A liquid, gas, or solid that exhibitsexplosive flammable characteristics suchas LPG, butane, gunpowder, paint storage,fuel, oil, etc.

Tyco Fire & Building Products is a leadingmanufacturer and distributor of water-based firesuppression systems and components for special hazardrisks, offering one of the broadest lines of fireprotection system equipment worldwide for SpecialHazard Systems to meet your needs.

Our complete line of standard sprinklers have afantastic record of performance, consistency, anddependability. However, many plants and buildingscontain fire hazards that standard automatic sprinklerscannot control or extinguish. These are termed"Special Hazards". In general, a special hazard is anarea, process, piece of equipment, or building that anormal sprinkler system will not effectively protect.

Generally the following “Special Hazards” fall under these criteria:

Special Hazards systems are sometimes foundwithin plants or areas that are protected bytraditional sprinkler systems. With the advent ofnew and different synthetics, sophisticated paintlines, flammable liquid handling, and criticalprocess equipment, the risk of serious fire scenarioslooms greater and greater. These circumstancesdictate the need for Special Hazards protection. Acompany should never assume that they do nothave a high hazard that requires additional specialhazards protection.

Tyco Fire & Building Products is availableworldwide under the leading brand names:CENTRAL®, GEM®, STAR™, and GRINNELL®.

Page 3: 111

3

The nature of a piece of equipment that is a hazard,or exposes nearby vital equipment, personnel, orstructures to a fire risk. Examples are coolingtowers, process pumps, transformers, mill stands,storage tanks, turbines, conveyors, etc.

NOZZLES & NOZZLE

ACCESSORIES. . . . . . . . . . . . . 6

RED-E CABINET® . . . . . . . . . 9

SINGLE INTERLOCK

PREACTION SYSTEMS . . . . . . 10

DOUBLE INTERLOCK

PREACTION SYSTEMS . . . . . . 11

DELUGE VALVE &DELUGE SYSTEMS . . . . . . . . 12

DELUGE VALVES . . . . . . . . . 13

AQUAMIST®

SYSTEMS & NOZZLES. . . . . . 14

Page 4: 111

4 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

Breadth of LineTyco Fire & Building Products (TFBP) offers more than 250 fire protectionproducts and over 1,200 items used in the fabrication of fire protectionsystems, including sprinklers, nozzles, valves, devices, CPVC pipe, fittings andhangers, and sprinkler system accessories.

Research and DevelopmentTFBP is backed by one of the largest research, design, developmentgroup and facilities in the industry. Our experienced staff ofengineers is continually working to develop new types of sprinklersand valves, as well as special hazard fire protection devices to fillpresent and future market needs. TFBP customers can contactR&D directly for technical assistance in unusual applications thatare outside our literature or existing situations.

Listings and ApprovalsProducts offered by TFBP are listed and approved by various fireprotection product approval laboratories and organizations. Generallisting and approval information for the following organizations isprovided for each product in the specification charts. Refer to the applicationTechnical Data Sheets for specific listing and approval information.

Customer ServiceServing a diverse group of specifiers, including architects, engineers,contractors, and associated industries, TFBP distributes its manufacturedproducts through TFBP locations and independent distributors that are strate-gically located to provide our customers with the quickest delivery possible oftheir complete order.

LeadershipTFBP offers the widest selection of special hazardsnozzles and valve packages. TFBP is committed tocontinuing our role as a leader in the development,manufacture, and marketing of quality fire protectionproducts.

UnderwritersLaboratories Inc.

UnderwritersLaboratories Inc.for use in Canada

UnderwritersLaboratories Inc.

of Canada

ScientificServices

Laboratory

Verband derSchadenversicherer

Factory MutualResearch

Corporation

Loss PreventionCertification Board

in association with AB & Lloyds

FM

Page 5: 111

5

Power Plants

Chemical Plants

Offshore Platforms

Aircraft Hangars

Cooling Towers

Computer Rooms

Switchgear Rooms

Transformers

Wet Benches

Ammunition Plants

Engine Test Cells

LPG Storage

Spray Paint Booths

Battery Rooms

Oil Quenching Pits

Petrochemical Storage

Records Vaults

Electronic/Telephone Rooms

Solvent Tanks and Storage

Shipboard Machinery Rooms

Flammable Liquid Storage

Hydraulic Oil, Lubricating Oil Rooms

Tank Farm/Truck Loading Facility

Page 6: 111

6 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

Nozzles & Nozzle Accessoriesare designed for use in a variety of specialhazards applications. Their uses include, butare not limited to, exposure protection, firecontrol, fire extinguishment, and explosionprevention. Many types of nozzles may berequired to provide a properly designedspecial hazard fire protection system.

D-3 Protectospray® Nozzle

• Open orifice design for use indeluge systems

• Nozzles are external deflectortypes that discharge a filled coneof water droplets at relativelylow velocity

• Spray angles available:65°, 80°, 95°, 110°, 125°, 140°,160°, and 180°

• UL, ULC, FM, LPCB, SSL

K=1.2 (17,3) • K=1.8 (25,9)

K=2.3 (33,1) • K=3.0 (43,2)

K=4.1 (59,0) • K=5.6 (80,6)

K=7.2 (108,7)

1/2" (15 mm)

Natural brass, chrome plated, electroless nickel plated, lead coated or Teflon coated. Stainless steel, plain only.

K Factor

Thread Size

Finish

Tech Data TD620A

EA-1 Automatic Protectospray® Nozzle

• Bulb type frangible element foruse in closed head systems

• Discharges a filled cone ofwater droplets at relatively lowvelocity

• Spray angles available:65°, 80°, 95°, 110°, 125°, 140°,160°, and 180°

• UL, ULC, FM, SSL

K=1.4 (20,2) • K=2.8 (40,3)

K=5.6 (80,6)

1/2" (15 mm)

Natural brass finish or chrome plated finish in 135˚F/57˚C through 500˚F/57˚C; Corroproof® or lead coated in 135˚F/57˚C and 175˚F/79˚C

K Factor

Thread Size

Finish

Tech Data TD610A

Page 7: 111

Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 7

F822 through F834 MULSIFYRE® Nozzles

• Open, internal scroll type nozzles

• Six different orifice sizes and spray angles afford a variety of designoptions

K=2.3 (33,1) • K=2.6 (37,4)

K=2.7 (38,9) • K=4.6 (66,2)

K=5.1 (73,4) •

3/4" (20 mm)

Natural Brass, Chrome Plated

K Factor

Thread Size

Finish

Tech Data TD675

• Designed to discharge a filledcone of water droplets at arelatively high velocity

• Used in either open or waterprimed systems

• A blow-off cap is available withthe nozzle for a primed system(chrome plated finish only)

• UL, ULC, FM

HV “High Velocity” Spray Nozzles

• Open, directional spray nozzles

• Designed for use in fixed water spray fireprotection systems where a high velocitywater application is needed, such as theprotection of flammable liquids, electricaltransformers, circuit breakers, oil-firedboilers and lube oil systems

K=1.6 (23,0) • K=1.8 (26,0)

K=2.9 (41,8) • K=4.3 (62,0)

K=5.5 (79,2) • K=6.0 (86,4)

1" (30 mm)

1 1/4" (38 mm) only K=6.0

Natural brass or stainless steel

K Factor

Thread Size

Finish

Tech Data TD680

• Available in six different orificesizes

• Produces a solid conical spraypattern

• Available in six angle spraypatterns

• UL, ULC, FM, SSL

• Air aspirating foam-water nozzles

• For use with all types of foam(required for Non-AFFF typefoams)

• Pendent & upright designs

• Open nozzle for use on foam-water sprinkler systems

• UL

B-1 Foam-Water Sprinkler

K=3.0 (42,2)

1/2" (15 mm)

Brass

K Factor

Thread Size

Finish

Tech Data TD760

Page 8: 111

8 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

F800 Nozzles

• Specifically designed to spray awater pattern

• Typical application: F800 Nozzlesare used to protect the tops oftransformers and may also be usedin areas such as between rollers ofmulti-tiered dryers

• Offered in a variety of orifices

• UL, FM

TI-MAX® Nozzles & Sprinklers

Contact a TFBP distributor for details

• Unique discharge devices are made fromtitanium and can be used in offshore and othermarine applications

• Designed for use where strength, low weight,and salt water corrosion resistance are required

• Medium and high velocity type nozzles areavailable in various orifice sizes and spray angles

• Standard spray sprinklers are available in uprightand pendent configurations

• Deluge valves, alarm valve, thermal valve, andshutoff valve all produced from titanium whichis 45% lighter than steel

Cooling Tower Nozzles Type 1 and 2

• Intended for use in fire protectionsystems for cross flow coolingtowers with combustible fill sections

• Open nozzle design for use in waterspray deluge system

• Installed under the distributionbasin, they discharge water in arelatively narrow, elongated spraypattern

• Type 1 has a waterway designed foruse in towers with diffusion decks,Type 2 for those without diffusiondecks

• UL, FM

K=2.9 (41,8)

3/4" (20 mm)

K Factor

Thread Size

Tech Data TD730

K=1.8 (26,0)

K=2.6 (37,4)

K=4.1 (59,0)

1/2" (15 mm)

K Factor

Thread Size

Tech Data TD750

Page 9: 111

Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 9

RED-E CABINET® Integrated Fire Protection Packages

Tech Data TD1110

• Complete riser assembly enclosedwithin a free-standing cabinet

• Package is preassembled with alltrim installed and electric switchesprewired, making the connectionsfor power, local, remote alarms, andother external electrical functionsthe only electrical connectionsneeded to complete the installation

• Cabinet is constructed from 14gauge steel

• Door is hinged for easy access

• Windows are provided for viewingsystem gauges and other functions

• Grooved connections are providedon the supply and discharge sidesof the valve assembly for easyconnections to the supply andsystem piping

• Available in deluge, single, anddouble interlocked preaction systemconfigurations in a variety of valvesizes

• Electrical control panel for thesystems is normally a Potter 4410releasing panel, but other controlsare available upon request

• Can be piped from eitherside for supply and drainfunctions

• Discharge is vertical

• Available with DV-1, DV-3, and DV-5 valves

• Listings and Approvals: All components - UL, C-UL, ULC, and FM

The aesthetically pleasing RED-E CABINETprovides all the mechanical controls, valves,and electrical detection and actuation controlsin one unit for ease of installation.

Page 10: 111

Single interlock preaction systems are used toprotect areas where there is danger of serious waterdamage that might result from damaged automaticsprinklers or piping. Typically, such areas includecomputer rooms, storage areas for valuableartifacts, libraries and archives. Also, preactionsystems are effectively used to protect propertieswhere a prealarm of a possible fire condition mayallow time for fire extinguishment by alternatesuppression means, prior to a sprinkler discharge.In the event the fire cannot otherwise beextinguished, the preaction sprinkler system willthen perform as the primary fire protection system.

Single interlock preaction systems employautomatic sprinklers attached to a piping systemcontaining 10 psi (0,7 bar) supervisory pressure,with a supplemental electric fire detection systeminstalled in the same area as the sprinklers.Preaction systems with 10 psi (0,7 bar) supervisorypressure may also be activated by either wet or drypilot sprinklers instead of electric detectors.Actuation of the fire detection system from a fireopens the deluge valve, allowing water to flow intothe sprinkler piping system and to be discharged

only from those sprinklers that have been operatedby heat over the fire. Loss of supervisory pressurefrom the system piping as a result of damagedsprinklers or broken piping will activate a troublealarm to indicate impairment of the system. Thedeluge valve will not open due to loss ofsupervisory pressure.

Available with: • DV-5 Valve (TFP1305)• DV-1 Valve (TFP1330)• DV-3 Valve (TFP1350)

10 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

Trim Assemblies

WET PILOT DRY PILOT ELEC. ACTUATION

DV-5 TFP1410 TFP1415 TFP1420

DV-1 TD1125 TD1125 TD1125

DV-3 TD1120 TD1120 TD1120

Water Pressure

Atmospheric Pressure

Air Pressure

Automatic Sprinklers

Gate Valve

Water Motor Alarm

Deluge Valve w/Single Interlock Trim

Fire Alarm Bell

Waterflow Pressure Alarm Switch

Electric Releasing

Panel

Electric Detectors

Electric �Manual Control

Station(s)

Low Air Pressure Alarm Switch

Air/Nitrogen Maintenance Device

Solenoid Valve normally closed

Check Valve

Single Interlock Preaction Systems Electric Shown

Page 11: 111

Double interlock preaction systems are designedfor applications such as refrigerated areas that requirethe maximum degree of protection against aninadvertent operation that could result inunnecessary flooding of the sprinkler system piping.

The double interlock system consists of a delugevalve and swing check valve with releasing trimfeaturing both a solenoid valve and a dry pilotactuator in a series configuration. The swing checkvalve isolates the body of the deluge valve from thesystem air or nitrogen pressure that holds the drypilot actuator closed. The solenoid valve remainsclosed until it is electrically energized by a delugereleasing panel that responds to the operation of afire detection device.

In order to actuate the double interlock preactionsystem, two independent events, caused by a firecondition, must occur. The sprinkler system pipingmust lose air or nitrogen pressure due to theoperation of one or more sprinklers, and the delugereleasing panel must energize and open thesolenoid valve upon the operation of a firedetection device.

The double interlock system will operate onlywhen both the dry pilot actuator and the solenoidvalve are open at the same time. Opening of thedry pilot actuator only (for example: a forklifttruck accidentally dislodges a sprinkler) or of thesolenoid valve only (for example: accidentaloperation of an electric manual pull station) willcause an alarm, and will not trip the system orflood the sprinkler system piping.

Available with: • DV-5 Valve (TFP1305)• DV-1 Valve (TFP1330)• DV-3 Valve (TFP1350)

Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 11

Trim Assemblies

ELEC./ELEC. ELEC./PNEUM. ACTUATION ACTUATION

DV-5 TFP1465 TFP1460

DV-1 TD1153 TD1151

DV-3 TD1148 TD1146

Automatic Sprinklers

Gate Valve

Water Motor Alarm

Deluge Valve w/Double Interlock Trim

Fire Alarm Bell

Dry Pilot Actuator normally closed

Waterflow Pressure Alarm Switch

Double Interlock

Electric Releasing

Panel�

Electric Detectors

Electric �Manual Control

Station(s)

Low Air Pressure Alarm Switch

Air/Nitrogen Maintenance Device

Solenoid Valve normally closed

Check Valve

Water Pressure

Atmospheric Pressure

Air Pressure

System Shut-Off Valve

Double Interlock Preaction Systems Pneumatic/Electric Shown

Page 12: 111

12 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

The “deluge valve” is the automatic water controlvalve that is used to control water flow into deluge,preaction, and special types of fire protection systems inresponse to a fire.

Deluge fire protection systems are normally used inspecial hazard installations where an entire areaapplication of water is required for protection. Typicalapplications may include flammable liquid handlingand storage areas, aircraft hangars, and other high-hazard installations where water is the most effectiveextinguishing agent. Deluge systems employ opensprinklers or spray nozzles attached to a piping system.The system is connected to a water supply through thedeluge valve. This valve is opened by the operation of afire detection system installed in the same areas as theopen sprinklers or nozzles. Deluge systems may beactivated by wet or dry pilot sprinklers, or electricdetectors. When the deluge valve opens, water flowsinto the piping system and discharges from all opensprinklers and nozzles.

Trim Assemblies

WET PILOT DRY PILOT ELEC. ACTUATION

DV-5 TFP1310 TFP1315 TFP1320

DV-1 TFP1330 TFP1330 TFP1330

DV-3 TFP1350 TFP1350 TFP1350

Deluge Valve & Deluge Systems Electric Shown

Page 13: 111

DV-5 Deluge Valve, External Resetting Diaphragm Style – 1-1/2" through 8"

Tech Data TFP1305

• Available sizes:1-1/2" (DN40), 2" (DN50),3" (DN80), 4" (DN100), 6" (DN150), 8" (DN200)

• Vertical or horizontal installation

• One internal working part

• No linkage or clapper assembly

• Light weight ductile iron body

• Available with deluge and single & doubleinterlock preaction trim

• Internally & externally coated

• Features external resetting

• Diaphragm operation

• For most seawater & brackishwater supplies for deluge systems

• For deluge, preaction & foamsystems

• Available as Flange x Flange,Flange x Groove, or Groove x Groove body styles

• Rated for 250 psi (17,2 bar) service

• Listings and Approvals:UL, C-UL, and FM

DV-1™ External Resetting Deluge Valve – 4" & 6"

Tech Data TFP1330

• Available sizes:4" (DN100) and 6" (DN150)

• Used as a system control valve in deluge,and single and double interlock preactionsystems

• Can be reset externally without having toremove the hand-hole cover and unlatch thewaterway clapper

• Positive mechanical latching style valve

• Available with three actuationtrim arrangements: wet pilot, drypilot, and electric

• Single and double interlockpreaction trims available

• Rated for 175 psi (12.1 bar)maximum service pressure

• Listings and Approvals: UL, ULC, FM, LPC, and SSL

DV-3™ Deluge Valve, Automatic Resetting – 2-1/2"

Tech Data TFP1350

• 2-1/2" (DN65), right angle type delugevalves

• Available with either a grooved or threadedinlet and outlet

• For use as a control valve in deluge, orsingle or double interlock preaction systems

• Can be reset externally without having toopen a hand-hole cover to manually unlatchand set the center valve

• Trim arrangements provide wetpilot, dry pilot, and electricactuation

• Valves may be installed with theoutlet facing either left or right

• DV-3 (F445) – 175 psi (12,1 bar)DV-3 (F446) – 250 psi (17,2 bar)

• Listings and Approvals: UL, ULC, FM, LPC, and SSL.

CV-1F Riser Check Valve

Tech Data TFP950

• Available sizes: 2" through 8"(DN65) through (DN200)

• Intended for use in a preaction system riser

• Furnished with grooved ends that arecompatible with grooved pipe andcouplings

• Can be installed with ANSI class150 or 300 Flanges utilizingflange adapters

• Designed with a removable coverfor ease of field maintenance

• Standard seal is grade “E” EPDM

• Maximum rated working pressureis 300 psi (20,68 bar)

Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 13

Page 14: 111

14 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

AQUAMIST® Systems utilize the newest and mostunique nozzles developed and approved for fire protection.They offer an alternative to gas systems, foam systems, orheavy density sprinkler systems. By utilizing a higherpressure than a normal sprinkler system, but a 50-80%lower water flow, the AquaMist Systems use less watermore effectively, reduce costs in pipe sizing and labor, andminimize cleanup and water damage.

a) By using smaller droplet sizes, a larger droplet surface area tovolume is created. This larger surface area allows heatextraction (evaporation).

b) Vapor is created that displaces, removes, and excludes oxygenfrom the fire tetrahedral equation.

c) Flammable vapors are diluted by the entrainment of watervapor, to the extent that the flammable vapor will not burn.

d) Larger droplets are designed to penetrate the fire plume andcool the combustibles similar to a standard sprinkler system.

e) The suspended mist will cool and “pre-wet” othercombustibles in the area and cool any fuels and gases.

AquaMist Systems are used in total compartmentalized areas andare pre-engineered systems that have specific guidelines as to theavailability of installation, design, and components. With theadvent of the publication of NFPA 750, the introduction andawareness of mist technology has never been higher. These pageshighlight some of the products available in the AquaMist productline from TFBP…the innovative leader in fire protection.

Typical Gas TurbineGenerator Room

AquaMist Systems operate differently from normal sprinkler or gaseous systems as follows:

3PFC4410 – Single zone, crosszone, or sequentialcross zone releasingpanel

2Variable Pressure AquaMist Fire Pump 1

DV-5 Deluge Valve

4Fire Pump Controller 5

Required Outlet Strainer –The pipe, fittings, hangers andAquaMist nozzles are to be connected to the strainer outlet.

To System

Page 15: 111

Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design

parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 15

AM10 AQUAMIST® Open Type Mist Nozzle

AM4 AQUAMIST® Open Type Mist Nozzle

• Open, directional spray nozzles

• Listed & Approved for theprotection of flammable liquidhazards (UL/FM)

• Approved for protection of gasturbines (FM)

• Maximum ceiling height, 26' 3" (8 m)

• Compartment volume

– UL - 56,500 ft3 (1,600 m3)– FM - 45,203 ft3 (1,280 m3)

• Maximum utilization of water forflammable liquid fire protection

• Nozzle coverage: maximum 172 ft2 (16 m2)

• Nozzle pressure: 185 to 250 psi(12,8 to 17,2 bar)

K=0.24 (3,5)

1/2" (15 mm)

Stainless Steel

K Factor

Thread Size

Finish

Tech Data TD1173

AM15 AQUAMIST®

• Available for use in IMO MandatedMSC 913 local application watermist systems

• 0.33 gpm/psi0.5

• 175-250 psi

• 4.36 gpm @ 175 psi

Since the water droplet sizes are muchsmaller, a larger surface area is createdto allow the water to absorb heatmore quickly than a conventionalsprinkler spray having largerdroplets.

The smaller droplets will be suspended and coat and cool anycombustibles in the room,while pre-wetting thecombustibles and thereby blocking themfrom radiant heat.

The fire will receive the directimpingement of the largerdroplets similar to a standardsprinkler

• Open spray nozzles

• Designed for use in water mistprotection systems protectingflammable liquids and turbinebearings

• Minimal water demand, approximately 3.1 GPM/nozzle at170psi (11,73 lpm at 11,6 bar)

• Mist represents latest in fire protection technology

• For use in “low pressure” mistapplications

• Minimum operating pressure is 170 psi (11,6 bar)

• Nozzle coverage: maximum 86 ft2 (8m2)

• UL, FM

K=0.24 (3,5)

1/2" (15 mm)

Stainless Steel

K Factor

Thread Size

Finish

Tech Data TD1174

When the mist comes in contactwith a fire, vapor (steam) is createdwhich displaces, and reduces theoxygen level at the fire.

Page 16: 111

WORLDWIDE HEADQUARTERSTyco Fire & Building Products451 N. Cannon AvenueLansdale, PA 19446215-362-0700, 800-523-6512Fax 215-362-5385www.Tyco-Fire.com

UNITED STATESCentral Sprinkler Company451 N. Cannon AvenueLansdale, PA 19446215-362-0700, Fax 215-362-5385

Brea, CA: Tel: 714-993-6111, Fax 714-993-6043Decatur, GA: Tel: 404-243-7336, Fax 404-244-7375Norristown, PA: Tel: 610-239-9925, Fax 610-239-9936Jessup, MD: Tel: 301-604-7133, Fax 301-604-7138Carol Stream, IL: Tel: 630-871-7700, Fax 630-871-7464Coppell, TX: Tel: 972-745-0043, Fax 972-745-8594Kent, WA: Tel: 253-872-6030, Fax 253-872-6547Avon, MA: Tel: 508-583-8447, Fax 508-583-0034Pompano Beach, FL: Tel: 954-781-0866, Fax 954-781-1475Murray UT: Tel: 801-269-0688, Fax 801-269-0733Tigard, OR: Tel: 503-620-4203, Fax 503-620-3817Parma, OH: Tel: 216-265-0505, Fax 216-265-8354Kansas City, MO: Tel: 816-842-2424, Fax 816-842-4433

National Distribution FacilityPO Box 2806Lubbock, TX 79408-2806

Gem Sprinkler Company & Star Sprinkler Inc.7071 S. 13th Street, Ste. 103Oak Creek, WI 53154877-436-8926, Fax 877-866-9250

CANADARegional Headquarters12-16715 Yonge Street, Suite 316Newmarket, Ontario L3X 1X4705-422-0010, Fax: 705-422-1396

© 2005 Tyco Fire Products LP. All rights reserved. /Printed in USA/TFP-SHz/2500/PP/07-05

LATIN AMERICARegional HeadquartersSouth America, Central America & Caribbean1802 S.W. 2nd St.Pompano Beach, FL 33069954-781-0866, Fax 954-781-9330

Regional Headquarters - MexicoHamburgo 231A Piso 2Colonia JuarezMexico, D.F. 06600 Mexico525-55-2075766, Fax: 525-55-2077566

EUROPE & MIDDLE EASTRegional HeadquartersKopersteden 1, NL-7547 TJ EnschedeP.O. Box 198, 7500 ADEnschede, The Netherlands31-53-428-4444, Fax 31-53-428-3377

Stockport, UK: Tel: 44-161-477-1886, Fax 44-161-477-6729Paris Nord II, France: Tel: 33-1-48-178-727 , Fax 33-1-48-178-720Rodgau Germany: Tel: 49-6106-84455, Fax 49-6106-18177Coslada Madrid, Spain: Tel: 34-1-669-3906, Fax 34-1-669-2018Lørenskog, Norway: Tel: 47-67-91-77-00, Fax 47-67-91-77-15Lammhult, Sweden: Tel: 46-472-269-980, Fax 46-472-269-989Dublin, Ireland: Tel: 353-166-839-82, Fax 353-166-822-54Bolzano,Italy: Tel: 39-0471-252-091, Fax 39-0471-254-058Milano, Italy: Tel: 39-0293-548-736, Fax 39-0293-548-690Dubai, United Arab Emirates: Tel: 971-488-38689, Fax 971-488-38674Budapest, Hungary: Tel: 36-148-11-383, Fax 36-120-34-427Wels/Thalheim, Austria: Tel: 43-072-42-65-054, Fax 43-072-42-74-393

ASIARegional HeadquartersNo.45 Tuas Avenue 9,Singapore 639189

Central Sprinkler CompanySingapore: 65- 6743-3212, Fax 65-6743-9181Shanghai, China: 86-21-5868-3300, Fax 86-21-5868-1160Beijing, China: 86-10-6515-6191, Fax 86-10-6515-6157Chengdu, China: 86-28-689-9440, Fax 86-28-666-2538

Gem Sprinkler Company & Star Sprinkler Inc.Singapore: 65-6861-1655, Fax 65-6861-1312Kuala Lumpur, Malaysia: 60-3-8024-6773, Fax 60-3-8024-2180Hong Kong: 852-2595-0686, Fax 852-2505-5826

Central, Gem, Star, Grinnell, G FOUNDED 1850 and Design, and Tyco are eitherregistered trademarks or trademarks of Tyco and/or its affiliates in the UnitedStates and/or other countries. All other brand names, product names, ortrademarks belong to their respective owners. Tyco Fire & Building Productsreserves the right to change product design and specifications without notice.