-
HARYANA VIDYUT PRASARAN NIGAM
TECHNICAL SPECIFICATION FOR 220 kV, 132 kV, 66 kV & 33 kV
CONTROL AND RELAY PANEL
BOARDS FOR SUBSTATIONS WITH SUBSTATION
AUTOMATION SYSTEM
[SPECIFICATION NO.HPD/S-63R/HPM-468/Vol-II/Prot. (MARCH,
2011)]
CHIEF ENGINEER/MM,
DESIGN DIRECTORATE, HVPNL, SHAKTI BHAWAN, Basement,
SEC-6, PANCHKULA 134109 (HARYANA)
Tel./Fax No. 0172-2583724
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 1
-
CONTENTS
--------------------------------------------------------------------------------
CLAUSE NO. TITLE PAGE NO.
---------------------------------------------------------------------------------
1.0 SCOPE 3 2.0 STANDARDS 3 3.0 SERVICE CONDITION 4 4.0 PRINCIPAL
PARAMETERS 5 5.0 GENERAL TECHNICAL REQUIREMENTS 5 6.0 TESTS 24 7.0
DOCUMENTATION 25 ANNEXURES A. GUARANTEED TECHNICAL PARTICULARS 27
B. TECHNICAL PARTICULARS OF CTs, NCTs, PTs & CVTs 32 C.
TRANSMISSION LINE DATA 51 D. SCHEDULE OF DEVIATIONS FROM THE
SPECIFICATION 52 E. LINE PARAMETERS 53 F. DETAILS OF CARRIER
EQUIPMENTS 54
---------------------------------------------------------------------------------
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 2
-
1.0 SCOPE: 1.1 This specification covers the design,
engineering, manufacture, inspection &
testing at manufacturer's work before despatch, packing,
forwarding and delivery at discretion of purchaser of Control &
Relay Panels for 220 kV, 132 kV & 66 kV S/Stns. having
Substation Automation System in the state of Haryana.
1.2 Unless specifically excluded from the offer, all fittings
and accessories, not specifically stated in this specification but
which are necessary for satisfactory operation of the scheme or to
complete the work in a good workman like manner shall be deemed to
have been included in the scope of supply of the Bidder.
1.3 CO-ORDINATION : Circuit Breakers, CT's, PT's/CVT's &
Isolating Switches, etc. are being purchased
against separate specification. The particulars of CTs, PTs and
CVTs existing/ to be arranged are listed at Annexure 'B'. The
Supplier of control & relay boards shall be responsible for
preparing complete wiring diagram of 33kV,66kV,132 kV & 220 kV
C&R panel boards and shall also undertake to mount & wire
any equipment received from other supplier. The schematic of
breakers & isolators are required to be incorporated in the
panel schematic.
1.4 EXPERIENCE: 1.4.1 For 400kV & 220kV C&R Panels: The
supplier of C&R panels shall be manufacturer of relays and all
the main
relays on the C&R panels shall be of his make only. However,
one of the distance protection schemes on each 220 kV feeder
C&R panel can be of different make in view of the fact that
both the distance protection scheme (Main-I & Main-II) should
have different measuring techniques.
1.4.2 For 132kV, 66kV & 33kV C&R Panels: The supplier of
C&R panels shall be manufacturer of relays and all the main
relays on the C&R panels shall be of his make only. The
suppliers own make relay includes the relays manufactured by their
Principals/Associates and they have their service centre with
them.
2.0 STANDARDS : 2.1 The equipment offered shall conform to
latest relevant Indian Standards listed
hereunder or equivalent IEC :- Sr. No. Standard Title 1. IS: 5
Colour for ready mix paints. 2. IS: 375 Marking & arrangements
for switchgear, bus bars, main
connections & auxiliary wiring. 3. IS: 694 PVC insulated
cable for working voltage upto and
including 1100 V. 4. IS: 722 AC Electricity meters. 5. IS:
1248
Part-I& IV Direct acting indicating analogue electrical
measuring instruments & their accessories.
6. IS: 2419 Dimensions for panel mounted indicating &
recording electrical instruments.
7. IS :3231 Electrical relays for power system protection. 8. IS
:8686 Static protective relays. 9. IS :2147 Degree of protection
provided by enclosures for low
voltage switchgear & control gear.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 3
-
2.2 The works covered by the specification shall be designed,
engineered, manufactured, built, tested and commissioned in
accordance with the Acts, Rules, Laws and Regulations of India.
2.3 The equipment to be furnished under this specification shall
conform to latest issue with all amendments of standard specified
above.
2.4 In addition to meeting the specific requirement called for
in the Technical Specification, the equipment shall also conform to
the general requirement of the relevant standards and shall form an
integral part of Specification.
2.5 The Bidder shall note that standards mentioned in the
specification are not mutually exclusive or complete in themselves,
but intended to compliment each other.
2.6 The Contractor shall also note that list of standards
presented in this specification is not complete. Whenever necessary
the list of standards shall be considered in conjunction with
specific IS/IEC.
2.7 When the specific requirements stipulated in the
specification exceed or differ than those required by the
applicable standards, the stipulation of the specification shall
take precedence.
2.8 Other internationally accepted standards which ensure
equivalent or better performance than that specified in the
standard referred shall also be accepted.
2.9 In case governing standards for the equipment is different
from IS or IEC, the salient points of difference shall be clearly
brought out alongwith English language version of standard or
relevant extract of the same. The equipment conforming to standards
other than IS/IEC shall be subject to Employer's approval.
2.10 The bidder shall clearly indicate in his bid the specific
standards in accordance with which the works will be conformed.
3.0 SERVICE CONDITIONS: 3.1 Equipment to be supplied against
this specification shall be suitable for
satisfactory continuous operation under the following tropical
conditions:- i) Location IN THE STATE OF HARYANA ii) Max. ambient
air temp (C) 50 iii) Min. ambient air temp (C) -2.5 iv) Maximum
Relative humidity (%) 100 v) Minimum Relative humidity (%) 26 vi)
Average annual rainfall (mm) 900
vii) Max. wind pressure (kg/sq. m.) 195 viii) Max. altitude
above mean sea level (meters). 1000 ix) Isoceraunic level
(days/Year) 50 x) Seismic level (horizontal acceleration) 0.3 g xi)
Average number of dust storm 35 (days per annum)
Note:-i)Moderately hot and humid tropical climate conducive to
rust and fungus growth.
The climatic conditions are also prone to wide variations in
ambient conditions. ii)Air conditioning or any special arrangement
for making the control room dust
proof shall not be provided in any of the S/Stn. 3.2 All control
wiring, equipment & accessories shall be protected against
fungus
growth, condensation, vermin & other harmful effects due to
tropical environments.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 4
-
3.3 AUX. POWER SUPPLY : i) A.C. Supply : 415/240 Volts, 3-phase,
4-wire, 50 Hz Voltage variation : 10% Frequency variation : 3%
ii) D C Supply : 220 Volts, 2 wire available from S/Stn.
battery(insulated)
Variation : 10%.
3.4. 220 kV, 132 kV, 66 kV & 33 kV voltages will be three
phase having normal frequency of 50 Hz subject to a variation of
3%. Neutrals of the Power Transformers at the S/Stn. covered in
this specification are solidly earthed.
4.0 PRINCIPAL PARAMETERS: 4.1 The panel shall have the principal
dimensions as detailed below:- i). Depth of panels = 610 mm ii).a)
Height of switchboard above base frame = 2210 mm b) Height of base
frame = 102 mm iii). Type of Panels = Simplex Control & Relay
Panel
Note:- The offer of the bidder not conforming to above
requirement shall be out rightly rejected.
4.2 ARRANGEMENT OF PANELS: The panels shall be fabricated so
that even if the serial of panels is changed no difficulty will be
faced in the placement of panels and cabling etc. The sequence of
various panels in a panel board at a S/Stn. shall be supplied to
successful bidder.
5.0 GENERAL TECHNICAL REQUIREMENTS:
5.1 MATERIAL & WORKMANSHIP: All material used in the
construction of the panels/relays shall be of the best
quality obtainable of their respective kind and whole of the
work shall be of the highest class, well finished and of approved
design and make.
Castings shall be free from blow-holes, flaws, cracks or other
defects and shall be smooth grained and of true dimensions and
forms.
The draw out mechanism in respect of draw out relays should be
smooth and convenient so as to give adequate service during their
use.
5.2 DEPARTURE FROM THE SPECIFICATION:
Should the tenderer wish to depart from the provisions of this
specification either on account of manufacturing practice or for
any other reasons, he will draw specific attention to the proposed
points of departure on the prescribed Performa (enclosed) at
annexure-D in his tender and submit such full information, drawings
and specifications as will enable the merit of his proposal to be
appreciated. In the event of contractor drawings, specification and
tables etc. disagreeing with this specification during the
execution of the contract this specification shall be held binding
unless the departures have been fully recorded as required
above.
5.3 PAINTING: All unfinished surfaces of steel panels and frame
works shall be sand blasted to
remove rust scale, foreign adhering matter & grease. A
suitable rust resistance primer shall be applied on the interior
& exterior of steel which will be followed by
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 5
-
application of an under coat suitable to serve as base for
finishing coat. The finishing coat shall be as under: - Exterior -
Stove enameled light grey as per shade No.631 of IS: 5.
Interior - stove enameled white. Base frame - Stove enameled
glossy black. 5.4. TESTING EQUIPMENT AND TESTING FACILITIES ON THE
RELAYS:
The tenderer shall recommend suitable testing equipment
(alongwith quantity) required for field testing of protective
schemes and other relays offered against this specification. The
actual quantity to be ordered shall be determined by the Purchaser.
Also adequate testing facilities should be provided on the relay so
as to test them without the necessity of their removal or making
any extra connections. The Bidder will clearly indicate the testing
procedure to be followed in respect of relays offered.
5.5 The transmission lines shall be either in form of overhead
conductor or combination of overhead conductor & underground
cable. The tentative transmission line data in respect of 220kV,
132kV & 66 kV lines covered in this specification is given at
Annexure-C. The standard chart providing the details of per unit
values of Z1, Z2 & Z0 on 100 MVA base per 100 km of line for
calculating these values for full lengths of lines are enclosed at
Annexure-E. The tentative details of carrier equipment are enclosed
at Annexure-F. The suitability of distance scheme offered with
reference to the above parameters may be seen. Guaranteed test
sheets as per Annexure A shall be submitted by the tenderer.
Relevant literature shall be supplied along with the bid for proper
appreciation of the offered equipment.
5.6 SUPERVISORY SERVICES: The tenderer may offer supervisory
services, panel wise testing & commissioning of 220kV, 132 kV,
66 kV & 33 kV panel included in the specification. The tenderer
may quote their rates on diem basis category-wise with their terms
& conditions. The rates quoted should be valid for at least
three years form the date of receipt of equipment by us.
5.7 TRANINING OF PERSONNEL: The contractor will provide free
facilities for training the purchaser's technicians /Engineers at
his works, design office and HVPNL's site. He will intimate in
advance the schedule of completion of designs and manufacture of
equipment against the contract (of this specification) or similar
equipment to be manufactured at the works so that the purchaser may
depute upto 3 technicians & 3 engineers for training at the
manufacture assembly, testing, operation and commissioning etc.
including testing and commissioning of protective relays, covering
training in detecting faults in static relays complete explanation
of the schematic wiring and wiring schedule of the relays/scheme
together with full understanding regarding the functional modules
of the relays/scheme shall be given to the Engineer / technicians.
The topics of CTs & PTs towards relay application shall also be
kept under the scope of training. The training shall be arranged by
the contractor at the works in such a way that the persons under
training shall be freely acquainted with
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 6
-
the equipment. The engineers / technicians shall also be
provided with relay/scheme guides/instruction manuals covering
drawings of functional modules of relays/schemes. The period of
training will be not exceeding 15 days and all expenses shall be
borne by the purchaser.
5.8 GENERAL DESCRIPTION:
5.8.1. SIMPLEX C&R PANEL BOARDS: The panels shall be of
`simplex' type & consisting of separate cubicles (for each
circuit complete with side covers) made of sheet steel of
thickness not less than 10 SWG for the base frame, door frame and
front portions of the cubicles and not less than 14 SWG for door,
side, top & bottom portion having provision for extension at
both ends with internal wiring, illumination with door operated off
& on switch. The cubicle shall be suitable for floor mounting
with its bottom open. Each cubicle shall be fitted with flush
mounted steel hinged door & lock at the back & all the
equipments will be mounted in front. The supply shall include
suitable grouting bolts and nuts etc. All holes and extension
windows shall be blanked and access doors shall be provided with
compressible liners at the edges.
These simplex panels offered may, therefore, match in following
respects:- i) Height-wise and depth-wise matching. The control
& relay Panels shall be completely dust & vermin proof. The
enclosure shall provide degree of protection not less than IP-31 in
accordance with IS: 2147 and shall be suitable for tropical
use.
NOTE:- For testing purpose a small opening with a cap to close
the same is required to be provided to extend the testing leads on
front side of the relay panel.
5.9 GENERAL REQUIREMENTS OF RELAYS:
All relays shall conform to the requirements of
IS:3231/IEC-60255/IEC 61000 or other applicable standards. Relays
shall be suitable for flush or semi-flush mounting on the front
with connections from the rear. All protective relays shall be in
draw out or plug-in type modular cases with proper testing
facilities. Necessary test plugs/test handles shall be supplied
loose and shall be included in contractors scope of supply.
All main protective relays shall be numerical type and
communication protocol shall be as per IEC 61850. Further, the test
levels of EMI as indicated in IEC 61850 shall be applicable to
these.
For numerical relays, the scope shall include the following: a)
Necessary software and hardware to up/down load the data to/from
the relay
from/to personal computer installed in the substation. However,
the supply of PC is not covered under this clause.
b) The relay shall have suitable communication facility for
future connectivity to SCADA. The relay shall be capable of
supporting IEC 61850 protocol (with fibre optical port) and shall
be compatible with existing SAS (may be of other make).
c) Numerical relays should have clock (Real Time Clock) with
inbuilt battery back up having life span of about 10 years.
d) Numerical relays shall have adequate no. of output contacts
and LEDs to meet the specification / Scheme requirement. All
numerical relays shall be supplied pre-configured as per
specification / scheme requirements / approved drgs.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 7
-
5.10 TRIP CIRCUIT SUPERVISION RELAY: The relay shall be capable
of monitoring the healthiness of each trip coil and associated
circuit of circuit breaker during "on & off" conditions. The
relay shall have time delay on drop-off of min. 200 milli seconds
and shall be provided with operation indicator.
220 kV circuit breakers being procured are generally equipped
with 2 trip coils in each phase/pole of the breaker. For monitoring
of trip circuits, both in `open' & `close' position of the
circuit breaker, 6 Nos. automatic trip circuit supervision relays
(one for each pole and each trip coil) are proposed. For monitoring
of entire trip circuit (from control & relay panel terminal to
the trip coil of circuit breaker) both in `open' & `close'
position of the circuit, 2 No. automatic trip circuit supervision
relays are proposed for 132kV,66kV & 33kV panels except 1No.
Automatic trip circuit supervision relay is proposed for 33kV Line
& Capacitor Panels.
5.11 D.C. FAIL ALARM RELAY: A suitable relay for monitoring the
Trip Circuit D.C. wiring of the control and relay panels shall be
provided. The relay shall have time delay on drop-off of min. 100
milli seconds and shall be provided with operation indicator.
5.12 VOLTAGE SELECTION SCHEME: The 220kV, 132kV, 66kV & 33kV
bus PTs exist on all the phases of both the
220kV, 132kV, 66kV & 33kV buses at substations having double
bus arrangement. Proper voltage selection scheme shall be provided
on panels.
5.13 AUTO RECLOSING SCHEME: 5.13.1The protective scheme shall
incorporate the necessary equipment to impart
auto-reclosing impulse to the circuit breaker when it has
tripped either due to the operation of the line protection scheme
in the first zone or the accelerated operation of it with the help
of carrier equipment. No auto-reclosing impulse shall be
transmitted in the event of a fault cleared by the 2nd, 3rd &
4th zone of line protection scheme. Auto-reclosing will also be
blocked in case the circuit breaker is tripped manually.
5.13.2The provision of single & three phase auto-reclosing
is to be made on 220 kV
feeder C&R panels. 5.13.3 CHECK SYNCHRONIZING & DEAD
LINE CHARGING SCHEME : Check synchronizing relay and dead line
charging equipment shall be provided for
220 kV feeder C&R panels. The check synchronizing relay
shall compare the phase angle & frequency of the `incoming' and
`running' supplies and allow the auto-reclose to take place only if
the said parameters are within the permissible limits. The dead
line charging equipment shall ensure auto-reclosing a circuit
breaker on to a `dead' line leaving the checking of synchronism of
two supplies to the other end of it.
Synchronizing check relay with necessary auxiliary equipments
shall be provided which shall permit breakers to close after
checking the requirements of synchronizing of incoming and running
supply. The phase angle setting shall not exceed 35 degree and have
voltage difference setting not exceeding 10%. This relay shall have
a response time of less than 200 milliseconds when the two
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 8
-
system conditions are met within preset limits and with the
timer disconnected. The relay shall have a continuously adjustable
time setting range of 0.5-3secs.
5.13.4 A four position stay-put non-locking type of auto-reclose
selector-switch shall be provided on each of the 220 kV feeder
C&R panels and shall have the following four positions:
a) `Single phase auto: In this position, the relay shall allow
single shot single pole auto reclosing for single line to ground
fault. For any other fault, the scheme shall allow all the three
poles of the circuit breaker to trip & lock them out.
b) `Single & three phase auto: In this position the relay
shall allow single shot single pole auto-reclosing for single line
to ground fault and three pole auto-reclosing for other faults such
as line to line, double line to ground and three phase faults.
c) `Three phase auto' : In this position, the relay shall impart
three pole, single shot-reclosing impulse irrespective of the type
of fault.
d) `Non - auto' : By putting the switch in this position it
shall be possible to make the reclosing scheme totally inactive and
all the three poles of the circuit breaker shall trip irrespective
of the nature of a fault.
5.13.5 The reclosing scheme shall automatically reset after any
successful reclosure and shall lock out in case the circuit breaker
trips immediately after reclosure. Also the (reclosing) scheme
shall not initiate reclosing upon an unsuccessful attempt to
manually close circuit breaker.
5.13.6 There shall be clear target indications for successful
& un-successful operation. 5.13.7 The auto-reclosing scheme
shall have continuously variable dead time setting
range of 0.1-2secs for single phase reclosing as well as for
three phase reclosing. The scheme shall have continuously variable
reclaim time setting range of 5-300secs.
Note:- The auto reclosing scheme in built with numerical
distance protection relays is acceptable provided it is available
in both Main -I and Main-II distance protection schemes and meets
the above specification.
5.14 PROTECTION SCHEME:
Note:- The Protection Scheme shall be suitable for 5A current
(instead of 1A) in case of 33kV Level.
5.14.1 PROTECTION SCHEME FOR POWER TRANSFORMERS. A) TRANSFORMER
DIFFERENTIAL PROTECTION :
The relay shall i) Be triple pole numerical type. ii) Have 3
instantaneous high set over-current units. iii) Have second
harmonic restraint or other inrush proof feature and be stable
under normal over fluxing condition.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 9
-
iv) Have fifth harmonic by pass filter or similar other
arrangement to prevent mal-operation of the relay under operating
conditions.
v) Be suitable for rated current of 1A and include necessary
ICTs for ratio & phase angle correction.
vi) Have operating current setting sufficiently low (15% or
less) so as to cover practically the whole of the transformer
against all types of faults.
vii) Have adjustable bias setting range of 20- 50%. viii) Have
maximum operating time of 30milli seconds at 5 times the rated
current. ix) Be provided with necessary terminals & links to
measure current in
restraining circuits & in the operating circuits of all the
phases under load without making any wiring changes.
x) Cover the lightning arrestors (proposed to be provided very
close to the transformer) in the zone of protection.
xi) The Scheme shall have in-built features of disturbance
recorder and event logger. For disturbance recorder and event
logger features, it shall have 8 analog and 16 digital channels
(out of which at least 8 shall be external digital inputs). It
shall have its own time generator and the clock of the time
generator shall be such that the drift is limited to +0.5
seconds/day, if allowed to run without synchronization. Further, it
shall have facility to synchronize its time generator from Time
Synchronization Equipment having output of following types.
Voltage signal: (0-5V continuously settable, with 50m Sec.
minimum pulse duration)
Potential free contact (Minimum pulse duration of 50 m Sec.)
IRIG-B RS232C
The recorder shall give alarm in case of absence of
synchronizing pulse within specified time.
a) The disturbance recorder shall meet the following
requirements: The frequency response shall be 5 Hz on lower side
and 250 Hz or better
on upper side. Scan rate shall be 1000 Hz/Channel or better.
Prefault time shall not be less than 100 milliseconds and the post
fault
time shall not be less than 2 seconds (adjustable). If another
system disturbance occurs during one post-fault run time, the
recorder shall also be able to record the same. However, the total
memory of acquisition unit shall not be less than 5.0 seconds.
b) The event logger shall meet the following requirements: The
time resolution shall be 1milli second. Cope with up to 40 changes
in any one 10milli seconds interval. The date and time should be
printed to the nearest 1milli second followed
by a message describing the point which has operated. Events
occurring whilst a previous event is in process of being printed
are
to be stored to await printing. Xii) Display resolution of
differential/pickup current should be 0.01A (10mA).
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 10
-
B) NON DIRECTIONAL THREE OVER CURRENT+ ONE EARTH FAULT
PROTECTION WITH HIGH SET: The 3 O/C & 1 E/F elements shall be
either independent or composite units. The relay shall be single
pole inverse definite minimum time lag having definite min. time of
3 secs. at 10 times settings. Over current relay with a setting
range of 50%-200% of 1 Amp. supplemented with high set units having
a setting range of 500% to 2000% of 1 Amp. shall be provided. Earth
fault relay with a setting range of 20%-80% of 1 Amp. supplemented
with high set units having a setting range of 200% to 800% of 1
Amp. shall be provided. The relay shall be numerical type.
C) RESTRICTED EARTH FAULT PROTECTION : It shall be single pole
type for the clearance of earth faults in the protected zone. The
relay shall be of high impedance type with a suitable setting to
cover at least 90% of the winding & shall have a setting range
of 10% to 40% of 1 Amp. or suitable voltage setting. The relay
shall be complete with tuned 50 Hz circuit & stabilizing
resistance. The tuned circuit will help reject harmonics produced
by CT saturation and thus make the relay operative for fundamental
frequency only. The stabilizing resistance may appropriately be set
to avoid mal-operation under through fault conditions. The relay
shall be numerical type.
D) 8No. auxiliary relays for various transformer trip functions
(Main Buch. Trip, OLTC Oil Temp. Trip, Winding Temperature Trip,
Oil Temp Trip, Pressure Relief Trip, Surge Relay Trip and two no.
spare) shall be provided.
E) OVER FLUXING PROTECTION: An over fluxing detecting relay for
the protection of the transformer against over-fluxing conditions
is proposed to be provided on each of the transformer C&R
panels covered by this specification. The relay shall be numerical
in design with adjustable setting so as to avoid its operation on
momentary system disturbances. The relay shall be suitable for 110
Volts. The relay shall have inverse time characteristics, matching
with transformer over-fluxing withstand capability curve. The relay
shall provide an alarm with v/f setting range of 100% to 130% of
rated values and time delay continuously settable from 0.1 to 6
seconds to draw the operator's attention about the existence of
over-fluxing conditions. The tripping time shall be governed by v/f
versus time characteristics to cause tripping of transformer
controlling circuit breaker if the over-fluxing conditions continue
to exist.
Note:- The over fluxing relay in built with the numerical
differential protection relay is acceptable provided it meets the
above specification.
F) OVER LOAD ALARM RELAY:
It is proposed to provide an over current (i.e. single phase)
relay for initiating an alarm during transformer overload condition
on the T/F C&R panels. The relay shall have CONTINUOUS VARIABLE
setting range of 50-120% of 1Amp. and shall be supplemented by a
continuously variable timer of 1 to 10 seconds. The relay shall be
arranged to sound an alarm when the transformer exceeds the setting
for a given period of time to draw the operator's attention.
Note:- The over load alarm relay in built with the numerical
differential protection relay or Over current & Earth Fault
Protection Relay is acceptable provided it meets the above
specification.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 11
-
5.14.2 PROTECTION SCHEME FOR LINES: A) MAIN- I NON-SWITCHED
DISTANCE PROTECTION [FOR 220 kV LINES]: The scheme shall:-
i) be numerical & modular in construction. Relay shall have
continuous self monitoring & diagnostic feature.
ii) have high speed non-switched distance relays for three phase
systems to clear all type of line faults within the set reach of
the relay.
iii) It should cover at least line sections completely with 20%
in hand margin. iv) Measure all type of faults without the need to
switch the measuring
elements to the faulty phase or phases. Zone switching to extend
the reach of the measuring elements is not allowed. The reach of
each zone shall be independently & individually adjustable and
shall have setting in steps of 1%. Memory circuits with defined
characteristics shall be provided in all three phases to ensure
correct operation during close-up 3 phase faults and other adverse
conditions.
v) have a max. operating time up-to trip impulse to circuit
breaker (complete protection time including applicable carrier
& trip relay time) under source to line impedance ratios (SIR)
under all possible combinations of fault with PT being used on the
line (with all filters included) at 50% of zone-1 reach :
for SIR 0.01-4:as 40 ms at nearest end & 60 ms at other end
of line. for SIR 4-15 :as 45 ms at nearest end & 65 ms at other
end of line.
(carrier transmission time is taken as 20 ms provided that any
reduction in carrier time shall be directly reflected as reduction
in maximum operating time).
vi) have stepped time-distance characteristics and shall have at
least four independently variable time graded distance protection
zones to cover two adjacent line sections out of which Zone-1, 2
& 3 should be selectable in forward direction and Zone-4 should
be selectable in reverse direction.
vii) The relay shall have mho or quadrilateral or other suitably
shaped characteristics for zone-1, 2, 3 & 4. The relay shall
have an adjustable characteristics angle setting range of 30 - 85
degree or shall have independent resistance(R) & reactance(X)
setting..
viii) ensure that this long coverage is consistent with
limitations imposed by heavy loading and sound phase component of
fault current. If the characteristics of starting relays are such
that it cannot pick-up because of very low in-feed, under-voltage
relays may also be used as supplementary relays.
ix) have two independent continuously variable time setting
range of 0-3 seconds for zone-2 and 0-5 seconds for zone-3 &
4.
x) have a maximum resetting time of less than 35milli-seconds.
xi) have facilities for offset features with adjustable 10-20% of
Zone-3 setting. xii) have residual compensation variable from
30-150%. xiii) operate instantaneously when circuit breaker is
closed to zero-volt 3 phase
fault. xiv) be suitable for single & three phase tripping.
xv) have a continuous current rating of two times of rated current.
The voltage
circuit shall be capable of operation at 1.2 times rated
voltage. The relay shall also be capable of carrying a high short
time current of 80 times rated current without damage for a period
of 1 sec.
xvi) be selective between internal and external faults.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 12
-
xvii) have adequate contacts to meet the complete scheme
requirements & if required incorporate three separate high
speed self reset trip relays for single phase faults and a fourth
high speed trip relay for multi-phase faults.
xviii) have suitable number of potential free contacts.
Multiplication relays, if required, shall be provided for Carrier
aided features, Auto reclosing, Event Logger, Disturbance recorder
& Data acquisition system.
xix) include power swing blocking protection which shall a1) be
of triple pole type a2) have suitable setting range to encircle the
distance protection described
above. a3) have a continuously adjustable time delay on pick up
of setting range
0-2seconds. a4) block tripping during power swing conditions.
a5) be of numerical type xx) include fuse failure protection which
shall a1) monitor all the three fuses of PTs/CVTs and associated
cable against open
circuit. a2) inhibit trip circuits on operation and initiate
annunciation. a3) remain inoperative for system earth faults. a4)
be of numerical type.
xxi) be wired for carrier inter-tripping (PUR/POR) & carrier
blocking features selectable at site. xxii) be suitable for 1 Amp.
rated CT secondary, 110V (phase to phase ) VT
supply and 220 V DC supply. Mode of conversation of DC supply
from 220 V DC to the voltage level required for their scheme may be
mentioned in detail. Requirement of CTs & VTs for the
satisfactory working of the scheme may also be indicated in the
tender.
xxiii) The relay shall be suitable for series compensated line
and must have a current reversal guard feature.
xxiv) The Scheme shall have in-built features of broken
conductor detection, distance to fault locator, disturbance
recorder and event logger. For disturbance recorder and event
logger features, it shall have 8 analog and 32 digital channels
(out of which at least 16 shall be external digital inputs). It
shall have its own time generator and the clock of the time
generator shall be such that the drift is limited to +0.5
seconds/day, if allowed to run without synchronization. Further, it
shall have facility to synchronize its time generator from Time
Synchronization Equipment having output of following types.
Voltage signal: (0-5V continuously settable, with 50m Sec.
minimum pulse duration)
Potential free contact (Minimum pulse duration of 50 m Sec.)
IRIG-B RS232C
The recorder shall give alarm in case of absence of
synchronizing pulse within specified time.
a) The disturbance recorder shall meet the following
requirements: The frequency response shall be 5 Hz on lower side
and 250 Hz or better
on upper side. Scan rate shall be 1000 Hz/Channel or better.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 13
-
Prefault time shall not be less than 100 milliseconds and the
post fault time shall not be less than 2 seconds (adjustable). If
another system disturbance occurs during one post-fault run time,
the recorder shall also be able to record the same. However, the
total memory of acquisition unit shall not be less than 5.0
seconds.
b) The event logger shall meet the following requirements: The
time resolution shall be 1 milli second. Cope with up to 40 changes
in any one 10 milli seconds interval. The date and time should be
printed to the nearest 1 milli second followed
by a message describing the point which has operated. Events
occurring whilst a previous event is in process of being printed
are
to be stored to await printing. Over 100 such events must be
stored. c) The distance to fault locator shall meet the following
requirements:
Be On-Line type and suitable for breaker operating time of 2
cycles. The display shall be directly in percent of line length or
kilometers without
requiring any further calculations. Shall have an accuracy of 3%
or better for the typical conditions defined for
operating timings measurement of distance relays. The above
accuracy should not be impaired by presence of remote end infeed,
predominant D.C. component in fault current, high fault arc
resistance, severe CVT transients.
Shall have parallel line mutual zero sequence compensation
feature.
B) MAIN -II NON-SWITCHED DISTANCE PROTECTION [FOR 220 kV LINES]
:
For Main-II distance protection, scheme shall be numerical and
shall have same features as that of Main-I protection against sub
para 5.14.2 (A) above but with different measuring technique.
C) NON-SWITCHED DISTANCE PROTECTION SCHEME [FOR 132kV & 66kV
LINES]:
The main protection scheme for these lines will be distance
scheme working on definite distance measuring principle both for
phase & earth faults. The scheme shall:- i) be numerical &
modular in construction. Relay shall have continuous self
monitoring & diagnostic feature. ii) have high speed
non-switched distance relays for three phase systems
to clear all type of line faults within the set reach of the
relay. iii) It should cover at least line sections completely with
20% in hand margin.
iv) measure all type of faults without the need to switch the
measuring elements to the faulty phase or phases. Zone switching to
extend the reach of the measuring elements is not allowed. The
reach of each zone shall be independently & individually
adjustable and shall have setting in steps of 1%. Memory circuits
with defined characteristics shall be provided in all three phases
to ensure correct operation during close-up 3 phase faults and
other adverse conditions.
v) have a max. operating time up-to trip impulse to circuit
breaker (complete protection time including trip relay time) under
source to line impedance ratios (SIR) :0.01-4 as 50ms under all
possible combinations of fault at 50% of zone-1 reach.
vi) have stepped time-distance characteristics and shall have at
least four independently variable time graded distance protection
zones to cover two
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 14
-
adjacent line sections out of which Zone-1, 2 & 3 should be
selectable in forward direction and Zone-4 should be selectable in
reverse direction.
vii) The relay shall have mho or quadrilateral or other suitably
shaped characteristics for zone-1, 2, 3 & 4. The relay shall
have an adjustable characteristics angle setting range of 30 - 85
degree or shall have independent resistance(R) & reactance(X)
setting.
viii) ensure that this long coverage is consistent with
limitations imposed by heavy loading and sound phase component of
fault current. If the characteristics of starting relays are such
that it cannot pick-up because of very low in-feed, under-voltage
relays may also be used as supplementary relays.
ix) have two independent continuously variable time setting
range of 0-3 seconds for zone-2 and 0-5 seconds for zone-3 &
4.
x) have a maximum resetting time of less than 55milli-seconds
(including the resetting time of trip relays).
xi) have facilities for offset features with adjustable 10-20%
of Zone-3 setting. xii) For correct measurement of earth faults
necessary equipment for residual
compensation shall be included. It shall have residual
compensation variable from 30-150%.
xiii) operate instantaneously when circuit breaker is closed to
zero-volt 3 phase fault.
xiv) be suitable for three phase tripping. xv) have a continuous
current rating of two times of rated current. The voltage
circuit shall be capable of operation at 1.2 times rated
voltage. The relay shall also be capable of carrying a high short
time current of 80 times rated current without damage for a period
of 1 sec.
xvi) have adequate contacts to meet the complete scheme
requirements & if required incorporate separate high speed self
reset trip relays.
xvii) have suitable number of potential free contacts.
Multiplication relays, if required, shall be provided for Event
Logger, Disturbance recorder & Data acquisition system.
xviii) include power swing blocking protection which shall
a1) be of triple pole type a2) have suitable setting range to
encircle the distance protection described
above. a3) have a continuously adjustable time delay on pick up
of setting range
0-2seconds. a4) block tripping during power swing conditions.
a5) be of numerical type
xix) include fuse failure protection which shall a1) monitor all
the three fuses of PTs/CVTs and associated cable against
open circuit. a2) inhibit trip circuits on operation and
initiate annunciation. a3) remain inoperative for system earth
faults. a4) be of numerical type.
xx) be suitable for 1 Amp. rated CT secondary, 110V (phase to
phase ) VT supply and 220 V DC supply. Mode of conversation of DC
supply from 220 V DC to the voltage level required for their scheme
may be mentioned in
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 15
-
detail. Requirement of CTs & VTs for the satisfactory
working of the scheme may also be indicated in the tender.
xxi) The Scheme shall have in-built features of broken conductor
detection, distance to fault locator, disturbance recorder and
event logger.
D) THREE OVER CURRENT+ ONE EARTH FAULT PROTECTION:
The 3 O/C & 1 E/F elements shall be either independent or
composite units. It shall include VT fuse failure relays for alarm
purposes.
DIRECTIONAL OVER CURRENT RELAY : The relay shall
i) have IDMTL characteristic with a definite minimum time of 3.0
seconds at 10 times setting.
ii) have a variable setting range of 50-200% of 1 Amp. iii) have
a characteristic angle of 45 degree lead. iv) include operatio
indicator. v) be suitable for 110V VT secondary. vi) be numerical
type.
DIRECTIONAL EARTH FAULT RELAY: The relay shall
i) be numerical type. ii) have IDMTL characteristic with a
definite minimum time of 3.0 seconds at
10 times setting. iii) have a variable setting range of 20-80%
of 1 Amp. iv) have a characteristic angle of 45 degree lag. v)
include operation indicator. vi) be suitable for connection across
open delta formed by 110/3 volt rated
secondary of VT.
E) FEEDER OVER LOAD ALARM RELAY:
It is proposed to provide a single pole over current relay for
the purpose of monitoring the load flow on feeders to sound an
alarm whenever load flow in the line exceeds the setting for a
given period of time to draw the operator's attention. The relay
shall have CONTINUOUS VARIABLE setting range of 50-200% of 1 Amp.
and shall be supplemented by a continuously variable timer of 1 to
10 seconds.
Note:- The Feeder over Load Alarm Relay in-built with numerical
distance
protection relay or Over current & Earth Fault Protection
Relay is acceptable provided it meets the above specification.
5.14.3 PROTECTION SCHEME FOR BUS COUPLER:
NON DIRECTIONAL THREE OVER CURRENT + ONE EARTH FAULT PROTECTION
WITH HIGH SET:
The 3 O/C & 1 E/F elements shall be either independent or
composite units. The relay shall be single pole inverse definite
minimum time lag having definite min. time of 3secs. at 10 times
settings. Over current relay with a setting range of 50%-200% of
1Amp. supplemented with high set units having a setting range of
500% to 2000% of 1Amp. shall be provided.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 16
-
Earth fault relay with a setting range of 20%-80% of 1Amp.
supplemented with high set units having a setting range of 200% to
800% of 1Amp. shall be provided. The relay shall be numerical
type.
5.14.4 BUS BAR PROTECTION SCHEME: One bus bar protection scheme
shall be provided for each main bus for 220kV having double bus
arrangement. Bus bar protection scheme shall:-
i. be of numerical, low impedance type and modular in
construction. The scheme shall be complete in all respects to cater
the need of at-least 14 feeders/ bays.
ii. have maximum operating time up-to trip impulse to trip relay
for all types of faults of 15milli seconds at 5 times setting
value.
iii. operate selectively for each bus bar. iv. give hundred
percent security up-to 40 kA fault level. v. incorporate check
feature. vi. incorporate continuous supervision for CT secondaries
against any possible
open circuit and if it occurs, shall tender the relevant zone of
protection inoperative and initiate an alarm.
vii. not give false operation during normal load flow in bus
bars. viii. incorporate clear zone indication. ix. be of phase
segregated, triple pole type and provide independent zones of
protection for each bus. x. include necessary auxiliary relays
for each circuit as required for the
scheme. xi. shall be biased differential type and shall have
operate and restraint
characteristics. xii. be transient free in operation. xiii
include continuous DC supply supervision for alarm and trip
circuits
separately and provide separately non-trip alarm for B/B
protection alarm circuit DC fail & B/B protection trip circuit
DC fail conditions.
xiv. shall include necessary multi-tap auxiliary CTs for each
bay. xv. include protection 'in/out' switch for each zone. xvi.
include necessary CT switching relays. Also provide indication to
monitor
`Operate' status of the CT switching relays with a common push
button and shall have CT selection incomplete alarm with adequate
time delay when proper CT switching has not taken place. CT
switching relay should have adequate contacts for selection of trip
bus instead of direct isolator contact.
xvii. bus bar protection scheme should cover the blind zone on
account of single CT on B/C circuit.
xviii. Include high speed tripping relays for each bay. xix The
Scheme shall have in-built features of disturbance recorder and
event
logger. The disturbance recorder should record the disturbance
data bay-wise (all bays phase and neutral current).
5.14.4.1 LOCAL BREAKER BACK UP PROTECTION SCHEME:
The relay shall be provided to take care of stuck breaker
conditions. The local breaker back up protection scheme will under
such conditions, immediately after the operation of primary / back
up protection, transmit the tripping impulse to all the circuit
breakers connected to that bus zone of which the circuit breaker
forms part. The scheme shall be supplemented
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 17
-
with a timer suitable for station DC supply and continuously
adjustable setting of .05 to .5 sec. on pick up.
The relay shall : i) be triple pole type with a setting range of
20% -80% of rated current. ii) have operating time of not more than
15 m-sec.
iii) have a resetting time of not more than 15 m-sec. iv) be of
numerical type.
v) have a continuous thermal with stand of two times rated
current irrespective of setting.
Note:- The LBB protection scheme in built with numerical bus bar
protection scheme is acceptable provided it meets the above
specification.
5.14.5 PROTECTION SCHEME FOR CAPACITOR C&R PANELS: A) NON
DIRECTIONAL THREE OVER CURRENT+ ONE EARTH FAULT
PROTECTION WITH HIGH SET: The 3 O/C & 1 E/F elements shall
be either independent or composite units. The relay shall be single
pole inverse definite minimum time lag having definite min. time of
3 secs. at 10 times settings. Over current relay with a setting
range of 50%-200% of 1 Amp. supplemented with high set units having
a setting range of 500% to 2000% of 1 Amp. shall be provided. Earth
fault relay with a setting range of 20%-80% of 1 Amp. supplemented
with high set units having a setting range of 200% to 800% of 1
Amp. shall be provided. The relay shall be numerical type.
B) TIME DELAY RELAY:- A time delay relay must be included with
adjustable setting range of 0-5 minutes to provide a time lag
before which the bank shall not be again switched on (to avoid
closing of the circuit breaker on a trapped charge).
C) UNDER VOLTAGE PROTECTION :- One inverse time under voltage
relay having setting range of 50% to 90% of 110/3 volt
(Phase-to-neutral) shall be provided to disconnect the capacitor
bank under low voltage conditions.
D) OVER VOLTAGE PROTECTION :- One inverse time over voltage
relay suitable for operation with 110/3 volt AC supply (Phase to
neutral) with setting range of 100% to 130% shall be provided.
E) UNBALANCE PROTECTION :- The unbalance protection shall be
provided through current unbalance relay connected to the NCT in
neutral of capacitor bank connected in double star. Two such
relays, one each for alarm & trip are required. The setting of
the relay shall be 10% to 40% of the CT secondary (i.e. 1A for 132
kV& 66kV voltage levels and 5A for 33 kV voltage levels)
followed by a time delay through a timer of 0.1 sec. for transient
free operation of the protection. The relays shall be numerical
type. The relay should not operate for healthy state spill current
in neutral. Number of units of failure on which alarm shall come
and tripping is initiated, be clearly mentioned for proper setting
of the relays.
Note:- The under voltage Relay and over voltage relay in-built
with numerical unbalance protection relay is acceptable provided it
meets the above specification.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 18
-
5.15 TRIPPING RELAY: High speed tripping relay shall
i) be instantaneous ( operating time not to exceed 10
milli-seconds.) ii) reset within 20 milli-seconds. iii) Be 220 Volt
DC operated. iv) Have adequate contacts to meet the scheme
requirement v) Be provided with operation indicators for each
element/coil.
5.16 RELAY SETTINGS : The successful bidder will be responsible
for calculating the relay setting of the protection schemes
included in the bid and obtain HVPN's M&P wing clearance before
their adoption. Any data\ information in regard to the power system
required by the supplier for this purpose shall be supplied by
HVPN.
5.17 TIME SYNCHRONISATION EQUIPMENT: i) The Time synchronisation
equipment shall receive the co-coordinated
Universal Time (UTC) transmitted through Geo Positioning
Satellite System (GPS) and synchronize equipments to the Indian
Standard Time in a substation.
ii) Time synchronisation equipment shall include antenna, all
special cables and processing equipment etc.
iii) It shall be compatible for synchronisation of Event
Loggers, Disturbance recorders and SCADA at a substation through
individual port or through Ethernet realized through optic fibre
bus.
iv) The synchronisation equipment shall have 2 micro second
accuracy. Equipment shall give real time corresponding to IST
(taking into consideration all factors like voltage &
temperature variations, propagation & processing delays
etc).
v) Equipment shall meet the requirement of IEC 60255 for storage
& operation.
vi) The system shall be able to track the satellites to ensure
no interruption of Synchronisation signal.
vii) The output signal from each port shall be programmable at
site for either one hour, half hour, minute or second pulse, as per
requirement.
viii) The equipment offered shall have six (6) output ports.
Various combinations of output ports shall be selected by the
customer, during detailed engineering, from the following:
Voltage signal : Normally 0-5V with 50milli Seconds minimum
pulse duration. In case any other voltage signal required, it shall
be decided during detailed engineering.
Potential free contact (Minimum pulse duration of 50milli
Seconds.) IRIG-B RS232C
ix) The equipment shall have a periodic time correction facility
of one second periodicity.
x) Time synchronisation equipment shall be suitable to operate
from 220V DC as available at Substation.
xi) Equipment shall have real time digital display in hour,
minute, second (24 hour mode) & have a separate time display
unit to be mounted on the top of control panels having display size
of approx. 100 mm height.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 19
-
5.18. SMALL WIRING : a) All wiring shall be of switch board type
consisting of stranded /single
annealed copper conductor insulated with polyvinyl chloride
insulation suitable for 650 volts service and in accordance with IS
: 694.
b) The wiring of the following circuits shall not be less than
the size specified below:
CTs, PTs & CVTs circuits : 2.5 mm2 Control, alarm &
supervision circuits etc. : 1.5 mm2 c) All wires will be continuous
from one terminal to the other and also will have
no tee - junction en-route. The connections shall be securely
made with the help of connecting lugs to ensure non-oxidation of
the bare copper conductor. At the terminal connections, washers
shall be interposed between stud type terminals and holding nuts.
All holding nuts shall be secured by locking nuts. The connection
studs shall project at least 6 mm from the lock nut surface.
d) Bus wires shall be fully insulated and run separately. MCBs
shall be provided to enable all the circuits in a panel to be
isolated from the bus wire. Wherever practicable, all circuits in
which the voltage exceeds 125 volts shall be kept physically
separated from the remaining wiring. The function of each circuit
shall be marked on the associated terminal boards.
e) All wiring diagrams for the control and relay boards shall be
drawn as viewed from the back of the cubicle and shall be in
accordance with IS:375 or equivalent IEC. Multi core cable tails
shall be so bound to its cable that each wire may be traced without
difficulty.
f) All potential bus wiring, non-trip and trip alarm bus wiring,
AC & DC control supply, panel lighting bus wires and such other
wiring which runs from panel to panel within a C&R panel board
shall be laid out in gutters and shall be suitably screened. In
case of `simplex' type C&R boards these common wires will run
through bus wire holes.
5.19. TERMINAL BOARDS, TEST BLOCKS & SPARE CONTACTS: a)
Terminal block connectors built from cells of moulded dielectric
and brass
stud inserts shall be provided for terminating the outgoing ends
of the panel wiring and the corresponding tail ends of control
cables. Insulating barriers shall be provided between adjacent
connections. The height of the barriers and the spacing between
terminals shall be such as to give adequate protection while
allowing easy access to terminals. Provision shall be made on each
pillar for holding 10% extra connectors.
b) The terminal blocks shall be suitable for 650 Volts service
and for connection with both copper and aluminum wires.
c) Terminal boards shall be mounted in such a manner as to
afford easy access to terminations and to enable ferrule numbers to
be read without difficulty. Wire ends shall be so connected at the
terminals that no wire terminal gets marked due to succeeding
connections. Terminal board rows shall be adequately spaced and
shall not be less than 100 mm apart so as to permit convenient
access to wires and terminations. Labels in the form of engraved
plastic plates shall be provided on the fixed portion of terminal
boards. No live metal parts shall be exposed at the back of
terminal boards.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 20
-
d) Switch board type back connected test block with contacts
shall be provided with links or other devices for shorting
terminals of CT leads before interrupting the normal circuit for
injection from an external source or for inserting testing
instruments in the circuit without causing open circuit of the CT.
The potential testing studs shall preferably be housed in narrow
recesses of the block, wherever required, shall be placed as close
to the equipments as possible. Test blocks shall be of flush
mounting pattern and the number of test blocks being provided on
each control and relay panel shall be stated in the tender.
e) The purpose of all the relays (including the auxiliary
relays) switches, lamps & push buttons etc. is required to be
indicated just below the respective equipment through engraving or
painting.
f) Spare contacts of relays are required to be brought on T.B's
and shall be indicated on the drawings.
5.20. BUS WIRES: The VT, DC, AC, trip alarm , non-trip alarm
& DC fail etc. inter panel bus wire
terminals shall be brought on Bus T.B's as well as on T.B's so
that any panel specified herein can be used separately at the
Substation specified in this specification. The said bus wires for
the panels specified in case of existing substations shall be
matched with the bus wires of the C&R panels already available
at site, the drawing for matching purposes for which shall be
supplied to the successful bidder. The bus wire terminals shall be
indicated on the panel schematic drawings as well. The bus wire
diagram shall also be supplied alongwith the schematic drawings for
each panel.
5.21. FERRULES : Wire No. shall be indicated on panel schematic
and wiring diagrams and
accordingly engraved ferrules with the same numbers and letters
as indicated in the said diagrams shall be provided on the terminal
ends of all wires for easy identification of circuits for
inspection and maintenance. Ferrules shall be of strong &
flexible insulating material with glossy finish to prevent
adhesion. These shall be engraved and marked clearly and shall not
be affected by dampness. Ferrule numbering shall be in accordance
with IS: 375. The same ferrule number shall not be used on wires in
different circuits on a panel. At those points of interconnection
between the wiring carried for equipments of different suppliers
where a change of number cannot be avoided double ferrules shall be
provided on each wire with the appropriate connection diagram of
the equipment.
5.22. SPACE HEATERS: Tubular space heaters suitable for
connection to the single phase 220 Volts AC
supply complete with switches located at convenient positions
shall be provided at the bottom of each control and relay panel to
prevent condensation of moisture. The watt loss per unit surface of
heater shall be low enough to keep surface temperature well below
visible heat.
5.23. ILLUMINATION:
The C&R panel shall be provided with 220/240 Volts AC
interior lighting. The lamp shall be free from hand shadows. A door
operated button switch shall be provided in each simplex panel.
Each simplex panel shall be provided with one no. illumination lamp
with door switch.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 21
-
5.24 POWER SOCKET : Single phase 240 volt AC, 5-Pin, 5/15A power
socket with power on/off switch shall be provided in each simplex
panel.
5.25 SAFETY EARTHING: Earthing of current free metallic parts or
metallic bodies of the equipment mounted
on the switch boards shall be done with bare copper conductor.
Copper bus of size 25 mm x 6 mm extending through entire length of
a control and relay board shall be provided. The earthing conductor
shall be connected by Rose Courtney terminals and clamp
junctions.
The neutral point of star connected secondary windings of
instrument transformers and one corner of the open delta connected
LV side of potential transformer, if used shall be similarly
earthed with the main earth bar of the switch board earthing
system. Multiple earthing of any instrument transformer shall be
avoided. An electrostatic discharge point shall be provided in each
panel connected to earth bus via 1 Mega Ohm resistor.
5.26 NAME PLATE: An easily accessible engraved or painted panel
name plate shall be provided
inside each panel. It must include G.A. drawing No., purchase
order No., Contractor's reference No., name of S/Stn. as per
purchase order and name of circuit. In addition to this, an
engraved plate indicating the purchase order no. alongwith name of
S/Stn. is required to be affixed on the panel at appropriate height
so that it is readable while standing in front of the panel. These
are required to be indicated on the G.A. drawings also. An engraved
label indicating the purpose of all the relays & switches shall
also be provided.
5.27 PANEL DETAILS: The mountings on various 220 kV, 132kV, 66kV
& 33kV C&R panels against
various Substations specified herein shall be as under. The
bidders shall give the details of the various panel mountings in
the same serial as specified herein as under for the convenience of
checking of the same w.r.t. the provision in the specification. Any
trip relay, auxiliary relay, timers, contact multiplication relay,
ICT, IVT & test block etc. required for the completeness of the
scheme shall be added by the Bidder as per scheme requirements and
no cost addition on these accounts shall be considered at a later
date.
The following is the general criteria for the selection of the
equipments to be provided in each type of panel.
(A) LINE PROTECTION PANEL Each Line Protection panel for
transmission lines shall consist of following: Sl. No. Description
220kV 132/66kV 33kV 1. Main-1 Numerical Distance protection Scheme
1 Set 1 Set NIL 2. Main-2 Numerical Distance protection Scheme 1
Set NIL NIL 3. Directional back up Over-current and
E/F protection scheme 1Set 1 Set 1 Set(with high set)
4. Overload alarm scheme 1Set 1 Set 1set 5. 3 phase Trip Relays
2 Nos. 2 Nos. 1 Nos 6. Voltage selection scheme 1 set 1 set 1
set
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 22
-
8. Flag relays , carrier receive relays ,aux. Relays, timers etc
as per scheme Requirements Lot Lot Lot 9. Under Voltage relay for
isolator/earth Switch 2 Nos 2 Nos 2 Nos
(B) TRANSFORMER PROTECTION PANEL Each protection panel for
Transformer shall consist of the following: Sl.No. Description HV
side MV/LVside 1. Transformer Differential Protection scheme 1 Set
Nil 2. Restricted Earth fault protection scheme 1 Set 1Set@ @ Not
applicable for autotransformer 3. Non-Directional back up O/C and
E/F scheme with high set feature 1 set 1 set 4. Over Fluxing
Protection scheme 1 Set. NIL 5. Overload alarm scheme 1 Set NIL 6.
Three phase trip relays 2 nos. 2 nos. 7. Voltage selection scheme 1
set 1 set 8. Flag relays ,aux .relays, timers etc as per scheme
requirement including transformer alarms and trip functions Lot
Lot
(C) BREAKER RELAY PANEL for 220kV Voltage Level Each breaker
relay panel shall consist of the following: Sl.No. Description With
A/R With out A/R 1. LBB Protection Scheme 1 set 1 set 2. DC supply
Supervision scheme 1 set 1 set 3. Trip Circuit supervision relays 6
Nos. 6 Nos. 4. Autoreclose scheme with check synchronising and dead
line charging scheme 1 set NIL 5. Flag relays, aux relays, timers,
trip relays as per scheme requirements Lot Lot
(D) BREAKER RELAY PANEL for 132kV, 66kV and 33kV Voltage Levels
Each breaker relay panel shall consist of the following: Sl.No.
Description With out A/R 1. DC supply Supervision scheme 1 set 2.
Trip Circuit supervision relays# 2 Nos.
# Trip supervision relays shall be 1No. for each 33KV Line and
Capacitor Circuit breakers.
3. Flag relays, aux relays, timers, trip relays as per scheme
requirements Lot
4. Special Energy Meter(Main) as per Interutility 1 No.*
Metering System Specification No.
HPD/S-59R/HPM-461/Vol-II/Prot (July, 2010) * applicable only for
33kV T/F I/C Panels
(E) BUS COUPLER PROTECTION PANEL Each bus coupler Protection
panel shall consist of following: Sl. No. Description 220kV
132/66/33kV 1. Non-Directional Overcurrent and E/F protection
scheme with Highset 1Set 1 Set
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 23
-
2. 3 phase Trip Relays 2 Nos. 1 Nos. 3. Flag relays , aux.Relays
timers etc as per scheme Requirements Lot Lot (F) BUS BAR
PROTECTION PANEL The bus bar Protection panel shall consist of
following: Sl. No. Description 220kV 1. Complete bus bar protection
scheme as Per clause 5.14.4 above 1Set (G) CAPACITOR PROTECTION
PANEL Each capacitor Protection panel shall consist of following:
Sl. No. Description 33kV 1. Neutral Unbalance protection Scheme 2
Set 2. Over Voltage Protection Scheme 1 Set 3. Under Voltage
Protection Scheme 1 Set 4. Non Directional Overcurrent and E/F
protection scheme with high set 1 Set 5. Time Delay relay 1 Set
6. 3 phase Trip Relays 1 Nos 7. Voltage selection scheme 1 set 8.
Flag relays, aux. Relays, timers etc as per scheme Requirements Lot
9. Under Voltage relay for isolator/earth Switch 2 Nos Note:- The
CT secondary current is 5A for 11kV & 33kV in all panels.
6.0 TESTS :
6.1 TYPE TESTS : The equipment offered should be type tested.
Type test report of similar
equipment should not be more than seven years old, reckoned from
the date of bid opening, in respect of the following tests, carried
out in accordance with ISS-3231(1965)/equivalent IEC from Govt./
Govt. approved test house & shall be submitted along with bid:
a) Insulation tests as per IEC 60255-5 b) High frequency
disturbance test as per IEC 60255-4 (Appendix -E) -Class
III (not applicable for electromechanical relays) c) Fast
transient test as per IEC 1000-4, Level-III (not applicable for
electromechanical relays) d) Relay characteristics, performance
and accuracy test as per IEC 60255.
e) Tests for thermal and mechanical requirements as per IEC
60255-6 f) Tests for rated burden as per IEC 60255-6 g) Contact
performance test as per IEC 60255-0-20 h) Conformance tests as per
IEC 61850
The above tests shall be supplied for distance protection, over
current and earth fault protection, restricted earth fault
protection, Bus bar protection and
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 24
-
transformer differential protection as per the applicability of
the relay alongwith bid.
The remaining type test reports of above relays & all the
type test reports of remaining relays and type test reports of
meters shall be submitted by the successful bidder within three
months of placement of order. These type test reports will also be
from Govt./ Govt. approved test house & should not be more than
seven years old, reckoned from the date of placement of order. The
failure to do so will be considered as a breach of contract.
6.2 ROUTINE TESTS: 6.2.1 All equipment shall be subject to
routine tests according to the relevant standards
/ Quality Assurance Program (QAP) and to such other tests as may
be required to ensure that all equipment is satisfactory and in
accordance with this specification. The Purchaser reserves the
right to witness all the tests, unless dispensed with in writing by
the Purchaser.
6.3 ACCEPTANCE TESTS: 6.3.1 The Supplier shall give sufficient
advance intimation (at least 15 days notice for
Indian Supplier and 30 days notice for Foreign Supplier) to the
Purchaser to enable him to depute his representative for witnessing
the tests. Following tests shall be carried out at the
manufacturer's works after complete assembly:-
i) Checking wiring of circuits and their continuity. ii) One
minute high voltage test. iii) Insulation resistance of complete
wiring, circuit by circuit with all equipment
mounted on the panel. iv) Checking the operation of protection
schemes. 7.0 DOCUMENTATION: 7.1 All drawings shall conform to
international standards organization (ISO) `A' series
of drawing sheet/Indian Standards Specification IS: 11065. All
drawings shall be in ink and suitable for microfilming. If drawings
are computerized than all drawings shall be nicely printed. All
dimensions and data shall be in S.I.Units.
7.2 The successful Supplier shall submit four sets of G.A. and
schematic drawings for Purchaser's approval within two weeks of the
date of placement of order. The Purchaser shall communicate his
comments/approval on the drawings to the Supplier within four weeks
of the date of receipt of above drawings. The Supplier shall, if
necessary, modify the drawings and resubmit four copies of the
modified drawings for Purchaser's approval within two weeks from
the date of Purchaser's comments. After receipt of Purchaser's
approval, the Supplier shall submit 10 prints of final drawings for
each Item/Circuit and one good quality soft copy (CD) of the
following drawings and instruction manuals :-
i) Board-wise arrangement drawing (applicable for the panel
board at a Substation having more than one panel).
ii) G.A. drawing alongwith G.A. legend and foundation details.
iii) Schematic drawings alongwith legend & internal wiring
details of main
relays like transformer differential relay, REF relay, and local
breaker back up schemes, distance protection scheme, bus-bar
protection scheme, voltage selection scheme etc.
iv) Equipment-wise & wire-wise wiring diagrams.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 25
-
Each set of drawings shall be bound separately. The final
documents shall be supplied before despatch of equipment.
7.3 The manufacturing of the equipment shall be strictly in
accordance with approved drawings and no deviation shall be
permitted without the written approval of the Purchaser. All
manufacturing & fabrication work in connection with the
equipment prior to the approval of the drawings shall be at the
Supplier's risk.
7.4 The Supplier shall furnish specified no. of nicely printed
and bound volumes of the instruction manuals in English language,
prior to the despatch of the equipment. The instruction manual
shall contain step by step instructions for all operational &
maintenance requirements for all the protective and aux. relays,
switches, instruments etc. mounted on the panel and shall include
the following aspects.
i) Storage for prolonged duration. ii) Unpacking. iii) Erection.
iv) Handling at site. v) Pre commissioning tests. vi) Operating
procedures. vii) Maintenance procedure. viii) Precautions to be
taken during operation & maintenance work.
ix) Catalogue numbers of all the components liable to be
replaced during the life of the panels.
x) Internal wiring diagrams of all the relays. 7.5 Ten (10)
copies of instruction manuals for each Circuit/Item shall be
supplied free
of cost before despatch of equipment. Each set of instruction
manuals shall be bound separately. One master set for all the
Circuits/Items shall be supplied with in a week of placement of
order to the Design Directorate to facilitate the checking and
approval of drawings.
7.6 Approval of drawings by Purchaser shall not relieve the
Supplier of his responsibility and liability for ensuring
correctness & correct interpretation of the latest revision of
applicable standards, rules & codes of practices. The equipment
shall conform in all respects to high standards of engineering,
design, workmanship and latest revisions of relevant standards at
the time of ordering.
NOTE:- In case the equipment offered by the Supplier does not
meet with the
requirements of technical specification, the offer of the firm
shall not be considered.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 26
-
ANNEXURE -A GUARANTED TECHNICAL PARTICULARS
CONTROL AND RELAY PANEL BOARDS FOR SUBSTATIONS WITH SUBSTATION
AUTOMATION SYSTEM
I. PANELS.
1. Dimension of the C&R panels. i) Depth ii) Overall
height
2. Dimension of supporting channel. 3. Thickness of the sheet
steel proposed
for fabrication of panels. II. SWITCH BOARD WIRING.
1. Insulation of wiring. 2. Material of wiring conductor. 3.
Size of wiring conductor for:
i) C.T. Circuits. ii) C.V.T./P.T. Circuits.
iii) D.C. supply circuits. iv) A.C. Supply Circuit. v) Other
circuits.
4. Size of earthing bar for safety earthing.
5. Type of terminals used in wiring the panel.
III. CONTROL SWITCHES FOR CIRCUIT
BREAKER & ISOLATORS. 1. Make. 2. Type. 3. Type of handle
provided. 4. Number of position . 5. Whether no. of Normally closed
&
Normally open contacts sufficient for seheme requirements? (Yes
/ No).
6. Whether spring return to neutral or stay-put type.
7. Type of lock provided. 8. Making capacity/breaking capacity
at
220 Volt DC for both inductive & non-inductive current.
9. Descriptive leaflet number submitted. IV. OVER CURRENT &
EARTH FAULT RELAY. 1. Make.
2. Type of relay. 3. Current coil rating. 4. Potential coil
rating (applicable only
in case of directional relays). 5. Tap range. 6. Range of high
set elements (wherever applicable).
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 27
-
7. VA burden. a) Highest tap. b) Lowest tap.
8. Time V/S current characteristics. 9. Trip contact rating. 10.
Descriptive leaflet No. submitted.
V. AUXILIARY RELAYS.
1. Make. 2. Type. 3. Capacity of contacts:
i) Continuously. ii) for 3 seconds.
4. Operating coil VA burden. 5. Voltage operated or current
operated. 6. No. of Normally closed & Normally open
contacts sufficient for scheme requirements (Yes / No).
7. Contacts hand or self reset type. 8. Descriptive leaflet
number submitted.
VI. TRANSFORMER DIFFERENTIAL RELAY. 1. Make. 2. Type.
3. Minimum differential current at which relay operations.
4. Range & steps of bias setting. 5. Operating time at twice
the relay
setting. 6. VA burden of the relay. 7. Descriptive leaflet No.
submitted.
VII. TRIP CIRCUIT SUPERVISION RELAY.
1. Make. 2. Type 3. Rating 4. Minimum voltage for
satisfactory
operation (% of rated voltage). 5. Monitoring of breaker trip
coil in both
close & open position provided. 6. Safety resistors provided
to limit
the current if the relay coil is short-circuited. 7. No. of
Normally closed & Normally open
contacts sufficient for seheme requirements (Yes / No).
VIII. RESTRICTED EARTH FAULT RELAY .
1. Make. 2. Type. 3. Tap range. 4. Timer setting range. 5. V A
Burden. 6. Time/Current characteristics 7. Short time rating of
relay. 8. Descriptive leaflet No. submitted.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 28
-
IX. T/F OVER FLUXING RELAY. 1. Make
2. Type. 3. Rated Voltage (V,AC) 4. Rated DC Voltage. 5.
Operating principle. 6. No. of Normally closed & Normally
open
contacts sufficient for seheme requirements (Yes / No).
7. Contacts self/hand reset. 8. Burden. 9. Setting range. i)
V/F
ii) Time for alarm. iii) Time for tripping.
10. Whether inverse time operating characteristics provided.
11. Whether different time multiplier settings provided.
12. Max. operating time of the relay at i) 1.4 times the rated
value of V/F. ii) 1.25 times the rated value of V/F.
13. Reset time. X. LOCAL BREAKER BACK UP RELAYS .
1. Make. 2. Type. 3. Setting range (% of rating)
a) Phase faults. b) Ground faults.
4. Operating time (m sec.) 5. Reset time (m sec). 6. Burden. 7.
Timer range. 8. Whether no. of Normally closed &
Normally open contacts sufficient for seheme requirements? (Yes
/ No). XI. OVER LOAD ALARM RELAY.
1. Make. 2. Type. 3. Rated Voltage. 4. Setting Ranges. 5.
Operating time. 6. Setting range continuously variable.
XII. SELECTOR SWITCHES (AUTO-
RECLOSING IN/OUT, CARRIER PROTECTION IN/OUT SWITCH,
TRIP TRANSFER SWITCH). 1. Make.
2. Type. 3. Type of handle.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 29
-
4. No. of positions. 5. No. of Normally closed & Normally
open
contacts sufficient for seheme requirements (Yes / No).
6. Making & breaking capacity of contacts.
7. Descriptive leaflet number submitted.
XIII. DISTANCE RELAYS. 1. Make. 2. Type of relay. 3. Type of
distance measuring elements. 4. Details of starting units and
their
switching sequence, if applicable. 5. Range of settings (in
secondary ohms).
for Zone-I, Zone-2 & Zone-3. 6. Operating times:
i) First zone timing. ii) Second zone time setting
adjustable between-------- secs to ------- secs.
iii) Third zone time setting adjustable between -------- secs to
------- secs.
7, Contacts rating: i) First Zone.
ii) Second Zone. iii) Third Zone.
8. VA burden : i) Current circuit of the scheme.
ii) Potential circuit of the scheme. 9 Is the VA burden at
Sr.No.8 above is
continuous ? (yes/No) 10. Operating time versus ZS/ZL curves
of the distance scheme. 11. Descriptive leaflet no.
submitted.
XIV. CHECK SYNCHRONIZING RELAY: 1. Make. 2. Type.
3. Rating ( V, ac ) 4. Aux. Voltage ( V, dc ) 5. Permissible
voltage difference (%) 6. Permissible phase angle difference
(degree) 7. Response time of relay (without timer)( m Sec )
XV. AUTO RECLOSING : 1. Make. 2. Type. 3. Multi shot or single
shot. 4. Rating (V, dc) 5. Suitable for 1 & 3 phase. 6. Dead
time setting range (Sec.) 7. Reclaim time setting range (sec.) 8.
Four position selector switch provided.
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 30
-
9. Alarm contacts provided for `Auto-reclosed', `Reclosure
unsuccessful'. XVI. BUS-BAR PROTECTION 1. Make.
2. Type. 3. Applicable standard. 4. Rated Voltage/Frequency. 5.
Operating time (maximum). 6. Resetting time (maximum). 7. Does the
offer meet the Yes/No
requirements of technical specification?
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 31
-
ANNEXURE B
TECHNICAL PARTICULARS OF CTs, PTs, CVTs & NCTs.
COREWISE DETAILS OF 245kV Transformer CTs
(300-150/.577-1-1-1-1A)
NUMBER OF CORES - 5 Core No.
Application Current Ratio (A)
Output burden(VA)
Accuracy class as per IEC 185
Formula for minimum knee-point voltage At CT Secondary
resistance at 750C at 300A tap (Volt)
Maximum Exciting Current (mA)
I.S.F./ A.L.F
1 2 3 4 5 6 7 8 1 DIFFERENTIAL
PROTECTION 300-150/ 0.577
- PS 40 (RCT+2) 30ATVk/4 -
2 REF PROTECTION 300-150/1 - PS 14 (RCT+2) 30ATVk/2 - 3 OVER
CURRENT
PROTECTION 300-150/1 25 5P - - 10
4 BUSBAR PROTECTION (FOR LOW IMPEDANCE SCHEME)
300-150/1 - PS 40 (RCT+4) 30ATVk/2 -
5 METERING 300-150/1 25 1.0 - -
-
COREWISE DETAILS OF 245kV LINE CUM BUS-COUPLER CTs
(1200-800-400/1-1-1-1-1 A)
NUMBER OF CORES 5
Core No.
Application Current Ratio (A)
Output burden (VA)
Accuracy class as per IEC 185
Formula for minimum knee point voltage At CT Secondary
resistance at 750C at 800Atap (Volt)
MaximumExciting Current (mA)
InstrumentSecurity factor
1 2 3 4 5 6 7 8 1. MAINI
DISTANCE PROTECTION
1200-800-400/1
- PS 80(RCT+9) 80AT Vk -
2. MAINII DISTANCE PROTECTION
1200-800-400/1
- PS 80(RCT+9) 80AT Vk -
3. BUS DIFFERENTIAL MAIN
1200-800-400/1
- PS 100(RCT+4) 30AT Vk/2 -
4. BUS DIFFERENTIAL CHECK
1200-800-400/1
- PS 100(RCT+4) 30AT Vk/2 -
5. METERING 1200-800-400/1
40 0.2S - - ISF
-
COREWISE DETAILS OF 245kV NEUTRAL CTs
(300-150/1A)
NUMBER OF CORE - 1
Application Current
Ratio (A) Accuracy class as per IEC 185
Formula for minimum knee-point voltage at CT Secondary
resistance at 750C at 300Atap(Volt)
Maximum Exciting Current (mA)
Minimum Insulation Voltage (kV)
1 2 3 4 5 6 REF PROTECTION
300-150/1 PS 14(RCT+2) 30AT VK/2
33
COREWISE DETAILS OF 145kV TRANSFORMER INCOMER CT
(500-250/.577-1-1-1A)
NUMBER OF CORES 4
Core No.
Application Current Ratio (A)
Output burden (VA)
Accuracy Class as per IEC 185
Formula for minimum knee-point voltage At CT Secondary
resistance at 750C at 500Atap (Volt)
Maximum Exciting Current (mA)
I.S.F./A.L.F.
1 2 3 4 5 6 7 8 1. DIFFERENTIAL
PROTECTION 500-250/
0.577 - PS 40 (RCT+2) 30AT Vk/4 -
2. REF PROTECTION
500-250/1 - PS 90 (RCT+2) 37.5AT Vk/2 -
3. OVER CURRENT ANDEARTH FAULTPROTECTION
500-250/1 25 5P - - ALF10
4. METERING 500-250/1 25 1.0 - - ISF
-
COREWISE DETAILS OF 145kV LINE/BUS COUPLER CT
(600-300-150/1-1-1A)
No. OF CORES = 3
Core No.
Application Current Ratio (A)
Output burden(VA)
Accuracy classas per IEC 185
Formula for minimum knee-point voltage At CT Secondary
resistance at 750C at 300Atap (Volt)
Maximum Exciting Current (mA)
A.L.F./I.S.F.
1 2 3 4 5 6 7 8 1 DISTANCE
PROTECTION 600-300-150/1 - PS 120 (RCT+4.5)
80AT VKP -
2 OVER-CURRENT
& EARTH FAULT PROTECTION
600-300-150/1 25 5P - - ALF 10
3 METERING 600-300-150/1 25 0.2S - - ISF
-
COREWISE DETAILS OF 72.5kV TRANSFORMER INCOMER CT
(1000-500/.577-1-1-1A)
NUMBER OF CORES - 4
Core No.
Application Current Ratio (A)
Output burden
(VA)
Accuracy class
as per IEC 185
Formula for minimum knee-point voltage At CT Secondary
resistance at 750C at 1000A tap (Volt)
Maximum Exciting Current (mA)
A.L.F./I.S.F.
1 2 3 4 5 6 7 8 1 DIFFERENTIA
L PROTECTION
1000-500/0.577 - PS 40 (RCT+2)
30AT VK/4 -
2 REF PROTECTION
1000-500/1 - PS 14 (RCT+2) 30AT VK/2
3 OVER CURRENT & EARTH FAULT PROTECTION
1000-500/1 15 5P - - ALF 10
4 METERING 1000-500/1 15 1.0 - - ISF
-
COREWISE DETAILS OF 72.5kV TRANSFORMER CT FOR 25/31.5 MVA
T/F
(300-150/.577-1-1)
No. OF CORES = 3 Core No.
Application Current Ratio (A)
Output burden(VA)
Accuracy class as per IEC 185
Formula for minimum knee-point voltage At CT Secondary
resistance at 750C at 300A tap (Volt)
MaximumExciting Current (mA)
A.L.F
1 2 3 4 5 6 7 8 1 DIFFERENTIAL
PROTECTION 300-150/0.577 - PS 40(RCT+1)
30AT VK/4 -
2 REF PROTECTION 300-150/1 - PS 20(RCT+1)
30AT VK/2 -
3 OVER CURRENT PROTECTION
300-150/1 25 5P - - 10
COREWISE DETAILS OF 72.5kV TRANSFORMER CT FOR 12.5/16 MVA &
16/20 MVA T/F
(200-150/.577-1-1A)
No. OF CORES = 3 Core No.
Application Current Ratio (A)
Output burden(VA)
Accuracy class as per IEC 185
Formula for minimum knee-point voltage At CT Secondary
resistance at 750C at 200A tap (Volt)
MaximumExciting Current (mA)
A.L.F
1 2 3 4 5 6 7 8 1 DIFFERENTIAL
PROTECTION 200-150/0.577 - PS 40(RCT+1)
30AT VK/4 -
2 REF PROTECTION 200-150/1 - PS 20(RCT+1)
30AT VK/2 -
3 OVER CURRENT PROTECTION
200-150/1 25 5P - - 10
C:\Users\ITMS4\Desktop\technical specification July11\nC&R
Panel (with automation)-MARCH,2011 (R1).doc 37
-
COREWISE DETAILS OF 72.5kV LINE/BUS COUPLER CT
(600-300-150/1-1-1A)
No. OF CORES = 3
Core No.
Application Current Ratio (A)
Output burden(VA)
Accuracy class as per IEC 185
Formula for minimum knee point voltage At CT Secondary
resistance at 750C at 300A tap (Volt)
MaximumExciting Current (mA)
A.L.F./ I.S.F.
1 2 3 4 5 6 7 8 1 DISTANCE
PROTECTION 600-300-150/1 - PS 110
(RCT+11) 80ATVKP -
2 OVER
CURRENT & EARTH FAULT PROTECTION
600-300-150/1 15 5P - - ALF 10
3 METERING 600-300-150/1 20 0.2S - - ISF
-
COREWISE DETAILS OF 72.5kV NEUTRAL CT FOR 12.5/16 MVA &
16/20 MVA T/F
(200-150/1)
No. OF CORE= 1
Core No.
Application Current Ratio (A)
Output burden(VA)
Accuracy class as per IEC 185
Formula for minimum knee point voltage At CT Secondary
resistance at 750C at 200A tap (Volt)
MaximumExciting Current (mA)
Minimum Insulation Voltage (kV)
1 2 3 4 5 6 7 8 1 REF
PROTECTION 200-150/1 - PS 20 (RCT+1)
30AT VK/2 15
COREWISE DETAILS OF 36kV TRANSFORMER INCOMER CT FOR 132/33KV
WITH 26.3KA STC
(600-400-300/.577-5-5-1)
No. OF CORES = 4
Core No.
Application Current Ratio (A)
Output burden(VA)
Accuracy class as Per IEC 185
Formula for minimum knee point voltage At CT Secondary
resistance at 750C at 300A tap (Volt)
MaximumExciting Current (ma)
A.L.F./ I.S.F.
1 2 3 4 5 6 7 8 1 DIFFER