1 ABSTRACT A Shunt Active Power Filter(APF) is a device that is connected in parallel to group of loads.APF cancels the reactive and harmonic currents drawn by the load so as to make supply current sinusoidal. Active Power Filter play a vital role in present day liberalized energy market. Active Power Filter are explored for executing different power conditioning function simultaneously along with harmonic elimination due to increase in nonlinear and unbalanced load, at the point of common coupling. The aim of present dissertation is to study different control strategies for Active Power Filter. More importantly to study instantaneous power theory based Shunt Active Power Filter which is predominantly used in present scenario. The shunt active power filter is investigated through Matlab/Simulink simulation under different load conditions. Simulation results are discussed in depth. Then the design issues of Active Power Filter for different load conditions are also discussed.
30
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 17113253 Shunt Active Filter Project Report

1

ABSTRACT

A Shunt Active Power Filter(APF) is a device that is connected in parallel to group

of loads.APF cancels the reactive and harmonic currents drawn by the load so as to make

supply current sinusoidal. Active Power Filter play a vital role in present day liberalized

energy market. Active Power Filter are explored for executing different power conditioning

function simultaneously along with harmonic elimination due to increase in nonlinear and

unbalanced load, at the point of common coupling. The aim of present dissertation is to

study different control strategies for Active Power Filter. More importantly to study

instantaneous power theory based Shunt Active Power Filter which is predominantly used in

present scenario. The shunt active power filter is investigated through Matlab/Simulink

simulation under different load conditions. Simulation results are discussed in depth. Then

the design issues of Active Power Filter for different load conditions are also discussed.

Page 2: 17113253 Shunt Active Filter Project Report

2

CHAPTER 6

SIMULATION DESIGN

The p-q theory based shunt APF is implemented for Harmonic compensation and power

factor correction. Logic utilized for shunt APF is discussed in chapter 5 and is summarized

in fig.5.2

6.1 Specification of the design:

Simulation is performed on 2 types of Three phase Balanced Non –Linear Load as

fallows:

System Parameters

Source Voltage 220 (line- line)

System Frequency 60 Hz

APF

Dc-link voltage 800V

Dc side capacitance C 1100

Ac side inductance 3.75mH

Ac side resistance 0.01 Ω

(Rating of APF is generally decided by peak voltage and RMS Current)

Load 1 Thyristor Rectifier (of rating 4 KVA)supplying to DC motor equivalent of 2.5KW

AC side inductance 1mH

AC side resistance 0.01 Ω

Page 3: 17113253 Shunt Active Filter Project Report

3

DC side Resistance 18 Ω

DC side Inductance 85mH

Load2 Diode rectifier (of rating around 3KVA) supplying to purely resistive load

AC side inductance NA

AC side resistance NA

DC side Resistance 18 Ω

DC side Inductance NA

(NOTE: Rating of APF is generally decided by peak voltage and RMS Current[14]

APF rating for Load1 is will result in rating of

.Thus in practical cases can be assumed to be around 1-1.5KVA}.

Page 4: 17113253 Shunt Active Filter Project Report

4

220

V rm

s L-L

3-ph

ase

Sour

ce

PI c

ontro

ller

Low

Pass

FIlt

er

Curre

nt m

easu

rem

ent

Volta

ge m

easu

rem

ent

RcLc

Cont

inuo

us

pow

ergu

i

A B C non-

linea

r loa

d curre

nt m

easu

rem

ent1

v+-

v+-

VcVbVa

Valp

ha

Vbet

a

pdc

plos

s

Isal

fa

Isbe

taIn

1

In2O

ut1

Load

Cur

rent

mea

sure

men

t

Isal

pha

Isbe

ta

Ia*

Ib*

Ic*

Inve

rse T

rans

form

atio

n

Isa*

Isb*

Isc*

Isa

Isb

Isc

A1 A2 B1 B2 C1

C2

Hyste

risis

Band

Cur

rent

Con

trolle

r

[Vdc

]G

oto7

[isc]

[Vsc

][V

sb]

[isb]

[isa]

[Vsa

]

[Vdc

]

[isc]

[isb]

[isb][isa]

[isc]

[Vsb

]

[Vsa

]

[Vsc

]

[isa]

i+

- i+

-

i+

-

i+

-

i+

-

i+

-

i+

-i+

-i+

-

800

g11

g12

g21

g22

g31

g32

Vdc

a b c

Com

pens

ator

Vsa

Vsb

Vsc

Isa

Isb

Isc

Valp

ha

Vbet

a p

Clar

ke T

rans

form

atio

n

Capa

cito

r vol

tage

butte

r

v+-

Fig 6.1 p-q theory based control block diagram of three-phase shunt APF system.

Page 5: 17113253 Shunt Active Filter Project Report

5

6.2 Clark Transformation:

is done in accordance with section 4.2.2

Fig 6.2 Block Diagram for Clark Transformation and p calculation

Fig 6.3 Clark transformation block diagram for both

3

p

2

Vbeta

1

Valpha

Vbeta

Ibeta

Valpha

Ialpha

p

Subsystem5

a

b

c

alpha

beta

Subsystem2

a

b

c

alpha

beta

Subsystem1

6

Isc

5

Isb

4

Isa

3

Vsc

2

Vsb

1

Vsa

2

beta

1

alpha

Sum of

Elements1

Sum of

Elements

-K-

K=sqrt(2/3)

-K-

K=sqrt(2/3)

-K-

K=-1/2

-1

1

1

-K-

K=-1/2

3

c

2

b

1

a

Page 6: 17113253 Shunt Active Filter Project Report

6

6.3 Calculation of

According p-q theory real and imaginary power can be separated into two parts:

Real power:

Imaginary power: (from eq)

and are average power due to component respectively

and are oscillating power due to components respectively.

And will produces a purely sinusoidal waveform. But in order to

achieve unity power factor APF must compensate for from component . Thus,

will produce purely sinusoidal waveform with unity power factor.

Thus, inverse transformation will produce reference current for each

phase. can deduced from which is filtered out using low pass filter from p.

Fig 6.4 Block diagram for calculation of p

1

p

Product1

Product

4

Ialpha

3

Valpha

2

Ibeta

1

Vbeta

Page 7: 17113253 Shunt Active Filter Project Report

7

Fig 6.5 from using Low Pass filter

6.4 DC-Bus Voltage Control

Under a loss free situation, the shunt APF need not provide any active power

to cancel the reactive and harmonic currents from the load. These currents show up as

reactive power. Thus, it is indeed possible to make the DC-bus capacitor delivers the

reactive power demanded by the proposed shunt APF. As the reactive power comes from the

DC-bus capacitor and this reactive energy transfers between the load and the DC-bus

capacitor (charging anddischarging of the DC-bus capacitor), the average DC-bus voltage

can be maintained at a prescribed value.

However, due to switching loss, capacitor leakage current, etc., the distribution

source must provide not only the active power required by the load but also the additional

power required by the VSI to maintain the DC-bus voltage constant. Unless these losses are

regulated, the DC-bus voltage will drop steadily.

A PI controller used to control the DC-bus voltage is shown in Figure6.6. Its transfer

function can be represented as

where is the proportional constant that determines the dynamic response of the

DC-bus voltage control, and is the integration constant that determines its settling time.

Fig 6.6 PI controller for DC-bus voltage control

(Note: )

It can be noted that if and are large, the DC-bus voltage regulation is dominant, and

the steady-state DC-bus voltage error is low. On the hand, if and are small, the real

1

ploss

Subtract

PID

PID Controller

2

constant

1

Vdc

Page 8: 17113253 Shunt Active Filter Project Report

8

power unbalance give little effect to the transient performance. Therefore, the proper

selection of and is essentially important to satisfy above mentioned two control

performances.

6.5Reference Current Calculation:

Reference Currents are calculated from inverse clark transformation.

Fig 6.7 Block diagram for calculation of

Fig 6.8 Reference Current calculation

2

Isbeta

1

Isalfa

Product3

Product2

Product1

Product

Divide1

Divide

4

ploss

3

pdc

2

Vbeta

1

Valpha

3

Ic*

2

Ib*

1

Ia*

Subtract

-K-

Gain3

-K-

Gain2

-K-

Gain1

-K-

Gain

2

Isbeta

1

Isalpha

Page 9: 17113253 Shunt Active Filter Project Report

9

6.6 Hysteresis Band Current Controller:

It is introduced in chapter 3 section 3.5.2

Fig 6.9 Hysteresis Band Current Controller

Actual source currents ( ) are compared with the reference currents

generated by the control algorithm in the hysteresis-band current controller. Three

hysteresis-band current controllers generate the switching pattern of the VSI. The switching

logic is formulated as follows

If < ( HB) higher switch is OFF and lower switch is ON for leg “A” (QA=1)

If > ( + HB) higher switch is ON and lower switch is OFF for leg “A” (QA=0).

The switching functions of QB and QC for legs „„B‟‟ and „„C‟‟ are determined similarly,

using corresponding reference and measured currents and hysteresis bandwidth (HB). The

hysteresis-band current control is the fastest control method with minimum hardware and

software but variable switching frequency is its main drawback

6

C2

5

C1

4

B2

3

B1

2

A2

1

A1

Subtract3

Subtract2

Subtract1

Relay3

Relay2

Relay1

NOT

Logical

Operator2

NOT

Logical

Operator1

NOT

Logical

Operator

6 Isc

5 Isb

4 Isa

3

Isc*

2

Isb*

1

Isa*

Page 10: 17113253 Shunt Active Filter Project Report

10

6.7 Compensator:

Switching is done according to gating signals from Hysteresis Band Current Controller.

Capacitor Voltage is continuously measured and fed to PI controller as explained earlier.

Fig 6.10 Compensator

1

Vdc

3

c

2

b

1

a

v+-

Voltage Measurement3

gm

12

gm

12

gm

12

gm

12

gm

12

gm

12

C

6 g32

5 g31

4 g22

3 g21

2 g12

1 g11

Page 11: 17113253 Shunt Active Filter Project Report

11

6.8 Non-Linear Loads

Case:1 Thyristor Converter Supplying to DC motor equivalent

Fig6.11 Block Diagram for Thyristor Converter controlled DC motor

Using PI controller DC motor current value is maintained at 20 Amps. PI controller varies

alpha of thyristor until motor current matches reference current. Pulse width is takes as .

Synchronization Voltages

DC motor equivalent circuit

PI Curent Regulator

LlacRlac

3 C

2 B

1 A

v+-

Vca

v+-

Vbc

v+-

Vab

g

A

B

C

+

-

Thyristor Converter

alpha_deg

AB

BC

CA

Block

pulses

Synchronized

6-Pulse Generator

1

s

Id_Refence

i+

-

Id

5

100

90

0

Page 12: 17113253 Shunt Active Filter Project Report

12

case2:Diode Rectifier supplying to pure resistive load

Fig 6.12 Block diagram for Diode rectifier supplying to pure Resistive Load

A pure resistive load is taken in order to APF performance. As in this load phase current

varies in abrupt manner on the contrary to RL load where load phase current is smooth

varying curve.

3 C

2 B

1 A

Diode5

Diode4

Diode3

Diode2

Diode1

Diode

Page 13: 17113253 Shunt Active Filter Project Report

13

CHAPTER 7

SIMULATION RESULTS

7.1 Case 1: Thyristor converter supplying to DC motor Equivalent(R-L Type Load)

FiFig 7.1 Source Voltages and Load Currents with APF(Case 1)

Page 14: 17113253 Shunt Active Filter Project Report

14

Fig 7.2 Harmonic Analysis of Load Current with APF(Case 1)

Fig 7.3 Reference Current (Case 1)

Page 15: 17113253 Shunt Active Filter Project Report

15

Fig 7.4 Source Current with APF(Case 1)

Fig 7.5 Compensating Current and Load Current(Case 1)

Page 16: 17113253 Shunt Active Filter Project Report

16

Fig 7.6 Source Voltage and Source Current with APF(Case 1)

Page 17: 17113253 Shunt Active Filter Project Report

17

Fig7.7 Harmonic Analysis of Source Current (Case 1)

Page 18: 17113253 Shunt Active Filter Project Report

18

Fig7.8 DC Capacitor Voltage for three-phase APF(Case 1)

Page 19: 17113253 Shunt Active Filter Project Report

19

7.2 Case 2: Diode Rectifier supplying to pure resistive

Fig 7.9 load Source Voltage & Load Current with APF

Page 20: 17113253 Shunt Active Filter Project Report

20

Fig 7.10 Harmonic Analysis of Load Current

Page 21: 17113253 Shunt Active Filter Project Report

21

Fig 7.11 Source Current after Compensation(Case 2)

Fig 7.12 Compensating Current and Load Current(Case 2)

Page 22: 17113253 Shunt Active Filter Project Report

22

Fig 7.13 Source Voltages and Source Current(Case 2)

Page 23: 17113253 Shunt Active Filter Project Report

23

Fig 7.14 Harmonic analysis of Source Current(Case 2)

Page 24: 17113253 Shunt Active Filter Project Report

24

Fig 7.15 DC Capacitor voltage for three-phase APF(Case 2)

Page 25: 17113253 Shunt Active Filter Project Report

25

7.3 Simulation Result Discussion:

As the source current and voltage are in phase,also the source current is almost

sinusoidal(very low THD) it can be said that source is providing only active power required

by the circuit. In instantaneous power theory view, source current is providing only average

real power component( ) while remaining components i.e real oscillating power( ),

imaginary average power( ) and imaginary oscillating power( ), is being provided by

Shunt APF.(see Discussion in section 6.3 )

From source currents and THD in case1 (RL load) and case 2 (purely resistive load

)it can be said that the effectiveness of the active filter in compensating for harmonic

components of the load current depends on the specific load current waveform involved.

Two different waveforms may have the same rms harmonic content but the active filter may

do a better job of compensating for one of the waveforms because of the waveshapes

involved. Source current has very less THD in case of RL load compared to purely resistive

one. Thus it can be inferred performance of shunt APF with RL load is much better than

purely resistive load.

In general, the current waveform of an ac regulator with resistive load is an example

of the waveshape that poses the severest challenge for an active filter. The problem is the

high di/dt that is required of the filter to compensate for the high di/dt at turn on of the

regulator. The problem is most severe when the regulator is turned on with a firing angle

close to 90 degrees because this is when the available driving voltage stored on the dc

capacitor is at a minimum. The output di/dt capability can be raised either by increasing the

dc voltage setting or by reducing the size of the interfacing inductance. The limiting factor

for increasing the dc voltage is the voltage withstand capability of the IGBT devices. The

limiting factors for reducing the interfacing inductance include the IGBT di/dt withstand

capability, control requirements, the interface passive filter requirement, and overall system

stability. If the interfacing inductance becomes too small, the dc voltage cannot be kept

constant for normal operation.

From harmonics analysis of Source Current it can be seen due to uneven switching

of compensator large number of interharmonics are introduced. But,it should be noted that

Page 26: 17113253 Shunt Active Filter Project Report

26

those components have very less magnitude.(Maximum magnitude of interharmonic is 0.11

% in case 1)

Using PI Controller DC capacitor is maintained at reference value. It was seen that

Settling time improved drastically using PI controller.

It is worth to also to note that p-q based APF can be used for complete harmonic

elimination not selective harmonic elimination.

7.4 Future Scope

As p-q theory can be implemented in three-phase with excellent results in terms of

THD, transient response, reference current generation. The work on extending use of p-q

theory in single phase APF is being done[13].

Switching required in APF is very high in order of 10 kHz. Resulting in appreciable

amount of power. Thus, one can further work on to reduce switching frequency and to

switching losses.

One can also work on linear control technique to replace hysteresis band controller

.So, that irregular switching in compensator can be removed.

Study of Control system of APF is also a possibility n order to get lesser steady state

error and improved settling time. Most importantly to study various APF techniques and

comparing them in terms of dynamic response, performance under various type of load, total

harmonic compensation is to be done.

Page 27: 17113253 Shunt Active Filter Project Report

27

CHAPTER 8

CONCLUSION

The validity in terms of eliminating p-q theory in terms of eliminating harmonics and power

factor improvement is confirmed from low THD source current which is in phase with source

voltage. But p-q theory utilizes large number of sensors and reference current calculation block.

Large number of calculation in p-q theory demands higher processing power. Resulting in utility to

be complex and expensive. The p-q theory base APF is predominantly utilized in three phase circuits

thus can not be used at remote single phase customer. As a result, Harmonics are present in large part

of system. From source currents of the both cases (i.e. RL Load and purely resistive load) it can be

inferred that APF is most effective when the load current waveform does not have abrupt changes.

The overall filtering effectiveness depends significantly on the types of loads being compensated. As

a result, it is very effective for most voltage source inverter-type loads, even when the distortion is

high.

From comparing reference current and source waveforms it can be concluded that hysteresis

band current controller done the compensation at the cost of high switching frequency. Which can

result in high switching losses in practical high power APF applications. PI controller performance is

also validated from the DC-bus capacitor voltage which shows decreased settling time.

In theoretical view p-q theory has some shortcomings which need to be addressed. Like

mathematical expression of instantaneous power does not fallow power conservation and real and

imaginary power needed to be more accurately defined as zero sequence instantaneous power can

not be defined by the theory. In practical approach also it can be noted that p-q theory is incapable of

providing selective harmonic elimination and specific power factor compensation.

Page 28: 17113253 Shunt Active Filter Project Report

28

References

1.H. Akagi, Y. Kanazawa and A. Nabae, "Generalized Theory of Instantaneous Reactive

Power and Its Applications," Transactions of he lEE-Japan, Part B, vol. 103, no.7, 1983, pp.

483-490

2.Power Quality C.Sankaran

3.H. Akagi. “New trends in active filters for power conditioning”, IEEE Trans. on Industry

Applications, vol. 32, pp. 1312-1322, (1996).

4. Das, J. C. Passive Filters – Potentialities and Limitations. IEEE Trans. On Industry

Applications. 2004. 40(1): 232-241.

5. Power Electronics Handbook CRC PRESS

6. El-Habrouk, M., Darwish, M. K., and Mehta, P. Active Power Filters: A Review. Proc.

IEE Electric Power Applications. 2000. 147(5): 403-413.

7. Characteristics of Three Phase Active Power

Filter using Extension pq Theory. Proceedings of the IEEE International

Symposium on Industrial Electronics (ISIE). July 7-11, 1997. Guimaraes,

Portugal: IEEE. 1997. 302-307.

8.Chen, C. L., Chen, E. L., and Huang, C. L. An Active Filter for Unbalanced

Three-Phase System using Synchronous Detection Method. Proceedings of

the Power Electronics Specialist Conference (PESC). June 20-25, 1994.

Taipei, Taiwan: IEEE. 1994. 1451-1455.

9.Chen, D. –H. and Xie, S. –J. Review of Control Strategies Applied to Active

Power Filters. Proceedings of the IEEE International Conference on Electric

Utility Deregulation, Restructuring and Power Technologies (DRPT). April

5-8, 2004. Hong Kong: IEEE. 2004. 666-670.

10.Textook of “Modern Power Electronics and AC Drives”, B.K.Bose

11.Instantaneous p-q Power Theory for Compensating Non-sinusoidal Systems

E. H. Watanabe, Senior Member, IEEE, H. Akagi, Fellow, IEEE and M. Aredes, Member,

IEEE

Page 29: 17113253 Shunt Active Filter Project Report

29

12.Instanteneous Power Theory and applications to power conditioning, IEEE Press, H.

Akagi, E. H. Watanabe, M. Aredes.

13. M. Tarafdar Haque “SINGLE-PHASE PQ THEORY”, IEEE Trans.

14 “Active filter design and specification for control of harmonics in industrial and

commercial facilities”, Mark McGranaghan Electrotek Concepts, Inc.