Top Banner
15 YEARS OF EXPERIENCE WITH 100% GENERATOR STATOR GROUND FAULT PROTECTION WHAT WORKS, WHAT DOESN’T AND WHY 15 YEARS OF EXPERIENCE WITH 100% GENERATOR STATOR GROUND FAULT PROTECTION WHAT WORKS, WHAT DOESN’T AND WHY Chuck Mozina Consultant Beckwith Electric
34

15 years of experience stator ground fault protection

Jan 16, 2017

Download

Engineering

michaeljmack
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 15 years of experience stator ground fault protection

15 YEARS OF EXPERIENCEWITH

100% GENERATOR STATOR GROUND FAULT PROTECTIONWHAT WORKS, WHAT DOESN’T AND WHY

15 YEARS OF EXPERIENCEWITH

100% GENERATOR STATOR GROUND FAULT PROTECTIONWHAT WORKS, WHAT DOESN’T AND WHY

Chuck MozinaConsultant

Beckwith Electric

Page 2: 15 years of experience stator ground fault protection

BACKGROUND:

Until the Late ’70’s 100% Stator Ground Schemes Were Not Widely Used in the US.

Users Accepted Ground Fault Coverage of Only 90-95% of the Stator Winding.

Conventional 59G Neutral Overvoltage Protection Used.

Stator Ground Fault Protection

Page 3: 15 years of experience stator ground fault protection

100% Schemes Using 3rd Harmonic Neutral Undervoltage Introduced in the Late ’70’s.

Early ’80’s 100% 3rd Harmonic Ratio Scheme was Introduced.

During this Period 100% Subharmonic Injection Schemes Were Being Used in Europe

BACKGROUND:

Stator Ground Fault Protection

Page 4: 15 years of experience stator ground fault protection

Conventional 59G Stator Ground Fault Application and Settings.

Undervoltage Neutral 3rd Harmonic scheme for 100% Stator Ground Fault Protection.

3rd Harmonic Ratio Scheme for 100% Stator Ground Fault Protection.

Limitation of These 3rd Harmonic Schemes and Some Methods of Overcoming these Limitations.

Subharmonic Injection Method for 100% Stator Ground Fault Protection.

PAPER ADDRESSES:

Stator Ground Fault Protection

Page 5: 15 years of experience stator ground fault protection

CONVENTIONAL (59G) STATOR GROUND FAULT

PROTECTION

CONVENTIONAL (59G) STATOR GROUND FAULT

PROTECTION

Stator Ground Fault Protection

Page 6: 15 years of experience stator ground fault protection

Conventional Stator Ground Fault Protection

Fault Position

Volta

ge a

t Neu

tral

(60

Hz)

0% 50% 100%0

0.5pu

1.0pu

N T

90-95%

59G

Stator Ground Fault Protection

Page 7: 15 years of experience stator ground fault protection

59G Coordination Issues

F1 – TRANSMISSION SYSTEM GROUND FAULTF2 – VT SECONDARY GROUND FAULT

CH-L

F1

F2

59G

Stator Ground Fault Protection

Page 8: 15 years of experience stator ground fault protection

Calculation of Generator Neutral Voltage for a Transmission System Ground Fault

C0

CH-L

VHO

Where:

= High side zero sequence voltage for a transmissionsystem ground fault.

= Generator step-up transformer high-to-low windingcapacitance

CH-L

VHO

C0= Generator system zero sequence capacitance perphase

3RN

3RN = Equivalent primary resistance in generator neutral

VR

Stator Ground Fault Protection

Page 9: 15 years of experience stator ground fault protection

VT Connection to Avoid 59G Coordination with VT Fuses

59G

Stator Ground Fault Protection

Page 10: 15 years of experience stator ground fault protection

3rd HARMONICSTATOR GROUNDFAULT DETECTION

SCHEMES

3rd HARMONICSTATOR GROUNDFAULT DETECTION

SCHEMES

Stator Ground Fault Protection

Page 11: 15 years of experience stator ground fault protection

100% SCHEMES USING 3RD HARMONIC

Undervoltage 3rd Harmonic Scheme

3rd Harmonic Ratio Scheme

Stator Ground Fault Protection

Page 12: 15 years of experience stator ground fault protection

Level of 3rd Harmonic Voltage Depends on:

The Construction of the Generator-- The Pitch of the Stator Windings

The MW and MVAR Output of the Generator

The Generator Terminal Capacitance

Stator Ground Fault Protection

Page 13: 15 years of experience stator ground fault protection

General 3rd Harmonic Behavior

Stator Ground Fault Protection

Page 14: 15 years of experience stator ground fault protection

3rd HARMONIC NEUTRAL

UNDERVOLTAGESCHEME

3rd HARMONIC NEUTRAL

UNDERVOLTAGESCHEME

Stator Ground Fault Protection

Page 15: 15 years of experience stator ground fault protection

Third Harmonic Neutral Undervoltage Scheme

59G

59G

Stator Ground Fault Protection

Page 16: 15 years of experience stator ground fault protection

Overlapping of 59G and 27TN to Provide 100% Stator Ground Fault Coverage

59G

59G

Stator Ground Fault Protection

Page 17: 15 years of experience stator ground fault protection

Field Measurements of the Magnitude of Third Harmonic Neutral Voltage

Stator Ground Fault Protection

Page 18: 15 years of experience stator ground fault protection

Advantages / Disadvantages:

Low Cost and Simple.

No New Equipment.

Requires Field Testing to Determine Minimum 3rd

Harmonic.

May Have to be Blocked During Some Operating Conditions.

Will not Work at all if 3rd Harmonic is Low – False Tripping.

Stator Ground Fault Protection

Page 19: 15 years of experience stator ground fault protection

3rd HARMONICRATIO SCHEME 3rd HARMONICRATIO SCHEME

Stator Ground Fault Protection

Page 20: 15 years of experience stator ground fault protection

3rd Harmonic Ratio Scheme

5 9 G

5 9 D T h ir d H a rm o n icR a t io R e la y

C o n v e n t io n G r o u n dO v e r v o lta g e R e la y

3 V 0

Stator Ground Fault Protection

Page 21: 15 years of experience stator ground fault protection

Field Measurements of the Magnitude of Third Harmonic Voltages

Stator Ground Fault Protection

Page 22: 15 years of experience stator ground fault protection

Advantages / Disadvantages:

More Secure Than Using Only Neutral 3rd Voltage.Requires Measurement of 3rd Harmonic Terminal Voltage.Requires Wye Grounded Primary VT with Broken Delta Secondary.This Generally Requires VT Additions or Modifications and Additional Wiring.Requires Extensive Field Testing to Determine Maximum 3rd Harmonic Ratio.Will Not Work at all if 3rd Harmonic is Low – But No False Tripping.

Stator Ground Fault Protection

Page 23: 15 years of experience stator ground fault protection

LIMITATIONS OF

3rd HARMONICSCHEMES

LIMITATIONS OF

3rd HARMONICSCHEMES

Stator Ground Fault Protection

Page 24: 15 years of experience stator ground fault protection

Hydro Plant Applications:

False Tripping during Load Rejection

Synchronous Condenser Operation

Performance of Third Harmonic Scheme on Parallel Generators

Stator Ground Fault Protection

Page 25: 15 years of experience stator ground fault protection

Parallel Generators on a Common GSU

BUS

G1

G2

59G

27TN

59G

27TN

GSU

Stator Ground Fault Protection

Page 26: 15 years of experience stator ground fault protection

Cross Compound and Large Generators Applications

27TN

W inding 1W inding 2

W inding not covered by27TN

G S U

Stator Ground Fault Protection

Page 27: 15 years of experience stator ground fault protection

Gas Turbine Third Harmonic Voltage Profile

Stator Ground Fault Protection

Page 28: 15 years of experience stator ground fault protection

Third Harmonic Neutral Undervoltage(27TN) Blocking

Stator Ground Fault Protection

Page 29: 15 years of experience stator ground fault protection

SUBHARMONIC VOLTAGEINJECTIONSCHEME

SUBHARMONIC VOLTAGEINJECTIONSCHEME

Stator Ground Fault Protection

Page 30: 15 years of experience stator ground fault protection

Subharmonic Voltage Injection Scheme

*

C o u p lin gF ilte r

V o lta g eIn je c to r

R e la yM e a s u re m e n ts

I

V

N a tu ra l C a p a c ita n c e

5 9 GN o te s :

S u b h a rm o n ic in je c t io n ty p ic a lly a t 1 5 -2 0 H zC o u p lin g f i l te r lo w p a s s o r n o tc h tu n e d fo r s u b h a rm o n ic f re q u e n c yM e a s u re m e n t in p u ts tu n e d to re s p o n d to s u b h a rm o n ic fre q u e n c y

Stator Ground Fault Protection

Page 31: 15 years of experience stator ground fault protection

Coupling Filter and Voltage Injector Stator Ground Fault Protection

Page 32: 15 years of experience stator ground fault protection

Advantages / Disadvantages:

Does Not Use 3rd Harmonic Voltage. Independent of Gen. MW and MVAR Loading.Can Detect Stator Ground Fault When Gen. is Off-Line.Detects Stator Ground Faults Over the Entire Winding–No Blind Spots. Requires Field Measurement of Subharmonic Charging Current – Off-Line Measurement.Requires Additional Equipment in Grounding Transformer Secondary – Added Cost.Cost have Reduced With Digital Technology.

Stator Ground Fault Protection

Page 33: 15 years of experience stator ground fault protection

CONCLUSIONSIt’s Important to Upgrade to 100% Stator Ground Fault Protection.If 3rd Harmonic Schemes are to Being Considered-- It is Important to First Determine 3rd Harmonic “Signature”of the Generator.Recognize that 3rd Harmonic Schemes Have Limitations. Subharmonic Injection Provides an Viable Alternative to 3rd Harmonic Schemes.Injection Scheme Cost have Reduced with Digital Technology – Good Choice for Important Generators.Injection Scheme can Detect Stator Grounds Over the Entire Stator Winding and in an Off-line Generator.

Stator Ground Fault Protection

Page 34: 15 years of experience stator ground fault protection

THE END

Questions ?

THE END

Questions ?

15 YEARS OF EXPERIENCEWITH

100% GENERATOR STATOR GROUND FAULT PROTECTIONWHAT WORKS, WHAT DOESN’T AND WHY

15 YEARS OF EXPERIENCEWITH

100% GENERATOR STATOR GROUND FAULT PROTECTIONWHAT WORKS, WHAT DOESN’T AND WHY

Stator Ground Fault Protection

©2008 Beckwith Electric Co., Inc.