Top Banner
A new control method for Dynamic Voltage Restorer with asymmetrical inverter legs based on fuzzy logic controller H. Ezoji * , A. Sheikholeslami, M. Rezanezhad, H. Livani Babol University of Technology, Department of Electrical and Computer Engineering, P.O. Box 484, Babol, Iran article info Article history: Received 10 July 2009 Received in revised form 18 November 2009 Accepted 30 January 2010 Available online 4 February 2010 Keywords: Dynamic Voltage Restorer (DVR) Asymmetrical voltage-source inverter Fuzzy logic Hysteresis controller abstract Dynamic Voltage Restorer (DVR) is used in power distribution system to protect sensitive loads in voltage disturbances. The performance of DVR is related to the adopted configura- tion and control strategy used for inverters. In this paper, an asymmetrical voltage-source inverter controlled with fuzzy logic method based on hysteresis controller, is used to improve operation of DVR to compensate voltage sag/swell. Simulation results using MAT- LAB/Simulink are presented to demonstrate the feasibility and the practicality of the pro- posed novel Dynamic Voltage Restorer topology. Total Harmonic Distortion (THD) is calculated. The simulation results of new DVR presented in this paper, are found quite sat- isfactory to eliminate voltage sag/swell. Ó 2010 Elsevier B.V. All rights reserved. 1. Introduction Due to the advent of a large numbers of sophisticated electrical and electronic equipments, such as computers, program- mable logic, electrical drives etc., power quality problems like voltage sag, voltage swell and harmonic distortion can cause serious problems to industrial and commercial electrical consumers [1,2]. For example, some special facilities are sensitive to voltage disturbances. Therefore, in such cases using compensator for the sensitive loads is necessary. There are some solutions to these problems. Installation of Dynamic Voltage Restorer (DVR) for sensitive loads can be considered as a solution [1–3]. DVR is a custom power device, which is connected to the load through a series transformer. To compensate voltage dis- turbances, series voltage is injected through the transformer by a voltage-source converter connected to dc power source [1,2]. The first DVR was installed in North Carolina, for the rug manufacturing industry. Another was installed to provide service to a large dairy food processing plant in Australia [4]. A DVR consists of a voltage-source inverter, a series-connected injection transformer, an inverter output filter, and an en- ergy-storage device that is connected to the dc link [1–5]. The voltage-source converter is a power electronic device, which can generate a sinusoidal voltage with any required magnitude, frequency and phase angle. This device employs insulated gate bipolar transistors (IGBT) as switches [5]. This converter injects a dynamically controlled voltage in series with the supply voltage through the three single-phase trans- formers to correct the load voltage. The main functions of the injection transformer include voltage boost and electrical iso- lation [6]. The DC side of the converter is connected to a DC energy-storage device. Energy-storage devices, such as batteries or super-conducting magnetic energy-storage systems (SMES) are required to provide active power to the load when voltage 1569-190X/$ - see front matter Ó 2010 Elsevier B.V. All rights reserved. doi:10.1016/j.simpat.2010.01.017 * Corresponding author. Tel./fax: +98 111 323 9214. E-mail address: [email protected] (H. Ezoji). Simulation Modelling Practice and Theory 18 (2010) 806–819 Contents lists available at ScienceDirect Simulation Modelling Practice and Theory journal homepage: www.elsevier.com/locate/simpat
14
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 1-s2-0-S1569190X10000298-main

Simulation Modelling Practice and Theory 18 (2010) 806–819

Contents lists available at ScienceDirect

Simulation Modelling Practice and Theory

journal homepage: www.elsevier .com/locate /s impat

A new control method for Dynamic Voltage Restorer withasymmetrical inverter legs based on fuzzy logic controller

H. Ezoji *, A. Sheikholeslami, M. Rezanezhad, H. LivaniBabol University of Technology, Department of Electrical and Computer Engineering, P.O. Box 484, Babol, Iran

a r t i c l e i n f o

Article history:Received 10 July 2009Received in revised form 18 November 2009Accepted 30 January 2010Available online 4 February 2010

Keywords:Dynamic Voltage Restorer (DVR)Asymmetrical voltage-source inverterFuzzy logicHysteresis controller

1569-190X/$ - see front matter � 2010 Elsevier B.Vdoi:10.1016/j.simpat.2010.01.017

* Corresponding author. Tel./fax: +98 111 323 92E-mail address: [email protected] (H. Ezoji).

a b s t r a c t

Dynamic Voltage Restorer (DVR) is used in power distribution system to protect sensitiveloads in voltage disturbances. The performance of DVR is related to the adopted configura-tion and control strategy used for inverters. In this paper, an asymmetrical voltage-sourceinverter controlled with fuzzy logic method based on hysteresis controller, is used toimprove operation of DVR to compensate voltage sag/swell. Simulation results using MAT-LAB/Simulink are presented to demonstrate the feasibility and the practicality of the pro-posed novel Dynamic Voltage Restorer topology. Total Harmonic Distortion (THD) iscalculated. The simulation results of new DVR presented in this paper, are found quite sat-isfactory to eliminate voltage sag/swell.

� 2010 Elsevier B.V. All rights reserved.

1. Introduction

Due to the advent of a large numbers of sophisticated electrical and electronic equipments, such as computers, program-mable logic, electrical drives etc., power quality problems like voltage sag, voltage swell and harmonic distortion can causeserious problems to industrial and commercial electrical consumers [1,2].

For example, some special facilities are sensitive to voltage disturbances. Therefore, in such cases using compensator forthe sensitive loads is necessary. There are some solutions to these problems. Installation of Dynamic Voltage Restorer (DVR)for sensitive loads can be considered as a solution [1–3].

DVR is a custom power device, which is connected to the load through a series transformer. To compensate voltage dis-turbances, series voltage is injected through the transformer by a voltage-source converter connected to dc power source[1,2].

The first DVR was installed in North Carolina, for the rug manufacturing industry. Another was installed to provide serviceto a large dairy food processing plant in Australia [4].

A DVR consists of a voltage-source inverter, a series-connected injection transformer, an inverter output filter, and an en-ergy-storage device that is connected to the dc link [1–5].

The voltage-source converter is a power electronic device, which can generate a sinusoidal voltage with any requiredmagnitude, frequency and phase angle. This device employs insulated gate bipolar transistors (IGBT) as switches [5]. Thisconverter injects a dynamically controlled voltage in series with the supply voltage through the three single-phase trans-formers to correct the load voltage. The main functions of the injection transformer include voltage boost and electrical iso-lation [6]. The DC side of the converter is connected to a DC energy-storage device. Energy-storage devices, such as batteriesor super-conducting magnetic energy-storage systems (SMES) are required to provide active power to the load when voltage

. All rights reserved.

14.

Page 2: 1-s2-0-S1569190X10000298-main

Fig. 1. Typical DVR circuit topology (single-phase representation).

H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819 807

sags occur [7]. In this paper, battery is used as a source of the DC voltage for the VSC. The output of the inverter (before thetransformer) is filtered by Passive filters in order to reject the switching harmonic components from the injected voltage [5].A typical DVR connected to the distribution system is shown in Fig. 1.

Different control strategies were proposed for DVR. Voltage-Space Vector PWM was implemented in [8]. Estimation ofsymmetrical components of voltage to control DVR is used in [9]. Hysteresis voltage control can be adopted to improve volt-age quality of sensitive loads [2,10].

In this paper, a DVR with a new inverter topology is presented to suppress the load harmonics and to compensate thevoltage disturbances. The adopted voltage-source inverter is based on an asymmetrical inverter leg to achieve five voltagelevels in output voltage. This inverter has less voltage harmonics generated on the ac terminal of the inverter compared withtwo-level PWM operation. In the adopted inverter, on the contrary of conventional inverter, no flying capacitor and clampeddiode are used in the circuit configuration. The adopted control scheme is fuzzy logic controller based on hysteresis method.

2. Proposed circuit configuration

Voltage-Source Converter (VSC) is one of the main parts of DVR. Commonly, a symmetrical VSC with two-level outputvoltage is utilized in DVR. In this paper, a new asymmetrical Voltage-Source Converter is proposed to improve the behaviorof DVR. The single–phase configuration of the proposed inverter for DVR is depicted in Fig. 2.

The voltage stress of power switches Sa2 and S0a2 is equal to half of the dc bus voltage and the voltage stress of activeswitches Sa1, S0a1, Sb and S0b is equal to dc bus voltage. In high switching frequency, the power switches placed in arms aand b produce five levels in the out put inverter. If the voltage of two capacitors, Vc1 and Vc2 are equal, five voltage levels(Vdc, Vdc/2, 0, �Vdc, �Vdc/2) are produced in the output of inverter [11].

Fig. 2. Adopted single-phase DVR based on asymmetrical inverter legs.

Page 3: 1-s2-0-S1569190X10000298-main

Fig. 3. Equivalent circuit of the adopted DVR.

808 H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819

To produce the mentioned voltage levels in the output, the switches can be defined as follows:

Fig. 4.gb = 1);

Sxy þ S0xy ¼ 1 ð1Þ

Therefore, the equivalent circuit of converter can be presented as shown in Fig. 3.Here ga and gb represent the switches in leg a and leg b. The ac side to neutral point voltages can be expressed as:

ma0 ¼gaðga þ 1Þ

2mc1 �

gaðga � 1Þ2

mc1 ð2Þ

mb0 ¼gbðgb þ 1Þ

2mc1 �

gbðgb � 1Þ2

mc1 ð3Þ

Operating states of the adopted inverter: (a) state 1 (ga = 1, gb = �1); (b) state 2 (ga = 0, gb = �1); (c) state 3 (ga = �1, gb = �1); (d) state 4 (ga = 1,(e) state 5 (ga = 0, gb = 1); (f) state 6 (ga = �1, gb = 1).

Page 4: 1-s2-0-S1569190X10000298-main

Fig. 5. Pre-sag compensation technique.

H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819 809

The ac terminal voltage Vab is expressed as:

mab ¼ ma0 � mb0 ¼ga � gb

2mdc þ

g2a � g2

b

2Dm ð4Þ

If the voltage of capacitors c1 and c2 are equal, therefore, the voltage variation between two capacitor voltages is zero(Dv = 0). Then, the Eq. (4) can be written as follows:

mab ¼ ma0 � mb0 ¼ga � gb

2mdc ð5Þ

There are three possible values for switching function ga and two possible values for gb. Therefore, five different voltage lev-els, Vdc, Vdc/2, 0, �Vdc/2 and�Vdc, can be generated on the ac terminal voltage Vab [10]. Fig. 4 gives six valid operating states inthe adopted inverter to generate five different voltage levels on the ac side of inverter. During the positive mains voltage, theoperating states 1–3 are used to generate three voltage levels. Vdc, Vdc/2 and 0, on the ac side to control the inverter. Duringthe negative mains voltage, the operating states 4–6 are selected to generate another three voltage levels, 0, �Vdc/2 and �Vdc,on the ac side of the inverter.

3. Conventional control strategy

The possibility of voltage sag compensation can be limited by a number of factors including finite DVR power rating, dif-ferent load conditions, and different types of voltage sag. Some loads are very sensitive to phase angle jump and others aretolerant to phase angle jump. Therefore, the control strategy depends on the type of load characteristics. There are three dis-tinguishing methods to inject DVR compensating voltage, that is, pre-sag compensation method, in-phase compensationmethod, and minimal energy method [12–14]. In this paper, the adopted control strategy is pre-sag compensation to main-tain load voltage at pre fault value.

3.1. Pre-sag compensation technique

Most nonlinear loads such as thyristor-controlled loads which use the supply voltage phase angle as a set point are sen-sitive to phase jumps. To overcome this problem, this technique compensates the difference between the sagged and the pre-sag voltages by restoring the instantaneous voltages to the same phase and magnitude as the nominal pre-sag voltage. Thedrawback is the capacity limitation of energy-storage device for the injection of real power.

Fig. 5 shows the single-phase vector diagrams of the pre-sag compensation where Vs; VL; VDVR; and VL pre-sag mean themagnitudes of the voltage vectors that are explained in Fig. 5 and Eq. (3). In this method, the load voltage can be restoredideally. When a fault occurs in other lines, the left hand side voltage of DVR, i.e., Vs drops and the DVR injects a series voltage,VDVR through the injection transformer as:

VDVR ¼ VL � Vs ð6Þ

a ¼ tan�1 Vpre-sag sinðdÞVpre-sag cosðdÞ � Vsag

� �ð7Þ

3.2. In-phase compensation technique

In in-phase compensation technique shown in Fig. 6, the injected DVR voltage (VDVR) is in phase with measured supplyvoltage (VS) regardless of the load current and the pre-sag voltage.

Page 5: 1-s2-0-S1569190X10000298-main

Fig. 6. In-phase compensation technique.

810 H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819

IL and u are load current and load power angle, respectively. The magnitude of VDVR is so that the magnitude of VL is 1 pu.

VDVR ¼ 1� Vs ð8Þ

The advantage of this method is that the magnitude of the injected voltage is minimum. Therefore, for a given load cur-rent and voltage sag the apparent power of DVR is minimized.

3.3. Minimal energy technique

Another existing control strategy is to use as much reactive power as possible to compensate the sag. Therefore, the DVRvoltage is controlled in such a way that the load current is in phase with the grid voltage after the sag. As long as the voltagesag is quite shallow, it is possible to compensate sag with pure reactive power and therefore, the compensation time is notlimited. Fig. 7 shows the phasor diagram for the minimal energy control strategy. In this diagram, d, a are the angles of VL andVDVR, respectively. In this case, a can be obtained as:

a ¼ p2�uþ d ð9Þ

and the d is calculated by the following equation:

d ¼ u� cos�1 VL � cosðuÞVs

� �ð10Þ

If the supply voltage parameters satisfy the following condition then the value of d is feasible.

VL � cosðuÞ � Vs ð11Þ

Inequality (11) means that the level of voltage sag is shallow sag. Therefore, injected active power of DVR is zero and theoptimum a is obtained from (9). If inequality (11) is not satisfied then level of voltage sag will be deep sag and injected activepower is not zero.

Fig. 7. Minimal energy compensation technique.

Page 6: 1-s2-0-S1569190X10000298-main

Fig. 8. Control structure of DVR.

H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819 811

4. Proposed method

The main considerations for the control system of a DVR include: detection of the start and finish of the sag, voltage ref-erence generation, transient and steady-state control of the injected voltage, and protection of the system. The control sys-tem presented in Fig. 8 is used to control the DVR.

As it is shown in Fig. 8, Vs is the supply voltage used to detect voltage sag and VL is the load voltage which is used as afeedback of the output voltage.

A new hysteresis voltage control using a user defined fuzzy logic controller in Matlab software is implemented to improvethe DVR performances in fault and abnormal conditions. The following sections, describe the controller unit of DVR indetailed.

4.1. Voltage sag detection

The essential part for well-performance of controller in DVR is the sag detection circuit. Voltage sag must be detected fastand corrected with a minimum of false operations. The voltage sag detection method is based on Root Means Square (RMS)of the error vector which allows detection of symmetrical and asymmetrical sags, as well as the associated phase jump. Thecontroller system is presented in Fig. 8.

The three-phase supply voltage is transformed from abc to odq frame using Park transformation. Phase Locked Loop (PLL)is used to track supply voltage phase. The park transformation matrix is shown as follows:

mdmqmo½ � ¼ffiffiffi23

r cosðhÞ cos h� 2p3

� �cos h� 4p

3

� �sinðhÞ sin h� 2p

3

� �sin h� 4p

3

� �1ffiffi2p 1ffiffi

2p 1ffiffi

2p

264

375

ma

mb

mc

264

375 ð12Þ

h ¼ h0 �Z t

0xt dt

jVsj ¼ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiV2

d þ V2q

qð13Þ

Closed loop load voltage feedback is added, and is implemented in the o-d-q frame in order to minimize any steady-stateerror in the fundamental component [2,15,16].

When the grid voltage is normal, the DVR system is held in a null state to lower its losses. When voltage sag is detected,the DVR switches into active mode to react as fast as possible to inject the required ac voltage. The injection voltage is alsogenerated according to the difference between the reference load voltage and the supply voltage and it is applied to the VSCto produce the preferred voltage, using the Hysteresis Voltage Control based on fuzzy logic controller.

4.2. Hysteretic voltage control combined with fuzzy logic controller

There are different methods to produce the signals needed for VSC switching. This part presents a new control approachwhich is based on hysteresis voltage control combined with fuzzy logic control method. Comparing with previous ap-proaches the proposed method is able to extend its control capability even to those operating conditions where linear controltechniques fail.

Page 7: 1-s2-0-S1569190X10000298-main

Fig. 9. Hysteresis band voltage control.

812 H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819

4.2.1. Hysteretic voltage controlThe hysteresis voltage control method is one of the several approaches which have been introduced to produce switching

signals.A hysteresis band voltage control scheme composed of a hysteresis band around the reference voltage is shown in Fig. 9.

Three-phase reference Voltages are obtained by subtraction of pre-sag voltages from three-phase detected voltages. Thismethod is based on the difference between the voltage produced by the converter and the reference voltage [2,17]. Theupper and lower bands are defined by hysteresis band width (HB). As long as the difference between reference voltageand the produced converter voltage remains between the bands, the switching signal will not change. If the differencereaches to the upper or (lower) bands, the signal causes the switch to turn off (turn on) [2,17].

The switching frequency of the hysteresis band voltage control method described above depends on how fast the voltagechanges from the upper limit of the hysteresis band to the lower limit of the hysteresis band, or vice versa. Therefore, theswitching frequency does not remain constant throughout the switching operation, but varies along with the voltage refer-ence wave form.

Fig. 10. Schematic of implemented method.

Fig. 11. Block diagram of fuzzy controller.

Page 8: 1-s2-0-S1569190X10000298-main

Table 1Rule bases of voltage fuzzy controller.

NL NS Z PS PL

N Sa1, Sa2, S0b Sa1, S0a2, S0b Sa1, Sa2, Sb Sa1, Sa2, Sb S0a1, Sb

Z Sa1, Sa2, S0b Sa1, S0a2, S0b Sa1, Sa2, Sb Sa1, S0a2, Sb S0a1, Sb

P Sa1, Sa2, S0b Sa1, Sa2, Sb Sa1, Sa2, Sb Sa1, S0a2, Sb S0a1, Sb

H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819 813

The hysteresis band voltage control is characterized by unconditioned stability, very fast response, needless from anyinformation about system parameters and good accuracy On the other hand, the basic hysteresis technique also exhibits sev-eral undesirable features; such as uneven switching frequency that causes acoustic noise and difficulty in designing inputfilters [2,18].

Fig. 12. Input and output membership functions of voltage controller.

Page 9: 1-s2-0-S1569190X10000298-main

Table 2Case study parameters.

Parameter Value

Supply voltage (VL–L) 400 VVdc, Cf, Rf 200 V, 500 lF, 1 OSeries transformer (VPh–Ph) 96/240 VZTrans 0.004 + j 0.008RLoad, LLoad 31.84 O, 0.139 H

814 H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819

4.2.2. Fuzzy logic controllerThe switching frequency of hysteresis control method with constant band width is high. This will make the system loss

considerable. In order to produce a five level voltage at the converters output, to reduce the switching losses and to improvethe behavior of DVR, fuzzy controller method is utilized. Fuzzy logic control (FLC) is based on mamdani’s system.

The fuzzy controller has two inputs:

� The difference between the injected voltage and the reference voltage.� The derivation of the error.

Moreover it has six outputs, the driving signals of switches. Considering the difference between converter output voltageand reference voltage and its derivation, the controller determines the voltage condition and directly commands theswitches to turn on or off. In conventional hysteresis voltage control, switching signals are determined when the errorreaches to upper or lower hysteresis band but as it is shown in Fig. 9, in this new proposed method, switching commandsare determined according to the error and derivation of the error. The schematic of implemented method is shown in Fig. 10.

The fuzzy logic controller consists of three stages: the fuzzification, rule execution, and defuzzification. In the first stage,the crisp variables e(k) and de(k) are converted into fuzzy variables E(k) and dE(k) using the triangular membership functionsshown in Fig. 11. Triangular membership functions are chosen to have smooth and constant region in the main points.

E(k) is divided into five fuzzy sets: NL (negative large), NS (negative small), ZE (zero), PS (positive small) and PL (positivelarge); and dE(k) is divided into three fuzzy sets: N (negative), ZE (zero), P (positive).

In the second stage of the FLC, the fuzzy variables E and dE are processed by an inference engine that executes a set ofcontrol rules contained in (10) rule bases. The control rules are formulated using the knowledge of the DVR behavior. Therules are expressed in Table 1:

Different inference algorithms can be used to produce the fuzzy set values for the output fuzzy variablesSa1; S0a1; Sa2; S0a2; Sb; S0b. In this paper, the max–min inference algorithm is used, in which the membership degree is equalto the maximum of the product of E and dE membership degree.

The inference engine output variables are converted into the crisp values in the defuzzification stage. Various defuzzifi-cation algorithms have been proposed in the literature. In this paper, the centroid defuzzification algorithm is used, in whichthe crisp value is calculated as the centre of gravity of the membership function. Fig 12 shows inputs and output member-ship functions.

The definition of the spread of each partition, or conversely the width and symmetry of the membership functions, is gen-erally a compromise between dynamic and steady-state accuracy.

5. Simulation results

To prove the capabilities of the above-mentioned control methods, the test system is modeled with MATLAB/Simulink(ver. 7) and SimPower-System block set. Total Harmonic Distortion (THD) is also calculated to verify the efficiency andwell-performance of the proposed control method. The supply network is modeled as an ideal voltage source; the injectiontransformer has been modeled as a linear element. The transformer winding’s resistances and core saturation effect wereneglected. The inverter is modeled as a typical two-pulse inverter with transistors assumed to be ideal switches. Lossesin the inverter were modeled as a resistance connected to the DC side capacitor. The rest of the components have been as-sumed to be ideal ones, and standard SimPower System block set elements were used. The parameters of the case study arepresented in Tables 2 and 3. In the simulated model, the following abnormal conditions are considered:

Table 3Parameters of induction motor.

Parameter Value

Rated voltage 380 VNominal supply frequency 50 HzRated out put power 3 kWPower factor 0.82Nominal speed, no. of poles 1430 rpm, 4

Page 10: 1-s2-0-S1569190X10000298-main

Fig. 13. Simulation result of DVR response for a balanced voltage sag and linear resistive load.

H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819 815

5.1. Resistive load and balanced voltage sag

The first simulation is carried out for a balanced voltage sag and linear resistive load (85 X). The PCC voltage drops to 70%of its nominal value from 0.1 to 1.8 s as shown in Fig. 13.

The DVR injected voltages and load voltages are shown in Fig. 13a and b.

Page 11: 1-s2-0-S1569190X10000298-main

Fig. 14. Simulation result of DVR response for a balanced voltage sag and induction motor load.

816 H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819

As it can be seen from the results, the DVR is able to produce the required voltage components for differentphases rapidly and help to maintain a balanced and constant load voltage at the nominal value (400 V) during faultcondition.

Page 12: 1-s2-0-S1569190X10000298-main

Fig. 15. Simulation result of DVR response for a balanced voltage sag and nonlinear load.

H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819 817

5.2. Induction motor load and balanced voltage sag

The parameters of the induction motor are listed in Table 3. Similar to the previous case, PCC voltage drops to 30% of itsvoltage nominal value from 0.1 s and it is kept until 0.18 s. The PCC sag and DVR injected voltages are shown in Fig. 14. It canbe observed that with starting of induction motors load voltage drops to 30% of its voltage nominal value. The DVR wouldinject the compensating voltage immediately after PCC voltage sag is detected; to maintain load voltages at desired level.

Page 13: 1-s2-0-S1569190X10000298-main

Fig. 16. Simulation result of DVR response for a unbalanced voltage sag and linear load.

818 H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819

5.3. Nonlinear load and balanced voltage sag

In this case, the nonlinear load is a diode rectifier bridge with a capacitor bank (200 lF) and resistive load (80 X) con-nected in parallel. Again, the PCC voltage drops to 70% of its nominal value from 0.1 s and lasts for four cycles. The PCC volt-ages and DVR injected voltages are shown in Fig. 15. It can be observed that with nonlinear load connected at downstream,the PCC voltages, DVR injected voltages, and load voltages become slightly distorted.

Page 14: 1-s2-0-S1569190X10000298-main

Table 4THD for load voltage in all simulation case studies.

Simulation case studies THD (%)

Resistive load and balanced voltage sag 0.12Induction motor load and balanced voltage sag 0.2Nonlinear load and balanced voltage sag 0.17Unbalanced voltage sag 0.16

H. Ezoji et al. / Simulation Modelling Practice and Theory 18 (2010) 806–819 819

As it can be observed from simulation results, DVR is capable to detect the voltage sag quickly and compensate the loadvoltage satisfactorily.

5.4. Unbalanced voltage sag

In this case, there is a 30% three-phase voltage sag with +30� phase jump in phase-a. Voltage is started at t = 0.1 s and it iskept until 0.18 s. Fig. 16 shows the result of voltage sag compensation using hysteresis voltage control based on fuzzy con-troller. As it can be seen from the results, DVR is able to produce the required voltage for different phases rapidly and a bal-anced and constant load voltage at the nominal value (400 V) is provided.

The calculated THD in all simulation case studies are described in Table 4. According to IEEE standard, the THD in distri-bution networks should be under 5% and as it can be seen in Table 4, the calculated THD satisfy the IEEE standard range.

6. Conclusion

This paper investigates a new control approach which is based on hysteresis voltage control combined with fuzzy logiccontrol method. All parameters and structures such as study system, and control unit are described in details. The validity ofproposed method is approved by results of the simulation in MATLAB/Simulink for different voltage sag condition. As it canbe seen, the new model of DVR with the presented control method is capable to compensate networks faults and mitigatetheir effects on sensitive loads in distribution power systems.

THD is also calculated to evaluate the quality of the load voltage during the operation of DVR. The simulation results showthat the calculated THD in sag conditions fulfill IEEE 519 std. range. The effectiveness of the proposed DVR controller inrejecting load voltage disturbance is proved by the good performance of the DVR under different loading conditions.

References

[1] P. Boonchiam, N. Mithulananthan, Dynamic control strategy in medium voltage DVR for mitigating voltage sags/swells, in: International Conference onPower System Technology, 2006, pp. 1–5.

[2] H. Ezoji, A. Sheikholeslami, M. Tabasi, M.M. Saeednia, Simulation of Dynamic Voltage Restorer using hysteresis voltage control, European Journal ofScientific Research (EJSR) 27 (1) (2009) 152–166.

[3] M.R. Banaei, S.H. Hosseini, S. Khanmohamadi, G.B. Gharehpetian, Verification of a new energy control strategy for Dynamic Voltage Restorer bysimulation, ELSEVIER Simulation Modeling Practice and Theory 14 (2006) 113–125.

[4] A. Ghosh, G. Ledwich, Compensation of distribution system voltage using DVR, IEEE Transactions on Power Delivery 17 (4) (2002) 1030–1036.[5] P.T. Nguyen, T.K. Saha, Dynamic Voltage Restorer against balanced and unbalanced voltage sags: modelling and simulation, IEEE Transactions on Power

Delivery (2004) 1–6.[6] K.A. Ramasamy, R.K. Iyer, V.K. Ramachandaramuthy, R.N. Mukerjee, Dynamic Voltage Restorer for voltage sag compensation, in: IEEE International

Conference on Power Electronics and Drive Systems, (PEDS), 2005, pp. 1289–1294.[7] M.A. Hannan, A. Mohamed, Modeling and analysis of a 24-pulse Dynamic Voltage Restorer in a distribution, system research and development, in:

SCOReD, 2002, pp. 192–195.[8] C. Zhan, V.K. Ramachandaramurthy, A. Arulampalam, C. Fitzer, S. Kromlidis, M. Barnes, N. Jenkins, Dynamic Voltage Restorer based on Voltage-Space-

Vector PWM control, IEEE Transactions on Industry Applications 34 (6) (2001) 1855–1863.[9] M.I. Marei, E.F. El-Saadany, M.M.A. Salama, A new approach to control dVR based on symmetrical components estimation, IEEE Transactions on Power

Delivery 22 (1) (2007) 2017–2024.[10] F. Al Jowder, Modeling and simulation of Dynamic Voltage Restorer (DVR) based on hysteresis voltage control, in: IEEE Conference on Industrial

Electronics Society (IECON), 2007, pp. 1726–1731.[11] B.R. Lin, T.Y. Yang, Implementation of active power filter with asymmetrical inverter legs for harmonic and reactive power compensation, Electric

Power Systems Research 73 (2005) 227–237.[12] C. Meyer, C. Romaus, R.W. De Doncker, Optimized control strategy for a medium-voltage DVR, in: IEEE Conference on Power Electronics Specialists

(PESC), 2005, pp. 1887–1993.[13] H. Kim, Minimal energy control for a Dynamic Voltage Restorer, in: Power Conversion Conference IEEE (PCC), vol. 2, 2002, pp. 428–433.[14] J.G. Nielsen, F. Blaabjerg, N. Mohan, Control strategies for Dynamic Voltage Restorer compensating voltage sags with phase jump, in: IEEE Conference

on Applied Power Electronics Conference and Exposition (APEC), 2001, pp. 1267–1273.[15] C. Fitzer, M. Barnes, P. Green, Voltage sag detection technique for a Dynamic Voltage Restorer, IEEE Transaction on Industry Applications 40 (1) (2004)

203–212.[16] J.G. Nielsen, M. Newman, H. Nielsen, F. Blaabjerg, Control and testing of a Dynamic Voltage Restorer (DVR) at medium voltage level, IEEE Transaction

on Power Electronics 19 (3) (2004) 806–813.[17] B.K. Bose, An adaptive hysteresis band current control technique of a voltage feed PWM inverter for machine drive system, IEEE Transaction Industrial

Electrons 37 (5) (1990) 402–406.[18] M. Kale, E. Ozdemir, An adaptive hysteresis band current controller for shunt active power filter, Electric Power Systems Research 73 (2005) 113–119.