Busbar Protection

Protection & Contrôle / Application

Rev. A JM, September 2004

Page 2: 07-Busbar Protection Busbar Protection Rf

08/0205/02/032 2

Without Busbar Protection

F2F1

There are fewer faults on busbars than on other parts of the power system. No risk of dislocation of system due to accidental operation of busbar protection.

Argues

Page 3: 07-Busbar Protection Busbar Protection Rf

08/0205/02/033 3

Without Busbar Protection

F2F1

Slow fault clearance.Busbar faults at F1 and F2 are cleared by remote time delayed protection on circuits feeding the faults:

Time Delayed Overcurrent orTime Delayed Distance Protection

Drawbacks

Page 4: 07-Busbar Protection Busbar Protection Rf

08/0205/02/034 4

With Busbar Protection

BUSBARZONE

F1

Fast clearance by breakers at the busbars

Page 5: 07-Busbar Protection Busbar Protection Rf

08/0205/02/035 5

With Busbar Protection

BUSBARZONE

F2F1

Where busbars are sectionalised,Protection can limit the amount of system

disruption for a busbar fault

Page 6: 07-Busbar Protection Busbar Protection Rf

08/0205/02/036 6

21 21

87BB

87BB

1/2

With Busbar Protection

SS 1

SS 2

SS 3

Page 7: 07-Busbar Protection Busbar Protection Rf

08/0205/02/037 7

21 21

87BB

87BB

2/2

With Busbar Protection

Page 8: 07-Busbar Protection Busbar Protection Rf

08/0205/02/038 8

21 21 21

21 21

1/2

With No Busbar Protection

Page 9: 07-Busbar Protection Busbar Protection Rf

08/0205/02/039 9

21 21

2/2

21

21 21

With No Busbar Protection

Page 10: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0310 10

21 21 21

21 21

21 21

87BB87BB

With Busbar protection

With No Busbar protection

Page 11: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0311 11

Busbar Faults Are Usually Permanent

Causes of Busbar Faults :

Falling debris

Insulation failuresCircuit breaker failuresCurrent transformer failuresIsolators switchs operated on load or outside their ratingsSafety earths left connected

Therefore :

Circuit breakers should be tripped and locked out by busbar protection

Page 12: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0312 12

Busbar Protection must be :

RELIABLE– Failure to trip could cause widespread damage to the substation

STABLE– False tripping can cause widespread interruption of supplies to

customers / possible power system instability

DISCRIMINATING– Should trip the minimum number of breakers to clear the fault

FAST– To limit damage and possible power system instability

Page 13: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0313 13

Methods of Providing Busbar ProtectionFrame to Earth (Leakage) Protection

Blocking Scheme Protection

Differential Protection : High ImpedanceLow Impedance

Insulation

>I

>I >I >I >I>I

Page 14: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0314 1405/02/0314

Frame Leakage Protection

Protection & Contrôle / Application

Rev. A JM, September 2004

Page 15: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0315 15

Insulation

>I

Frame Leakage Busbar Protection

Page 16: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0316 16

>I

Frame Leakage Busbar Protection

Page 17: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0317 17

>I

Frame Leakage Busbar Protection

Page 18: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0318 18

>I

Frame Leakage Busbar Protection

>I

Page 19: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0319 19

Can detect only earth faults

Switchgear must be insulated from earth (by standing on concrete plinth)

Only one single earth conductor allowed on switchgear

All cable glands must be insulated

Switchgear sections must be insulated

Frame Leakage Busbar Protection

Page 20: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0320 20

>I

>I

Frame Leakage Busbar Protection

Neutral Check

False Operation because induced loop

No operation prevents from false trip

Page 21: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0321 21

>I

>I

Frame Leakage Busbar Protection

Neutral Check

Page 22: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0322 22

>I

>I

Neutral Check

Frame Leakage Busbar Protection

Page 23: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0323 2305/02/0323

Blocking Scheme Protection

Protection & Contrôle / Application

Rev. A JM, September 2004

Page 24: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0324 24

>I >I >I >I>I

Blocking Scheme Busbar Protection

Page 25: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0325 25

>I >I >I >I>I

Blocking Scheme Busbar Protection

Page 26: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0326 26

>I >I >I >I>I

Blocking Scheme Busbar Protection

Page 27: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0327 2705/02/0327

High Impedance Protection

Protection & Contrôle / Application

Rev. A JM, September 2004

Page 28: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0328 2808/0205/02/0328

Single Bus Substation

Page 29: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0329 29

P1

P2

S1

S2

P1

P2

S1

S2

P1

P2

S1

S2

Single Bus Substation

Page 30: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0330 30

Single Bus Substation

Page 31: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0331 31

Single Bus Substation

Page 32: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0332 32

Single Bus Substation

Page 33: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0333 3308/0205/02/0333

Double Bus Substation

Page 34: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0334 34

Isolator Auxiliary Switches Current switching

Bus A

Bus B

ab

Current

P1

P2

S1

S2

P1

P2

S1

S2

P1

P2

S1

S2

P1

P2

S1

S2

P1

P2

S1

S2

Page 35: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0335 35

Isolator Auxiliary Switches Current switching

Bus A

Bus B

ab

Current

Page 36: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0336 36

Isolator Auxiliary Switches Current switching

Bus A

Bus B

ab

Current

Page 37: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0337 37

Isolator Auxiliary Switches Current switching

Bus A

Bus B

ab

Current

Page 38: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0338 38

Isolator Auxiliary Switches Current switching

Bus A

Bus B

ab

Current

Page 39: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0339 39

Isolator Auxiliary Switches Current switching

Bus A

Bus B

ab

Current

Page 40: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0340 40

Bus A

Current

Bus B

ab

Isolator Auxiliary Switches Tripping switching

Tripping ab

Page 41: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0341 41

Main CT must be identical

Current switching via auxilliary relay is not acceptable.

Requirement of number of position contact (Disconnector switch) is high

Interposing CT are not acceptable

Page 42: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0342 42

Isolator Auxiliary Switches Current switching

Bus A

Bus B

abCurrent

Page 43: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0343 43

Isolator Auxiliary Switches Current switching

Bus A

Bus B

abCurrent

Bus A

Bus B

abCurrent

Page 44: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0344 44

Bus A

Bus B

abCurrent

Isolator Auxiliary Switches On Load Transfer

Page 45: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0345 45

Bus A

Bus B

abCurrent

Isolator Auxiliary Switches On Load Transfer

Page 46: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0346 46

Bus A

Bus B

abCurrent

Isolator Auxiliary Switches On Load Transfer

Page 47: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0347 47

Bus A

Bus B

abCurrent

Isolator Auxiliary Switches On Load Transfer

Page 48: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0348 48

Bus A

Bus B

ab

Current

Isolator Auxiliary Switches On Load Transfer

Page 49: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0349 49

Bus A

Bus B

abCurrent

Isolator Auxiliary Switches On Load Transfer

Page 50: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0350 50

Bus A

Bus B

abCurrent

Isolator Auxiliary Switches On Load Transfer

Page 51: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0351 51

Bus A

Bus B

Trip

Bus

A

Trip

Bus

B

Zone AZone B

Isolator Auxiliary Switches Check Zone

Page 52: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0352 52

Bus A

Bus B

Trip

Bus

A

Trip

Bus

B

Zone AZone B

Isolator Auxiliary Switches Check Zone

Current switching failure

False Tripping

Page 53: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0353 53

Bus A

Bus B

Trip

Bus

A

Trip

Bus

B

Check Zone

Zone AZone B

Isolator Auxiliary Switches Check Zone

Page 54: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0354 54

Bus A

Bus B

Trip

Bus

A

Trip

Bus

B

Zone AZone B

Isolator Auxiliary Switches Check Zone

Page 55: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0355 55

Bus A

Bus B

Trip

Bus

A

Trip

Bus

B

Check Zone

Isolator Auxiliary Switches Check Zone

Page 56: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0356 5608/0205/02/0356

One Breaker and a Half Substation

Page 57: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0357 57

Bus A Bus B

P1

P2

S1

S2

P1

S1

P2

S2

P1P2

S1S2

Page 58: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0358 58

Bus A Bus B

Page 59: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0359 59

Bus A Bus B

Page 60: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0360 60

Bus A Bus B

Page 61: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0361 61

Bus A Bus B

Page 62: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0362 62

Bus A Bus B

Page 63: 07-Busbar Protection Busbar Protection Rf

08/0205/02/0363 63

Bus A Bus B

P1

S1

P2

S2

P1

S1

P2

S2

P1

S1

P2

S2

P1

S1

P2

S2