Technical Data1756 ControlLogix I/O Modules Catalog Numbers1756 series The ControlLog ix architecture pro vides a wide range of input an d output modules to span many applications , from high-speed digital to process control. The ControlLog ix architecture uses Producer-Co nsumer technol ogy, wh ich allows input information and output status to be shared among multiple ControlLogix controllers. Each ControlLog ix I/O module mounts in a ControlLogix chassis and requireseither a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring . RTBs and IFMs are not included with the I/O modules. They must be ordered separately. T opic Page Available 1756 I/O Modules page 2 Environmental Specifications - 1756 I/O Modules page 3 Digital I/O Modules page 3 Analog I/O Modules page 5 Specialty I/O Modules page 6 Module Specifications page 7 ControlLogix I/O Accessories page 156 ControlLogix Controllers Input Modules Output Modules
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
The ControlLogix architecture provides a wide range of input and outputmodules to span many applications, from high-speed digital to process control.
The ControlLogix architecture uses Producer-Consumer technology, whichallows input information and output status to be shared among multipleControlLogix controllers.
Each ControlLogix I/O module mounts in a ControlLogix chassis andrequires either a removable terminal block (RTB) or a 1492 interface module(IFM) to connect all field-side wiring. RTBs and IFMs are not included with
1756 digital AC output modules • Scheduled outputs: Synchronization within 16.7 seconds maximum, referenCoordinated System Time
• Fault states per point: Hold last state, on or off (off is default)• States in Program mode per point: Hold last state, on or off (off is default)• Fusing:
− 1756-OA8D, 1756-OA8E: Electronically fused per point− 1756-OA16: Mechanically fused/group, 3.15 A @ 250V AC slow blow,
interruption current, Littelfuse p/n H2153.15− All other modules: Not protected. A fused IFM is recommended to prote
1756 digital DC input modules • Reverse polarity protection: All modules except 1756-IG16 module• Change of state: Software configurable• Timestamp of inputs:
− ±100μs for sequence of events modules− ±200μs for all other modules
http://slidepdf.com/reader/full/1756-series-io-modules 5/158Publication 1756-TD002A-EN-E - May 2009 5
1756 ControlLogix I/O Modu
Analog I/O Modules The 1756 digital I/O modules support these features:
1756 digital DC output modules • Scheduled outputs: Synchronization within 16.7 seconds maximum, referencCoordinated System Time
• Fault states per point: Hold last state, on or off (off is default)• States in Program mode per point: Hold last state, on or off (off is default)• Fusing:
− 1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OV16E, 1756-OV32E: fused per point
− All other modules. Not protected. A fused IFM is recommended to protec(see publication 1492-2.12)
1756 digital contact modules • Scheduled outputs: Synchronization within 16.7 seconds maximum, referencCoordinated System Time
• Configurable fault states per point: Hold last state, on or off (off is default)• Configurable states in Program mode per point: Hold last state, on or off (off• Fusing: Not protected. A fused IFM is recommended to protect outputs (See
1756 analog modules with HART interface • Data format: Integer mode (left justified, 2s complement), Floating point IE• Input conversion method: Successive approximation• Output conversion method: R-Ladder DAC, monotonicity with no missing c• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
Module Type Features
Module Type Features
1756-CFM configurable flow meter module The 1756-CFM module provides Totalizer mode for metering applicatfrequency measurements for speed or rate control applications, on two channelconnected to flowmeters.• Totalizer fill and prover• High-resolution 100 kHz max• Frequency 0.0005 Hz resolution• Reverse polarity protection: Outputs only• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IA8D
Certification (1) 1756-IA8D
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size0.324...2.08 mm
2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IA16
Certification (1) 1756-IA16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IA16I
Certification (1) 1756-IA16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IA32
Certification (1) 1756-IA32
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size0.324...2.08 mm
2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB16
Certification (1) 1756-IB16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB16D
Certifications (1) 1756-IB16D
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB16I
Certification (1) 1756-IB16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
http://slidepdf.com/reader/full/1756-series-io-modules 21/158Publication 1756-TD002A-EN-E - May 2009 21
1756 ControlLogix I/O Modu
1756-IB16ISOEControlLogix DC (10...55V) sequence of events input module
Technical Specifications - 1756-IB16ISOE
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Non isolatedWir in g
Isolated Wir in g
Daisy Chain to Other RTBs
DC (-)
Jumper Bar(Cut to Length)
)+(6-CD)-(6-CD
DC (+)
DC-0 (+)DC-1 (+)
DC-0 (-)
DC-5 (-)
IN-0IN-1IN-2IN-3
IN-8
IN-4IN-5IN-6IN-7
Not Used
IN-9IN-10IN-11IN-12IN-13IN-14IN-15Not Used
GND-0GND-1GND-2GND-3
GND-8
GND-4GND-5GND-6GND-7
Not Used
GND-9GND-10GND-11GND-12GND-13GND-14GND-15GND-15
DC-5 (+)
Sin k In pu t Wir in g
Sour ce In pu t Wir in gSour ce In pu t Wir in g
Sin k In pu t Wir in g
1756-IB16ISOE
ControlLogixBackplaneInterface
Simplified Schematic
Display
GND-0
IN-0
Electronic CurrentLimit Circuit
+5V
Attribute 1756-IB16ISOE(1)
Inputs 16 individually isolated, sequence of events
Voltage category 24/48V DC sink/sourceOperating voltage range 10...55V DC
Digital filter, off to on 0…50 ms
Input delay, off to on Hardware delay (10 μs nominal/20 μ s max)+ Firmware scan (up to 25μs)+ Input filter time (user selectable time: 0ms...50ms)+ ASIC delay (175μs - FIFO/625μs - Coordinated SystemTime per point)
Input delay, on to off Hardware delay (25 μs nominal/50 μ s max)+ Firmware scan (up to 25μs)+ Input filter time (user selectable time: 0ms...50ms)+ ASIC delay (175μs - FIFO/625μs - Coordinated SystemTime per point)
(1) If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-Smodule to coordinate system time.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB16ISOE(1)
Certification (1) 1756-IB16ISOE
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Off-state current, max 1.5 mAOn-state current, min 2 mA
On-state current, max 5.5 mA
Inrush current, max 250 mA (decaying to < 37% in 22 ms, without ac
Input impedance, max 5.67 kΩ @ 31.2V DC
Cyclic update time 100μs...750 ms
Isolation voltage 250V (continuous), Reinforced Insulation Type bInput group to system250V (continuous), Basic insulation type between Ingroup to Input groupRoutine tested at 1900V AC for 2 s, between Input gto Input group and Input group to system
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 25/158Publication 1756-TD002A-EN-E - May 2009 25
1756 ControlLogix I/O Modu
Certifications - 1756-IB32
Certification (1) 1756-IB32
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IC16
Certification (1) 1756-IC16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6
in.) insulation(2)
Wire category 2(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 31/158Publication 1756-TD002A-EN-E - May 2009 31
1756 ControlLogix I/O Modu
Certifications - 1756-IF6CIS
Certification (1) 1756-IF6CIS
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
http://slidepdf.com/reader/full/1756-series-io-modules 35/158Publication 1756-TD002A-EN-E - May 2009 35
1756 ControlLogix I/O Modu
Certifications - 1756-IF6I
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF6I
Certification (1) 1756-IF6I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Open circuit detection time Differential voltage: Positive full scale reading Single-ended/diff. current: Negative full scale readinwithin 5 sSingle-ended voltage: Even numbered channels go tpositive full scale reading within 5 s, odd numberedchannels go to negative full scale reading within 5 s
Overvoltage protection, max Voltage: 30V DCCurrent: 8V DC
Normal mode noise rejection >80 dB @ 50/60 Hz(1)
Common mode noise rejection >100 dB @ 50/60 Hz
Calibrated accuracy 25 °C Voltage: Better than 0.05% of rangeCurrent: Better than 0.15% of range
Calibration interval 12 months
Offset drift 45μV/°C
Gain drift with temperature Voltage: 15 ppm/°CCurrent: 20 ppm/°C
Module error Voltage: 0.1% of rangeCurrent: 0.3% of range
http://slidepdf.com/reader/full/1756-series-io-modules 39/158Publication 1756-TD002A-EN-E - May 2009 39
1756 ControlLogix I/O Modu
Certifications - 1756-IF8
Wire category 2(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF8
Certification (1) 1756-IF8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
http://slidepdf.com/reader/full/1756-series-io-modules 41/158Publication 1756-TD002A-EN-E - May 2009 41
1756 ControlLogix I/O Modu
Input impedance > 1 MΩ voltage250Ω current
Open circuit detection time Positive full scale reading within 5 s
Overvoltage protection, max Voltage: 30V DCCurrent: 8V DC
Normal mode noise rejection > 80 dB @ 50/60 Hz
Common mode noise rejection > 100 dB @ 50/60 Hz
Calibrated accuracy Voltage: Better than 0.05% of rangeCurrent: Better than 0.15% of range
Calibration interval 12 months
Offset drift 90μV/°C
Gain drift with temperature Voltage: 10 ppm/°CCurrent: 20 ppm/°C
Module error Voltage: 0.1% of rangeCurrent: 0.3% of range
Module input scan time, min 18...488 ms (filter dependent)
Module HART scan time Typically 1 s per HART channel enabled. Estimall 8 channels have HART enabledPass through messages, handheld communicators,secondary masters, communication errors, orconfiguration changes can significantly increase theupdate time
Isolation voltage 50 V (continuous), Basic Insulation TypeTested at 1500V AC for 60 s, I/O to backplane
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF16
Certification (1) 1756-IF16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Power dissipation, max Voltage: 4.3 WCurrent: 4.7 W
Thermal dissipation, max Voltage: 14.66 BTU/hrCurrent: 16.02 BTU/hr
Isolation voltage 250V (continuous), Basic Insulation Type
125V (continuous), Reinforced Insulation TypeType Tested at 3100V DC for 60 s, I/O to systemRoutine Tested at 2121V DC for 2 s, I/O to systemNo isolation between channels
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF4FXOF2
1756-IF4FXOF2F Input and Output SpecificationsAttribute Inputs Outputs
Number 4 high-speed, sub-millisecond, differential 2 high-speed voltage or current
Output range ± 10.5V0…10.5V0…5.25V0…21 mA
± 10.4V0…21 mA
Resolution Approx. 14 bits across ±10V DC (21V total)±10V: 1.3 mV/bit, 14-bit effective0…10.5V: 1.3 mV/bit, 13-bit effective0…5.25V: 1.3 mV/bit, 12-bit effectiveApprox. 12 bits across 21 mA0…21 mA: 5.25μA/bit
13 bits across 21 mA = 2.8μA/bit14 bits across 21.8V = 1.3 mV/bit
Impedance Voltage: >1 MΩCurrent: 249Ω
—
Open circuit detection Positive full-scale reading within 1 s Current output only (Output must be set to >0.
http://slidepdf.com/reader/full/1756-series-io-modules 49/158Publication 1756-TD002A-EN-E - May 2009 49
1756 ControlLogix I/O Modu
Certifications - 1756-IF4FXOF2F
Certification (1) 1756-IF4FXOF2
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Low to True Format - 1756-IG16• -0.2…0.8V = Input guaranteed to be in on-state• 0.8…2.0V = Input state not guaranteed• 2.0…5.5V = Input guaranteed to be in off-state
1
3
5
7
9
19
17
15
13
11
2
4
6
8
10
20
18
16
14
12
IN-1
IN-3
IN-5
IN-7
DC-0(+)
IN-0
IN-2
IN-4
IN-6
DC COM 0
IN-9
IN-11
IN-13
IN-15
DC-1(+)
IN-8
IN-10
IN-12
IN-14
DC COM 1
5V DC
+ DC
– DC
1756-IG16
1
3
5
7
9
19
17
15
13
11
2
4
6
8
10
20
18
16
14
12
IN-1
IN-3
IN-5
IN-7
DC-0(+)
IN-0
IN-2
IN-4
IN-6
DC COM 0
IN-9
IN-11
IN-13
IN-15
DC-1(+)
IN-8
IN-10
IN-12
IN-14
DC COM 1
Capacitor0.01µF Typical(See notes below.)
5V DC Power
DC PowerW ire
I/OW ire+
–
I/OW ire
TTL InputDevice
+
–
1756-IG16
+5 DC
IN
1.5 K
1 K 74HCT14
1.5 K
1 K
560
74HCT14560
DC COM
IN
Standard Wiring CE Compliant Wiring
Simplified Schematic
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 51/158Publication 1756-TD002A-EN-E - May 2009 51
1756 ControlLogix I/O Modu
Technical Specifications - 1756-IG16
Attribute 1756-IG16
Inputs 16 (8 points/group)
Voltage category 5V DC TTL source (Low=True)(1)
(1) TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in yourconvert to traditional True - High logic.
Operating voltage range 4.5...5.5V DC50 mV P-P ripple max
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 450μs + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 700μs + filter
Current draw @ 5.1V 110 mA
Current draw @ 24V 2 mA
Power dissipation, max 1.4 W @ 60 °C
Thermal dissipation 4.8 BTU/hr @ 60 °C
Off-state voltage, max 2V
Off-state current, max 4.1 mA
On-state current, min 3.7 mA @ 5V DC
On-state current, max 4.1 mA @ 5V DC
Input impedance, max 1.4 kΩ min1.5 kΩ typical
Cyclic update time 100μs...750 ms
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
Wire category 2(3)
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Enclosure type rating None (open-style)(1) 90...146V DC @ 50°C,12 channels on90...132V DC @ 55°C, 14 channels on90...125V DC @ 60°C, 16 channels on90...146V DC @ 30°C, 16 channels on.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IH16I
Certification (1) 1756-IH16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IH16ISOE(1)
Certification (1) 1756-IH16ISOE
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Wire type CopperEnclosure type rating None (open-style)
(1) 159…265V AC, 47…63Hz @ 30°C all channels on159…265V AC, 47…63Hz @ 40°C 8 points on159…253V AC, 47…63Hz @ 45°C all channels on159…242V AC, 47…63Hz @ 60°C all channels on.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IM16I
Certification (1) 1756-IM16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IN16
Certification (1) 1756-IN16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Open circuit detection time Negative full scale reading within 5 s with anycombination of lost wires, except input terminal A alIf input terminal A is lost by itself, the module reads positive full scale reading within 5 s
Overvoltage protection, max 24V AC/DC
Normal mode noise rejection 60 dB at 60 Hz(1)
Common mode noise rejection 120 dB @ 60 Hz100 dB @ 50 Hz
Channel bandwidth 15 Hz(1)
Settling time <80 ms to 5% of full scale(1)
Calibrated accuracy @ 25 °C Better than 0.1% of range
Calibration interval 6 months
Offset drift 10 MΩ /°C
Gain drift with temperature 50 ppm/°C, 90 ppm/°C max
Module error 0.54% of range
Module scan time 25 ms min floating point (ohms)50 ms min floating point (temperature)10 ms min integer (ohms)(1)
Isolation voltage 250V continuousTested at 1700V DC for 1 s, channel to channel, chanto system
Wire type CopperEnclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IR6I
Certification (1) 1756-IR6I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
http://slidepdf.com/reader/full/1756-series-io-modules 67/158Publication 1756-TD002A-EN-E - May 2009 67
1756 ControlLogix I/O Modu
Certifications - 1756-IT6I
Wire category 2(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IT6I
Certification (1) 1756-IF4FXOF2
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
http://slidepdf.com/reader/full/1756-series-io-modules 69/158Publication 1756-TD002A-EN-E - May 2009 69
1756 ControlLogix I/O Modu
Thermocouples B, E, J, K, R, S, T, N, C, D, L (TXK/XK)
Current draw @ 5.1V 200 mA
Current draw @ 24V 150 mA
Power dissipation, max 4.6 WThermal dissipation 15.7 BTU/hr
Open circuit detection time Positive full scale reading within 2 s
Overvoltage protection, max 120V AC/DC
Normal mode noise rejection 60 dB at 60 Hz(1)
Common mode noise rejection 160 dB min, tested at 600V AC/60 Hz applied wΩ differential resistance
Channel bandwidth 15 Hz(1)
Settling time <80 ms to 5% of full scale(1)
Calibrated accuracy @ 25 °C Better than 0.1% of range
Calibration interval 12 monthsLocal CJC sensor accuracy ±0.3 °C
Remote CJC sensor accuracy ±0.3 °C
Offset drift 0.5μV/°C
Gain drift with temperature 15 ppm/°C, 25 ppm/°C max1.4μV/°C, 2.3μV/°C max, -12…78 mV0.6μV/°C, 1.1μV/°C max, -12…30 mV
Module error 0.15% of range
Module scan time 25 ms min floating point (millivolt)50 ms min floating point (temperature)10 ms min integer (millivolt)(1)
Isolation voltage 250V (continuous), Reinforced Insulation Type, usystem, tested at 3250V DC for 60 s250V (continuous), Reinforced Insulation Type, grougroup, tested at 1900V DC for 60 s
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
TÜV TÜV Certified for Functional Safety: up to and including SIL 2
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IV16
Certification (1) 1756-IV16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Off-state current, max 1.5 mAOn-state current, min 2 mA
On-state current, max 3.5 mA
Inrush current, max 250 mA (decaying to <37% in 22 ms, without ac
Input impedance, max 8.6 kΩ @ 30V DC
Cyclic update time 100μs...750 ms
Isolation voltage 250V (continuous), Reinforced Insulation Type bInput group to system250V (continuous), Basic insulation type between Ingroup to Input groupRoutine tested at 1900V AC for 2 s, between Input grto Input group and Input group to system
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 75/158Publication 1756-TD002A-EN-E - May 2009 75
1756 ControlLogix I/O Modu
Certifications - 1756-IV32
Certification (1) 1756-IV32
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)
insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loThe commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/ms maxcommutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating exceeded in the 10…50 mA range, a resistor may be added across the output and L2. The purpose of to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will d
(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waat fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattene
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 81/158Publication 1756-TD002A-EN-E - May 2009 81
1756 ControlLogix I/O Modu
Certifications - 1756-OA8D
Certification (1) 1756-OA8D
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6
in.) insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loThe commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/ms maxcommutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating exceeded in the 10…50 mA range, a resistor may be added AC ross the output and L2. The purpose is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a highdv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC wavfault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened s
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 87/158Publication 1756-TD002A-EN-E - May 2009 87
1756 ControlLogix I/O Modu
Certifications - 1756-OA16
Certification (1) 1756-OA16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loThe commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/ms maxcommutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating exceeded in the 10…50 mA range, a resistor may be added AC ross the output and L2. The purpose is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a highdv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will d(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC wavfault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened s
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Wire type CopperEnclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB8
Certification (1) 1756-OB8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
On-state voltage drop, max 0.5V DC @ 2 ACurrent per point, max 2 A @ 60 °C
Current per module, max 16 A @ 60 °C
Surge current per point 4 A for 10 ms each, repeatable every 1 s @ 60 °
Load current, min 2 mA
Isolation voltage 250V user to backplane, Reinforced Insulation Ty250V channel to channel, Basic Insulation TypeTested to withstand 1900V DC for 2 s user to backplTested to withstand 1900V DC for 2 s channel to cha
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slotChassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Maximum wire size requires extended housing, cat. no. 1756-TBE.(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 95/158Publication 1756-TD002A-EN-E - May 2009 95
1756 ControlLogix I/O Modu
Certifications - 1756-OB8EI
Certification (1) 1756-OB8EI
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used
2468101214161820222426283032
3436
135791113151719212325272931
3335
DaisyChain toOtherRTBs
DaisyChain toOtherRTBs
1756-OBI
Isolated Wir in g
Non isolated Wir in g
Continuous @ 60oC
ControlLogix BackplaneInterface
Display OutputDevice
OUT-0
RTNOUT-0
DC-0(+)
OUT-0
Surge Current Chart
Simplified Schematic
Surge
+5V
C u r r e n
t
Time0 10 ms
2 A
4 A
Attribute 1756-OB8I
Outputs 8 individually isolated
Voltage category 12/24V DC source
Operating voltage range 10...30V DC
Output delay, off to on 1 ms
Output delay, on to off 2 ms
Current draw @ 5.1V 165 mA
Current draw @ 24V 2 mA
Power dissipation, max 4.6W A @ 60 °C
Thermal dissipation, max 15.70 BTU/hrOff-state leakage current, max 0.5 mA per point
On-state voltage drop, max 0.5V DC @ 2 A
Current per point, max 2 A @ 60 °C
Current per module, max 16 A @ 60 °C
Surge current per point 4 A for 10 ms each, repeatable every 1 s @ 60 °
Load current, min 2 mA
DC OUTPUT
ST 0 1 2 3 4 5 6 7 OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 97/158Publication 1756-TD002A-EN-E - May 2009 97
1756 ControlLogix I/O Modu
Certifications - 1756-OB8I
Isolation voltage 250V user to backplane, Reinforced Insulation Ty250V channel to channel, Basic Insulation TypeTested to withstand 1900V DC for 2 s user to backplTested to withstand 1900V DC for 2 s channel to cha
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB8I
Certification (1) 1756-OB8I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB16E
Certification (1) 1756-OB16E
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB16I
Certification (1) 1756-OB16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB16IS
Certification (1) 1756-OB16IS
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1)When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB32
Certification (1) 1756-OB32
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Enclosure type rating None (open-style)(1) Maximum wire size requires extended housing, cat. no. 1756-TBE. Maximum wire size requirehousing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OC8
Certification (1) 1756-OC8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 113/158Publication 1756-TD002A-EN-E - May 2009 113
1756 ControlLogix I/O Modu
Certifications - 1756-OF4
Certification (1) 1756-OF4
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
1756-OF6CIControlLogix current loop output analog module
Technical Specifications - 1756-OF6CI
12
34
56
78
910
1112
1314
1516
1718
1920
iOUT-1
ALT-1
RTN-1
OUT-3
RTN-3
Not Used
OUT-5
ALT-5
ALT-3
RTN-5
OUT-0
ALT-0
RTN-0
OUT-2
RTN-2
Not Used
OUT-4
ALT-4
ALT-2
RTN-4
User AnalogOutput Device
ShieldGround
1756-OF6CI 0...550 Ω
12
34
56
78
910
1112
1314
1516
1718
1920
iOUT-1
ALT-1
RTN-1
OUT-3
RTN-3
Not Used
OUT-5
ALT-5
ALT-3
RTN-5
OUT-0
ALT-0
RTN-0
OUT-2
RTN-2
Not Used
OUT-4
ALT-4
ALT-2
RTN-4
User AnalogOutput Device
Shield Ground
1756-OF6CI 551...1000 Ω
• Place additional devices anywhere in the loop.
• Do not connect more than two wires to any single terminal.
• Place additional devices anywhere in the loop.
• Do not connect more than two wires to any single termina
Input Signal to User Count Conversion - 1756-OF6CI
Range Low Signal and User Counts High Signal and User Counts
0...20 mA 0 mA-32768 counts
21.074 mA32767 counts
Attribute 1756-OF6CI
Outputs 6 individually isolated
Output range 0…21 mA
Resolution 13 bits across 21 mA (2.7μA)
Current draw @ 5.1V 250 mA for 0...550 W loads terminated on OUTRTNs(Total backplane power in this range 6.7 W)250 mA for 551...1000 W loads terminated on OUTsALTs(Total backplane power in this range 8.5 W)
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OF6VI
Certification (1) 1756-OF6VI
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 121/158Publication 1756-TD002A-EN-E - May 2009 121
1756 ControlLogix I/O Modu
Certifications - 1756-OF8
Certification (1) 1756-OF8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
http://slidepdf.com/reader/full/1756-series-io-modules 125/158Publication 1756-TD002A-EN-E - May 2009 125
1756 ControlLogix I/O Modu
1756-OG16ControlLogix TTL output module
Low to True Format - 1756-OG16• 0…0.4V DC = Output guaranteed to be in on-state• 0.4…4.5V DC = Output state not guaranteed• 4.5…5.5V DC = Output guaranteed to be in off-state
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
Wire category 2(3)
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 127/158Publication 1756-TD002A-EN-E - May 2009 127
1756 ControlLogix I/O Modu
Certifications - 1756-OG16
Certification (1) 1756-OG16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1)When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Enclosure type rating None (open-style)(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OH8I
Certification (1) 1756-OH8I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loThe commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/ms maxcommutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating exceeded in the 10…50 mA range, a resistor may be added AC ross the output and L2. The purpose is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a high
dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will d(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waat fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattene
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
http://slidepdf.com/reader/full/1756-series-io-modules 135/158Publication 1756-TD002A-EN-E - May 2009 135
1756 ControlLogix I/O Modu
Certifications - 1756-OV16E
Certification (1) 1756-OV16E
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1)When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Load dependent output voltage range 5…30V DC @ 2 A resistive48V DC @ 0.5 A resistive125V DC @ 0.25 A resistive125V AC @ 2 A resistive240V AC @ 2 A resistive
Resistive output current rating (at rated power) 2 A @ 5…30V DC0.5 A @ 48V DC0.25 A @ 125V DC2 A @ 125/240V AC
Inductive output current rating (at rated power) 2 A steady state @ 5…30V DC
0.5 A steady state @ 48V DC0.25 A steady state @ 125V DC2 A steady state, 15 A make @ 125V AC2 A steady state, 15 A make @ 240 V AC
Power rating (steady state), max 250 W for 125V AC resistive output480 W for 240V AC resistive output60 W for 30V DC resistive output24 W for 48V DC resistive output31 W for 125V DC resistive output250VA for 125V AC inductive output480VA for 240V AC inductive output60VA for 30V DC inductive output24VA for 48V DC inductive output31VA for 125V DC inductive output
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Operating voltage range 5...150V DC10...265V AC @ 47…63
Load dependent output voltage range 5…30V DC @ 2 A resistive48V DC @ 0.5 A resistive125V DC @ 0.25 A resistive125V AC @ 2 A resistive240V AC @ 2 A resistive
Resistive output current rating (at rated power) 2 A @ 5…30V DC0.5 A @ 48V DC0.25 A @ 125V DC2 A @ 125/240V AC
Inductive output current rating (at rated power) 2 A steady state @ 5…30V DC0.5 A steady state @ 48V DC0.25 A steady state @ 125V DC2 A steady state, 15 A make @ 125V AC2 A steady state, 15 A make @ 240 V AC
Power rating (steady state), max 250 W for 125V AC resistive output480 W for 240V AC resistive output60 W for 30V DC resistive output24 W for 48V DC resistive output31 W for 125V DC resistive output250VA for 125V AC inductive output480VA for 240V AC inductive output60VA for 30V DC inductive output24VA for 48V DC inductive output31VA for 125V DC inductive output
Output delay, off to on 13 ms
Output delay, on to off 13 ms
S T 0 1 2 3 4 5 6 7 O
K
RELAY OUTPUT
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 143/158Publication 1756-TD002A-EN-E - May 2009 143
1756 ControlLogix I/O Modu
Current draw @ 5.1V 100 mA
Current draw @ 24V 100 mA
Power dissipation, max 3.1 W @ 60 °C
Thermal dissipation, max 10.57 BTU/hrOff-state leakage current per point, max 0 mA
Initial contact resistance, max 100 MΩ @ 6V 1 A
Switching frequency, max 1 operation/3 s (0.3 Hz at rated load)
Bounce time, mean 1.2 ms
Expected contact life 300 K cycles resistive100 K cycles inductive
Isolation voltage 265V continuousTested at 2546V DC for 1 s, channel to channel, I/O to sy
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
http://slidepdf.com/reader/full/1756-series-io-modules 145/158Publication 1756-TD002A-EN-E - May 2009 145
1756 ControlLogix I/O Modu
1756-CFMControlLogix configurable flow meter module
ShieldGround
InputDevice
1756-CFM Stan dar d Magn etic Picku p
Z0 12-24V DC
Z0 5V DC
Z0 Return
CustomerVCC
F0
F0 Return
Not Used
Not Used
Output 0
CustomerVCC
Z1 12-24V DC
Z1 5V DC
Z1 RET
Not Used
CustomerCommon
Not Used
Output 1
F1
F1 Return
12
34
56
78
910
1112
1314
1516
1718
1920CustomerCommon
+
–
1756-CFM Stan da rd Ou tpu t
12
34
56
78
910
1112
1314
1516
1718
1920
Load
+
–
Z0 12-24V DC
Z0 5V DC
Z0 Return
CustomerVCC
F0
F0 Return
Not Used
Not Used
Output 0
CustomerVCC
Z1 12-24V DC
Z1 5V DC
Z1 RET
Not Used
CustomerCommon
Not Used
Output 1
F1
F1 Return
CustomerCommon Load
+
–+
–
• This wiring diagram can be used in applications with 50 mV(magnetic pickup), 1.3V (TTL), or 4V (preamp level) thresholds.You must use RSLogix 5000 software to choose the appropriatethreshold level for your specific application.
• If separate power sources are used, do not exceed the specified
isolation voltage.
If separate power sources are used, do not exceed the specifieisolation voltage.
• Detectors 1 and 2 must be wired in parallel.• Customer VCC may be used to power detectors. In this case, though, the maximum curre
wiring arm must be less than 4 A.• The wiring example above shows a 12-24V DC standard prover connected to the module
5V DC standard prover, make sure the positive wire is connected to the 5V terminal (such• If separate power sources are used, do not exceed the specified isolation voltage.
Attribute 1756-CFM
Inputs 4 (2 per channel)
Inputs per channel 2 Flowmeter (F) inputs used for all modes2 Gate inputs used in Totalizer mode for prover/storecount
Outputs 2 current sourcing
Current draw at 5.1V 300 mA
Current draw at 24V 6 mA
Backplane power, total 1.7 W
Power dissipation, max 6 W @ 60 °C
Thermal dissipation, max 20.4 BTU/hr
Isolation voltage 125V continuousTested at 1700V DC, I/O group to group, I/O to syste
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
METERING
DC I/O
OK
F0
Z0
F1
Z1
O0
O1
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 147/158Publication 1756-TD002A-EN-E - May 2009 147
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
1756-CFM Input Specifications
Attributes Value
Inputs 4 (2 per channel)
Inputs per channel 2 Flowmeter (F) inputs used for all modes2 Gate inputs used in Totalizer mode for prover/store count
Input type IEC Type 2 (6…30 mA) @ 24V DC
Count range, max 2,147,483,647
Input frequency, max 100 kHz @ flowmeter inputs (overrange occurs at 100 kHz)
Flowmeter input voltage ±30V, selectable input thresholds of 50 mV, 1.3V and 4V:• ±30V peak unterminated open circuit voltage, magnetic pickup• TTL compatible, input voltage >1.3V DC is Logic 1 and -0.7…1.3Logic 0• 12…24V DC powered preamp output, 4V DC threshold
Output voltage source Customer suppliedOutput voltage range 5V operation: 4.5…5.5V DC for 3…20 mA load per point
12/24V operation: 10…31.2V DC for 40 mA…1 A load per point
Output type IEC 1A 24V DC
Output Current per point 1 A @ 10…31.2V DC20 mA @ 4.5…5.5V DC(1)
(1) All outputs can be on simultaneously without derating.
Surge current, max 2 A for 50 ms, repeatable every 2 s
Off-state leakage current, max < 300μA @ 31.2V DC
On-state voltage drop, max 0.6Ω x current
Output control Any number of outputs is assignable to any of 2 flowmeter channEach output can have 2 “turn-on” and “turn-off” preset values
Output switching time < 50μ
s turn on, <300μ
s turn offOutputs triggered by Total; all other “turn-on” and “turn-off” times
Overload current Electronic (< 4A)
Output short circuit protection Electronic (No indication of fault. Remove overload and togglon/off to restore.)
Output reverse polarity protection Yes (If wired incorrectly, module outputs may be permanently
Certification (1) 1756-CFM
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
Wire category 1(2)
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Wire type Copper
Enclosure type rating None (open-style)
1756-HSC Input Specifications
Attribute Value
Number of counters 2Inputs per counter 3 (A, B, Z for gate/reset)
Input frequency, max 1 MHz in counter modes (A input)500 kHz in rate measurement mode (A input)250 kHz in encoder mode (A/B inputs, X1 or X4)70 Hz with filter enabled
http://slidepdf.com/reader/full/1756-series-io-modules 151/158Publication 1756-TD002A-EN-E - May 2009 151
1756 ControlLogix I/O Modu
Certifications - 1756-HSC
1756-HSC Output Specifications
Attribute Value
Outputs 4 (2 per common)
Output delay, off to on 20μs typical, 50μs maxOutput delay, on to off 60μs typical, 300μs max
Off-state leakage current perpoint, max
300μA
On-state voltage drop, max 0.55V
Output current rating, per point 20 mA @ 4.5…5.5V DC1.0 A @ 10…31.2V DC
Current limit < 9 A
Surge current per point 2 A for 10 ms every 1s @ 60 °C
Load current per point, min 5V operation: 3 mA12/24V operation: 40 mA
Output control Any number of output channels is assignable to each counter cha
Each output can have 2 "turn-on" and "turn-off" preset valuesShort circuit protection Electronic (Remove overload and toggle On/Off to restore.)
Reverse polarity protection Yes (If wired incorrectly, module outputs may be permanently d
Certification (1) 1756-HSC
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
http://slidepdf.com/reader/full/1756-series-io-modules 153/158Publication 1756-TD002A-EN-E - May 2009 153
1756 ControlLogix I/O Modu
Technical Specifications - 1756-PLS
Attribute 1756-PLS
Module configuration Left section: 2 groups of 4 outputs and 4 inputs Center section: resolver interface and I/O controlRight section: 2 groups of 4 outputs and 4 inputs eac
Current draw at 5.1V 1000 mACurrent draw at 24V 125 mA
Power dissipation, max 25.7 W @ 30 °C21.3 W @ 60 °C
Thermal dissipation, max 87.74 BTU/hr @ 30 °C72.72 BTU/hr @ 60 °C
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block Requires 3 RTBs: 1756-TBNH or 1756-TBSH
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
Wire category 2 - Center slot1 - Left & right slots(2)
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Wire type Left and right: Copper
Enclosure type rating None (open style)
OK
0OK
31 42 5 6 7
0 31 42 5 6 7
OUT
IN
PROG. LIMIT SWITCHPROG. LIMIT SWITCH
REVLOSERO/ICD
8OK
119 1210 13 14 15OUT
IN
PROG. LIMIT SWITCH
DC I/O
8 119 1210 13 14 15
Indicator for LeftS lot I/O Module
Indicator for Resolver Module Indicator for RightSlot I/O Module
2V rms, sine and cosine inputs (2 differential pairs)
Reference voltage 2V rms ±20%
Reference frequency 5 kHz ±20%
Digital resolution 12 bits (4096 counts from hardware)
Angular resolution 0.088 °/bit
Digital count range 0…4095 (decimal)
Maximum tracking rate ±1800 RPM
Repeatability ±0.0488% of full scale
Accuracy ±0.0976% of full scale
Isolation voltage 100% tested at 1700V DC for 1 s
1756-PLS Input Specifications
Attribute Value
Inputs 16 (2 groups of 4 per I/O section)
Voltage category 12/24V DC
Operating voltage range 10.8…31.2V DC
Input delay, off to on < 15μs @ 30 °C< 150μs @ 60 °C
Input delay, on to off < 30μs @ 30 °C< 200μs @ 60 °C
Power dissipation, inputs, max 2.8 W @ 60°C
Thermal dissipation, inputs, max 9.56 BTU/hr
Off-state voltage, max 5V DC
Off-state current, max 1.5 mA
On-state current, min 3 mA
On-state current, max 10 mA
Input impedance, max 3.3 kΩ @ 24V DC
Reverse polarity protection Yes
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O to system
1756-PLS Output Specifications
Attribute Value
Outputs 16 (2 groups of 4 per I/O section)
Voltage category 12/24V DC
Operating voltage range 10…31.2V DC
Output delay, off to on < 15μs @ 60 °C
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 155/158Publication 1756-TD002A-EN-E - May 2009 155
1756 ControlLogix I/O Modu
Certifications - 1756-PLS
Output delay, on to off < 25μs @ 60 °C
Power dissipation, outputs, max 6 W @ 30 °C
3.8 W @ 60 °CThermal dissipation, outputs, max 21.48 BTU/hr @ 30 °C
11.93 BTU/hr @ 60 °C
Off-state leakage current perpoint, max
300μA @ 60 °C
On-state voltage drop, max 0.55V DC
Current per point, max 1 A @ 30 °C(1)
Current per module, max 8 A @ 30 °C(2)
Current limit < 4A
Surge current per point 2 A for 10 ms every 1s @ 60 °C
Load current per point, min 40 mA
Output switching time Switching 1 A @ 24V DCShort circuit protection Electronic (No indication of fault. Remove load and toggle on/o
restore.)
Reverse polarity protection Yes, current limited. (If wired incorrectly, outputs may be permdisabled.)
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O to system
(1) Derate 16.7 mA/ °C above 30 °C: 0.5 A @ 60 °C.
(2) Derate 133.6 mA/ °C above 30 °C: 4 A @ 60 °C.
1756-PLS Output Specifications
Attribute Value
Certification (1) 1756-PLS
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
Removable terminal blocks (RTBs) provide a flexible interconnection betweenyour plant wiring and 1756 I/O modules. The RTB plugs into the front of the
I/O module. The type of module determines which RTB you need. You canchoose screw-clamp or spring-clamp RTBs.
RTBs are not shipped with I/O modules. You must order them separately. Thestandard housing on the front of the wiring arm is not deep enough for 2.5mm2 (14 AWG) wiring. If you plan to use 2.5 mm 2 (14 AWG) wiring, alsoorder the extended housing.
Wiring Systems As an alternative to buying RTBs and connecting the wires yourself, you canbuy a wiring system of:
• interface modules (IFMs) that provide the output terminal blocks fordigital I/O modules. Use the pre-wired cables that match the I/O
module to the IFM.• analog interface modules (AIFMs) that provide the output terminal
blocks for analog I/O modules. Use the pre-wired cables that match theI/O module to the AIFM.
• I/O module-ready cables. One end of the cable assembly is an RTB thatplugs into the front of the I/O module. The other end has individuallycolor-coded conductors that connect to a standard terminal block.
Rockwell Automation provides technical information on the Web to assist you in usingits products. At http://support.rockwellautomation.com , you can find technicalmanuals, a knowledge base of FAQs, technical and application notes, sample code andlinks to software service packs, and a MySupport feature that you can customize tomake the best use of these tools.
For an additional level of technical phone support for installation, configuration, andtroubleshooting, we offer TechConnect support programs. For more information,contact your local distributor or Rockwell Automation representative, or visithttp://support.rockwellautomation.com .