Top Banner

of 56

0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

Feb 20, 2018

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    1/56

    Power Swing Relaying

    in the Texas Panhandle

    An Out

    -

    Of

    -

    Step Odyssey

    Presented by Kevin W. Jones, P.E.

    Principal System Protection Engineer

    68th Annual Conference for Protective Relay Engineers

    March 31, 2015

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    2/56

    2

    Outline

    History of the Southwestern Public ServiceCompany (SPS) System

    Brief Review of Power Swing Basics

    Early SPS Power Swing Philosophy Modern SPS Power Swing Philosophy

    Early Philosophy in the Modern World

    Conclusions

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    3/56

    3

    SPS System History

    Company history began as anelectric franchise in 1904 inRoswell, NM

    By the early 1930s, SPS had

    expanded throughout the TexasPanhandle and Texas SouthPlains

    The southeast New Mexicoregion was electrically isolatedfrom the Texas region until1946

    Electrically

    Isolated

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    4/56

    4

    SPS System History

    In the Fall of 1946, SPS placedits first 115 kV line in servicefrom Carlsbad, New Mexico toDenver City, Texas

    This line stretched 109 milesand completed theinterconnection of all the SPSservice territory

    UFO crash in June, 1947 nearRoswell???

    109 Mile 115 kV

    Transmission

    Line

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    5/56

    5

    SPS System History

    The electrical system continuedto grow through the 1950s andearly 1960s

    The SPS system remained

    isolated from the rest of theEastern grid

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    6/56

    6

    SPS System History

    In May 1963, the 115 kV linefrom Guymon, Oklahoma toLiberal, Kansas wassynchronized and closed tyingSPS to the Eastern Interconnect

    for the first time

    Too weak to be left closedpermanently

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    7/56

    7

    SPS System History

    In 1964, a major outage foreverchanged SPSs approach to system-wide protection

    A large Amarillo generating unit

    tripped while another unit was off-line for maintenance

    The northsouth tie lines tripped,resulting in a Texas North blackout

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    8/56

    8

    SPS System History

    Out-of-step tripping was allowed toforce islanding at strategic locationsto create three load/generation

    islands PSB was installed on all looped

    transmission lines

    Under frequency relaying wasinstalled throughout the system at

    three steps

    About 10% of system load was to beshed at each UF step

    Texas

    North

    New

    Mexico

    Texas

    South

    1964 Lessons Learned

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    9/56

    9

    SPS System History

    In May 1972, SPS connected to theEastern Interconnect via a new 230kV line from Amarillo, Texas to Elk

    City, Oklahoma From 1983 to 1985, 11 tie line

    power swing trips occurred,resulting in islanding with theEastern Interconnect and UF loadshed

    Five events were caused by theloss of a single 350 MW generationunit

    Growing Pains

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    10/56

    10

    SPS System History

    By 1985, the first 345 kV line wasbuilt from Abernathy, Texas toOklaunion, Texas

    This new line strengthened the SPS

    connection to the EasternInterconnect, allowing the 115 kVties to be operated closed

    This stronger system stabilized theSPS system, and no power swingtrips occurred again until an event in1996 and another event in 2008

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    11/56

    11

    SPS System History

    11

    In 1996, A 230 kV bus fault resultedin the loss of about 1000 MW ofgeneration and the loss of nineinternal 230 kV transmission lines

    All the Eastern Interconnect andTexas North to Texas South tie linestripped

    All levels of UFLS tripped

    75% (~2000 MW) of system load waslost by UFLS and tie line trips

    This is the largest system outage tothe SPS system

    Stronger System, Test #1

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    12/56

    SPS System History

    12

    Stronger System, Test #2 In 2008, a loss of 800 MW of

    generation caused EasternInterconnect tie line trips

    The tie line trips resulted in a decayof system frequency, resulting inlevel 1 UFLS tripping (59.3 Hz)

    Around 650 MW of load was shed(about 15% of system load)

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    13/56

    13

    SPS System History

    Today, the SPS connection to theEastern Interconnect has beenfurther strengthened by the addition

    of three 345 kV lines

    SPSs islanding scheme has beentested and proven to preventsystem-wide blackouts

    The increased strengthening of the

    SPS system has resulted in lessfrequent islanding events

    Strongest System

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    14/56

    14

    Power Swing Basics

    What is a power swing?

    Power Swing: a variation in three

    phase power flow which occurs

    when the generator rotor anglesare advancing or retarding relative

    to each other in response to

    changes in load magnitude and

    direction, line switching, loss of

    generation, faults, and other

    system disturbances [1].

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    15/56

    Power Swing Basics

    What causes power swings?

    15

    Faults

    o Generators accelerate until fault clears

    Loss of Loado Generators accelerate Pm > Pe

    Loss of Generation

    o Generators decelerate Pm < Pe

    Switching (line, capacitor, inductor, etc.)o Changes in power flow affect generator

    output

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    16/56

    Power Swing Basics

    Stable power swing (generator)

    16

    Rotor Angle

    (degrees)

    Time (seconds)

    Angle damps out with time

    0

    120

    System Angle < 120 degrees

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    17/56

    Power Swing Basics

    Un-stable power swing (generator)

    17

    Time (seconds)

    0

    180

    Rotor Angle

    (degrees)

    120

    Angle continues to

    increase with time

    System Angle > 120 degrees

    Pole Slip

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    18/56

    Power Swing Basics

    Effects of power swings

    18

    Relays can trip undesirably for stable power swings if not

    set properly

    Generators can be damaged after they slip a pole during

    unstable power swings Breakers can be damaged if they try to open during

    unstable power swings if the system angle is near 180

    degrees

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    19/56

    19

    Power Swing Basics

    Power Swing Studies in the R-X Impedance Plane

    Data required to perform a power swing study

    o Line impedance (ZL)

    o Sending end source impedance (ZS)

    o Receiving end source impedance (ZR)o Parallel transfer impedance (ZTR)

    o System maximum slip rate (Hz or degrees/second)

    ZS ZR

    ZTR

    ZL

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    20/56

    20

    Power Swing Basics

    Line Impedance

    Sending end source

    impedance

    Receiving end

    source impedance

    System Impedance

    in the R X Plane

    Total system source

    impedance

    Equal emf power

    swing trajectory

    Equal emf stabilityboundary

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    21/56

    21

    Power Swing Basics

    System Impedance

    in the R X Plane

    ES

    ER

    ES > ER

    ES = 1.0 p.u.

    ER = 0.7 p.u.

    ES / ER = 1.43

    ES < ERES = 0.7 p.u.

    ER

    = 1.0 p.u.

    ES / ER = 0.7

    ES = ER

    ES / ER = 1.0

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    22/56

    22

    Power Swing Basics

    Slip Rate Calculation:

    Inner angle Ai

    Outer angle Ao

    =( ) ()

    360

    ()

    =(120 90) 60()

    360

    2.0()

    = 2.5

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    23/56

    23

    Power Swing Basics

    23

    PSB timer starts

    here when outer

    blinder is entered

    PSB timer expires

    before inner blinder is

    reached blocking Z1

    and Z2

    Swing ends and new

    steady state operatingpoint is achieved

    Steady state load

    operating point

    pre-swing

    PSB Example:

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    24/56

    24

    Power Swing Basics

    OST Example:

    OST timer starts

    here when outer

    blinder is entered

    OST timer expires

    before inner blinder is

    reached

    Breaker trips as the

    system angle is getting

    smaller

    Steady state load

    operating point

    pre-swing

    OST armed to trip on-the-way-out when inner blinder is

    entered (can also trip here)

    Systems slip-a-pole where

    the system angle is 180

    degrees

    TOWO occurs whenswing leaves inner

    blinder

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    25/56

    25

    Early SPS Power Swing Philosophy

    Power Swing Tools of the Early Years

    Prior to 1962, graph paper, slide rules and DCcalculating boards were used

    Stability studies were run off-site on AC networkanalyzers

    In 1962, SPS used an IBM 1620 computer to run loadflow, short circuit and stability studies

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    26/56

    26

    Early SPS Power Swing Philosophy

    Early PSB (Mho) Relay Settings Philosophy

    Only block tripping of 3-phase elements on zone 1and zone 2 relays

    Set PSB mho concentric about zone 2 The PSB timer was fixed at 3 to 4 cycles, depending

    on manufacturer

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    27/56

    27

    Early SPS Power Swing Philosophy

    Early PSB (Mho) Relay Settings Philosophy

    The first PSB philosophy seta buffer zone of half zone 2around zone 2

    As zone 2 grew, the gapbetween the relays grewproportionally

    This philosophy allowed forhigher slip rates, but less line

    loadability This philosophy remained

    until about the mid 1990s(~40 years)

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    28/56

    28

    Early SPS Power Swing Philosophy

    Early PSB (Mho) Relay Settings Philosophy

    The next philosophy set theoffset mho a fixed 2-ohmssecondary separation from

    zone 2

    With this philosophy, as thezone 2 grew, the gap betweenzone 2 and the PSB relaydecreased

    This philosophy allowed forbetter line loadability, butlower slip rates

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    29/56

    29

    Early SPS Power Swing Philosophy

    Early OST Relay Settings Philosophy

    Identify lines to be tripped to form balancedload/generation islands

    One end of line was typically tripped to keep tappedload energized or to keep the line energized for VARsupport

    OST Philosophy in a nutshell:

    Set Per I.M.

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    30/56

    30

    Early SPS Power Swing Philosophy

    Early OST Relay Settings Philosophy

    OST Relays:

    Concentric mho

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    31/56

    31

    Early SPS Power Swing Philosophy

    Early OST Relay Settings Philosophy

    OST Relays:

    Dual blinder

    Inner blinders set between arc

    impedance region and 120 degrees

    (120 150 degrees typically)

    Arc Impedance

    Region

    Outer blinders set to

    accommodate a

    3.33 Hz slip rate

    =(144.5 84.0) 60()

    360

    3.0()

    = 3.36

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    32/56

    32

    Early SPS Power Swing Philosophy

    Early OST Relay Settings Philosophy

    OST Relays:

    Lens

    Outer tomato set at70 degrees

    Middle circle set at

    108 degrees

    Inner lens set at

    151 degrees

    Reach set beyond

    system impedance

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    33/56

    33

    Modern SPS Power Swing Philosophy

    Power Swing Tools of the Modern Years

    Short circuit programmacro to plot reducedsystem impedance and

    theoretical swingtrajectories

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    34/56

    34

    Modern SPS Power Swing Philosophy

    Power Swing Tools of the Modern Years

    Out-of-step analysisspreadsheet

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    35/56

    35

    Modern SPS Power Swing Philosophy

    Power Swing Tools of the Modern Years

    Out-of-step COMTRADE filecalculator using MathCAD

    COMTRADE file play-backthrough relay using test set

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    36/56

    36

    Modern SPS Power Swing Philosophy

    Modern PSB Relay Settings Philosophy

    PSB Major Considerations

    NERC PRC-023 load limit

    o Outer blinder must not encroach upon load region

    Worst case system slip rate (Hz)

    o Typically 2-5 Hz for stable swings

    Worst case expected arc impedance

    o Inner blinder must not be set too close to arc

    impedance region if used to supervise Z1 or Z2tripping

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    37/56

    37

    Modern SPS Power Swing Philosophy

    Modern PSB Relay Settings Philosophy

    37

    Set outer PSB blinders

    just inside the NERC

    PRC-023 limit

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    38/56

    38

    Modern SPS Power Swing Philosophy

    Modern PSB Relay Settings Philosophy

    Set inner PSB blinders

    just outside zone 2

    phase mho circle

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    39/56

    39

    Set top inner blinder a

    percentage BEYOND

    the apparent impedance

    for a L-L fault at the

    remote bus

    Why???

    Modern SPS Power Swing Philosophy

    Modern PSB Relay Settings Philosophy

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    40/56

    40

    Fault at end of the line could fall

    between inner and outer top

    blinders, allowing the OOS block

    timer to expire before the Z2

    timer, thus delaying the Z2 trip

    until the negative sequence

    unblock timer times out!

    This would be considered a slow

    trip mis-operation.

    Modern PSB Relay Settings Philosophy

    Modern SPS Power Swing Philosophy

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    41/56

    41

    Set top outer blinder to 0.1 ohms

    secondary higher than top inner

    blinder

    Set bottom blinders to mirror top

    blinders (current philosophy)

    Modern SPS Power Swing Philosophy

    Modern PSB Relay Settings Philosophy

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    42/56

    42

    PSB spreadsheet final graph

    Modern PSB Relay Settings Philosophy

    Modern SPS Power Swing Philosophy

    Set OOS block time delay to

    achieve a slip rate of at least 2.5

    Hz (current philosophy)

    Set higher than minimum distanceelement operating time based

    upon SIR (see relay instruction

    manuals)

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    43/56

    43

    Modern SPS Power Swing Philosophy

    Modern OST Relay Settings Philosophy OST Major Considerations

    NERC PRC-023 load limit

    Worst case system slip rate (Hz)

    o Typically 2-10+ Hz for un-stable swings

    Worst case expected arc impedance

    Slow evolving faults

    o OST time delay should be > 1.5 cycles!!!

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    44/56

    44

    Modern SPS Power Swing Philosophy

    Modern OST Relay Settings Philosophy

    OST Settings

    Outer blinder settings are set the same as PSB blinders

    Inner blinder set between arc impedance zone and 120

    degree system angle

    Top and bottom blinders should be set to account for areasonable worst case weak system

    Set for minimum slip rate of 3 Hz (current philosophy)

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    45/56

    45

    Modern SPS Power Swing Philosophy

    Modern OST Relay Settings Philosophy

    Final actual in-service settings

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    46/56

    46

    Modern SPS Power Swing Philosophy

    Modern OST Relay Settings Philosophy

    Final actual in-service settings

    Arc Impedance

    Region

    Inner Blinder

    Supervision of

    Z1 and Z2Required!

    =

    (147.6 93.0) 60()

    360

    2.0()

    = 4.55

    Supervise Breaker Tripping

    with Outer Blinder

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    47/56

    47

    Modern SPS Power Swing Philosophy

    Modern OST Relay Settings Philosophy

    NERC PRC-026

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    48/56

    48

    Early Philosophy in the Modern World

    SPS still has over 100 Electromechanical PSB relays inservice

    NERC PRC-023 will be effective for 100-200 kV lineswithin the next couple of years

    Some of these relays will have to be evaluated toensure they comply with PRC-023

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    49/56

    49

    Early Philosophy in the Modern World

    50% of zone 2 buffer philosophy check:

    NERC PRC-023

    Load Region

    NERC Region

    Violation!!!

    =(98 50) 60()

    360

    4.0()

    = 2.0

    23-mile 115 kV line

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    50/56

    50

    Early Philosophy in the Modern World

    50% of zone 2 buffer philosophy check:

    =

    (114 59) 60()

    360

    4.0()

    = 2.29

    Pull Z2 back to

    125% of line

    impedance

    =(114 59) 60()

    3603.0()

    =3.06

    23-mile 115 kV line

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    51/56

    51

    Early Philosophy in the Modern World

    2-ohm secondary separation philosophy check:

    = (121 69) 60()360

    3.0()

    = 2.89

    Different 23-mile115 kV line

    Good!!!

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    52/56

    52

    Early Philosophy in the Modern World

    2-ohm secondary separation philosophy check:

    = (105 79) 60()360

    3.0()

    = 1.44

    Same line, impedancedoubled, ignore load limit

    NOT Good!!!

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    53/56

    53

    Conclusions

    Conclusions

    SPSs external and internal islanding strategy has beenproven to avoid total system blackouts

    Technological advancements in analysis tools have

    improved confidence in power swing settings Technological advancements in power swing relaying

    have added much needed flexibility to allow relays to beset to achieve desired slip rates

    NERC Reliability Standards PRC-023 and PRC-026 will

    require re-evaluation of power swing philosophies

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    54/56

    54

    Conclusions

    Moving Forward

    SPS will have to re-evaluate its existing islanding schemevalidity with SPP performing Balancing Authorityfunctions

    SPS will continue to refine and test power swing settingsusing simulations and COMTRADE play-back

    IEEE PSRC Working Group D29 will create a tutorial onsettings conventional blinder power swing settings in asimulated environment

    The Odyssey Continues

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    55/56

    55

    Questions???

  • 7/24/2019 0810 Power Swing Relaying in the Texas Panhandle - An Out-Of-Step Odyssey FINAL 03312015

    56/56

    56

    References

    [1] IEEE Power System Relaying Committee WG D6, Power Swing and Out -of-Step Considerations on Transmission Lines, July2005. Available: http://www.pes-psrc.org.