) to provide the
control, configure, and data collection capabilities for industrial devices.
Taps
Select a ControlLogix System
Publication 1756-SG001M-EN-P - May 2009 27
Cat. No. Description Communication Rate Number of
Nodes
1756-DNB DeviceNet communication bridge module 125 Kbps (500 m max)
250 Kbps (250 m max)
500 Kbps (100 m max)
64
Example Configuration - DeviceNet Network
Accessories - DeviceNet Network
Cat. No. Description
KwikLink Lite flat media KwikLink Lite flat media is a newer, ODVA-approved solution for wiring DeviceNet networks. Drop-lines for connecting nodes are added by using the KwikLink Lite two-piece connectors. This cable system supports the intermixing of DeviceNet cable types (thin-round with flat). All of the KwikLink Lite connectors provide insulation displacement technology with reduced
assembly time.
KwikLink flat media The KwikLink flat media system provides a modular cabling method with its flat 4-wire
cable and insulation displacement connectors (IDCs). The KwikLink system allows nodes
to be added to the network without severing the trunkline. Cutting or stripping of the
trunkline is eliminated, as is the need for predetermined cable lengths.
Round media Round trunk cable is available in bulk spools or as pre-molded cordsets or patchcords in varying lengths. A wide variety of rugged, durable DeviceNet components is available for use in round trunk systems. Stainless steel versions of round cable system components are also available.
• Thick-trunk round media systems use thick cable for maximum DeviceNet trunk line
length.
• Round media thin-trunk systems use thin cable to reduce maximum trunk line
distances with a more compact and cost-effective installation for some applications.
Thin-cable outer jacket material is TPE for additional chemical resistance.
Select a ControlLogix System
28 Publication 1756-SG001M-EN-P - May 2009
Data Highway Plus and Remote I/O Communication
Modules
The Data Highway Plus network supports messaging between devices. The
remote I/O link connects to remote I/O chassis and other intelligent devices.
The 1756-DHRIO module supports messaging between devices on DH+
networks. The remote I/O functionality enables the module to act as a scanner
for transferring digital and block-transfer data to and from remote I/O devices.
The 1756-RIO module can act as a scanner or adapter on a remote I/O
network. In addition to digital and block-transfer data, the 1756-RIO module
transfers analog and specialty data without message instructions.
Cat. No. Description Communication Rate DH+
Connections
RIO
Connections
Logix
Connections
1756-DHRIO Data Highway Plus/Remote
I/O communication module
DH+: 57.6 Kbps
RIO: 57.6 Kbps, 115.2
Kbps, 230.4 Kbps
32 DH+
messages per
DH+ channel
32 logical rack connections per remote I/O channel
16 block-
transfer
connections
per remote I/O
channel
32
1756-RIO Remote I/O communication
module
RIO: 57.6 Kbps, 115.2
Kbps, 230.4 Kbps
na 32 physical
racks (0...76),
any
combination of
rack size and
block transfers
10 scheduled
I/O
1756-
DHRIOXT
ControlLogix-XT, Data
Highway Plus/Remote I/O
communication module
DH+: 57.6 Kbps
RIO: 57.6 Kbps, 115.2
Kbps, 230.4 Kbps
32 DH+
messages per
DH+ channel
32 logical rack connections per remote I/O channel
16 block-
transfer
connections
per remote I/O
channel
32
Select a ControlLogix System
Publication 1756-SG001M-EN-P - May 2009 29
Example Configuration - DH+ Network
Example Configuration - Remote I/O Network
Accessories - DH+ and Remote I/O Networks
Cat. No. Description Specifications
1770-CD Cable to connect communication module to DH+
network
Belden 9463 twinaxial
9300-RADKIT Remote access dial-in kit 56 Kbps modem connection to devices on a DH+ network, includes:
• pre-configured modem
• communication module
• DIN rail mounting hardware
• associated cables
Foundation Fieldbus Linking Devices
Foundation Fieldbus is a communication network created by the Fieldbus
Foundation. It is a protocol designed for robust, distributed control of process
Select a ControlLogix System
30 Publication 1756-SG001M-EN-P - May 2009
control applications. Devices connected by a Foundation Fieldbus network can
be used for sophisticated, highly-distributed process control.
Cat. No. Description Communication
Rate
Number of H1
ports
Number of
Devices per H1
Link
Number of
Devices per
Linking Device
1757FFLD2 Foundation Fieldbus linking
device bridges from an
Ethernet network
Foundation
Fieldbus:
31.25 Kbps
EtherNet/IP:
10/100
Mbps
2 16 (8…10
recommended)
32
1757-FFLD4 4 64
1757-FFLDC2 Foundation Fieldbus linking
device bridges from a
ControlNet network
Foundation
Fieldbus:
31.25 Kbps
ControlNet: 5
Mbps
2 16 (8…10
recommended)
32
1757-FFLDC4 4 64
Example Configuration - EtherNet/IP Network to
Foundation Fieldbus Network
Select a ControlLogix System
Publication 1756-SG001M-EN-P - May 2009 31
Example Configuration - ControlNet Network to
Foundation Fieldbus Network
Accessories - Foundation Fieldbus Network
Cat. No. Description
DIN rail 35 x 7.5 or 35 x 15 DIN (EN 50 022), zinc-plated yellow chromate
steel
Serial Communication
The controller serial port is compatible with RS-232 serial communication. The
serial port supports the DF1 protocol to communicate with other devices on
the serial link.
Select a ControlLogix System
32 Publication 1756-SG001M-EN-P - May 2009
Example Configuration - Serial Communication
Modbus Support
To use Logix5000 controllers on Modbus, you connect through the serial port
and execute a specific ladder logic routine. The controller project is available
with RSLogix 5000 Enterprise programming software. For more information,
see Using Logix5000 Controllers as Masters or Slaves on Modbus Application
Solution, publication CIG-AP129.
DH-485 Communication Module
The controller serial port is compatible with DH-485 communication. The
DH-485 connection does support remote programming and monitoring via
RSLogix 5000 software.
Cat. No. Description Communication Rate
1756-DH485 DH-485 communication bridge module 19.2 Kbps
RSLogix 5000 software, version 17 has been tested on the following operating
systems:
• Microsoft Windows XP Professional with Service Pack 2 • Microsoft Windows Server 2003 R2 Standard Edition with Service Pack 1 and User Account Control (UAC) turned off • Microsoft Windows 2000 Professional with Service Pack 4
• Microsoft Windows Vista Home Basic with SPI
• Microsoft Windows Vista Business with SPI
RSLogix 5000 software is expected to operate correctly on the following operating systems, but has not been tested: • Microsoft
• Microsoft Windows XP Home
• Microsoft Windows Server 2003 Standard Edition with Service Pack 1
• Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3
• Microsoft Windows Vista Ultimate
• Microsoft Windows Vista Home Premium
The Chinese, Japanese, and Korean editions of RSLogix 5000 software are supported
only on Microsoft Windows XP, Microsoft Windows Vista, and Microsoft Windows
Server 2003. RSLogix 5000 software is supported for 32-bit architectures (x86) and
has not been tested with 64-bit architectures (x64).
RAM 128 MB min
256 MB recommended
Hard disk space 3 GB of free hard disk space (or more based on application requirements)
Optical drives DVD
Video requirements 256-color VGA graphics adapter
800 x 600 min resolution (True Color 1024 x 768 recommended)
Select a ControlLogix System
Publication 1756-SG001M-EN-P - May 2009 45
RSLogix 5000 Enterprise Series Software Packages
• Replace xx in the catalog number with the appropriate language
IT=Italian, JP=Japanese, KO=Korean, PT=Portuguese, and
ES=Spanish.
• For upgrades from one package to another, see the StepForward
program.
Available Features Service Edition
9324-RLD000xxE Mini Edition 9324-RLD200xxE
Lite Edition 9324-RLD250xxE
Standard Edition: Node Locked 9324-RLD300xxE Concurrent License(1) 9324-RLD300xxF
Standard/
NetWorx Edition 9324-
RLD300NXxxE
Full Edition: Node Locked 9324-RLD600xxE Concurrent License(1) 9324-RLD600xxF
Professional Edition: Node Locked: 9324-
RLD700NXxxE Concurrent License(1) 9324-
RLD700NXxxF
Logix5000
controllers
supported
All(2) CompactLogix
FlexLogix CompactLogix
FlexLogix All All All(3) All
Relay ladder diagram
editor(4) Upload/download
and view Full support Full support Full support Full support Full support Full support
Function block
diagram 9324-RLDFBDENE(4)
Upload/download
and view Upload/download Available
separately
Full support Upload/download Available
separately
Upload/download Available
separately
Full support Full support
Sequential function
chart editor 9324-
RLDSFCE(4)(5)
Upload/download
and view Upload/download Available
separately
Full support Upload/download Available
separately
Upload/download Available
separately
Full support Full support
Structured text 9324-RLDSTXE(4)
Upload/download
and view Upload/download Available
separately
Full support Upload/download Available
separately
Upload/download Available
separately
Full support Full support
PhaseManager 9324-
RLDPME Upload/download Upload/download
Available
separately
Upload/download Available
separately
Upload/download Available
separately
Upload/download Available
separately
Full support Full support
GuardLogix Safety 9324-RLDGLXE(6)
Upload/download
and view NA NA Upload/download
Available
separately
Upload/download Available
separately
Full support Full support
Highly integrated
motion Upload/download
and view Upload/download Full support Full support Full support Full support Full support
Graphical trending Full support Full support(7) Full support(7) Full support Full support Full support Full support
DriveExecutive Lite
9303-4DTE01ENE Available
separately Available
separately Available
separately Included Included Included Included
PIDE autotune 9323-ATUNEENE(8)
Available
separately Available
separately Available
separately Available
separately Available
separately Included Included
Advanced Process Control instructions 9324-RLDAPCENE 9324-RLDAPCLENE(9)
Upload/download
and view Available
separately Available
separately Available
separately Available
separately Available
separately Available
separately
Routine source
protection Included Included Included Included Included Included Included
RSLogix 5000 project
compare Included Included Included Included Included Included Included
(1) As of RSLogix 5000 programming software, version 16. The software is designed to grab the highest functionality license first. For example, if Standard,
Full and Professional Concurrent licenses are available on the FactoryTalk Activation server, RSLogix 5000 software will grab the highest functionality
license first.
Select a ControlLogix System
46 Publication 1756-SG001M-EN-P - May 2009
(2) Service Edition supports controllers with firmware revision 12 and later.
(3) Full Edition supports controllers with firmware revision 10 and later.
(4) A multiple language editor package is available as 9324-RLDMLPE. It contains the function block, sequential function chart, and structured text editors.
(5) The Structured Text editor option (9324-RLDSTXE) is required to program SFC actions in structured text.
(6) As of RSLogix 5000 programming software, version 16.
(7) As of RSLogix 5000 programming software, version 15.
(8) PIDE Autotune is not supported on 1769-L23x controllers.
(9) Select 9324-RLDAPCENE for a design license for software and a runtime license for one controller. Select 9324-RLDAPCLENE for only a runtime license for one
controller (for pay to deploy).
RSLogix 5000 Integration with Other Applications
Available Features Service Edition
9324-RLD000xxE Mini Edition 9324-RLD200xxE
Lite Edition 9324-RLD250xxE
Standard Edition: Node Locked 9324-RLD300xxE Concurrent License(1) 9324-RLD300xxF
Standard/
NetWorx Edition 9324-RLD300NXxxE
Full Edition: Node Locked 9324-RLD600xxE Concurrent License(1) 9324-RLD600xxF
Professional Edition: Node Locked: 9324-RLD700NXxxE Concurrent License(1) 9324-RLD700NXxxF
RSLinx Classic
software Lite included Lite included Lite included Lite included Lite included Lite included Lite included
RSNetWorx
ControlNet, RSNetWorx
DeviceNet,
RSNetWorx
EtherNet/IP
software(2)
Available
separately Available
separately Available
separately Available
separately Included Available
separately Included
FactoryTalk
AssetCentre audit
support
Included Included Included Included Included Included Included
FuzzyDesigner 9324-RLDFZYENE(3)
NA Available
separately Available
separately Available
separately Available separately Available
separately Available separately
RSLogix Emulate
5000 9310-WED200ENE(4)
Available
separately NA NA Available
separately Available separately Available
separately Included
FactoryTalk security
server(5) Included Included Included Included Included Included Included
Security server
emulator(5) Included Included Included Included Included Included Included
RSLogix Architect 9326-LGXARCHENE(6)
Available
separately Available
separately Available
separately Available
separately Available separately Available
separately Included
FactoryTalk View SE demo (50 tags/2 hours)
Available
separately Available
separately Available
separately Available
separately Available separately Available
separately Included
(1) As of RSLogix 5000 programming software, version 16. The software is designed to grab the highest functionality license first. For example, if Standard,
Full and Professional Concurrent licenses are available on the FactoryTalk Activation server, RSLogix 5000 software will grab the highest functionality
license first.
(2) RSNetWorx for ControlNet software is 9357-CNETL3. RSNetWorx for DeviceNet software is 9357-DNETL3. RSNetWorx for EtherNet/IP software is
9357-ENETL3. They are available together as 9357-ANETL3.
(3) As of RSLogix 5000 programming software, version 16.
(4) RSLogix Emulate 5000 software does not support Microsoft Windows Vista at this time.
Select a ControlLogix System
Publication 1756-SG001M-EN-P - May 2009 47
(5) FactoryTalk AP install required - included on disk.
(6) As of RSLogix 5000 programming software, version 15.
Notes:
Rockwell Automation
Support
Rockwell Automation provides technical information on the Web to assist you in
using its products. At http://support.rockwellautomation.com, you can find technical
manuals, a knowledge base of FAQs, technical and application notes, sample code
and links to software service packs, and a MySupport feature that you can customize
to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and
troubleshooting, we offer TechConnect support programs. For more information,
contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the
information that's contained in this manual. You can also contact a special Customer
Support number for initial help in getting your product up and running.
United States 1.440.646.3434
Monday – Friday, 8am – 5pm EST
Outside United
States
Please contact your local Rockwell Automation representative
for any technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational
when shipped from the manufacturing facility. However, if your product is not
functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer
Support case number (call the phone number above to obtain
one) to your distributor in order to complete the return
process.
Outside United
States
Please contact your local Rockwell Automation representative
for the return procedure. Allen-Bradley, Rockwell Automation, ControlLogix, CompactLogix, FactoryTalk, GuardLogix, NetLinx, PanelView, RSLinx, RSLogix 5000,
RSLogix Emulate 5000, RSNetWorx, SERCOS, Ultra3000, Ultra5000, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.