Top Banner
1 Arrester Arrester Application Application bringing it all bringing it all together together ! ! Selection (see EM Selection (see EM Section 14 SI 1.00 Section 14 SI 1.00 and and IEEE C62.11-1999 IEEE C62.11-1999 1. 1. Overvoltage Overvoltage 2. 2. Energy Energy 3. 3. Margins Margins 4. 4. Coordinating across Coordinating across the transformer the transformer
24

1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

Dec 15, 2015

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

1

Arrester Application Arrester Application bringing it all togetherbringing it all together!!

Selection (see EM Selection (see EM

Section 14 SI 1.00 andSection 14 SI 1.00 and

IEEE C62.11-1999IEEE C62.11-1999

1.1. OvervoltageOvervoltage

2.2. EnergyEnergy

3.3. MarginsMargins4.4. Coordinating across the Coordinating across the

transformertransformer

Page 2: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

2

Arrester Selection – Step 1Arrester Selection – Step 1

a.a. Select an MCOV rating that is just greater than Select an MCOV rating that is just greater than the maximum continuous operating voltage of the maximum continuous operating voltage of the systemthe system

b.b. Check the system maximum temporary 60hz Check the system maximum temporary 60hz over-voltage (magnitude and duration) with the over-voltage (magnitude and duration) with the arrester temporary over-voltage capability from arrester temporary over-voltage capability from the manufacturer’s curvethe manufacturer’s curve

c.c. Choose the higher rating from a or b aboveChoose the higher rating from a or b above

Page 3: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

3

Arrester Selection – Step 2Arrester Selection – Step 2

a.a. Select the arrester class based on the available Select the arrester class based on the available fault duty. The available fault duty should be fault duty. The available fault duty should be less than the arrester pressure relief ratingless than the arrester pressure relief rating

b.b. Check the energy dissipation capability of the Check the energy dissipation capability of the arrester. This is given in kilo-joules per kv of arrester. This is given in kilo-joules per kv of rating (either MCOV or duty cycle rating). rating (either MCOV or duty cycle rating). Usually this is determined from switching Usually this is determined from switching studies of the transmission system and is not a studies of the transmission system and is not a concern on the distribution system.concern on the distribution system.

Page 4: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

4

Arrester Selection – Step 3Arrester Selection – Step 3

a.a. Calculate the protective margins and Calculate the protective margins and check they are adequate:check they are adequate:

a.a. PMPM11> > 20% 20% Front-of-WaveFront-of-Wave

b.b. PMPM22> 15> 15%% Lightning Lightning

c.c. PMPM33> 15> 15%% SwitchingSwitching

Page 5: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

5

Arrester Selection – example:Arrester Selection – example:

Let’s pick arresters for the 230kv system. Step one is to select the MCOV rating.Let’s pick arresters for the 230kv system. Step one is to select the MCOV rating.

1a.1a. Maximum voltage for the 230kv system is 242kv from Maximum voltage for the 230kv system is 242kv from ANSI ANSI C84.1 – 1995 so the MCOV must be at least C84.1 – 1995 so the MCOV must be at least = 242kv 3 = = 242kv 3 = 139.7kv139.7kv

Standard ratings available above 139.7kv are:Standard ratings available above 139.7kv are:

IEEE C62.11-1999

Page 6: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

6

Arrester Selection – example cont:Arrester Selection – example cont:

1b. 1b. The next step is to check the maximum possible system 60hz over-voltage The next step is to check the maximum possible system 60hz over-voltage

– First let’s check First let’s check the maximum voltage rise on the un-faulted phase for the maximum voltage rise on the un-faulted phase for

a phase to ground fault. System analysis shows a worst case maximum a phase to ground fault. System analysis shows a worst case maximum voltage rise of voltage rise of 197kv197kv for a phase to ground fault on the system for a phase to ground fault on the system (COG of (COG of 81.4%). Assume a clearing time of 5 cycles.81.4%). Assume a clearing time of 5 cycles.– Next check for the possibility of back-feed during clearing of a 230kv fault.Next check for the possibility of back-feed during clearing of a 230kv fault.

Consider a 230-34.5kv delta-wye transformer. A high side fault is also back-fedConsider a 230-34.5kv delta-wye transformer. A high side fault is also back-fed

from the 34.5kv system: from the 34.5kv system:

Page 7: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

7

Neutral shift And Back-feed:

Phase to ground fault

230-34.5kv

Neutral shifts duringclearing of a phase to

ground fault

The 230kv line fault is back-fed from the 34.5kvsystem until the reversepower relaying clears (up to 1 sec).

The 230kv breakers clearin 3-5 cycles

The xfmr high side arresters must withstand the increasedphase to ground voltage on the unfaulted phases until thefault clears

Arrester voltage

140kv

197kv

242k

v

Page 8: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

8

Arrester Selection – example cont:Arrester Selection – example cont:

1c. 1c. The highest stress for the back-feed condition could be a maximum of The highest stress for the back-feed condition could be a maximum of

242kv for 1 second. The minimum MCOV = 242/1.46 = 165.7kv 242kv for 1 second. The minimum MCOV = 242/1.46 = 165.7kv

1.46

Pick a 228kvduty cycle:

Page 9: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

9

Arrester Selection – example cont:Arrester Selection – example cont:

2a. 2a. Next select the arrester class: Next select the arrester class:

The worst case phase to ground fault duty on the 230kv system is at The worst case phase to ground fault duty on the 230kv system is at

Doubs and is around 50ka. Doubs and is around 50ka.

Need to select a station class arrester since the fault duty is > 16ka.Need to select a station class arrester since the fault duty is > 16ka.

2b. Check transmission line discharge duty. Transmission studies show the 2b. Check transmission line discharge duty. Transmission studies show the maximum switching duty on the 230kv system is within the 7KJ/kv rating for maximum switching duty on the 230kv system is within the 7KJ/kv rating for standard station class metal oxide arresters.standard station class metal oxide arresters.

Page 10: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

10

Arrester Selection – example Arrester Selection – example cont: cont:

3a.3a. Calculate the protective margins and check they are adequate:Calculate the protective margins and check they are adequate:

a.a. PMPM11> > 20% 20% Front-of-WaveFront-of-Wave

b.b. PMPM22> 20> 20%% Lightning Lightning

c.c. PMPM33> 15> 15%% SwitchingSwitching

Normally margins are calculated for the transformers since theyNormally margins are calculated for the transformers since they

usually have reduced insulation (less than full BIL)usually have reduced insulation (less than full BIL)

Page 11: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

11

Protective Ratios for LiquidFilled Transformers

Time in u-seconds

BSL

100001000101.0.1

60 HZ

100

BIL

CWW

SPL

FOW

5KA

20KA

10KA

Vol

tage

Discharge voltage at Appropriate system

Impulse current

= CWW FOW

PR1

= BIL LPL

PR2

= BSL SPL

PR3

Page 12: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

12

Oil Filled Equipment characteristics

Page 13: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

13

Transformer BILs:Transformer BILs:

Page 14: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

14

Arrester characteristics

Page 15: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

15

Arrester characteristics Arrester characteristics from the manufacturerfrom the manufacturer::

Page 16: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

16

Protective MarginsProtective Margins

Example: 230-34.5kv transformer high side:

PRPR11 = CWW/FOW=(825x1.1)/(559) = 1.62 = CWW/FOW=(825x1.1)/(559) = 1.62

PMPM11= (PR= (PR11-1) x 100%=(1.62-1)x100%= -1) x 100%=(1.62-1)x100%= 62%62%

PRPR22= BIL/LPL= 825/(525) =1.57= BIL/LPL= 825/(525) =1.57

PMPM22= (PR= (PR22-1) x 100% =(1.57-1)x100%= -1) x 100% =(1.57-1)x100%=

57%57%

PRPR33 = BSL/SPL=(825x.83)/(451)= 1.52 = BSL/SPL=(825x.83)/(451)= 1.52

PMPM33= (PR= (PR33-1) x 100%=(1.52-1)= -1) x 100%=(1.52-1)= 52%52%

PRPR11 = CWW/FOW = CWW/FOW

PRPR22 = BIL/LPL = BIL/LPL

PRPR33 = BSL/SPL = BSL/SPL

PMPM11= (PR= (PR11-1) x 100% > -1) x 100% > 20%20%

PMPM22= (PR= (PR22-1) x 100% > -1) x 100% > 20%20%

PMPM33= (PR= (PR33-1) x 100% > -1) x 100% > 15%15%

Page 17: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

17

Protective MarginsProtective Margins

Example: 230-34.5kv transformer low side:

PRPR11 = CWW/FOW=(200x1.1)/(95.8) = 2.30 = CWW/FOW=(200x1.1)/(95.8) = 2.30

PMPM11= (PR= (PR11-1) x 100%=(2.30-1)x100%= -1) x 100%=(2.30-1)x100%= 130%130%

PRPR22= BIL/LPL= 200/(84) =2.38= BIL/LPL= 200/(84) =2.38

PMPM22= (PR= (PR22-1) x 100% =(2.38-1)x100%= -1) x 100% =(2.38-1)x100%= 238%238%

PRPR33 = BSL/SPL=(200x.83)/(66)= 2.52 = BSL/SPL=(200x.83)/(66)= 2.52

PMPM33= (PR= (PR33-1) x 100%=(2.52-1)= -1) x 100%=(2.52-1)= 252%252%

Why are the low side margins so high?

Page 18: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

18

Page 19: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

19

Coordination across the transformer:Coordination across the transformer:

Should you worry about Mixing Silicon Carbide and metal oxide arresters?

Arrester Duty cycle = 228 kv

MOV low side arresters would be stressed since MCOV= 24.4 kvUse MOVs on BOTH sides of the transformer

V low side = 30.0 kv

Consider a temporary 60hz over-voltage on the 230kv side of 200kv ph-gnd:SiC Duty cycle high side = 228kvWill the high side arrester conduct??V low side = 200 x (34.5/230)V low side = 30.0kv

Page 20: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

20

Page 21: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

21

OMU:

Page 22: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

22

Page 23: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

23

The OMUThe OMU(optical metering unit)(optical metering unit)

What is the BIL? BSL? 60 hertz withstand?What is the BIL? BSL? 60 hertz withstand? How do you know? What impulse testing has been done? How do you know? What impulse testing has been done?

Is there a design test report?Is there a design test report? Should it be protected by an arrester? Is the insulation self-Should it be protected by an arrester? Is the insulation self-

restoring? Will it flashover on the outside or the inside? restoring? Will it flashover on the outside or the inside? What happens when it loses SF6? What is the withstand at What happens when it loses SF6? What is the withstand at

reduced gas pressure? Can we add gas if its energized?reduced gas pressure? Can we add gas if its energized? Should we trip it for low gas? What is the minimum Should we trip it for low gas? What is the minimum

pressure that is acceptable?pressure that is acceptable? When its switched out could the switching surge cause a When its switched out could the switching surge cause a

flashover? (could the porcelain explode?)flashover? (could the porcelain explode?)

Page 24: 1 Arrester Application bringing it all together! Selection (see EM Selection (see EM Section 14 SI 1.00 and Section 14 SI 1.00 and IEEE C62.11-1999 IEEE.

24

Thanks for your attention…… Your substation support staff!Luxor substation - 1936