Top Banner
Part number 173089-01 Revision C, April 2006 1900/65A General Purpose Equipment Monitor Field Wiring Diagrams
22
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 173089

Part number 173089-01 Revision C, April 2006

1900/65A General Purpose Equipment Monitor Field Wiring Diagrams

Page 2: 173089

1900/65A Field Wiring Diagrams

ii

Copyright © 2005 Bently Nevada, LLC

All Rights Reserved.

The information contained in this document is subject to change without notice The following are trademarks of Bently Nevada, LLC in the United States and other countries:

ACM™, Actionable Information®, Actionable Information to the Right People at the Right Time®, ADRE®, Asset Condition Management™, Asset Condition Monitoring™, Bently ALIGN™, Bently BALANCE®, Bently DOCUVIEW™, Bently LUBE™, Bently PERFORMANCE™, Bently Nevada®, CableLoc™, ClickLoc™, Data Manager®, Decision SupportSM, DemoNet™, Dynamic Data Manager®, Engineer Assist™, FieldMonitor™, flexiTIM™, FluidLoc®, Helping You Protect and Manage All Your Machinery®, HydroScan®, HydroView™, Key ∅®, Keyphasor®, Machine Condition Manager™ 2000, MachineLibrary™, Machine Manager™, MicroPROX®, Move Data, Not People®, Move Information, Not Data™, NSv™, Prime Spike™, PROXPAC®, Proximitor®, REBAM®, RuleDesk™, SE™, Seismoprobe®, Smart Monitor®, Snapshot™, System 1™, System Extender™, TDXnet™, TDIXconnX™, TipLoc™, TorXimitor®, Transient Data Manager®, Trendmaster®, TrimLoc™, Velomitor®. Bently Nevada’s orbit logo and other logos associated with the trademarks in bold above, are also all trademarks or registered trademarks of Bently Nevada in the United States and other countries

The following ways of contacting Bently Nevada are provided for those times when you cannot contact your local Bently Nevada representative:

Mailing Address 1631 Bently Parkway South Minden, NV 89423 USA

Telephone 1 775 782 3611 1 800 227 5514

Fax 1 775 215 2873 Internet www.bently.com

Page 3: 173089

iii

Additional Information

Notice: This document does not contain information required to operate and maintain the 1900/65A. Refer to the Following manuals for other required information. 1900/65A Datasheet (173401-01) • Description • Features • Specifications • Ordering Options • Approvals • Accessories 1900/65A Manual (173400-01) • System Description • Receiving and Handling Instructions • Installation • Configuration • Maintenance • Troubleshooting 1900/65A Hazardous Area Approvals • Throughout this document where Division 2, Division 1, Zone 1, and Zone 0 are used

the following agency approvals exist:

North American:

Ex/AEx nA [L] IIC Class 1 Div. 2 Groups A,B,C,D T4 @-20°C ≤ Ta ≤ 70°C Vn = 18 to 36 Vdc @ Imax = 1A per drawing 173089

European:

II 3G Ex nA [nL] IIC T4 @-20°C ≤ Ta ≤ 70°C Sira 06 ATEX 4053X IECEx SIR 06.0012X per drawing 173089

Notice: No changes to this document without authorization from approvals agencies.

Page 4: 173089

1900/65A Field Wiring Diagrams

iv

Contents

1. Connection Overview .................................................................. 5 1.1 Power and Signal Output Connections............................................................... 5 1.2 Transducer Connection ...................................................................................... 7 1.3 Transducer Connection with Barriers ................................................................. 9 1.4 Transducer Connection with Galvanic Isolators ............................................... 11

2. Non-Incendive Field Wiring Details .......................................... 13 2.1 Vibration Channel Connections ........................................................................ 13 2.2 Temperature Channel Connections.................................................................. 14

3. I.S. Field Wiring Details (Safety Barriers) ................................ 15 3.1 Vibration Channel Connections ........................................................................ 15 3.2 Temperature Channel Connections.................................................................. 16

4. I.S. Field Wiring Details (Galvanic Isolators) ........................... 17 4.1 Vibration Channel Connections ........................................................................ 17 4.2 Temperature Channel Connections.................................................................. 18

5. Appendix..................................................................................... 19

Page 5: 173089

Section 1 — Connection Overview

5

1. Connection Overview

1.1 Power and Signal Output Connections Safe or Division 2 / Zone 2 Area

Figure 1.1

1. To minimize ground loop problems, connect earth ground and system common only at the 1900/65A or other single point ground. For I.S. installations using external barriers, disconnect single point earth system connection by removing the jumper located inside the 1900/65A monitor under the protective cap. For intrinsically safe (I.S.) external barrier installations, system common to barrier I.S. ground impedance must not exceed 1Ω.

1

2

4

Communications Port

Transducer Buffered Outputs

4-20 mA Outputs

Ethernet

Reset

Inhibit / Trip Multiply 2

24Vdc Power Input Relays 1-3Relays 4-6

3

Page 6: 173089

1900/65A Field Wiring Diagrams

6

2. Wire gauge and type selected per local code requirements. Power terminals can accept

12AWG maximum. Power Input requirements: 18-36 Vdc, 1.0A Maximum Must follow Division 2 / Zone 2 wiring methods.

3. Install the 1900/65A only in a housing that is acceptable with the local authority having jurisdiction for Division 2 / Zone 2 installations. See the appendix for more housing requirements.

4. Do not connect or disconnect the buffered outputs except when de-energized or area is known to be non-hazardous.

Page 7: 173089

Section 1 — Connection Overview

7

1.2 Transducer Connection Safe or Division 2 / Zone 2 Area

Figure 1.2

1. Electrostatic Hazard: Wipe with a damp cloth only.

2. Non-Incendive (limited energy) wiring between 1900/65A monitor and transducers. See table 5.1 in the appendix for channel parameters.

3. Temperature channels may be connected to unapproved thermocouples or RTDs located in a Class I Division 2 Groups A,B,C,D and Zone 2 IIC,IIB,IIA areas.

4. Temperature channel wiring recommendations:

• 1900/65A to Thermocouple - Thermocouple extension cable must be of the same type as thermocouple. Recommended positive (RP) and negative (RN) extension wire gauge for proper operation. See table 1.1. Note that signal terminals on 1900/65A monitor will accept a 16AWG maximum conductor.

1

2

2 3 4

5

Sensor

Sensor

Sensor

Sensor

Transducer

Transducer

Transducer

Transducer

Vibration Channels

Temperature Channels

1900/65A Monitoring System

Approvals Label

Page 8: 173089

1900/65A Field Wiring Diagrams

8

AWG for Cable Length ft [m] Color Code Thermocouple

100 [31] 500 [152] 1000 [305] RP RN

Type J 22 14 12 White Red

Type K 20 12 10 Yellow Red

Type E 24 16 14 Purple Red

Type T 20 12 10 Blue Red

Table 1.1: Thermocouple Connections

• 1900/65A to RTD – Use twisted shielded pair or triad with stranded conductors and insulating sheath. Wire gauge is shown in table 1.2.

AWG for Cable Length ft [m] RTD Type

100 [31] 500 [152] 1000 [305]

Pt, Ni 28 26 22

Cu 26 18 16

Table 1.2: RTD Connections 5. Vibration channel wiring recommendations:

• 1900/65A to standard Bently Nevada vibration transducer – Use 16 to 22 AWG twisted shielded pair or triad with stranded conductors and insulating sheath. Cable length is not to exceed 1000ft [305m].

• For non-standard transducers, consult systems integrator or field applications engineer.

Page 9: 173089

Section 1 — Connection Overview

9

1.3 Transducer Connection with Barriers Safe or Division 2 / Zone 2 Area Division 1 / Zone 0 or 1 Area

Figure 1.3

1. Electrostatic Hazard: Wipe with a damp cloth only.

2. Connect shields to I.S. earth at barrier ground. Continuity between the shield of the field wiring from the hazardous area and the I.S. earth should be verified.

3. External barriers installed in a safe area must be approved.

4. Refer to table 5.2 in the appendix for external barrier parameters.

5. Wiring recommendations: 1900/65A to barrier and barrier to standard Bently Nevada transducer – use 16 to 22 AWG twisted shielded pair or triad with stranded conductors and insulating sheath. Cable length is not to exceed 1000 ft [305m].

6. Each channel is a separate I.S. circuit and must be wired separately from other channels. Use a separate screened cable for each channel or a cable containing wiring for many channels with each cable separated from other channel wiring by an earthed screen.

7. Temperature channels may be connected to unapproved thermocouples or RTDs located in a Class I Division 1 Groups A,B,C,D; Class II Division 1 Groups E,F,G; and Class III Division 1 areas when connected through the safety barriers recommended in table 5.2 or equivalent. For Division 1 / Zone 0 or Zone 1, non-grounded thermocouples or RTDs are required.

1

2

2

6 7

6

Sensor

Sensor

Sensor

Sensor

Transducer

Transducer

Transducer

Transducer

Vibration Channels

Temperature Channels

1900/65A Monitoring System

Approvals Label

External Barriers

External Barriers

3

3

4

4

5

5

Page 10: 173089

1900/65A Field Wiring Diagrams

10

8. Separate all I.S. wiring from non-I.S. wiring by a minimum of 2 in [50 mm]. When installing systems over one another, take care to ensure separation of I.S. and non-I.S. wiring.

Page 11: 173089

Section 1 — Connection Overview

11

1.4 Transducer Connection with Galvanic Isolators Safe or Division 2 / Zone 2 Area Division 1 / Zone 0 or 1 Area

Figure 1.4

1. Electrostatic Hazard: Wipe with a damp cloth only.

2. Connect shields for incoming field cables to earth at the galvanic isolator rail or at the entry into the 1900/65A monitors weatherproof enclosure. Connect shields for the wiring between the 1900/65A monitor and the galvanic isolators to earth at the 1900/65A monitor and the single point ground jumper as shown in figure 1.1 should be installed.

3. Galvanic isolators installed in a safe area must be approved.

4. Refer to table 5.3 in the appendix for galvanic isolator parameters.

5. Wiring recommendations: 1900/65A to galvanic isolator and galvanic isolator to standard Bently Nevada transducer – use 16 to 22 AWG twisted shielded pair or triad with stranded conductors and insulating sheath. Cable length is not to exceed 1000 ft [305m].

6. Each channel is a separate I.S. circuit and must be wired separately from other channels. Use a separate screened cable for each channel or a cable containing wiring for many channels, with each cable separated from other channel wiring by an earthed screen.

1

2

2

6 7

6

Sensor

Sensor

Sensor

Sensor

Transducer

Transducer

Transducer

Transducer

Vibration Channels

Temperature Channels

1900/65A Monitoring System

Approvals Label

Galvanic Isolators

Galvanic Isolators

3

3

4

4

5

5

Page 12: 173089

1900/65A Field Wiring Diagrams

12

7. Temperature channels may be connected to unapproved thermocouples or RTDs located in a Class I Division 1 Groups A,B,C,D; Class II Division 1 Groups E,F,G; and Class III Division 1 areas when connected through the galvanic isolators recommended in table 5.3 or equivalent. For Division 1 / Zone 0 or 1 areas, non-grounded thermocouples or RTDs must be used.

8. Separate all I.S. wiring from non-I.S. wiring by a minimum of 2 in [50 mm]. When installing systems over one another, take care to ensure separation of I.S. and non-I.S. wiring.

Page 13: 173089

Section 2 — Non-Incendive Field Wiring Details

13

2. Non-Incendive Field Wiring Details

2.1 Vibration Channel Connections Safe or Division 2 / Zone 2 Area

Figure 2.1

1. Connect shields to earth at 1900/65A end only.

2. Components are shown for single channel only (i.e., one transducer to one monitor channel). Connect other channels similarly.

3. Use non-Incendive wiring between 1900/65A monitor and transducers.

4. Wiring is shown cut away for clarity.

5. Refer to table 5.1 in the appendix for non-incendive parameters.

6. Refer to specific transducer datasheet for maximum cable length.

1Signal Monitor Transducer Side View

Non-Incendive Device(s)

Non-Incendive 2 Wire Device(s)

23 4

51 2

3 4

5

6

6

Page 14: 173089

1900/65A Field Wiring Diagrams

14

2.2 Temperature Channel Connections Safe or Division 2 / Zone 2 Area

Figure 2.2

1. Connect shields to earth at 1900/65A end only.

2. Components are shown for single channel only (i.e., one transducer to one monitor channel). Connect other channels similarly.

3. Use non-Incendive wiring between 1900/65A monitor and transducers.

4. Wiring is shown cut away for clarity.

5. Refer to table 5.1 in the appendix for non-incendive parameters.

6. Temperature channels may be connected to unapproved thermocouples or RTDs located in a Class I Division 2 Groups A,B,C,D and Zone 2 IIC, IIB, IIA areas.

1

Signal Monitor Transducer Side View Thermocouples not supplied by

BN

23 4

5

1 23 4

5

6

6

2 wire RTDs not supplied by BN

3 wire RTDs not supplied by BN

1 23 4

5 6

Page 15: 173089

Section 3 — I.S. Field Wiring Details (Safety Barriers)

15

3. I.S. Field Wiring Details (Safety Barriers)

3.1 Vibration Channel Connections Safe or Division 2 / Zone 2 Area Division 1 / Zone 0

or Zone1 Area

Figure 3.1

1. Components are shown for single channel only (i.e., one transducer to one monitor channel). Connect other channels similarly.

2. Use non-Incendive wiring between 1900/65A monitor and barriers.

3. Join cable shields to terminate at the barrier ground as shown. Use insulated shields. Verify continuity between the shield of the field wiring from the hazardous area and the I.S. earth. See note 1 in section 1.1.

4. Independent connection to system earth.

5. Wiring is shown cut away for clarity.

6. Refer to table 5.2 in the appendix for external barrier parameters.

Signal Monitor Transducer Side View

1

1

I.S. 2 Wire Device(s)

I.S. 3 Wire Device(s)

2

33 4

5

6

2

33

4

5

6

MTL 796-Barrier

MTL 728-Barrier

Page 16: 173089

1900/65A Field Wiring Diagrams

16

3.2 Temperature Channel Connections Safe or Division 2 / Zone 2 Area Division 1 / Zone 0

or Zone1 Area

Figure 3.2

1. Components are shown for single channel only, (i.e., one transducer to one monitor channel). Connect other channels similarly.

2. Use non-incendive wiring between 1900/65A monitor and barriers.

3. Join cable shields to terminate at the barrier ground as shown. Use insulated shields. Verify continuity between the shield of the field wiring from the hazardous area and the I.S. earth. See note 1 in section 1.1.

4. Independent connection to system earth.

5. Wiring is shown cut away for clarity.

6. Refer to table 5.2 in the appendix for external barrier parameters.

7. Bently Nevada does not supply thermocouples and 3-wire RTDs. Temperature channels may be connected to unapproved thermocouples or RTDs located in a Class I Division 1 Groups A,B,C,D; Class II Division 1 Groups E,F,G; and Class III Division 1 areas when connected through the external barriers recommended in table 5.2 or equivalent. For Division 1 / Zone 0 or 1 areas, use non-grounded thermocouples or RTDs.

Signal Monitor Transducer Side View

12

33 4

5

6

MTL 760acBarrier 7

MTL 755acBarrier

12

33 4

5

6

7MTL 755ac

Barrier

Page 17: 173089

Section 4 — I.S. Field Wiring Details (Galvanic Isolators)

17

4. I.S. Field Wiring Details (Galvanic Isolators)

4.1 Vibration Channel Connections Safe or Division 2 / Zone 2 Area Division 1 / Zone 0

or Zone1 Area

+

+

+

Figure 4.1 1. Components are shown for single channel only (i.e., one transducer to one monitor

channel). Connect remaining channels similarly.

2. Galvanic isolators require external 24Vdc power.

3. Use non-incendive wiring between 1900/65A monitor and galvanic isolators. Connect cable shields for this wiring to earth at the 1900/65A monitor. Use insulated shields.

4. Connection to system earth.

5. Wiring is shown cut away for clarity.

6. Refer to table 5.3 in the appendix for galvanic isolator parameters.

7. Install jumper between terminals 2 and 3.

Signal Monitor Transducer Side View 1 2

3

4

5

6

MTL 5031

P+F KFD2-VR4-Ex1.26

1

2

3

4

5

6

I.S. 2 Wire Device(s)

I.S. 3 Wire Device(s)

7

I.S. 3 Wire Device(s)

P+F KFD2-VR4-Ex1.26

4

5

63

1

2

Page 18: 173089

1900/65A Field Wiring Diagrams

18

4.2 Temperature Channel Connections Safe or Division 2 / Zone 2 Area Division 1 / Zone 0

or Zone1 Area

+

+

+

+

Figure 4.2

1. Components are shown for single channel only (i.e., one transducer to one monitor channel). Connect remaining channels similarly.

2. Galvanic isolators require external 24Vdc power.

3. Use non-incendive wiring between 1900/65A monitor and galvanic isolators. Connect cable shields for this wiring to earth at the 1900/65A monitor. Use insulated shields.

4. Connection to system earth.

5. Wiring is shown cut away for clarity.

6. Refer to table 5.3 in the appendix for galvanic isolator parameters.

7. Bently Nevada soes not supply thermocouples and 3-wire RTDs. Temperature channels may be connected to unapproved thermocouples or RTDs located in a Class I Division 1 Groups A,B,C,D; Class II Division 1 Groups E,F,G; and Class III Division 1 areas when connected through the galvanic isolators recommended in table 5.3 or equivalent. For Division 1 / Zone 0 or 1 areas, non-grounded thermocouples or RTDs must be used.

8. Install jumpers between terminals 1 and 3 and terminals 2 and 5.

Signal Monitor Transducer Side View

1 2

3 4

5

6

MTL 5081

7

12

3

57

P+F KFD2-VR-Ex1.50M

1

1

2

3

3

2MTL 5082

4

4

4

5

5

6

6

6

7

7P+F KFD2-RR-Ex1

8

Page 19: 173089

Section 5 — Appendix

19

5. Appendix Typical Housing

(Bently Nevada P/N 168944 Shown)

Figure 5.1

1. Install the 1900/65A monitoring system in a suitable enclosure with an IP54 / Type 4 rating for all outdoor and Division 2 / Zone 2 installations.

2. Install conduit above this height to avoid internal mounting hardware. Never install conduit through the top of the housing.

Front View Right Side View

Bottom View

Window Area

2

2

8.4 (0.33) DIA.Mounting Hole4 Places

Page 20: 173089

1900/65A Field Wiring Diagrams

20

IIA

1 1 1 1

IIB

1 1 1 1

Lo(m

H)

IIC

1 1 1 1

IIA

188

188

1000

1000

IIB

188

188

1000

1000

Co(

nF)

IIC

188

188

996

996

IIA

1 1 1 1

IIB

1 1 1 1

La(m

H)

IIC

1 1 1 1

IIA

200

200

1000

1000

IIB

200

200

1000

1000

Ca(

nF)

IIC

200

200

1000

1000

Li(µ

H)

60

60

20

20

Ci(n

F)

12

12

4 4

Io(m

A)

45.5

45.5

0.5

0.91

3

Uo(

V)

23.9

23.9

5 5

Term

inal

N

umbe

r

J6, 5

-8

J6, 1

-4

J6, 1

3-16

J6, 9

-12

J6, 5

-8

J6, 1

-4

J6, 1

3-16

J6, 9

-12

J8, 5

-8

J8, 1

-4

J8, 9

-12

J8, 1

3-16

J8, 5

-8

J8, 1

-4

J8, 9

-12

J8, 1

3-16

Sign

al

Ch

1

Ch

2

Ch

3

Ch

4

Ch

1

Ch

2

Ch

3

Ch

4

Ch

5

Ch

6

Ch

7

Ch

8

Ch

5

Ch

6

Ch

7

Ch

8 Non

-Ince

ndiv

e P

aram

eter

s (p

er c

hann

el, a

ll ch

anne

ls m

ust b

e ke

pt s

epar

ate)

I/O T

ype

2 W

ire

trans

duce

r In

puts

3 W

ire

Tran

sduc

er

Inpu

ts

Ther

moc

oupl

e In

puts

RTD

In

puts

Tabl

e 5.

1

Page 21: 173089

Section 5 — Appendix

21

IIA

mH

16.8

37

2

0.88

IIB

mH

8.4

18.5

1

0.44

Lo

IIC

mH

2.1

4.62

0.25

0.11

IIA

nF

2300

2150

5400

0

1000

IIB

nF

690

650

1260

0

1000

Co

IIC

nF

89

83

1840

4000

0

Po

mW

821

651

1000

450

Io

mA

138

93.4

400

600

Uo V 27.2

28

11.2

3

mA

39.5

93.4

112

150

Ω

690

300

100

20

Serie

s

V 27.2

28

11.2

3

mA

138

93.4

400

600

Ω

169.

6

300

25

5

Cha

nnel

Par

amet

ers

Wor

st C

ase

Com

bine

d

Para

llel

V 23.4

28

10

3

Sugg

este

d M

TL B

arrie

r M

odel

s

796-

70

96-

7196

- 77

96-

728-

70

28-

7128

- 77

28-

760a

c 77

60ac

755a

c 70

55ac

70

56ac

77

55ac

77

56ac

Po

mW

566

255

651

500

500

225

225

225

Io

mA

87

51

93

200

200

300

300

300

R

Ω

298

392

300

50

50

10

10

10

Circ

uit P

aram

eter

s pe

r Cha

nnel

Uo V 26

20

28

10

10

3 3 3

Circ

uit

Pow

er

Sig

nal

Pow

er

Pow

er

Pow

er

Pow

er

Sig

nal

Sig

nal

Dev

ice

Pro

xim

itor

or

Acc

el.

Vel

omito

r or

2 W

ire

Acc

el.

TC

3-W

ire

RTD

s

Ext

erna

l Bar

rier P

aram

eter

s (p

er c

hann

el, a

ll ch

anne

ls m

ust b

e ke

pt s

epar

ate)

See

Sect

ion

Num

ber

3.1

3.1

3.2

3.2

I.S. e

quip

men

t cer

tifie

d fo

r con

nect

ion

to in

divi

dual

bar

rier c

ircui

ts:

Cho

ose

barr

ier c

ircui

t par

amet

ers

(Vm

ax/R

min

or U

o/Io

or V

oc/Is

c) a

nd c

able

in a

ccor

danc

e w

ith th

e co

ntro

l dra

win

g of

the

I.S. d

evic

e.

I.S. e

quip

men

t with

ent

ity p

aram

eter

s : M

atch

cer

tifie

d I.S

. equ

ipm

ent p

aram

eter

s w

ith b

arrie

r cha

nnel

pa

ram

eter

s su

ch th

at th

e fo

llow

ing

cond

ition

s ar

e m

et:

Vm

ax o

r Ui i

s ≥

Voc

or U

o Ii

or Im

ax is

≥ Io

or I

sc

Ca

or C

o is

≥ C

i + C

cabl

e La

or L

o is

≥ L

i + L

cabl

e

Tabl

e 5.

2

Page 22: 173089

1900/65A Field Wiring Diagrams

22

IIA

mH

39

1000

120

1100

IIB

mH

19.7

1000

60

554

Lo

IIC

mH

4.9

1000

15

138

IIA

µF

2.48

1000

1000

30

IIB

µF

0.74

1000

1000

7.9

Co

IIC

µF

0.09

6

100

100

1.24

Po

mW

595

0.03

6

3.3

53

Io

mA

90.2

0.12

2.4

17

Uo V 26.4

1.2

5.5

12.4

mA

2.6

0.12

2.4

17

Ω

10.3

K

10K

2292

729

Serie

s

V 26.4

1.2

5.5

12.4

mA

90.1

2

0.12

2.4

17

Ω

272.

4

10K

2292

730

Cha

nnel

Par

amet

ers

Wor

st C

ase

Com

bine

d

Para

llel

V

24.5

5

1.2

5.5

12.4

Po

mW

570

0.03

6

0.03

6

3.3

53

Io

mA

90

0.12

0.12

2.4

17

R

Ω

280

10K

10K

2292

730

Circ

uit P

aram

eter

s pe

r Cha

nnel

Uo V 25.2

1.2

1.2

5.5

12.4

Circ

uit

Pow

er

Sig

nal

Pow

er

Pow

er

Pow

er

and

Sig

nal

Dev

ice

Pro

xim

itor

or

Acc

el.

Vel

omito

r or

2 W

ire

Acc

el.

TC

RTD

Gal

vani

c Is

olat

or P

aram

eter

s (p

er c

hann

el, a

ll ch

anne

ls m

ust b

e ke

pt s

epar

ate)

See

Sect

ion

Num

ber

4.1

4.1

4.2

4.2

Tabl

e 5.

3

I.S. e

quip

men

t cer

tifie

d fo

r con

nect

ion

to in

divi

dual

gal

vani

c is

olat

or c

ircui

ts:

Cho

ose

galv

anic

isol

ator

circ

uit

para

met

ers

(Vm

ax/R

min

or U

o/Io

or V

oc/Is

c) a

nd c

able

in a

ccor

danc

e w

ith th

e co

ntro

l dra

win

g of

the

I.S.

devi

ce.

I.S. e

quip

men

t with

ent

ity p

aram

eter

s: M

atch

cer

tifie

d I.S

. equ

ipm

ent p

aram

eter

s w

ith g

alva

nic

isol

ator

ch

anne

l par

amet

ers

such

that

the

follo

win

g co

nditi

ons

are

met

:

Vm

ax o

r Ui i

s ≥

Voc

or U

o Ii

or Im

ax is

≥ I

o or

Isc

Ci +

Cca

ble ≤

Ca

or C

o Li

+ L

cabl

e ≤

La

or L

o S

ee s

ectio

n 4

for s

ugge

sted

gal

vani

c is

olat

or m

odel

s fo

r the

diff

eren

t cha

nnel

type

s.