    10A

    HUBBELL

    Power SystemsCHANCE CENTRALIA, MISSOURI

    JULY 2010

    Se

    10HUBBELL

    Type C-POLYMER

    Cutouts (Standard, Linkbreak & Loadbreak)

    and

    Cutout-Arrester Combinations

    CAUTION: The equipment covered in this catalog section should be installed, used, and serviced only by competent per-sonnel amiliar with and ollowing good work and saety practices. This equipment is or use by such personnel and is notintended as a substitute or adequate training and experience in sae procedures or this type o equipment.

    This catalog inormation and any related instruction sheets do not cover all details or situations in equipment use nor dothey provide or every possible contingency to be encountered in relation to installation, operation or maintenance. Shouldadditional inormation and details be desired, or i specic situations arise that are not covered adequately or the user'spurpose the specics should be reerred to Hubbell Power Systems, Inc.

    Warranty - MaterialHubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defned in the Uniorm Commercial Code) and to be ree rom deects in material and workmanship.

    Buyer must notiy the Company promptly o any c laim under this warranty. The Buyer's exclusive remedy or breach o this warranty shall be the repair or replacement, F.O.B. actory, at the Company'soption, o any product deective under the warranty which is returned to the Company within one year rom the date o shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR ARISING BY

    OPERATION OF LAW, COURSE OF DEALING, USAGE OF TRADE OR OTHERWISE IMPLIED, SHALL EXIST IN CONNECTION WITH THE COMPANY'S PRODUCTS OR ANY SALE OR USE

    THEREOF. The Company shall in no event be l iable or any loss o profts or any consequential or special damages incurred by Buyer. The Company's warranty shall run only to the frst Buyer o aproduct rom the Company, rom the Company's distributor, or rom an original equipment manuacturer reselling the Company's product, and is non-assignable and non-transerable and shall be o

    no orce and eect i asserted by any person other than such frst Buyer. This warranty applies only to the use o the product as intended by Seller and does not cover any misapplication or misuse o

    said product.

    Warranty - ApplicationHubbell Power Systems, Inc. does not warrant the accuracy o and results rom product or system perormance recommendations resulting rom any engineering analysis or study. This applies

    regardless o whether a charge is made or the recommendation, or i it is provided ree o charge.

    Responsibility or selection o the proper product or application rests solely with the purchaser. In the event o errors or inaccuracies determined to be caused by Hubbell Power Systems, Inc., its

    liability will be l imited to the re-perormance o any such analysis or study.

    Photos show 15 kVproducts.

    27 kV products alsoare available.

    Copyright 2010 Hubbell Incorporated 210 North Allen Street Centralia, MO 65240 USAwww.hubbellpowersystems.com

    E-mail: [email protected]

    NOTE: Because Hubbell has a policy o continuous product improvement, we reserve the right to change design and specifcations without notice.

    Printed in USA

    NOTICE: For latest revision o our Catalog and Literature, please visit our web site: www.hubbellpowersystems.com

  • 7/30/2019 10AA

    2/12

    0AA-2

    CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL

    Power Systems

    HUBBELL Type C-POLYMER Cutouts

    the ground, rom a bucket truckor rom the pole.

    The toggle type trunnion is aselective silver-plated bronzecasting or eicient currenttranser to the lower hinge con-tacts. A cam shaped projectionon each side o the trunnioncasting provides high pressureparallel current paths to thelower contacts. These projections,or pivot pins, are cast ull roundor smooth rotational operationin the hinge. The link ejector as-sists in arc interruption duringlow ault current or excessiveoverload conditions. A groove inthe center o the link ejector al-lows the use links pigtail to godirectly rom the use tube to theattachment nut. A curved ejectorminimizes bending stresses in thepigtail to prevent broken strands.

    A stainless steel torsion spring onthe link ejector helps to rapidlyeject the link rom the bore o theuseholder during interruption.The 200 amp link ejector has a

    wider groove area and increasedspring orce to accommodate thelarger links.

    The link ejector is pinned to thetrunnion casting with a stainlesssteel pin to provide resistance to

    corrosive elements and provide smooth pivotal action. Aninterlocking eature between the link ejector and tube castingprevents excessive tension on the use link during closure,thereby preventing link breakage.

    The link ejector employs a hammer eect to enhance toggleaction o the trunnion during low ault and overload inter-ruptions, hence dropout action is enhanced. The link ejectorprovides sucient surace area to acilitate re-using by

    linemen wearing gloves.

    Ratings/Specifcations

    STANDARD Type C-Polymer cutouts are maximum designvoltage rated to eliminate application and selection conusion.There are no restrictions on application to grounded wye,ungrounded wye, or delta systems having maximum operat-ing voltages (line-to-line) equal to or less than the cutoutmaximum design voltage rating. (See the LINKBREAK andLOADBREAK cutouts or their specications.) Interruptiontests have been perormed at ull system line-to-line voltage.100-amp and 200-amp use tubes and 300-amp disconnectblades are available or each voltage class. They all t into acommon mounting assembly rated at 300 amps continuous.

    QualityConstructionEfcient Current Transer

    The Type C-Polymer cutout hasan all copper current path. Allcontacts are silver-plated. Ter-minals are tin-plated bronze oruse with copper or aluminumconductors.

    Loadbreak Hooks

    Galvanized steel hooks arestandard on all Type C cutouts,except the arc chute version, oruse with a portable loadbreaktool. These sturdy hooks aremounted on the top support andserve to guide the useholderinto the latch socket.

    Top Contact

    The top contact is attached tothe galvanized-steel hood bya stainless rivet to provide asmooth sel-aligning action

    during closing even in severelycorrosive environments. Thetop contact provides a socket-type cavity or latching theuseholder and prevents anypossible over-travel o theuseholder. The top contact ismade o a highly conductive copper strip with silver-platedembossments or ecient current transer. The contacts areheld under constant pressure designed to maintain rmcontact with the useholder contact surace until ault inter-ruption is accomplished.

    Hinge

    The hinge on the Type C-Polymer cutout employs large pivot

    areas or the useholders trunnion and is cast o a copper alloychosen or its strength and corrosion resistance. The hingecontacts are highly conductive copper alloy stampings andare plated to assure low resistance current transer rom thetrunnion casting. The parallel current paths are backed up byhigh strength cantilever springs and are riveted to the hingecastings. Fuseholder can be dropped into place and easilylited up and out. No tricky maneuvering is required.

    Fuseholders

    The solid cap on the single vent useholder is a copper alloy,silver-plated to provide ecient current transer. An integralring is provided in the top tube casting or opening and clos-ing the useholder with an appropriate disconnect tool rom

    ApplicationThe primary purpose o any cutout is to provide protec-tion to the lines o your system and the various apparatuson those lines such as transormers and capacitor banks.Hubbell Type C-Polymer cutouts provide reliable protectionrom low-level overloads that just melt the use link, inter-

    mediate aults, and very high aults, through maximum

    interrupt rating.

    In addition, Type C-Polymer cutouts can also be used as asectionalizing device. With the use o a portable loadbreaktool, Type C-Polymer cutouts can unction much like anoverhead disconnect switch. A 300 amp disconnect blade

    is also available or this purpose.

    Polymer InsulatorsType C-Polymer cutout insulators are manuacturedwith ESP silicone alloy rubber, the same material usedin Ohio Brass PDV arresters and Hi*Lite insulators.ESP is a polymer compound made by alloying siliconeand EPDM rubber. This alloy oers the desirable tough-ness and resistance to tracking o our original EPR,with the hydrophobic characteristics derived rom lowmolecular weight silicone oils.

    Hubbell Power Systems uses several tests to evaluate

    materials. Tracking, QUV, corona cutting, salt og,oxidative stability and variations o dierential ther-mal analysis tests conrm the quality o the material.For urther inormation on our polymers, ask yourHubbell Power Systems representative or the publica-tion "Polymer Materials or Insulator Weathersheds"EU1264-H.

    Upgrades to Cutout Perormance

    The increased metal-to-metal leakage distance o TypeC-Polymer Cutouts compares to their porcelain coun-terparts at 12.6" (319 mm) vs 8.7" (220 mm) or 15kVand 17.1" (434 mm) vs 12.6" (319 mm) or 27kV.

    Signicantly lighter, Type C-Polymer Cutouts typicallyweigh only approximately hal their porcelain counter-

    parts. This ergonomic advantage makes them simpleto install and, o course, ar less ragile than porcelain.That means reduced or eliminated losses rom routineshipping, storage and handling.

  • 7/30/2019 10AA

    3/12

    10A

    HUBBELL

    Power SystemsCHANCE CENTRALIA, MISSOURI

    JULY 2010

    HUBBELL Type C-POLYMER Cutouts

    STAINLESS-STEELSPRING PROVIDESPROPER TOGGLE ACTIONOF FUSELINK EJECTOR(CAST-BRONZE ON ALL 200AND LINKBREAK FUSEHOLDERS;STAINLESS-STEEL ON ALL 100A)

    Compare Hubbellquality and technical expertise

    SILVER-TO-SILVERCONTACTS

    CAST BRONZE HINGEFOR CORROSION RESISTANCE

    COPPERCURRENTPATH

    FUSEHOLDER TOGGLE LATCHLIMITS TENSION OF FUSELINK

    CAST BRONZELOWER TUBE

    CASTING

    CAST BRONZE TOP TUBE CASTINGAND PULL RING

    HIGH-STRENGTH FIBERGLASS FUSETUBECOATED WITH ULTRA-VIOLET INHIBITOR

    GALVANIZED STEEL HOOKSFOR LOADBREAK TOOL

    STAINLESS STEELBACKUP SPRINGTO MAINTAINCONTACT PRESSURE

    POLYMERINSULATOR

    TIN-PLATED BRONZE TERMINALSFOR USE WITH COPPEROR ALUMINUM CONDUCTOR

    GALVANIZED-STEEL CHANNEL

    COPPERARC-SHORTENING ROD(ON SOME RATINGS)

    TWO-PLACE LOCKINGTO PREVENT SIDEMOVEMENT OF HOOD,CONTACTS OR HOOKS

    COPPER CURRENT PATH

    All Type C Cutouts meet or exceed ANSI/NEMA specifcations.

    SYNTHETICFUSE TUBELINER

    LARGE NUT TOFASTEN FUSELINKWITHOUT BREAK-ING STRANDS

    MECHANICAL ASSIST:

    FUSEHOLDER IS AVAIL-ABLE WITH A TORSIONALSPRING ON TRUNNION TOAID DROP OUT OPERATIONIN CORROSIVE ENVIRON-MENTS.

    15 kV product shown. 27 kV cutout varies slightly in appearance.

  • 7/30/2019 10AA

    4/12

    0AA-4

    CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL

    Power Systems

    Type C-Polymer

    STANDARD Cutout

    kVLIW (BIL)

    110

    125

    STANDARD Type C-Polymer Cutoutwith NEMA Type B Bracket

    A

    155/8"

    395 mm

    161/16"

    408 mm

    B

    47/8"

    125 mm

    65/8"

    167 mm

    C

    115/8"

    295 mm

    131/16"

    332 mm

    D

    31/4"

    82 mm

    27/8"

    72 mm

    E

    221/16"

    561 mm

    27"

    686 mm

    InterchangeabilityChance was the rst to design a cutout that could interchangeuseholders and mounting assemblies with those o anothermanuacture. Standard Type C useholders and mounting as-semblies are mutually interchangeable with the S&C ElectricCompanys Type XS cutout (within the same voltage class).

    The Type C-Polymer Standard cutout is mutually interchange-able with Chance Type C Porcelain Standard cutout.

    Synthetic Arc-Quenching FusetubeThe1/2-inch inside diameter o the Type C-Polymer cutouts 100ampere usetube increases internal pressure giving superiorand reliable expulsion action. During requently encounteredintermediate ault ranges this diameter also permits higherTRV (transient recovery voltage) values to be tolerated. Thissmall bore design eliminates any concern related to highimpedance phase-to-phase aults on ungrounded wye anddelta systems.

    The inside liner is a synthetic arc-quenching ormulation inpart consisting o polyester ber, epoxy and Aluminum TriHydrate. The liner is chemically bonded to the tube's glass-reinorced shell. This combination provides a moisture sourceto extinquish the arc during interrupt operations without

    absorption o atmospheric moisture leading to potentialswelling and delamination, and provides a high burstingstrength. It is protected rom the weather and environmentby a special ultra-violet resistant coating. For more inor-mation on the synthetic arc-quenching material, reer toBulletin 10-0201.

    The Hubbell use tube operates with uselinks rom all majorsuppliers.

    100 amp or smaller uselinks shall not be used in 200-ampuseholders.

    BracketsType C-Polymer cutouts come packed one per carton includ-ing a NEMA Heavy Duty B bracket with captive 11/2" boltor crossarm mounting.

    Type X brackets, also or crossarm mounting, provides 2 5/8"additional clearance between the crossarm and the cutout.

    D brackets are used to mount cutouts and/or arrestersdirectly to the pole. Three brackets may be used or three-phase application. Type D brackets provide a clean, quickmounting without crossarm or special pole bands.

    All the above brackets are galvanized steel or long lastingservice. Cutouts can be ordered without any brackets.

    Higher Interrupt CapacitiesBy using a copper arc shortening rod inside the top o theusetube, higher interrupt ratings are obtainable. An arcshortening rod is attached to the cap o some usetubes andlowers the use link within the usetube. This permits amuch shorter arc, resulting in less arc energy, and higher

    interrupting capacities. For 200 A tubes, it allows or ullvoltage ratings.

    It is necessary to use use links with removable buttonheadswhen arc shortening rods are employed.

    TerminalsTin-plated bronze parallel groove type terminals are standardon Type C cutouts. They can accommodate aluminum orcopper conductor sizes ranging rom No. 6 (13.3 mm2) solidcopper through 4/0 (160.6 mm2) ACSR or 250 (167.5 mm2)kcmil stranded copper. The parallel groove design is perector handling two dierent sizes o conductor as is the casewhen arresters are being used. Eyebolts are also available.See ordering data, page 10AA-11.

    100 Amp Single Vent

    15 kV/110 kV LIW (BIL)

    110 kV LIW (BIL) product isdepicted.125 kV LIW (BIL) product variesslightly in appearance.

  • 7/30/2019 10AA

    5/12

    10A

    HUBBELL

    Power SystemsCHANCE CENTRALIA, MISSOURI

    JULY 2010

    No option (may not beused with Z in Option 2)Mechanical Assist Fuse-holder (may not be usedwith Blank in Option 2)Fargo cutout cover(available or 15 kVonly) (may not be usedwith Blank in Option 2)

    NEMA Heavy Duty B bracketor crossarm (11/2" bolt)Extended type bracket or cros-sarm (Horizontal sectionis 25/8" longer than Type Bbracket)D-shape bracket (pole)No bracket (must be used withM in Option 3)No bracket (cannot use with Min Option 3)

    27 kV - 17.1" leakage

    TP7102MMPB

    Type C-Polymer STANDARD Cutout

    Maximum

    DesignVoltage15 kV15 kV15 kV15 kV

    NominalSystem VoltageThru 14.4 kVThru 14.4 kVThru 14.4 kVThru 14.4 kV

    319 mm319 mm319 mm319 mm

    Arc

    ShorteningRodNo

    Yes

    Yes

    N/A

    Continuous

    Current(Amps)

    100100200300

    12.6"12.6"12.6"12.6"

    Leakage to GroundMetal to Metal

    Interrupt

    Capacity(Asym Amps)

    10,00016,00012,00012,000**

    Specifcations and Ordering InormationAll Type C Cutouts meet or exceed ANSI/NEMA specifcations.

    15 kV - 110 kV LIW (BIL) RUS LISTED

    See page 10AA-11 or Accessories.

    *Weight(lb./kg.)

    9.6/4.49.8/4.510.4/4.79.9/4.5

    Replacement

    FusetubeCap

    P7001535PE7001767PE7002146PP7001535P

    434 mm434 mm434 mm434 mm

    P7001535PE7001768PE7002479PP7001535P

    27 kV - 125 kV LIW (BIL)27 kV27 kV27 kV27 kV

    NoYes

    Yes

    N/A

    100100200300

    8,00012,00010,000

    12,000**

    Thru 24.9 kVThru 24.9 kVThru 24.9 kVThru 24.9 kV

    CP710211CP710213CP710242CP710233

    17.1"17.1"17.1"17.1"

    11.0/5.011.0/5.011.6/5.311.2/5.1

    1.8 lb.2.0 lb.2.6 lb.2.1 lb.

    CutoutBase Catalog

    NumberCP710112CP710114CP710143CP710133

    Fuseholders and Mounting Assemblies

    0.76 kg.0.79 kg.1.18 kg.0.95 kg.

    15 kV - 110 kV LIW (BIL)Mounting Assembly

    only*Base Catalog No.

    TP7101MM

    Fuseholder orBlade onlyCatalog No.

    T710112TT710114TT710143TT710133T

    3.6 kg.8.0 lb.

    Weight *Weight

    **Momentary rating -Solid blade. Must use removable buttonhead use links. *Adjust total weight when selecting Options below.

    CP710211CP710213CP710242CP710233

    T710211TT710213TT710242TT710233T

    1.9 lb.2.0 lb.2.5 lb.2.1 lb.

    0.86 kg.0.91 kg.1.13 kg.0.97 kg.

    4.1 kg.9.16 lb.TP7102MM

    27 kV - 125 kV LIW (BIL)

    300A

    Blade

    100A 200AFuseholders

    *Option Sufx 1

    Terminal Variations

    *Option Sufx 2

    Bracket Variations

    *Option Sufx 3

    Mechanical AssistFuseholder

    *Option

    sufxesbelow

    1 2 31 2 31 2 31 2 3

    1 2 31 2 31 2 31 2 3

    *Adjust total weight when se-lecting Option suxes above.

    *Weight(lb./kg.)

    0.33/0.150.16 /0.070.31/0.14

    Sufx1

    PEL

    Description

    Parallel-groove clampsSmall eyeboltsLarge eyebolts

    Sufx3

    Blank

    M

    F

    Description

    *Weight(lb./kg.)

    2.84/1.29

    3.75/1.70

    7.67/3.48

    Sufx2

    B

    X

    DZ

    Blank

    Description

    Must specify one selection for Option 1.

    300ABlade

    200AFuseholders

    100A

    15 kV

    12.6" leakage

    *Catalog No.

    TP7101MMPB

    MountingAssembly only

    *Base

    CatalogNo.

    CP710112CP710114CP710143CP710133

    Universal Cutout ToolIdeal or Standard and Linkbreak 100 amp useholders (ABB, Chance S&C) to easily lit out, place,*open and close. Inverted, secure method also tsChance Electronic Sectionalizers.Cat. No. PSC4033484 (Wt. 4 oz.) See Tools Catalog Section 2100.*When opening a cutout, follow all work rules and OSHA regula-tions. Not for use with Loadbreak cutouts.

  • 7/30/2019 10AA

    6/12

    0AA-6

    CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL

    Power Systems

    15 kV - 110 kV LIW (BIL)

    15/27 kV - 125 kV LIW (BIL)

    A sharp downward pull on the lever with a hookstickbreaks the fuselink. (15/27 kV product shown here)

    Application

    The Type C-Polymer 100 amp Linkbreak cutout provides shortcircuit protection to utility lines with the added eature omechanical linkbreak capability in a loadbreaking unction.Linkbreak cutouts provide reliable protection rom overloadsthat just melt the uselink through the maximum interruptcapacity o the useholder and also provide inductive andcapacitive loadbreak capability. For loadbreak ratings seechart, next page.

    The unit will also accept the Type C-Polymer 200 amp non-loadbreak useholder or a 300 amp disconnect blade. EachLinkbreak cutout includes standard loadbreak hooks to usewith portable loadbreak tools. This method is particularlyuseul or switching o the 200 amp useholder and 300 ampdisconnect blade.

    Design / Product FeaturesConstruction and product details shown on page 10AA-3 ap-ply to the Linkbreak cutout except that the link-ejector onthe linkbreak useholder is a copper-alloy casting instead oa stainless-steel stamping.

    The unit utilizes a stainless-steel linkbreak lever to me-chanically break uselink elements thereby obtaining loadinterruption within the useholder. The Type C-PolymerLinkbreak useholder is not designed to be interchangeablewith any other manuacturers cutout.

    All standard non-loadbreak useholders and the linkbreakuseholders are interchangeable and t into both the non-

    loadbreak and Type C-Polymer or Porcelain Linkbreak cutoutmounting assemblies. Mounting assemblies are the same asthose or Type C-Polymer or Porcelain STANDARD cutouts,shown on page 10AA-5.

    Ratings / Specifcations

    The 15 kV Type C-Polymer Linkbreak cutout has a maximumdesign voltage rating o 15 kV. There are no voltage restric-tions on application to grounded wye, ungrounded wye, ordelta systems having maximum operating voltages (line toline) equal to or less than the cutout maximum design volt-age rating.

    The 15/27kV Type C-Polymer LINKBREAK cutout hasmaximum design slant voltage ratings. These cutouts are tobe used on systems which have phase-to-ground voltages nogreater than the value listed to the let o the slant (/) and

    which have phase-to-phase voltages no greater than the valuelisted to the right o the slant.

    The Type C-Polymer Linkbreak cutout is to be used withuselinks requiring 1 inch or less elongation beore break-ing. Fuselinks requiring more than 1 inch elongation beorebreaking must not be used with the Type C-Polymer Link-break cutout.

    Type C-Polymer

    LINKBREAK Cutout

    (15 kV product shown here)

  • 7/30/2019 10AA

    7/12

    10A

    HUBBELL

    Power SystemsCHANCE CENTRALIA, MISSOURI

    JULY 2010

    125 kV LIW (BIL)

    Type C-Polymer100-Amp LINKBREAK Cutout

    LINKBREAK Cutout with NEMA Type B Bracket

    LIW (BIL)kV

    110

    125

    CapacitiveAmperes

    100100100100

    *See specications and ordering inormation below.Limited to grounded-wye systems with grounded-wye loads.

    InductiveAmperes

    100100100100

    kV,Nominal

    System Voltage

    14.414.424.924.9

    *Base CutoutCatalogNumber

    CP720112CP720114CP720211

    CP720213

    Loadbreak Ratings

    Dimensions

    lb.2.52.72.72.9

    kg.1.131.221.221.32

    WeightFuseholderCatalog No.T720112TT720114TT720211TT720213T

    Cutout BaseCatalog Number

    CP720112CP720114CP720211CP720213

    kV& LIW (BIL)

    15 kV110 kV BIL

    15/27 kV125 kV BIL

    *Mounting assemblies are same as STANDARD cutouts, on 10AA-5.

    *Fuseholders (100 Amp only)

    110 kV LIW (BIL)product is depicted.125 kV LIW (BIL) product varies

    slightly in appearance.

    For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the let o the slant; and or application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltages not exceeding the value to the right o the slant.

    Must use removable buttonhead use links. *Adjust total weight when selecting Options below.

    Specifcations and Ordering InormationAll Type C Cutouts meet or exceed ANSI/NEMA specifcations.15 kV - 110 kV LIW (BIL) RUS LISTED

    15/27 kV - 125 kV LIW (BIL)

    Sufx1

    PEL

    Description

    Parallel-groove clampsSmall eyeboltsLarge eyebolts

    Must specify one selection for Option 1.

    *Option Sufx 1Terminal Variations

    MaximumDesignVoltage15 kV15 kV

    NominalSystem Voltage

    Thru 14.4 kVThru 14.4 kV

    319 mm319 mm

    ArcShortening

    Rod

    NoYes

    ContinuousCurrent(Amps)

    100100

    12.6"12.6"

    Leakage to GroundMetal to Metal

    InterruptCapacity

    (Asym Amps)10,00016,000

    See page 10AA-11 or Accessories.

    *Weight(lb./kg.)

    10.2/4.610.3/4.7

    ReplacementFusetube

    Cap

    P7001469PE7001784P

    434 mm434 mm P7001469PE7001785P15/27 kV15/27 kV NoYes100100 8,00012,000

    No Restrictions

    thru 14.9 kV; 20.8thru 24.9 kV

    17.1"17.1" 11.4/5.211.5/5.2

    *Option Sufx 2Bracket Variations

    *Optionsufxesbelow

    1 2 31 2 3

    1 2 31 2 3

    *Weight(lb./kg.)

    0.33/0.150.16 /0.070.31/0.14

    *Weight(lb./kg.)

    2.84/1.29

    3.75/1.70

    7.67/3.48

    Sufx2

    B

    X

    DZ

    Blank

    Description

    110 kV LIW (BIL)

    F167/16"417

    mm157/8"403mm

    A1515/16"

    405

    mm167/8"418mm

    B415/16"125

    mm69/16"167mm

    C115/8"295

    mm131/4"337mm

    D31/4"82

    mm27/8"72

    mm

    E221/8"561

    mm271/4"692mm

    *BaseCatalog

    No.CP720112CP720114

    CP720211CP720213

    NEMA Heavy Duty B bracketor crossarm (11/2" bolt)Extended type bracket or cros-sarm (Horizontal sectionis 25/8" longer than Type Bbracket)

    D-shape bracket (pole)No bracket (must be used withM in Option 3)No bracket (cannot use with Min Option 3)

    No option (may not beused with Z in Option 2)Mechanical Assist Fuse-holder (may not be usedwith Blank in Option 2)

    Fargo cutout cover(available or 15 kVonly) (may not be usedwith Blank in Option 2)

    *Option Sufx 3Mechanical Assist

    Fuseholder

    Sufx3

    Blank

    M

    F

    Description

  • 7/30/2019 10AA

    8/12

    0AA-8

    CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL

    Power Systems

    B

    63/8"162 mm

    713/16"199 mm

    C

    115/8"295 mm

    131/4"337 mm

    A

    2413/16"630 mm

    273/4"704 mm

    D

    31/4"82 mm

    27/8"72 mm

    E

    265/16"668 mm

    317/16"798 mm

    kV LIW(BIL)

    110

    125

    Dimensions

    Application

    The Type C-Polymer Loadbreak Cutout is available orapplication on 15 and 27 kV distribution systems. The ad-dition o the arc chute expands the fexibility o the Chanceprotective devices amily by providing loadbreak capabilityor cutouts and disconnect solid blade units. The loadbreakcutout provides short circuit protection to utility lines withthe added eature o a loadbreaking unction.

    The loadbreak cutout is applicable or transormer andcapacitor bank switching or line sectionalizing. Loadbreakcutouts provide protection rom overloads that just melt theuselink through the maximum interrupt capacity o theuseholder. They also provide loadbreak capability through300 amperes.

    Design

    All design eatures and most components o the loadbreakunit are identical to those incorporated in the Type C-Poly-mer standard cutout. The loadbreak portion o the TypeC-Polymer Loadbreak cutout is a heavy duty, reliable loadinterrupter that provides a positive visible loadbreak. A com-mon loadbreak mounting assembly will accept the ChanceType C-Polymer 100 amp and 200 amp loadbreak useholdersor a 300 amp loadbreak disconnect blade.

    Ratings/Specifcations

    The 15kV Type C-Polymer loadbreak cutout has a maximumdesign voltage rating o 15kV. There are no voltage restric-tions on applicaton to grounded wye, ungrounded wye, ordelta systems having maximum operating voltages (line toline) equal to or less than the cutout maximum design volt-age rating.

    The 15/27 and 20/34.5 kV Type C loadbreak cutouts havemaximum design slant voltage ratings. These cutouts areto be used on systems which have phase-to-ground voltages

    Type C-Polymer

    LOADBREAK Cutout with Arc Chute Interrupter

    110 kV LIW (BIL) product isdepicted.125 kV LIW (BIL) product variesslightly in appearance.

    no greater than the value listed to the let o the slant (/)and which have phase-to-phase voltages no greater than the

    value listed to the right o the slant.

    Fuseholders and mounting assemblies rom other manu-acturers' loadbreak cutouts are not interchangeable withChance loadbreak cutouts. Likewise, Chance useholdersand mountings are not interchangeable with other manu-acturers' loadbreak cutouts.

    OperationThe sel-contained loadbreak device enables the lineman tointerrupt load current by means o a simple hookstick opera-tion. To break the current, the lineman inserts a hookstickinto the operating ring and rapidly opens the device. Uponopening, a spring-loaded stainless steel blade mechanismsnaps out through a gray arc chute and elongates, cools andextinguishes the conned arc. The loadbreaking operationis independent o the operating speed o the lineman. Theuse remains undamaged. No special or portable tools arerequired to operate the unit. In the open position, the use-holder or blade hangs in an approximate vertical positionor the visible-break.

  • 7/30/2019 10AA

    9/12

    10A

    HUBBELL

    Power SystemsCHANCE CENTRALIA, MISSOURI

    JULY 2010

    300A

    Blade

    *Adjust total weight when selecting Option suxes above.

    Extra corrosion resistance:Not Available*Adjust total weight when selecting Options below. **Momentary rating Solid blade Must use removable buttonhead use links.For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the let o the slant; and or application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltages not exceeding the value to the right o the slant.

    Specifcations and Ordering InormationAll Type C Cutouts meet or exceed ANSI/NEMA specifcations.

    Type C-Polymer LOADBREAK Cutout

    3.3 lb.3.5 lb.4.1 lb.3.6 lb.

    Base CutoutCatalogNumber

    CP730112CP730114CP730143CP730133

    1.5 kg.1.6 kg.1.9 kg.1.6 kg.

    15 kV - 110 kV LIW (BIL) MountingAssembly only

    *Base Catalog No.

    TP7301MM

    Fuseholder orBlade onlyCatalog No.T730112TT730114TT730143TT730133T

    4.5 kg.10.0 lb.

    Weight Weight

    Fuseholders and Mounting Assemblies

    3.6 lb.3.8 lb.4.4 lb.4.0 lb.

    5.0 kg.11.1 lb.TP7302MM

    1.6 kg.1.7 kg.2.0 kg.1.8 kg.

    T730211TT730213TT730242TT730233T

    15/27 kV - 125 kV LIW (BIL)CP730211CP730213CP730242CP730233

    15 kV - 110 kV LIW (BIL) RUS LISTED

    15/27 kV - 125 kV LIW (BIL)CP730211CP730213CP730242CP730233

    100AFuseholders

    *Option Sufx 1Terminal Variations

    Sufx1

    PEL

    Parallel-groove clampsSmall eyeboltsLarge eyebolts

    Must specify one selection for Option 1.

    See page 10AA-11 or Accessories.

    MaximumDesignVoltage

    15 kV15 kV15 kV15 kV

    NominalSystem VoltageThru 14.4 kVThru 14.4 kVThru 14.4 kVThru 14.4 kV

    319 mm319 mm319 mm319 mm

    ArcShortening

    Rod

    NoYes

    Yes

    N/A

    ContinuousCurrent(Amps)

    100100200300

    12.6"12.6"12.6"12.6"

    Leakage to GroundMetal to Metal

    InterruptCapacity

    (Asym Amps)10,00016,00012,00012,000**

    *Weight(lb./kg.)

    15.1/6.815.2/6.915.8/7.215.4/7.0

    ReplacementFusetube

    CapP7001535PE7001767PE7002146PP7001535P

    434 mm434 mm434 mm434 mm

    P7001535PE7001768PE7002479PP7001535P

    15/27 kV15/27 kV15/27 kV15/27 kV

    NoYes

    Yes

    N/A

    100100200300

    8,00012,00010,00012,000**

    17.1"17.1"17.1"17.1"

    15.5/7.015.6/7.116.2/7.415.8/7.2

    *Optionsufxesbelow

    1 2 31 2 31 2 31 2 3

    1 2 31 2 31 2 31 2 3

    No Restrictions

    thru 14.4 kV;20.8 thru 24.9 kV

    15/27 kV

    TP7302MMPB

    300A

    Blade200A

    Fuseholders100A

    200A

    *Option Sufx 2Bracket Variations

    *Option Sufx 3Mechanical Assist

    Fuseholder*Weight(lb./kg.)

    0.33/0.150.16/0.070.31/0.14

    DescriptionSufx

    3

    Blank

    M

    Description

    No option (may not beused with Z in Option2)Mechanical AssistFuseholder (may notbe used with Blank inOption 2)

    *Weight(lb./kg.)

    2.84/1.29

    3.75/1.70

    7.67/3.48

    Sufx2

    B

    X

    DZ

    Blank

    Description

    NEMA Heavy Duty B bracketor crossarm (11/2" bolt)Extended type bracket or cros-sarm (Horizontal sectionis 25/8" longer than Type Bbracket)D-shape bracket (pole)No bracket (must be used withM in Option 3)No bracket (cannot use with Min Option 3)

    Replacement Arc

    Chute InterrupterCat. No. T7300080

    (1.2 lb. / 0.54 kg.)

    *BaseCatalog

    No.

    CP730112CP730114CP730143CP730133

    15 kVCat. No. TP7301MMPBMountingAssembly only

  • 7/30/2019 10AA

    10/12

    0AA-10

    CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL

    Power Systems

    Direct

    Direct

    Direct

    Small BlockNormal Duty

    5 kA

    Large BlockHeavy Duty

    10 kA

    RiserPole

    OhioBrass

    9

    DL

    EL

    FL

    10

    DM

    EM

    FM

    110

    Polymer

    Metal Oxide Varister

    (MOV)

    OperatingDesign

    Housing

    kV LIW (BIL)

    or Cutout

    kV RatingMCOVDuty

    Cycle

    kVRating

    ArresterMa

    nufacturer

    Arrester

    Connection

    Method

    Type C-PolymerCutout-Arrester Combinations

    15 kV cutout with direct-connected Ohio Brass MOV,

    polymer 9 kV lightning arrester

    Advantages o combinationThe total installed cost o a Hubbell cutout-arrester com-bination is less than the total installed cost o separatelypurchased components. The combination units install aster,more economically and take up less space in storage, transitand service. Each combined unit takes up a minimum o spaceon the crossarm and has a avorable weight distribution orminimal o-center loading. The eld-proven quality o both

    Over-the-Arm Type onlyCutout-Arrester

    Dimensions

    cutout and arrester assure consistent high perormance orthe combinations.

    These units include Chance cutouts tted with only OhioBrassMOV arresters, superseding previous silicon-carbideunits. For easy conversion to the new arrester designationsystem, reer to the Cutout Cross-Reerence Guide, Bulletin10-0203.

    For other dimensions see STANDARD Cutout, page 4.

    18

    DN

    EN

    FN

    125

    110 kV LIW (BIL) product is depicted.125 kV LIW (BIL) product varies slightly in appearance.

    Ordering InormationTo speciy a Cutout-Arrester Combination:

    1. Select a two-letter designation or the appropriate arresterrom the shaded section o the Table at let.

    2. Substitute the two letters or the 0 in the Base CatalogNo. or the appropriate Cutout listed on page 5, 7 or 9.

    G

    245/16" (617 mm)

    257/8" (657 mm)

    E

    207/8" (531 mm)

    261/4" (667 mm)

    kV LIW (BIL)110

    125

  • 7/30/2019 10AA

    11/12

    10A

    HUBBELL

    Power SystemsCHANCE CENTRALIA, MISSOURI

    JULY 2010

    Type C-Polymer CutoutsAccessories

    Catalog No.T7001325T7001326T7001327

    Terminal Connectors

    Min. Order Qty.

    101010

    Description

    Parallel-Groove Clamp, tin-plated bronze or No. 6 solid thru 4/0 ACSR or 250 kcmil strandedSmall Eyebolt or No. 8 solid thru 2/0 strandedLarge Eyebolt or No. 6 solid thru 4/0 ACSR or 250 kcmil stranded

    C2060283C2060280C2060299C2060632

    Mounting Brackets

    NEMA Heavy Duty B Bracket with 11/2" captive bolt or crossarm mountingExtended Crossarm Bracket (Horizontal section is 25/8" longer than NEMA B bracket)D Pole Mounting BracketCutout/Arrester Bracket complete with carriage bolts and backstrap

    Mounting Bracket Dimensions

    Wt. (lb./kg.)0.33 / 0.150.16 / 0.070.40 / 0.14

    2.84 / 1.293.75 / 1.707.67 / 3.484.00 / 1.81

    Universal Cutout Tool

    Ideal or Standard and Linkbreak 100 amp use holders (ABB,Chance, S&C) to easily lit out, place, *open and close. Inverted,

    secure method also ts Chance Electronic Sectionalizers.

    Cat. No. PSC4033484 (Wt. 4 oz.) See Tools Catalog Section 2100.*When opening a cutout, follow all work rules and OSHA regula-tions. Not for use with Loadbreak cutouts.

    Fargo Cutout Cover

    ONE PIECE WILDLIFE PROTECTOR

    Available as an Option on Standard and Linkbreak Type C-Polymer Cutouts(see pages 10AA-5 and 10AA-7), Cover also may be ordered as a separate lineitem as Catalog No. CC101. Material: Proprietary low track vinyl that is UV

    stabilized or long-term perormance. Gray color.

    Designed to provide protection for cutouts from accidental contact by squir-rels, birds or other wildlie.

    Universal one-piece design for easy installation or retrot. Fits Chance 15 kVStandard and Linkbreak Cutouts, both Polymer and Porcelain types.

    Fastener installation locations(2 asteners per assembly)

  • 7/30/2019 10AA

    12/12

    0AA-12

    CHANCE CENTRALIA MISSOURI HUBBELL

    Web: http://www.hubbellpowersystems.comE-mail: [email protected]

    MEXICO

    HUBBELL DE MEXICO, S.A. DE C.V.Av. Insurgentes Sur #1228, Piso 8Col. Tlacoquemacatl Del Valle

    Mexico, D.F. 03200Phone: 52-55-9151-9999Fax: 52-55-9151-9988Website: hubbell.com.mx

    UNITED STATES