Top Banner

of 58

103333596 Discrimination Setting

Jun 03, 2018

Download

Documents

mad_sam282729
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/12/2019 103333596 Discrimination Setting

    1/58

    0.1kA 1kA 10kA

    1E-2s

    0.1s

    1s

    10s

    100s

    1E3s

    1E4s

    Curva Tempo-Corrente FFF

    Discrimination of

    protection devices

    on installations

    Janet Roadway

    Product Manager, Power

    Breakers

  • 8/12/2019 103333596 Discrimination Setting

    2/58

    Topics of Discussion

    Explaining the terminology

    Degrees of discrimination

    Different techniques to achieve discrimination

    Backup protection

    Protection devices

    Any Questions?

  • 8/12/2019 103333596 Discrimination Setting

    3/58

  • 8/12/2019 103333596 Discrimination Setting

    4/58

    Protection - Overload

    What do we mean by a fault?

    Overload

    Operating condition in an electrically undamaged circuit which

    causes an current to flow in excess of the full load current

    Example: Starting condition during DOL start

    If this type of fault continues indefinitely because of an anomolous

    operating condition., damage begins to occur creating.

  • 8/12/2019 103333596 Discrimination Setting

    5/58

    ProtectionShort Circuit

    What do we mean by a fault?

    Short Circuit

    Operating condition in an electrically damaged circuit where there is an

    accidental or intentional connection by a relatively low resistance

    between two points of a circuit which are normally at different

    voltages

    This type of fault can generate high current flows, arcing and fire if

    not cleared quickly

  • 8/12/2019 103333596 Discrimination Setting

    6/58

    Discrimination

    Coordinate devices to:

    Guarantee safety for people and installations

    Identify and exclude only the zone affected by a problem

    Limiting the effects of a malfunction

    Reducing the stress on components in the affected zone

    Ensuring service continuity with good quality supply voltage

    Achieving a valid compromise between reliability, simplicity and cost

    effectiveness

  • 8/12/2019 103333596 Discrimination Setting

    7/58

    Explaining the terminology

    Discrimination or Selectivity

    To make it possible to isolate a part of an installation involved in a fault

    condition from the overall system such that only the device located

    immediately on the supply side of the fault intervenes

  • 8/12/2019 103333596 Discrimination Setting

    8/58

    Discrimination

    Needs

    Fast Fault Detection

    Fast Fault Elimination

    Let-Through Energy Reduction

    High Fault Current Withstanding

    GO!WAIT!

    FAULTCONTINUITY OF

    SERVICEFAULT DAMAGE

  • 8/12/2019 103333596 Discrimination Setting

    9/58

    A

    B CFault oc curs h ere

    X

    X X

    Explaining the terminology

  • 8/12/2019 103333596 Discrimination Setting

    10/58

    Degrees of discrimination

    Total Discrimination

    This means that the isolation described occurs for all fault

    levels possible at each point of the circuit

  • 8/12/2019 103333596 Discrimination Setting

    11/58

    AB

    Prospect ive FaultCurrent Icc

    I

    t

    Degrees of discrimination

  • 8/12/2019 103333596 Discrimination Setting

    12/58

    Degrees of discrimination

    Partial Discrimination

    This means that above certain current levels there is

    simultaneous operation of more than one protection device

  • 8/12/2019 103333596 Discrimination Setting

    13/58

    AB

    Prospect ive FaultCurrent Icc

    I

    t

    Degrees of discrimination

  • 8/12/2019 103333596 Discrimination Setting

    14/58

    Discrimination

    Traditional solutions

    Current discrimination

    Time discrimination

    Energy discrimination

    Zone (logical) discrimination

  • 8/12/2019 103333596 Discrimination Setting

    15/58

    Discrimination

    Current discrimination

    Discrimination among devices

    with different trip threshold

    setting in order to avoid

    overlapping areas.

    Setting different device tripthresholds for different

    hierarchical levels.

  • 8/12/2019 103333596 Discrimination Setting

    16/58

    Discrimination

    Current discrimination

    An example:

  • 8/12/2019 103333596 Discrimination Setting

    17/58

  • 8/12/2019 103333596 Discrimination Setting

    18/58

    Discrimination

    Time discrimination

    Discrimination among devices

    with different trip time settings

    in order to avoid overlapping

    areas

    Setting different device tripdelays for different hierarchical

    levels

  • 8/12/2019 103333596 Discrimination Setting

    19/58

    Discrimination

    Time discrimination

    An example:

    Electronic release L (Long delay) S (Short delay) I (IST)

    E4S 4000 PR111-LSI R4000

    E3N 2500 PR111-LSI R2500

    S7H 1600 PR211-LSI R1600

    Setting: 0.9

    Curve: B

    Setting: 1

    Curve: A

    Setting: 1

    Curve: A

    Setting: 8

    Curve: D

    Setting: 10

    Curve: C

    Off

    Off

    Setting: 10

  • 8/12/2019 103333596 Discrimination Setting

    20/58

    Discrimination

    Time discrimination

    Applications: low complexity plant

    Fault area: short circuit and overload

    Discrimination limit current: low, depending

    on the Icw of the upstream device

    Discrimination levels: low, depending on the network

    Devices: ACBs, MCCBs and devices with adjustable

    time curves

    Feasibility & discrimination study: easy

    Customer cost: medium

  • 8/12/2019 103333596 Discrimination Setting

    21/58

    Types of Discrimination

    Energy Discrimination

    Many Low Voltage protection devices such as Circuit breakers

    and Fuses have the ability to limit the peak of the current let

    through them to a value lower than the prospective short circuit

    peak.

    Any protective device which clears short circuits in less than 1/2

    cycle of the sinusoidal wave (i.e 10mS for 50Hz) will current limit

    to a certain degree

    Energy based discrimination is the only way to determine true

    discrimination between current-limiting devices

  • 8/12/2019 103333596 Discrimination Setting

    22/58

    Discrimination

    Energy discrimination

    Discrimination among devices with different mechanical and

    electrical behaviour depending on energy level

    It is necessary to verify that the let-through energy of the circuit-

    breaker upstream is lower than the energy value needed to complete

    the opening of the CB downstream

  • 8/12/2019 103333596 Discrimination Setting

    23/58

    Discrimination

    Energy discrimination

    An example:Time-currents Curve

    Energy

    discrimination

    up to 24 kA

  • 8/12/2019 103333596 Discrimination Setting

    24/58

    Discrimination

    Energy discrimination

    Applications: medium complexity networks

    Fault area: Short circuit only

    Discrimination limit current: medium/high

    Discrimination levels: medium, CBs size

    dependent

    Devices: ACBs, MCCBs, MCBs & Fuses

    Feasibility & discrimination study: medium complexity Customer cost: medium

  • 8/12/2019 103333596 Discrimination Setting

    25/58

    Discrimination

    Zone discrimination

    Discrimination among devices in order to isolate the faultzone keeping unchanged feeding conditions of maximum

    number of devices

    Zone discrimination is implemented by means of an

    electrical interlock between devices

    Zone

    1

    Zone

    2

    Zone

    3

  • 8/12/2019 103333596 Discrimination Setting

    26/58

    Discrimination

    Zone discrimination

    Applications: high complexity plant

    Fault area: short circuit, overload, ground fault

    Discrimination limit current: medium,

    depending on Icw

    Discrimination levels: high

    Devices: ACBs, MCCBs with dialogue and control

    features Feasibility & discrimination study: complex

    Customer cost: high

  • 8/12/2019 103333596 Discrimination Setting

    27/58

    Explaining the terminology

    Cascading or Backup protection

    Uses supply circuit breakers or fuses with currentlimitation effects to protect downstream devices fromdamage

    The amount of energy let through (i2t) by the supply

    device needs to be lower than that which can bewithstood without damage by the device on the load side

    By using this effect it is possible to install devicesdownstream that have short circuit breaking capacities

    lower than the prospective short circuit current

  • 8/12/2019 103333596 Discrimination Setting

    28/58

    Back-up protection/Cascading

    Back-up protection or Cascading is recognised and

    permitted by the 16th Edition of the IEE WiringRegulations 434-03-01 and is covered by IEC 364-4-437

    standard

  • 8/12/2019 103333596 Discrimination Setting

    29/58

    Why Use Back-up Protection?

    Substantial savings can be made on downstream

    switchgear and enclosures by using lower short circuitratings

    Substantial reductions in switchgear volumes can also

    result

  • 8/12/2019 103333596 Discrimination Setting

    30/58

    What about Discrimination?

    Backup protection should not be confused with

    discrimination.

    Backup protection does not infer discrimination can be

    achieved but in practice, discrimination is normally

    achieved up to the maximum breaking capacity of the

    downstream device

    GO!WAIT!

    FAULTCONTINUITY OFSERVICE FAULT DAMAGE

    BACKUPDiscrimination

  • 8/12/2019 103333596 Discrimination Setting

    31/58

    Practical Example

    Problem:

    Installation requires the use of Busbar rather than cable

    to distribute electrical power.

    Fault level calculations reveal 25kA prospective fault

    level at the point of installation of standard MCB

    distribution board

  • 8/12/2019 103333596 Discrimination Setting

    32/58

    Practical Example

    Solution - Using a standard Isolator as the distribution board

    incoming device - all the MCBs would need to be

    25kA or above

    Using an MCCB as the incoming device such as anABB Tmax T3N250TMD100, 6kA S200 MCBs could

    be safely used

  • 8/12/2019 103333596 Discrimination Setting

    33/58

    A word of caution ...

    Back-up protection can only be checked by laboratory

    tests and so only device combinations specified by themanufacturer can be guaranteed to provide co-

    ordination of this type.

  • 8/12/2019 103333596 Discrimination Setting

    34/58

    Types of protection available

    Fuses

    Miniature Circuit Breakers

    Moulded Case Circuit breakers

    Air Circuit breakers

  • 8/12/2019 103333596 Discrimination Setting

    35/58

    Typical fuse

    Current (A)

    Time (s)

    Ultra Reliable

    Standard CharacteristicHigh current limitation

    effects

    High threshold on low

    overloads ( clears overloads

    at approx 1.45x rated FLC)

  • 8/12/2019 103333596 Discrimination Setting

    36/58

    Fuseless technology

    Two main types:-

    Thermomagnetic protection-

    MCB and lower rated MCCB

    plus older type protection

    relays

    Electronic protection

    Microprocessor based relays

    fed from CTs either external to

    switches or integral within a

    circuit breaker

  • 8/12/2019 103333596 Discrimination Setting

    37/58

    Thermomagnetic

    Thermal

    curve

    Time (s)

    Current (A)

    Magnet ic c urve

    Offer thermal longtime

    overcurrent protection using Bi-

    metal technology ( operates at1.3x FLC)

    Uses the magnetic effect of

    short circuit currents to offer

    shorttime short circuit

    protection

  • 8/12/2019 103333596 Discrimination Setting

    38/58

    Electronic Relays

    Time (s)

    Current (A)

    Overcurrent functions such as:-

    Long time overcurrent

    Short time instantaneous

    protection

    Short time time delayed

    protection

    Ground fault or Earth fault

    protection

  • 8/12/2019 103333596 Discrimination Setting

    39/58

  • 8/12/2019 103333596 Discrimination Setting

    40/58

    Protection releases: general features

    Complete set of advanced protection functionsRc D U

    OT UV OV

    RV

    RP

    MORE

    Complete set of standard protection functions

    MORE

    Complete set of measurements functions

    MORE

    A V Hz

    W VA VAR E THD

  • 8/12/2019 103333596 Discrimination Setting

    41/58

    Data logger:a professional built-in fault recorder.

    BACK

    Data logg er: a profess ional bui l t- in faul t recorder.

    Standard in PR122 and PR123

    Recording of 8 measurements (currents and voltages);

    Configurable trigger (i.e. During a fault);

    Sampling frequency up to 4.800kHz;

    Sampling time up to 27s;Output data through SD-Pocket or TestBus2.

    Exclus ive from ABB SACE.

    -500

    -400

    -300

    -200

    -100

    0

    100

    200

    300

    400

    500

    time

    Voltage L1-L2

    Neutral

    Current phase 1

    Current phase 2

    Current phase 3

    C l i

  • 8/12/2019 103333596 Discrimination Setting

    42/58

    So what is the secret to achieving a successful

    discrimination study

    The secret is to be aware of the capability of thetechnology you are using and to design your installation

    within the limits of the protection you have chosen

    Conclusion

  • 8/12/2019 103333596 Discrimination Setting

    43/58

  • 8/12/2019 103333596 Discrimination Setting

    44/58

    Double S*

    Used to obtain discrimination in critical conditions

    Double G*

    Two different protection curves, one with the signal coming from

    internal CTs and the other from an external toroid

    Dual Setting*

    Two different set of protection parameters in order to protect in the best

    way, two different network configurations (e.g. normal supply and

    emergency supply)

    Protectionreleases: news on standard protection functions

    * = These features are available on PR123/P

    BACK

    MORE

    MORE

    MORE

  • 8/12/2019 103333596 Discrimination Setting

    45/58

  • 8/12/2019 103333596 Discrimination Setting

    46/58

    Protection releases: news on standard protection functions

    Without double S

  • 8/12/2019 103333596 Discrimination Setting

    47/58

    Protection releases: news on standard protection functions

    With double S

    BACK

  • 8/12/2019 103333596 Discrimination Setting

    48/58

    Double G

    Its possible to protect the network, with the same protection

    release, against earth fault both upstream and downstream the

    circuit-breaker

    Restricted Earth Fault: the fault is upstream the LV circuit-

    breaker

    Protection releases: news on standard protection functions

    Restricted Earth Fault

    MV LV

  • 8/12/2019 103333596 Discrimination Setting

    49/58

    Double G

    Its possible to protect the network, with the same protection

    release, against earth fault both upstream and downstream the

    circuit-breaker

    Restricted Earth Fault: the fault is upstream the LV circuit-

    breaker Unrestricted Earth Fault: the fault is downstream the LV circuit-

    breaker

    Protection releases: news on standard protection functions

    Unrestricted Earth Fault

    MV LV

  • 8/12/2019 103333596 Discrimination Setting

    50/58

    Double G

    The combination of both Unrestricted and Restricted Earth Fault

    protection is named Source Ground Return. The new PR123/P

    is able to detect and to discriminate both earth faults

    If the fault is downstream the LV circuit-breaker the PR123/P will

    trip Emax circuit-breaker

    Protection releases: news on standard protection functions

    L1

    L2

    L3

    NPE

    Trafo secondary windings

    External toroid

    Emax internal CTs

  • 8/12/2019 103333596 Discrimination Setting

    51/58

    Double G

    The combination of both Unrestricted and Restricted Earth Fault

    protection is named Source Ground Return. The new PR123/P

    is able to detect and to discriminate both earth faults

    If the fault is downstream the LV circuit-breaker the PR123/P will

    trip Emax circuit-breaker

    If the fault is upstream the LV circuit-breaker the PR123/P will trip

    the MV circuit-breaker

    Protection releases: news on standard protection functions

    L1

    L2

    L3

    NPE

    Trafo secondary

    windings

    External

    toroid

    Emax internal CTs

    BACK

  • 8/12/2019 103333596 Discrimination Setting

    52/58

    Dual setting

    It allows to program twodifferent protection parametersets in order to adapt them tothe different networkconfigurations

    The most representative

    example is a network withsupply by the utility and byemergency generator

    With dual setting thediscrimination between CBs isguaranteed in both network

    conditions

    Protection releases: news on standard protection functions

  • 8/12/2019 103333596 Discrimination Setting

    53/58

    Dual setting

    Normal network condition

    CB A >>> closed

    CB B >>> open

    Discrimination is guaranteed

    between A and C

    Protection releases: news on standard protection functions

  • 8/12/2019 103333596 Discrimination Setting

    54/58

    Dual setting

    Emergency networkcondition

    CB A >>> open

    CB B >>> closed

    Discrimination is not

    guaranteed between B and

    C, due to the low settings

    (protection of the generator)

    of C protection functions

    Protection releases: news on standard protection functions

  • 8/12/2019 103333596 Discrimination Setting

    55/58

    P t ti l d d t ti f ti

  • 8/12/2019 103333596 Discrimination Setting

    56/58

    Protectionreleases: advanced protection functions

    BACK

    Residual current

    Protection against directional short-circuit with adjustable time-delay

    Protection against phase unbalance

    Protection against overtemperature (check)

    Protection against undervoltage

    Protection against overvoltage

    Protection against residual voltage

    Protection against reverse active power

    Thermal memory for functions L and S

    Underfrequency

    Overfrequency

    D

    U

    OT

    UV

    OV

    RV

    RP

    M

    UF

    OF

    RC

    P t ti l t f ti

  • 8/12/2019 103333596 Discrimination Setting

    57/58

    Protectionreleases: measurements functions

    BACK

    Voltage (phase-phase, phase-neutral, residual). Accuracy: 1%

    Power (active, reactive, apparent) Accuracy: 2,5%

    Power factor Accuracy: 2,5%

    Frequency and peak factor Accuracy: 0,1Hz

    Energy (active, reactive, apparent, meter) Accuracy: 2,5%

    Harmonics calculation (display of waveforms and RMS spectrum up to 40 th@50Hz)

    Current (phases, neutral, earth fault). Accuracy: 1,5%

    Protection releases: t f ti

  • 8/12/2019 103333596 Discrimination Setting

    58/58

    Protectionreleases: measurements functions

    BACK

    Voltage (phase-phase, phase-neutral, residual). Accuracy: 1%

    Power (active, reactive, apparent) Accuracy: 2,5%

    Power factor Accuracy: 2,5%

    Frequency and peak factor Accuracy: 0,1Hz

    Energy (active, reactive, apparent, meter) Accuracy: 2,5%

    Harmonics calculation (display of waveforms and RMS spectrum up to 40 th@50Hz)

    Current (phases, neutral, earth fault). Accuracy: 1,5%