Top Banner
Cooling Load
61

12 Cooling Load Calculations

Nov 29, 2014

Download

Documents

sp su
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 12 Cooling Load Calculations

Cooling Load

Page 2: 12 Cooling Load Calculations

Contents

• Principle of cooling load• Why cooling load & heat gains are different • Design conditions• Understand CLTD/CLF method• An example

Page 3: 12 Cooling Load Calculations

Cooling Load • It is the thermal energy that must be removed

from the space in order to maintain the desired comfort conditions

• HVAC systems are used to maintain thermal conditions in comfort range

Page 4: 12 Cooling Load Calculations

Purpose of Load Estimate

• Load profile over a day• Peak load (basis for equipment sizing)• Operation Energy analysis• HVAC Construction cost

Page 5: 12 Cooling Load Calculations

• Enclosure heat transfer characteristics– Conduction– Convection– radiation

• Design conditions– Outdoor & indoor

• Heat Gains– Internal – External or Solar

• Thermal capacity

Principles of cooling Load Estimate

Page 6: 12 Cooling Load Calculations

Space Characteristics

• orientation• Size and shape• Construction material• Windows, doors, openings• Surrounding conditions• Ceiling

Page 7: 12 Cooling Load Calculations

Space Characteristics

• Occupants (activity, number, duration)• Appliances (power, usage)• Air leakage (infiltration or exfiltration)• Lighting (W/m2)

Page 8: 12 Cooling Load Calculations

Indoor Design ConditionsBasic design parameters• Air temperature

– Typically 22-26 C• Air velocity

– 0.25 m/s• Relative humidity

– 30-70 % • See ASHRAE 55 – 2004 Comfort Zone

Page 9: 12 Cooling Load Calculations

Indoor Design Conditions• Indoor air quality

– Air contaminants– Air cleaning

• Acoustic requirements• Pressurization requirements

Page 10: 12 Cooling Load Calculations

Outdoor Design Conditions• Weather data required for load calculation

– Temperature & humidity– Wind speed, sky clearness , ground reflectance etc

• Design outdoor conditions data can be found in ASHRAE Fundamentals Handbook

Page 11: 12 Cooling Load Calculations

Outdoor Design Conditions• ASHRAE Fundamentals 2001

– Design severity based on 0.4%, 1%, & 2% level annually (8760h)

– For example at 1% level, the value is exceeded in 0.01x8760h = 87.6 h in a year

Page 12: 12 Cooling Load Calculations

Outdoor Design For Cooling

Criteria: 0.4% DB and MWB

Station Cooling DB/MWB

MiriMalaysia

0.4% 1% 2%

DB (˚C ) MWB ( ˚C )

DB MWB DB MWB

32.2 26.3 31.8 26.3 31.4 26.2

Source: ASHRAE Fundamentals 2001

Page 13: 12 Cooling Load Calculations

Terminology• Space- a volume without partition or a group

of rooms

• Room- an enclosed space

• Zone- a space having similar operating characteristics

Page 14: 12 Cooling Load Calculations

Heat Gain • Space Heat gain

– The instantaneous rate at which heat enters into , out of, or generated within a space. The components are:

• Sensible gain• Latent gain

Heat gains Convective (%)

Radiant (%)

Solar radiation with internal shading

42 58

Fluorescent lights

50 50

People 67 33

External wall 40 60

Page 15: 12 Cooling Load Calculations

Heat Gain

Page 16: 12 Cooling Load Calculations

Cooling Load

• Space Cooling load– The rate at which heat must be removed from a

space to maintain air temperature and humidity at the design values

• Cooling load differs from the heat gain due to– delay effect of conversion of radiation energy to

heat– Thermal storage lag

Page 17: 12 Cooling Load Calculations

Heat Gain = Cooling Load

Page 18: 12 Cooling Load Calculations

Heat Gain = Cooling LoadThermal storage and Construction Type

Page 19: 12 Cooling Load Calculations

Time of the Day: Solar Radiation

Page 20: 12 Cooling Load Calculations

Time-delay Effect: Example Lighting

Page 21: 12 Cooling Load Calculations

Extraction Rate

• Space Heat extraction rate – The actual heat removal rate by the cooling

equipment from the space – The heat extraction rate is equal to cooling load

when the space conditions are constant which is rarely true.

Page 22: 12 Cooling Load Calculations

The principal terms of heat Gains/Losses are indicated below.

(Source: ASHRAE Handbook Fundamentals 2005)

Heat Balance

Page 23: 12 Cooling Load Calculations

Coil Load

• Cooling coil load– The rate at which energy is removed at the cooling

coil– Sum of:

• Space cooling load (sensible + latent)• Supply system heat gain (fan + supply air duct)• Return system heat gain (return air duct)• Load due to outdoor ventilation rates (or ventilation

load)

Page 24: 12 Cooling Load Calculations

External Loads

1. Heat gains from Walls and roofs– sensible

2. Solar gains through fenestrations– Sensible

3. Outdoor air– Sensible & latent

Page 25: 12 Cooling Load Calculations

Internal Loads

1. People– Sensible & latent

2. Lights– sensible

3. Appliances– Sensible & latent

Page 26: 12 Cooling Load Calculations

Total Cooling Load

Page 27: 12 Cooling Load Calculations

Cooling Load Components

• Space cooling load– Sizing of supply air flow rate, ducts, terminals and

diffusers– It is a component of coil load– Bypassed infiltration is a space cooling load

• Cooling coil load– Sizing of cooling coil and refrigeration system– Ventilation load is a coil load

Page 28: 12 Cooling Load Calculations

Refrigeration Load

• The capacity of the refrigeration system to produce the required coil load.

Page 29: 12 Cooling Load Calculations

Profiles of Offshore Systems Cooling Loads

Components % Load LQ (L)

%LoadLQ (U)

%Load CCR

%LoadSG/MCC

Solar Transmission 3 4 7 4

Occupants 3 3 3 0

Lights 5 5 8 4

Equipment 10 1 29 21

Outdoor air bypassed 7 8 5 6

Outdoor air not bypassed

72 79 48 64

Total 100 100 100 100

Page 30: 12 Cooling Load Calculations

Heat Load Components

Outdoor air & Electrical Equipment loads (77-85% )

People: 3%

Lighting: 4-8%

Solar Transmission: 3-7%

Infiltration : 5-8%

Page 31: 12 Cooling Load Calculations

Calculation Methods

1. Rule of thumb method– Least accurate– eg 100 btu/ft2 for a space

2. Static analysis (Room temperature is constant)– CLTD/CLF method

3. Dynamic analysis– Computer modeling

Page 32: 12 Cooling Load Calculations

CLTD/CLF Method

• Cooling load is made up of – Radiation and conduction heat gain– Convection heat gain

• Convective gain is instantaneous– No delay– Heat gain equals cooling load

• Conductive and radiation heat gains are not instantaneous– Thermal delay – Heat gain is not equal to cooling load– Use CLTD & CLF factors

Page 33: 12 Cooling Load Calculations

CLTD/CLF Method (ASHRAE 1989)

Cooling load due to solar & internal heat gains• Glazing (sensible only)

– Radiation & conduction– Convection (instantaneous)

• Opaque surface ( wall, floor, roof) load (sensible only)– Conduction– Convection (instantaneous)

• Internal loads (sensible & latent)– Radiation & conduction– Convection (instantaneous)

Page 34: 12 Cooling Load Calculations

Cooling Load Temperature Difference CLTD

Compare Q transmission = UA (T o – T i )

Q transmission = UA (CLTD)• CLTD is theoretical temperature difference defined

for each wall/roof to give the same heat load for exposed surfaces to account for the combined effects of radiation, conductive storage, etc – It is affected by orientation, time , latitude, etc– Data published by ASHRAE

Page 35: 12 Cooling Load Calculations

Cooling Load Factor (CLF)

• This factor applies to radiation heat gain• If radiation is constant, cooling load = radiative

gain• If radiation heat is periodical, than

Q t = Q daily max (CLF)

CLF accounts for the delay before radiative gains becomes a cooling load

Page 36: 12 Cooling Load Calculations

Glazing

• Q = A (SC) (SHGF) (CLF)A= glass areaSC= shading coefficientSHGF= solar heat gain factor,

tabulated by ASHRAECLF= cooling load factor, tabulated

by ASHRAE• Q = U x A x CLTD

U= surface U-factorA= surface areaCLTD= cooling load temperature

difference

transmitted

absorbed

reflected

Solar ray

glass

Page 37: 12 Cooling Load Calculations

Opaque Surfaces

• Q 2 = UA (CLTD)U= surface U-factorA= surface areaCLTD= cooling load temperature difference

• Tabulated or chart values for CLTD can be referred

• Offshore enclosure– Light weight– Metal frame with insulation – Group G wall with U-value about 0.5-1.0 W/m2 K

Page 38: 12 Cooling Load Calculations

CLTD for Sunlit Wall Group G

Source: ASHRAE Fundamental

Page 39: 12 Cooling Load Calculations

Opaque Surface Calculations

• Use Table for wall CLTD• Use Table for roof CLTD

– Select wall/roof type– Look up uncorrected CLTD– Correct CLTDCLTD c=(CLTD+LM)+ (25.5-t r) + (t m-29.4)

• LM= latitude /month correction (Table )• T r = indoor temperature (22C)

• T m= average temperature on the design day = (35+22)/2 = 28.5 C

Eg. If CLTD=40 C, LM=-1.7 (west face)CLTD c= (40-1.7) + (25.5-22)+ (28.5-29.4) = 40.9 C

Page 40: 12 Cooling Load Calculations

Types of Internal Load

• Internal loads are– People– Lights– Equipment or appliances

• Consist of convective and radiant components– Light (mostly radiant)– Electrical heat (radiant and convective)– People (most convective)

• Time-delay effect due to thermal storage

Page 41: 12 Cooling Load Calculations

Internal Load- Lighting Area Light Power   Density W/m2Office 25Corridor 10Sleeping 10CCR 25MCC/SG 25Kitchen 25Recreation 20

•Heat gain (lighting)= 1.2 x total wattage x CLFOr based on light power density ranging from 10-25 W/m2(average density, say=20 W/m2)•Where light is continuously on, CLF=1

Page 42: 12 Cooling Load Calculations

Internal Loads- People

• Q people-s = No x sensible heat gain/p x CLF

• Q people-L = No x latent heat gain/p

Page 43: 12 Cooling Load Calculations

Internal Load – Equipment Heat

• Cooling of electrical equipment in MCC/SG is an important function of HVAC system offshore. The components include:

• Transformers• Motors• Medium/high voltage switchgears• Cables & trays• Motor starters• Inverters• Battery chargers• Circuit breakers• Unit panel board etc

• Heat dissipation from these equipments are mainly based data published by the manufacturers

Page 44: 12 Cooling Load Calculations

Typical Outdoor & Indoor Design Conditions Used Here

Conditions Dry-bulb temperature (C)

% RH Moisture content, kg/kg

Outdoor air 35 70 0.025

Indoor air 22 55 0.009

Difference 13 0.016

ASHRAE fundamental Handbook published data, at 0.4%, 1% and 2% design level. At 0.4% design level, Miri has only 35h (out of 8760 h a year) at 32.2 DB & 26.3 WB or higher

Page 45: 12 Cooling Load Calculations

Infiltration Air is Cooling Load

• Load due to Ventilation air into the space Sensible load, (W) = mass flow rate x specific heat x (∆T)= 1.23 x l/s x (To – T i) or (1.08 x cfm x ∆T)Where To = Outside temperature, C Ti = indoor air temperature, C

Page 46: 12 Cooling Load Calculations

Ventilation Cooling Load

Ventilation latent load, (W)= mass flow rate x latent heat of vaporization x

(humidity difference)= 3010 x l/s x (∆ẁ) or (4840 x cfm x ∆ẁ)

Where ∆ẁ = Inside-outside humidity ratio

difference of air ( kg/kg)

Page 47: 12 Cooling Load Calculations

Total Cooling Load

• This is also call the Grand total load• Sum of

– Space heat gain – System heat gain

– load due to outdoor air supplied through the air handling unit

• Air bypassed the coil• Air not bypassed the coil

Room Total Load

Page 48: 12 Cooling Load Calculations

System Heat Gain

• These are sometimes external to the air conditioned space

• HVAC equipment also contributes to heat gain – Fan heat gain– Duct heat gain

Page 49: 12 Cooling Load Calculations

Bypass Factor

Bypass factor is an important coil characteristic on moisture removal performance .

It’s value depends on: • Number of rows/fins per inch• Velocity of air

Page 50: 12 Cooling Load Calculations

Bypass Factor of the coil

• When air streams across the cooling, portion of air may not come into contact with the coil surface

• BPF = un-contacted air flow total flow

BPF is normally selected at 0.1 for offshore cooling and dehumidification.

Page 51: 12 Cooling Load Calculations

Typical Coil Bypass Factor

Row Deep 14 fins/inch

Face velocity=

2 m/s

2.5 m/s 3 m/s

1 0.52 0.56 0.59

2 0.274 0.31 0.35

4 0.076 0.10 0.12

6 0.022 0.03 0.04

Source: Refrigeration and Air Conditioning by CP Arora

Page 52: 12 Cooling Load Calculations

Effect of Bypass Factor on Ventilation Load

• Coil load due to outdoor airSH= (OASH)(1-BPF)LH= (OALH)(1-BPF)

• Effective room load ERSH=RSH+(OASH)(BPF)ERLH=RLH + (OALH)(BPF)

Page 53: 12 Cooling Load Calculations

Cooling Load Classroom Exercise

• Estimate the cooling load of a portal cabin shown here:

• Assuming that– Outdoor condition is 35C,

70% RH– Indoor condition is 22C , 55

% RH– U-factor=0.5 W/m2 K– Occupied by 2 persons– Electrical equipment heat is

3 kW– 100l/s leakage due to

pressurization

PlatformLower Deck

4 x 4 x 3 h

N

Page 54: 12 Cooling Load Calculations

Cooling Load CalculationsItems Procedures

Transmission- sensibleWall- West sideWall- East sideWall – North Wall- SouthRoofFloorTotal (T1)

Q = UA (CLTD)

Internal load- sensible PeopleEquipmentLightTotal (T2)Safety Factor (5% of T1+ T2)Fan heat & supply Duct Gain (7 % of T1+T2)RSH (Total of the above)

Page 55: 12 Cooling Load Calculations

Coil Load CalculationsItems Procedures

Room Latent Heat (RLH)People

Room Total HeatRSH + RLH

Page 56: 12 Cooling Load Calculations

Cooling Load CalculationsItems Procedures

Design conditions Outdoor 35C, 70% RHIndoor 22C, 55 RH

Ventilation- sensibleBypass air (0.1 bypass factor)Sensible heat of bypass air

10% x outdoor air

Ventilation - LatentLatent heat of bypass air

Page 57: 12 Cooling Load Calculations

Cooling Load CalculationsItems ProceduresDesign conditions Outdoor 35C, 70% RH

Indoor 22C, 55 RH

ERSHRSHSensible heat of air bypassEffective Room Sensible Heat

ERLHPeopleLatent heat of air bypassEffective Room Latent Heat

Effective Room Total Heat (ERTH)ERSH+ESLH

Page 58: 12 Cooling Load Calculations

Coil Load CalculationItems ProceduresDesign conditions Outdoor 35C, 70% RH

Indoor 22C, 55 RH

Coil Load – SensibleEffective Room Sensible HeatSH of Outdoor air not bypassedTotal (Coil Sensible heat)

Coil Load – LatentEffective Room Latent HeatLH of Outdoor air not bypassedTotal (Coil latent heat)

Total coil load (GTH)

Page 59: 12 Cooling Load Calculations

Sensible Heat Factor (SHF)

• Ratio of sensible to total heat – SHF = Sensible heat/ total heat

= SH/ (SH + LH)A low value of SHF indicates a high latent heat load,

which is common in humid climate.• In the above example,

– Calculate the SHF of the room (RSHF)– Calculate the effective room sensible heat factor (ESHF)– Calculate the SHF of the coil (GSHF)

Page 60: 12 Cooling Load Calculations

Selection of Air Conditioning Apparatus

• The necessary data required are:– GTH ( Grand total heat load)– Dehumidified air quantity– Apparatus dew point

These determine the size of the apparatus and refrigerant temperature.

Page 61: 12 Cooling Load Calculations

Sensible Heat Factor (SHF)SHF

RSHF

ESHF

GSHF