1 2012-09-17 Sec 09-1 Teleprotectin Fundamentals Course CHP592 - FOX515
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 1/201
2012-09-17
Sec 09-1 Teleprotectin Fundamentals
Course CHP592 - FOX515
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 2/20
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 3/203
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
Teleprotection is:
A discipline between protection and telecommunication.
Sometimes under responsibility of the protection organization, sometimes under the responsibility of the
communication organization.
Sometimes a barrier between the communication engineer and the protection engineer (on customer’s and
on supplier’s site !)
Teleprotection is used:
Mainly at production and transport level where the distances of the transmitted power and short-circuit
currents are much larger than at the distribution level. The requirements for network stability are also
much more in the transport power systems.
At low and medium voltage levels (distribution level) distance protection is usually used without
Teleprotection.
Arguments for Teleprotection:
Minimization of material damage and reduction in time and extent in case of failures
Keeping up the supply and distribution of electric power as long and as well as possible under all
circumstances
At the production and transport level, clearance of line faults must be absolutely selective and faults mustbe cleared within the shortest possible time, so called zone 1 time of the Protection Device.
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 4/204
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
A Protection System in a Power Network includes the fol lowing elements:
•The Circuit Breaker to isolate the faulty part
•The Protection Device to detect the fault via Current- and Voltage Transformer and to give the order
to trip the Circuit Breaker
•The Telecommunication and the Teleprotection equipment to transfer the trip to the other end of the
Power Line
A Teleprotection equipment is:
•The interface between Protection Device and telecommunication system
•A converter of the signal from the Protection Device into a signal suitable to transmit over a
telecommunication link
For analog channels FSK modulation is used, for digital channels CODING of different models is applied.
The Teleprotection Unit is also multiplexing several command signals into one telecom channel.
A Telecommunication System is:
•A PLC, an optical Multiplexer, a Microwave or a direct link using a copper wire or an optical fiber
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 5/205
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
On this slide the two different signal families used in Teleprotection are listed:
Continuous signals are:
Longitudinal current differential
Phase comparison
Command type signals on/off are:
permissive tripping
direct intertripping
blocking
directional comparison
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 6/206
Here you see different protection schemes which are using telecommunication
COMMUNICATION IS ESSENTIAL in the following Protection schemes using quantitative signal
information:
Phase comparison
Longitudinal current differential
These applications are absolutely selective
COMMUNICATION IS ESSENTIAL in the following Protection schemes using ON/0FF information:
Permissive overreach distance
Blocking Distance
These applications are relatively selective
COMMUNICATION IS SUPPLEMENTARY in the following Protection schemes using ON/0FF information:
Permissive underreach distance
Accelerated distance
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 7/207
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
The distance line Protection Devices use different zones to detect line faults.
The stepped time and distance characteristic of the line protection system provides main protection of the
line section in Zone 1 as well as back-up protection of the adjacent Busbars in Zone 2.
At the production and transport level, clearance of line faults must be absolutely selective and faults must
be cleared within the shortest possible time ,so called ZONE 1 TIME.
For example with the underreaching mode, without command transmission, the distance protection
cannot clear all faults in the protected line section within the zone 1 time. Faults near the ends of the line
section will be cleared at zone 2 time, with additional delay. This is often acceptable at the distribution
level, where fast reclosure is not required.
Fast coordinated tripping at the ends of the protected line section reduces the effect of short circuit current
on network stability as well as the stressing of the plant and finally permits fast auto reclosure.
Absolutely selectivity and fast fault clearance for any fault position on the protected line section requires
Teleprotection between the ends of the line.
Consequently, the reliability of the line protection depends largely on the reliability of the communication
link.
Protective communication links are often duplicated on important lines to improve the reliability of tripping
on internal faults.
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 8/208
.
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
PUTT mode is used in Line Protection were the protected section is more than about 20 km long.
In PUTT mode the zone 1 of the Protection Device is set to underreaching for example 85 percent of the line section
without delay. Zone 2 is set for example to 120 percent of the line section and is time delayed of for example 200
milliseconds
The sequence of events for thi s example is:
• A fault occurs at point F in zone 1 of Protection Device RBC, zone 1 has no time delay.
•The line is switched off without any delay by the Circuit Breaker in station B.
• At the same time an permissive tripping command is sent to station C by means of the Teleprotection equipment.
•The Protection Device RCB in station C has already detected a fault in Zone 2 which is time delayed for example of
200 milliseconds
• Additional after a transmission time delay of typical 10 milliseconds the tripping command is received by Protection
Device RCB in station C and the zone 2 t ime is accelerated to zone 1 time.
•The Circuit Breaker in station C is tripping the power line without any additional delay
In case the fault happens in the common part Zone 1 of both Relay protection, the relays trip the breakers without
waiting for the command of the Teleprotection.
Advantage: Faster than POTT und Blocking mode
Disadvantage: Not selective for short lines
Without Teleprotection the breaker in station C would be activated only in the zone 2 time after for example 200
millisecond and therefore auto reclosure of the power line is not assured. As the zone 2 is overreaching the section
of the protected line, the selectivity would be not accurate without the communication.
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 9/209
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
POTT mode is used in Line Protection were the protected section i s less than about 20 km long or
on Power Lines where PUTT mode can not be set.
In POTT mode the zone 1 of the Protection Device is set to overreaching for example 130 percent of the
line section. It has a AND logic therefore both Protection Device must detect the fault in the first zone and
must receive the trip from the opposite Teleprotection equipment. Only in this case tripping in first zone
time is possible.
The sequence of events of the example is:
• A fault F1 is detected by Distance Relays RBC and RCB. The trips are send to both ends of the line
section via Teleprotection equipment.
•The Relays in station B and station C receiving the tripping command. As they are already started by the
fault detection the AND logic is fulfilled and circuit breakers in station B and C trip in zone 1 time.
•A fault F2 is only detected by distance Relay RCB. Distance relay RBC is not sending a tripping signal to
the Station C therefore relay RCB will not trip the Breaker C in zone 1 time.
Advantage: POTT mode has a high selectivity and prevents tripping of a healthy line section in zone 1
time.
Disadvantage: It is slower than the PUTT mode because of any fault within the protected section will have
the time delay of the Teleprotection equipment. Without telecommunication no tripping in zone 1 is
possible.
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 10/2010
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
The Blocking mode for Line Protection may work for any length of the protected line section.
The Zone 1 time is delayed of for example 10 millisecond and is adjusted overreaching for example 130%
of the protected line section. Reverse zone towards the Busbars is set for example to -40 percent.
The sequence of events of the example is:
The fault F1 is detected by Distance Relays RBC and RCB in there Zone 1. After countdown of the delay
time both Protection Devices in Station B and C will trip the breakers.
The fault F2 is detected by Distance Relay RBC in Zone 1, the delay counter starts counting down. The
Protection Device RCB is detecting a fault in the reverse Zone and sends through Teleprotection link a
blocking signal DO NOT TRIP to the Protection Device RBC. If this happens within the delay time of Zone
1, the relay will not trip the Breaker.
Blocking mode was developed for PLC which is using the Power line to communicate.
Advantage: Blocking command is only transferred if the line fault is out of the PLC section and the line for
communication is clean.
Disadvantage: The first zone is always time delayed for example of 10 milliseconds; if Teleprotection fails
zone 1 is not selective any more
In new projects the Blocking mode is not used
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 11/2011
Breaker Failure Protection is needed to assure the function of the protection system in case of a Line
Breaker failure .
The local Protection Devices for Busbars, Earth fault and Distance Protection are connected to the Line
Breaker. In case of a faulty Breaker the Substation can not be isolated from the power network.
The sequence of events of the example is:
The Breaker control system blocks the opening of the Breaker “B” if the SF6 gas pressure is low.
Trips from the local Protection system are diverted by the breaker control to the Teleprotection equipment.
Through the communication channel “L” the tripping command is transferred to the station “C” where the
Line Breaker opens and isolates the power flow to station “B”.
Remark:
To assure high security and dependability the processing time in the direct tripping feature is longer.
Therefore the total transmission time of the Teleprotection system is more than in the Distance Protection
for Permissive and Blocking mode.
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 12/2012
This a example for direct transfer tripping where the transformer is connected to the system without a
Circuit Breaker:
Line faults from station “A” up to connection of transformer at station “B” are protected by distance relay at
station “A” in overreaching mode.
Faults in station “B” within and beyond the transformer detected by a Buchholtz or a Busbar Protection
Device are transferred to the circuit breaker at “A” by means of the Teleprotection direct tripping signal.
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 13/2013
Configurable settings in the Teleprotection equipment are the followings:
Security is the ability of a equipment to prevent interference and noise from producing unwanted
commands
Dependabil ity is the abil ity of a equipment to issue and receive wanted commands in the presence
of interference and noise
Transmission time is the time elapsed between the instant of change of state at the transmitter
input and the instant of the corresponding change of state at the receiver output .
Bandwidth is the total frequency range or bit rate util ized by the Teleprotection equipment.
In Permissive and Blocking schemes the processing time has to be short and therefore the overall
transmission t ime is also shor ter. In the Direct t ripping applications the Security and Dependabilitymust be high, therefore the processing and transmission time will be longer.
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 14/2014
All these impairments may cause unwanted or missing commands
In case of interference and noise, more processing time will be needed: -The
feature “adaptive transmission time” will act in the Teleprotection equipment
In case of excessive interference and noise, processing time would be too long and commands not save.
To prevent incidents the Teleprotection unit can take different actions:
-Puts in operation the feature “Unblocking”
-Activates Contact Freezing for continuous commands
-Extends the zone 1 of distance Protection Device in PUTT mode from underreaching to overreaching with
the help of the alarm contacts of the Teleprotection equipment
–Blocks the command outputs of the Teleprotection equipment
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 15/2015
On this diagram the available transmission parameters of Teleprotection equipment are shown:
The transmission time is the delay between the moment a command initiated on the input of
Teleprotection equipment until this command is received at the output of the Teleprotection equipment on
the other end of the protection system
The Tx Input delay is used in direct tripping mode to make the system more save against EMC
interference. With this parameter the command is sent delayed by the Teleprotection equipment at the
input side.
The Tx and Rx trip duration time can be limited in Permissive tripping applications. With this parameter,
the duration of the command coming from the Protection Device can be increased, decreased or fixed by
the Teleprotection command.
The Rx trip prolongation time is the delay from the moment the transmission of a command from the input
of the transmitting Teleprotection equipment stops until the receiver contacts of the receiving
Teleprotection equipment are deactivated
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 16/2016
This example is valid for permissive tripping scheme and a Power Frequency of 50 Hertz
The total fault clearance time is the sum of the Protection Device processing time, the Transmission Time
of the Teleprotection equipment and the switching time from the Circuit Breaker.
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 17/2017
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
If the Teleprotection equipment is connected to a digital network the addressing facility has to be used. In
the worst case mixed up cross connections without using addressing could cause tripping of a wrong
Circuit Breaker and a wrong Power Line!
In the example in place B, if by mistake of the administrator or the failure of the multiplexer the command
of one of the protection devices goes over a wrong communication line, the remote breaker will not trip
because of the addressing facility.
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 18/2018
This summary shows you the Teleprotection products from the ABB portfolio
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 19/2019
In this slide you see the layout of a protection system for an important transmission line.
On this type of critical line, most of the protection equipment are doubled. We speak about Main 1 System
and Main 2 System.
2012-09-17Course CHP592 - FOX515
Sec 09-1 Teleprotectin Fundamentals
8/12/2019 09-1 Teleprotection Fundamentals
http://slidepdf.com/reader/full/09-1-teleprotection-fundamentals 20/20
2012-09-17Course CHP592 - FOX515
Questions