Tips & Insights to Prepare for Sanitary Survey Inspections

(TIPSSI) What to expect What to have on hand What to check

For Florida’s Water SectorIn coordination with FRWA and FDEP

Updated 1/11

Page 2: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 2

Sanitary Survey Form

Standard Info~Current Facility ID

Capacity, etc.,

~Well Construction~Treatment Process~Storage Data~Distribution System

Page 3: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 3

Paper Work (part 1…) Well Construction Information Cross Connection Control Plan. Bacteriological Sampling Plan System Diagrams

Flow Plans, Schematics, etc.)

MORs, Sampling Data Submittals DEP Notices, Correspondence, etc.

Page 4: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 4

Paper Work (part 2…) Uni- Directional Flushing Program Pump Specifications Valve Maintenance / Exercising Plan Tank Inspection Report

Signed, Sealed by a P.E. Within Last 5 Years

Auxiliary Power Plan Emergency Response Plan (ERP)

Page 5: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/235

Annual Flow Data

Flows rates determine if appropriate pumping capacity, storage capacity and auxiliary power requirements are being met.

Page 6: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 6

O & M Log BooksLog books must be maintained at the treatment plant and current to the most recent visit.

Page 7: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 7

Wells

Housekeeping

Needed

All wells should be equipped with a well casing vent. In cases with no vent the disinfection port may be converted to act as a vent.

Page 8: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 8

Flow Meters

Flow meters must be checked periodically for accuracy.

Page 9: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 9

Piping• All piping must be screened (especially dump lines, overflow pipes, vents, etc.) and , labeled & color-coded (ex.: reuse = purple).

Page 10: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 10

Lime Hoppers

Lime hoppers should be covered. The rooms should be kept clean. A ventilating fan is recommended.

Page 11: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 11

Additives/Lubricants

Oil -lubed pumps must utilize food grade oils.

NSF Standard 60 Approved (or equivalent).

Hypo chlorination systems must use NSF 60 approved chlorine.

Page 12: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 12

Maintenance

Clean, well- maintained facilities let the inspector know you share their dedication to providing safe drinking water.

Page 13: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 13

Safety Be sure sources of contamination are not stored in close proximity to wells.

Page 14: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 14

Safety

Prevent unauthorized entry. Consider fences, locked doors, gates, alarms, etc.

Open windows at a well house encourage unwanted visitors.

Page 15: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 15

Safety

If fencing is not an option, other forms of well protection are available.

Page 16: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 16

Safety Devices

SCBA* is required at all Gas Chlorination Facilities.

…MUST be inspected often (according to NIOSH guidelines).

Page 17: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 17

Chlorine Rooms

Chlorine rooms must be designed to meet

Ten State Standards

Page 18: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 18

Chlorine Rooms

Open drains in gas chlorine rooms are not acceptable (why not?).

Page 19: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 19

Chlorine Rooms

All gas cylinders should be properly secured to a wall…

And kept out of direct sunlight.

Page 20: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 20

Chlorine Rooms Hypochlorination

tanks must meet with ANSI / NSF 60 standards.

All openings must be protected and the tank kept out of direct sunlight.

Page 21: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 21

Chlorine Rooms Exhaust vents

must not discharge near entrances.

Chlorine vents must be low …preferably as far as possible from entrances.

Chlorine Rooms

Page 22: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 22

Plants Labeling of all

equipment and piping gets extra points from the inspector.

Operating Pressures and chemical feed rates will be noted.

Page 23: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 23

Alarms Chlorine alarms must be

fully operational at all times;

Must be tested frequently to insure proper working condition.

Page 24: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 24

Elevated Storage Tanks

Overflows should be brought down to 12” to 24” above ground level

Discharge should be to a splash plate

Page 25: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 25

Elevated Storage Tanks

Storage tanks with elevated overflow outlets must have both a flapper valve and a screen.

Page 26: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 26

Elevated Storage Tanks

Some systems become creative in meeting certain requirements. This may not work as well as intended.

Page 27: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 27

Storage Tanks All vents must be

properly screened to help prevent contamination.

Tanks should be kept in good condition w/a proper pressure release valve.

Page 28: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 28

Concerns noted on Report:

“DEFICIENCY 1: Storage tank protectionPipe inlet openings should be sealed from rainwater. 

RULE REFERENCE: 62‑555.330(3) RECOMMENDED ACTION: Refer to

Ten State Standards: finished water structures shall have suitable watertight roofs which exclude birds, animals, insects, and excessive dust.Please correct by August 31, 2011.”

 

Page 29: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 29

Site Review

Surrounding areas are noted for possible sources of contamination.

Page 30: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

04/11/23 30

TestingChlorine and pH readings will be conducted during the survey. Proper testing equipment must be on-hand and properly maintained.

Page 31: 1 Tips & Insights to Prepare for Sanitary Survey Inspections ( TIPSSI ) What to expect What to have on hand What to check For Florida’s Water Sector In.

31

Storage Tanks

Some pictures need

no explanation.