Top Banner

of 816

04.Control Valves (ABB Kent)

Oct 16, 2015

Download

Documents

anhkietvt
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 'Alpha' Series 12/19Single Seated Body

    Instructions for Series 12/19 Range of Control Valves

  • 1ABB Control Valves

    P3300 Series Pneumatic Valve Positioner

    Single acting, force-balance operatingprinciple

    Excellent dynamic response, shortpositioning time and neglegiblepositioning error

    Field adjustable for valve strokesbetween 14 mm and 102 mm (1/2 inand 4 in)

    Single feedback cam with threestandard characteristics

    Convenient, no range springchanging required and accuratemeans of split-ranging the signal and/or the valve action.

    Compatible with all spring anddiaphragm-operated control valves

    Set and forget reliability

    Complies with relevant internationalstandards for test procedures andenvironmental protection againstharsh plant conditions

    Specification DataFile

  • 2Physical SpecificationsConstructionCase and by-pass assembly

    Standard: die-case aluminium alloy (low copper andmagnesium).Optional: AISI 316 ss.

    Case coverStandard: P.B.T. 20, glass fibre reinforcedpolibutilentereftalathe.Impact-resistant self-extinguishing polyester.Epoxy-resin painted - RAL 1001.Optional: AISI 316 ss.

    Input bellowsStandard: brass.Optional: AISI 316 ss.

    Flapper/NozzleAISI 303 ss.

    Cam and Feedback lever:AISI 304 ss.

    IntroductionModel W-PP, the pneumatic valve positioner of the P3300Series of field mounting instruments, ensures that the controlvalve plug position is always directly proportional to thepneumatic input signal, regardless of diaphragm actuatorhysteresis, packing-box friction or off-balance force on thevalve plug.

    The valve responds to infinitely small changes in the controlleroutput signal when process lags require the use of wideproportional band.

    Problems usually associated with plant instability due either tooversized valves or non-linear trim characteristics areminimized by selecting one of the three feedback camalternative positions.

    By-pass option allows positioner to be removed withoutdisturbing the control valve operation.

    Turn-down ratio 5 to 1 by a single controller output signal splitranging for sequential operation of two or more control valvesis standard.

    Functional SpecificationsInput Pressure Range

    0.2 - 1 bar, 20 - 100 kPa, 3 - 15 lb/in*0.4 - 2 bar, 40 - 100 kPa, 6 - 30 lb/in*

    Auxiliary Supply Pressure1.4 - 4 bar, 140 - 400 kPa, 20 - 60 lb/in*

    Start Point and Span AdjustmentsSeparate, internal, continuous.

    Split-rangeAny value down to 20% of specified input range.

    Stroke LengthAny value between 14 mm and 102 mm (1/2 in and 4 in)providing feedback lever rotation is 50Q.

    Output to ActuatorUp to 95% of auxiliary supply pressure, direct or reverseacting.

    Environmental Conditions

    ylppuS ylppuS ylppuS ylppuS ylppuSrab

    ylppusyrailixuA ylppusyrailixuA ylppusyrailixuA ylppusyrailixuA ylppusyrailixuA)citats(noitpmusnoc

    )mfcs(h/lN

    )cimanyd(yticapacwolF )cimanyd(yticapacwolF )cimanyd(yticapacwolF )cimanyd(yticapacwolF )cimanyd(yticapacwolF)mfcs(h/lN

    erusserptupnisasesaercnI sesaercnI sesaercnI sesaercnI sesaercnI sesaerceD sesaerceD sesaerceD sesaerceD sesaerceD

    4.1 )12.0(053.xam )45.5(0009otpu )45.5(00094 )63.0(006.xam )6.9(00651otpu )45.5(0009

    Cam Characteristics

    )rab(ylppuSyrailixuA erutarepmeT C %ytidimuHevitaleR erusserPcirtemoraB )sbarabm(noitarbiV

    )3-456CEIgnidrocca(ecnerefeR 4.1.nim %14.xam %1 53+ot51+ 57ot54 0801ot068 enoN

    lamroN 4.1.nim %54.xam %5 58+ot52-

    001oot0gnisnednoc

    0801ot007

    f1 zH01ot1= )mm5.1.pmA(f2 zH06ot01= )mm51.0.pmA(f3 zH005ot06=A( cc s/m6.91. 2)

    emertxE 4.1.nim %514.xam %51021+ot34-

    ottropsnarTegarotS 0801ot066

    zH051ot1=f)s/mm0032.leV(

    latnedicca

  • 3Physical SpecificationsSpring

    AISI 302 ss.Internal connections

    AISI 316 ss.Identification tag

    AISI 316 ss permanently mounted - 20 characters max.(legend to be specified).

    GaugesBrass with plastic case or AISI 316 ss, as specified.

    Pneumatic connectionSupply, output and instrument: 1/4in. NPT female.

    Natural gas exhaust1/2 in NPT female.

    Net Weight2.5 Kg approx. without optional extras

    Optional ExtrasPositioner by-pass switch

    Externally operated.Gauges

    Supply and Output: 0 to 4 bar/0 to 60 PSI, 0 to 4 kg.cm2Signal: 0 to 2 bar/0 to 30 PSI 0 to 2kg.cm2

    Natural gas auxiliary supplyFor applications where instrument air is not available.Tapped 1/2 in. NPT.

    Performance SpecificationsUnless otherwise stated performance specifications are givenat reference environmental condition, 0.2 to 1 bar or 0.4 to2 bar input pressure standard ranges, with standard linearcam and direct acting positioner. All errors are quoted aspercentage of the associated actuator stroke. Test proceduresare in accordance with relevant international standards.

    Accuracy1% (includes combined effects of non-linearity,hysteresis and repeatability).

    Terminal based linearity05%

    RepeatabilityBetter than 0.3%

    HysteresisBetter than 0.5%.

    Indication accuracy2% f.s.d.

    Environmental protectionIP 55 according to IEC 529.

    Operating InfluencesAmbient temperature over the range 25 to +55 C:

    Better than 0.3%/10KAuxiliary supply:

    0.65%/0.1 bar.Humidity and barometric pressure:

    No influence.

    Outline Dimensions

  • 4ABB Control ValvesKent IntrolBrighouseWest Yorks.England, HD6 1QFTel: +44 (0) 1484 710311Fax: +44 (0) 1484 407407

    ABB Control ValvesABB KK6-2-2, Takatsukadai Nishi-kuKobe 651-22JapanTel: +81 78 991 5920Fax: +81 78 991 5900

    ABB Control ValvesABB Instrumentation22016 LennoComoItalyTel: +39 (0) 344 58111Fax: +39 (0) 344 58278

    ABB Control ValvesIntrol (India) LimitedH-34, MIDC, AmbadNashik 422 010IndiaTel: +91 253 381434Fax: +91 253 384413

    SS

    /330

    0Is

    sue

    1

    The Companys policy is one of continuous productimprovement and the right is reserved to modify theinformation contained herein without notice. ABB 1999 Printed in UK (11.99)

    Ordering Information

    .onredrO .onredrO .onredrO .onredrO .onredrO 0033P 0033P 0033P 0033P 0033P XXXXX XXXXX XXXXX XXXXX XXXXX XXXXX XXXXX XXXXX XXXXX XXXXXnoitcurtsnoCfoslairetaM noitcurtsnoCfoslairetaM noitcurtsnoCfoslairetaM noitcurtsnoCfoslairetaM noitcurtsnoCfoslairetaM

    dnaswolleBtupnIstraPtnaveleR

    esaC revoCesaC

    ssarBSS613ISIASS613ISIA

    muinimulAmuinimulA

    SS613ISIA

    retseyloPretseyloPSS613ISIA

    135

    ylppuSyrailixuA ylppuSyrailixuA ylppuSyrailixuA ylppuSyrailixuA ylppuSyrailixuAriAtnemurtsnI

    saGlarutaNyrD15

    edoCesU edoCesU edoCesU edoCesU edoCesU 1)*(hctiwSssaP-yB )*(hctiwSssaP-yB )*(hctiwSssaP-yB )*(hctiwSssaP-yB )*(hctiwSssaP-yBtuohtiW

    htiW12

    seguaGerusserP seguaGerusserP seguaGerusserP seguaGerusserP seguaGerusserPtupnI

    oNseYseYseYseY

    tuptuO

    oNseYseYseYseY

    ylppuS

    oNoNseY

    oNseY

    seguaGfolairetaM

    ssarBssarB

    SS613ISIASS613ISIA

    12345

    citsiretcarahCmaC citsiretcarahCmaC citsiretcarahCmaC citsiretcarahCmaC citsiretcarahCmaCdradnatS

    )**(laicepS19

    edoCesU edoCesU edoCesU edoCesU edoCesU 1edoCesU edoCesU edoCesU edoCesU edoCesU 1

    )***(egnaRerusserPtupnI )***(egnaRerusserPtupnI )***(egnaRerusserPtupnI )***(egnaRerusserPtupnI )***(egnaRerusserPtupnIni/bl5ot3 2

    rab1ot2.0/APk001ot02ni/bl03ot6 2

    rab2ot4.0/APk002ot04)*(egnaRtilpS

    12569

    edoCesU edoCesU edoCesU edoCesU edoCesU 0)*()**()***(.etoN

    .snoitacilppanoitcaesreverroegnartilpsrofdednemmocertoN.redroehthtiwdeificepsebtsumpihsnoitalerlevartmetsevlavfotnecrep/erusserptupnifotnecreP

    .redrohtiwdeificepsebtsumegnarerusserptupnI.noitcatceridroftes-erpeblliwrenoitisopehtdetatsesiwrehtosselnU

  • TZID-C Intelligent Positioner,Compact and Efficient

    10/18-0.22 EN

    Compact and efficient, through well-proven technology and intelligence

    Communication based on the HART protocol Simple commissioning procedure

    through fully automatical Autoadjust function Easily understandable adjustment mode,

    adjustment via the built-in operator panel or remotely using the standardized configuration program

    4...20 mA input, 2-wire, supply voltage 8.7 V DC for the standard model and 9.7 V DC for the intrinsically safe model

    Approved explosion protection for intrinsically safe operation, EEC type acceptance certificate, TV 98, ATEX 1370 X

    Complies with the directives for EMC and CE conformity Robust aluminum case, IP 65 Influence of shock and vibration

  • TZID-CIntelligent Positioner 10/18-0.22 EN

    Construction and mode of operationPage 2 of 16 08.01

    The concept

    The TZID-C positioner is an intelligent and electronically config-urable instrument with communication capabilities, mounting topneumatic actuators. The TZID-C stands out for a small and com-pact design, a modular construction, and an excellent cost-perfor-mance ratio.

    The functional heart of the TZID-C positioner is its microprocessor-controlled CPU where the operating system is running. The inputsignal and the position feedback signal are polled with a samplingrate of 20 ms and an A/D resolution of 4000 steps. This ensures arapid and high-precision signal processing for the input and theposition feedback. The power for the CPU is derived from the setpoint signal.The operating program includes an Autoadjust routine for auto-matic adjustment of the device in the commissioning phase, andan adaptation program which provides for optimal control of theposition to minimize control deviation.

    The pneumatic actuator is driven by an I/P module with subse-quent 3/3-way valve. The electrical positioning signal from theCPU is proportionally converted into a pneumatic signal which, inturn, proportionally adjusts the 3/3-way valve. The cross-sectionalarea of the valve air channels for filling the actuator with air orevacuating air from it is changed in proportion with the adjustment.When reaching the set point, the 3/3-way valve is closed in centerposition.

    The positioner has an operating panel consisting of a 2-line LCDand 4 push-buttons. The operating panel has the perfect design foroptimal local configuration, commissioning, and operational moni-toring. Alternatively, the TZID-C can be configured, commissionedand monitored remotely from a PC via its communication port,using the HART protocol. You can either tap at a local connector,or frequency-modulated at any chosen point of the 4...20 mA sig-nal line.

    The modular design of the positioner allows you to add furtherfunctionality at a later time. Plug-in modules for analog and digitalposition feedback as well as assembly kits for mechanical positionindication and digital position feedback using proximity switches or24 V microswitches are available. Additionally, the plug-in modulefor the shutdown function is available.

    Various TZID-C features ensure safe valve operation on site: Compliance with the EMC directive Robust aluminum case, protection IP 65 (NEMA 4X) High resistance to shock and vibration up to 10 g Operational reliability through permanent monitoring and

    error indication in case of troubles Operation at ambient temperatures of - 30 ... + 85 C

    (- 22 ... + 185 F)

    LKS connector

    Signal4 20 mA

    Digital input

    Digital output

    FSK module

    Microprocessor

    EEPROM

    CPU

    ENTER

    MODE

    Air supply1.46 barOutgoing air

    I/P modulewith 3/3-way valve

    Position sensing

    Plug-in modulefor analog

    position feedback4 20 mA

    Plug-in modulefor digital

    position feedbackMin - Max

    Kit for mechanicalposition indicator

    Kit for digitalposition feedback

    Min. Max.

    Options

    and/or

    or

    Plug-in modulefor analog

    position feedback4 20 mA

    (48 V supply)

    orPlug-in module

    for safety shutdown(forced decompression)

    Kit for24 V microswitchesMin./Max. positionor

    optionally for rotation angle of up to 270

    Optocoupler(Shutdown function)24 V DC

    TZID-C schematic diagram

  • 08.01 Page 3 of 16

    TZID-CIntelligent Positioner 10/18-0.22 EN

    Construction and mode of operation

    Mounting

    To linear actuators in accordance with the standard

    Lateral attachment is in accordance with DIN/IEC 534 (lateralattachment to Namur). The attachment kit required for lateralattachment is a complete set of attachment material, except forscrewed pipe connections and air pipes.

    To rotary actuators in accordance with the standard

    Attachment to rotary actuators is in accordance with VDI/VDE3845. The attachment kit contains two items: the adapter for cou-pling the positioner feedback shaft to the actuator shaft, and amounting bracket for mounting the positioner to the actuator.Screwed pipe connections and air pipes are not included in the kitand have to be provided by the customer

    Integral mounting to control valvesThe TZID-C positioner is ready for integral mounting (e.g. to theABB 23/24, 23/25 and 23/26 control valves). The appropriatethreaded holes are available at the positioners back. The benefitof this design is that the point for mechanical stroke measurementis inside the yoke and, thus, protected by it. No external tubing isrequired, since the air flow from the positioner to the actuator isguided through an internal channel bore.Special actuator-specific mountingIn addition to the mounting methods described above, there arespecial actuator-specific attachments.

    Please contact us for details.

    Mounting to linear actuators to DIN/IEC 534

    Integral mounting to 23/24 and 23/25 control valves

    Mounting to rotary actuators to VDI/VDE 3845

    Integral mounting to 23/26 control valves

  • Page 4 of 16 08.01

    TZID-CIntelligent Positioner 10/18-0.22 EN

    Operating system

    General

    With its operating program the intelligent microprocessor-con-trolled TZID-C positioner is best suited for achieving optimalresults - both in terms of rapid and precise control until reaching theset point and in terms of a high operational reliability. The activa-tion and adjustment of parameters necessary to achieve this goalis in parts automatic (auto-adjustment) and in parts manual.

    The total range of parameters includes: Operating parameters Adjustment parameters Monitoring parameters Diagnosis parameters

    Operating parametersThe following operating parameters can be activated and adjusted:

    Signal rangeIt can be selected whether the full range of 4 .. 20 mA or a split-range is to be used.

    Valve actionDirect: Range 4...20 mA/direction 0...100 %Reverse: Range 20...4 mA/direction 0...100 %

    Characteristic curve (travel = f {pos. signal})linear,equal percentage 1:25 or 1:50 or 25:1 or 50:1,or user-configurable with 20 reference points

    Tolerance band (sensitivity limit)The factory setting of 0.3 % is a typical value, which only has to be increased in case of very short strokes or high hystere-sis values of the valve. Normaly, the controller automatically optimizes itself during the Autoadjust function.

    Travel limitingThe positioning travel, i.e. the stroke or angle of rotation, can be reduced as required within the full range of 0...100%, provided that a minimum value of 20% is observed.

    Shut-off valueThis function causes immediate closing of the actuator. The threshold can be configured.

    Time-out monitoringThis function is used to monitor the time needed to reach the set point. It triggers an alarm if the unit is not able to adjust the deviation such that it fits into the tolerance band within the set time.

    Adjusted speed for full travel 100 %This function is used to increase the natural speed for con-trolling the full travel until reaching the set point. The speed can be set independently for each direction.

    Alarm limits for minimum and maximum positionsThis parameter is used to define the switching points for the minimum and the maximum position.

    Digital inputWith the digital input you can disable or limit configuration access or directly adjust the actuator by

    holding the current actuator positionorsetting the actuator to the 0% or 100 % position

    Adjustment parametersThe following parameters can be activated and adjusted:

    Valve range 0 ... 100 %Valve end positions, start of range "0% and end of range "100 %".

    Effective direction of the actuatorAdjustment to either of the two possible directions:

    Air to open/spring force to closeorAir to close/spring force to open

    Display 0 ... 100 %Adjusting the display (0 ... 100 %) to the direction of action for opening or closing the valve.

    Control parametersTo adapt the TZID-C positioner to the control action of the valve, the control parameters can be adjusted individually to achieve optimal control until reaching the set point.

    The TZID-C positioner has a program (Autoadjust) for automaticadjustment of all relevant parameters. The Autoadjust routine canbe started by pressing the respective push-buttons on the devicesfront panel.

  • TZID-CIntelligent Positioner 10/18-0.22 ENOperating system08.01 Page 5 of 16

    Monitoring parametersThe TZID-C operating system allows for permanent self-monitor-ing. The following list gives some examples for errors that aredetected and can be indicated:

    Internal output circuit monitoring Leakage in the actuator or air pipe from / to it Signal out of 4 .... 20 mA range Position out of adjusted range (rotation angle) for position

    feedback Positioning time-out (adjustable time parameter) Limit of stroke counter or travel counter exceeded

    (limits can be adjusted during diagnosis)If any of these disturbances occurs, an alarm is generated andindicated as an error code on the built-in LC display, or reported asa collective alarm via the digital output, which is already providedby the basic TZID-C version.

    Extended monitoring is possible via the communication port. Themost important process variables like the output signal in mA, theposition in %, the deviation and, last not least, troubles occurringduring operation are indicated as plain text in a special line.

    The TZID-C positioner operator panel alllows for monitoring manual control TZID-C configuration (all operating data, except for the user

    configurable characteristic curve with 20 reference points)The operator panel consists of an LC display and four push-but-tons (see illustration to the right).The display indicates the following data:

    Current process value or parameter number,shown by the upper, 4-digit segment display

    Designator / name of indicated parameter or value,shown by the lower, 8-digit segment display

    TZID-C operating status, indicated by the following symbolsshown on the left hand side of the display

    Local configuration is disabledAutomatic control through the TZID-C

    Position is adjusted manually by actuating the and push buttons

    conf TZID-C has been changed over to theconfiguration level, control is interrupted

    On the operating level, i.e. while either automatic control is inprogress or the TZID-C is ready for manual position adjustment,the upper 4-digit 7-segment display indicates the position as a per-centage (0 ... 100 %). If an operating error should occur, the dis-play changes over to an error code (see "Monitoring parameters"for details).

    Diagnosis parametersThe diagnosis parameters of the TZID-C program inform the oper-ator about the operating conditions of the valve. From this informa-tion the operator can derive which maintenance works arerequired, and when. The parameters also provide informationabout the use of the valve and, thus, its possible wear.

    The following values are determined: Number of control actions performed by the valve Total stroking distance

    The diagnosis parameters can be set externally, i.e. via the com-munication port, by using the special TZID-C configuration pro-gram.

    conf

    mA

    ENTER

    MODE

    %C

    TZID-C operating elements

    Operation

  • TZID-CIntelligent Positioner 10/18-0.22 ENCommunication and special software for remote control and configurationPage 6 of 16 08.01

    GeneralThe TZID-C communication port allows for remote operation, mon-itoring and configuration.The "HART" Protocol is used for communication. Signals can betapped either locally at the connector or frequency-modulated atany chosen point of the 4 ... 20 mA signal transmission. Communi-cation is done on line, without impairing operation. New parametersettings become active immediately after being downloaded intothe device, but have to be stored in the TZID-C non-volatile mem-ory with a special command.

    The following equipment is needed for communication: a special connecting device

    (LKS adapter or FSK modem) an off-the-shelf PC

    (meeting special hardware requirements) a program for remote control and configuration

    (e.g. Smart Vision )

    LKS adapter as a communication linkThe LKS adapter is a connection solution which is both easy toinstall and cost-saving. On the TZID-C side, a local communicationinterface (LKS) is used. On the PC-side, a double sub-D jack witha 9-pole and a 25-pole connector is used. The connector alsoaccommodates an RS-232 interface converter for connection tothe PC.

    The TZID-C can be configured via the LKS without requiring that a4...20 mA signal is fed to it. As a result, this kind of configurationcan be performed in the workshop prior to commissioning. In thiscase the positioner is powered by the PC.

    FSK modem as a communication linkThe FSK modem is used to establish digital frequency-modulatedcommunication (Frequency Shift Keying). The digital signal "0"corresponds to 2.2 kHz, the digital signal "1" to 1.2 kHz. Tapping ispossible at any chosen point of 4...20 mA transmission, i.e. directly on site at the TZID-C or in a remote place, e.g. at an OCSin the control room. Frequency-modulated communicationrequires a circuit with a resistance of at least 250 ohms.

    The FSK modem is available in 2 versions: with or without electri-cal isolation. In conjunction with a special isolating amplifier, e.g.Contrans I or Contrans I_remote, the modem with electrical isola-tion is suitable for connection to a bus. Communication is also pos-sible with an intrinsically safe TZID-C, provided that the modemitself is placed outside the hazardous area. If these capabilities arenot required, you can also use the cost-saving modem withoutelectrical isolation (FSK Modem II). For details and technical data refer to the data sheets 10/15-6-97EN (FSK modem) and 10/18-0.31 EN (FSK Modem II).

    TZID-CLKS

    TZID-C

    TZID-C

    TZID-C

    TZID-C

    CONTRANS I

    CONTRANS I

    CONTRANS I

    FSK modem

    FSK modem

    FSK modem

    Source

    Source

    Source

    Source

    Communication via LKS adapter

    Communication via "HART"-protocol and FSK modem

  • 08.01 Page 7 of 16

    TZID-CIntelligent Positioner 10/18-0.22 ENCommunication and special program for remote control and communication

    Smart Vision Smart Vision is a windows-type graphical user interface withuser-friendly and intuitively operable standardized windows. Theprogram offers comfortable functions for configuring, monitoringand diagnosing the TZD-C positioner. Smart Vision is very similarto "Windows", i.e. it has similar intuitively operable windows, andcommands can be entered in the same way. Users familiar with"Windows" can easily adapt to Smart Vision.

    InputSignal range

    Nominal range 4...20 mA, split range configurable between 20...100% of nominal range

    Two-wire circuitrySupply voltage 8.7 V DC, without explosion protection

    9.7 V DC for intrinsically safe deviceResistance 435 ohms at 20 mA and 8.7 V DC

    485 ohms at 20 mA and 9.7 V DCDigital input

    Control voltage 12 ... 24 V DCCurrent max. 4 mA

    Smart Vision can be used with all our HART-compatible devices.It is ABBs communication platform for all products using HART.

    Hardware requirements

    Computer PC/Notebook for WINDOWS(IBM-compatible) 486 or higher

    Operating system Microsoft WINDOWS 95 or higherMicrosoft WINDOWS NT

    Hard disk at least 2 Mbytes free memory

    RAM at least 500 Kbytes free memory

    Disk drive CD ROM

    Interface RS 232 C for communication

    If you should need more information please dont hesitate to con-tact us.

    OutputRange

    0...6 bar (0...90 psi)Air capacity

    at supply pressure of 1.4 bar (20 psi) 5.0 kg/h = 3.9 Nm3/h = 2.3 scfm

    at supply pressure of 6 bar (90 psi) 13 kg/h = 10 Nm3/h = 6.0 scfm (Booster, for increasing air capacity, on request)

    Functionfor single or double acting actuators, air is vented from actua-tor or actuator is blocked in case of an electrical power failure

    Shut-off valueRange 0...20% of positioning signal (if the value falls below the set value, the positioner immediately moves the actuator to the closing position)

    Digital output (control current circuit to DIN 19234)Supply voltage 5 ... 11 VDCCurrent < 1.2 mA Logical "0"Current > 2.1 mA Logical "1"Effective direction: Normally logical "0" or logical "1"

    (configurable)

    Smart Vision - typical window

    Technical data

  • Page 8 of 16 08.01

    TZID-CIntelligent Positioner 10/18-0.22 ENTechnical data

    TravelAngle of rotation

    Used range 25 ... 120 (rotary actuatorsoptionally 270)25 ... 60 (linear actuators)

    Stroke timeRange 0...200 seconds, individually configurable for each direction

    Dead band time limitRange 0...200 seconds (monitoring parameter for control until the deviation is within the tolerance band)

    Stroke limitingMin. and max. limits, freely configurable within 0...100% of total travel (> 10 %)

    Air supplyInstrument air

    free of oil, water and dust to DIN/ISO 8573-1pollution and oil contents according to Class 3(Purity: max. particle size 5 m, max. particle density 5mg/m3; Oil contents: max. concentration 1 mg/m3; Dew point at least 10 C below operating temperature)

    Supply pressure1.4...6 bar (20...90 psi)Caution: Do not exceed the max. operating pressure of the actuator!

    Air consumption< 0.03 kg/h (0.08 scfm) (independent of supply pressure)

    Transmission data and influencesDirection (output signal or pressure in the actuator)

    Increasing: Increasing signal 4...20 mA Increas. pressure OUT1 in the actuator

    Decreasing: Increasing signal 4...20 mA Decreas. pressure OUT1 in the actuator

    Valve actionDirect: Signal 4...20 mA = position 0...100%Reverse: Signal 20...4 mA = position 0...100%

    Characteristic curve (travel = f signal)linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1and freely configurable with 20 reference points

    Characteristic deviation< 0.5%

    Tolerance band (sensitivity threshold)0.3...10%, adjustable

    Resolution (A/D conversion)> 4000 steps

    Sample rate20 ms

    Influence of ambient temperature< 0.5% for every 10 C change in temperature

    Influence of vibration +/-1% up to 10g and 80 Hz

    Seismic requirementsMeets requirements of DIN/IEC 68-3-3 Class III for strong and strongest earthquakes

    Influence of mounting positionNo effect

    Meets the following requirementsEMC directive 89/336/CEE as of May 1989EC directive for the CE conformity marking

    CommunicationHART protocol

    Communication link viaConnector for LKS adapter (standard)FSK modem for frequency-modulated tapping (optional)

    Environmental capabilitiesAmbient temperature

    - 30 to + 85 C (- 22 ... + 185 F)for operation, storage and transport

    Relative humidity< 75% (95% for a short time), non-condensing

    Explosion protection II 2G EEx ib II C T6EC type approval certificate TV 98 ATEX 1370

    EEx ia under preparationFM/CSA

    CaseMaterial/surface

    Aluminum, protection IP 65 (Type 4x)Bottom part of case varnished black, RAL 9005, matt,Cover white aluminum RAL 9006

    Electrical connectionsScrew terminals, internal, for CSA of 2.5 mm2

    Cable entry2 threads Pg. 13.5, 1/2-14 NPT or M20x1.51 with cable gland and 1 with pipe plug

    Pneumatic connectionsThreads G 1/4 or 1/4-18 NPT

    Weight: 1.7 kgMounting position: any orientation allowedDimensions: see dimensional drawings

  • 08.01 Page 9 of 16

    TZID-CIntelligent Positioner 10/18-0.22 EN

    Options

    Plug-in module for analog position feedback *Signal range 4 ... 20 mA (split ranges configurable)Two-wire circuitry, power supply 10...30 V DC(or 48 V DC without explosion protection)Valve action direct or reverse (configurable)Characteristic deviation < 1%(The module can be configured for alarm reporting throughmodulation of the output signal to < 4 mA or > 20 mA.)

    Plug-in module for digital position feedback *2 switches for the min. and max. positions(position adjustable within the range of 0 ... 100%)Current circuits to DIN 19234Supply voltage 5 ... 11 V DCControl current < 1.2 mA= switching state logical "0"Control current > 2.1 mA= switching state logical "1"Eff. direction: normally logical "0" or logical "1" (configurable)

    Plug-in module for the shutdown function*In case of a 24 V DC power failure, the positioner can let thevalve move to the safe position by depressurizing the actuatorindependently of the processor. To achieve this, the I/P modulepower supply is separated by an optocoupler. Both the commu-nication and feedback are still active, since the positioner ispowered via the 4 ... 20 mA 2-wire cable. The shutdown input iselectrically isolated from the 4 ... 20 mA signal.Due to the shutdown function no additional solenoid valves are required. It has a safety certificate from TV Rheinland in ac-cordance with AK4. The plug-in module also has an Ex certifi-cate for use in intrinsically safe current circuits.

    Mounting materialAttachment kit for linear actuators to DIN/IEC 534(lateral attachment to Namur)Attachment kit for rotary actuators to VDI/VDE 3845Attachment kit for integral mountingAttachment kit for actuator-specific attachment on request

    Pressure gage blockWith pressure gages for supply and output pressure,Pressure gages with plastic case 28 mm,with connection block made of aluminum, varnished black inclusive of mounting material for attachment to TZID-C.

    Filter regulatorAll metal version, brass varnished blackBronze filter element, 40 m, with condensate drainMax. pre-pressure 16 bar, output adjustable to 1.4...6 bar

    PC adapter for communicationLKS adapter for cnnector on TZID-CFSK modem for frequency-shift-keying

    PC software for remote configuration and operationSMART VISION (standard) as CD-ROM

    Isolating amplifier for signal range 0/4...20 mAContrans I or Contrans I_remote(see separate data sheets)

    Kit for mechanical position indicatorIndicator diskCover with transparent domeSymbol stickersExtension for the feedback shaft

    Kit for digital position feedback with proximity switches **2 proximity switches for min. and max. position(position adjustable within range of 0 ... 100%)Current circuit to DIN 19234Supply voltage 5 ... 11 V DCControl current < 1 mA= switching state logical "0"Control current > 3 mA= switching state logical "1"(works independently of the software and the electronics of thepositioner)Direction of action (logical state):

    Kit for digital position feedback with 24 V microswitches**Two 24 V DC/AC microswitches for the min. and max. position.Switching points adjustable between 0 and 100 %Not approved for use in the hazardous areas ! * The plug-in modules for analog and for digital position feedback are

    plugged in different slots and, thus, can be installed together. The plug-in module for the shutdown function, however, plugs into the same slotas the module for digital position feedback, so that these two modulescannot be used together.

    ** The digital position feedback option is directly actuated by the rotatingshaft of the TZID-C positioner and can only be used together with themechanical position indicator described above.

    Spare parts kitContains the following spare parts:

    Slot-typeinitiator

    Position< min. > min. < max. > max.

    SJ2-SN (NC) 0 1 1 0SJ2-S1N (NO) 1 0 0 1

    No. Designation Description5 Filter Filter element (housing)5 Filter Filter element (I/P module)1 Sealing ring Sealing ring for cap2 Screws Screws for cap1 Dust cap Dust cap IP651 Filter screw plug Filter screw plug for filter element

    (housing)1 Sealing ring Sealing ring washer for filter

    screw plug1 Optical position

    indicatorOptical position indicator

    1 Sticker Sticker for mechanical position indicator

    1 Hinging bolt Hinging bolt with plastic cone5 Spring Spring on hinging bolt1 Brief operating

    instructionsBrief operating instructions

    Accessories

  • Page 10 of 16 08.01

    TZID-CIntelligent Positioner 10/18-0.22 EN

    Ordering informationCatalog No EUR Deliv. time

    TZID-C Intelligent Positioner V18345- 0 0electro-pneumatic, configurablewith indicator and operator panelCase/MountingCase made of aluminium, varnished, protection IP 65 (NEMA 4X)

    For mounting to linear actuators acc. to DIN/IEC 534 or to rotary actuatorsacc. to VDI/VDE 3845, also ready for integral mounting 1 664,00 4 wks.

    As above, but with mechanical position indicator 2 690,00 4 wks.For mounting to rotary actuators acc. to VDI/VDE 3845 with extended rotation angle up to 270 5 742,00

    As above, but with mechanical position indicator 6 768,00

    Note:Special mounting material as specified under"Accessories" is requiredInput/communication port

    Input 4...20 mA, two-wireWith connector plug for LKS adapter 1 -With connector plug for LKS adapter andFSK module for frequency shift keying 2 78,00

    Explosion protectionwithout 0 -Ex II 2 G EEx ib II C T6 (EEx ia under preparation) 1 47,00FM/CSA 2 47,00Explosion protection certificate upon special agreement (on request)

    Output/safe position (in case of an electrical power failure)Single acting, fail safe 1 -

    fail freeze 2 -Double acting, fail safe 4 95,00

    fail freeze 5 95,00Connections

    Cable: Thread Pg. 13.5 Air pipe: Thread G 1/4 1 -Cable: Thread 1/2-14 NPT Air pipe: Thread 1/4-18 NPT 2 -Cable: Thread Pg 13.5 Air pipe: Thread 1/4-18 NPT 3 -Cable: Thread M20 x 1,5 Air pipe: Thread M12 x 1 4 -Cable: Thread M20 x 1,5 Air pipe: Thread 1/4-18 NPT 5 -Cable: Thread M20 x 1,5 Air pipe: Thread G 1/4 6 -

    Option modules for analog or digital position feedbackWithout 0 -Plug-in module for analog position feedback, signal range 4...20mA, two-wire 1 134,00

    digital feedback of minimum and maximum position 3 124,00shutdown module (temperature: -30+60) 4 90,00analog position feedback, sign. range 4...20 mA, two-wire and digital feedback of minimum and maximum position 5 258,00analog position feedback, sign. range 4...20 mA, two-wire and shutdown module (temperature: -30+60) 6 224,00analog position feedback, 48 VDC without Ex protection 7 171,00

    Mechanical Kit for digital position feedback (option)Without 0 -Mechanical kit for digital feedback of minimum and maximum position1)

    With slot-type initators SJ2-SN (NC or logical 1) 1 216,00With slot-type initiators SJ2-S1N (NO or logical 0) 3 216,00With 24 V DC/AC microswitches (change-over contacts) 5 103,00

    1) only for model with mechanical position indicator Continued on the next page

  • 08.01 Page 11 of 16

    TZID-CIntelligent Positioner 10/18-0.22 EN

    Ordering information (continued)Catalog No EUR Deliv. time

    TZID-C Intelligent Positioner V18345-electro-pneumatic, configurablewith indicator and operator panelDesign (varnish/coding)

    Standard 1 -Special version chemistry (details on request) E -As specified (on request)

    Device identification labelincudes lettering (plain text, max. 16 letters)

    stainless steel 11.5 x 60 mm on requ.sticker 41 x 32 mm on requ.sticker 11 x 25 mm on requ.

    Note: The modules for analog and digital position feedback and the kit for digital position feedback (slot-type initiators) are identical for the positioners with or without explosion protection.The 24V microswitches must not be used in hazardous areas.

    AccessoriesCatalog No EUR Deliv. time

    Mounting material and costAttachment kit for linear actuators (lateral attachment to DIN/IEC 534 or Namur)

    Stroke 10... 35 mm 18391-7959125 58,00 1 wk.Stroke 20 ... 100 mm 18391-7959126 58,00 1 wk.

    Attachment kit for integral mounting to23/24 and 23/25 cont. valve DN 15 up to DN 100, stroke 10...35 mm 18391-7959106 42,00 1 wk.

    DN 125 up to DN 150, stroke 25...65 mm 18391-7959107 42,00 1 wk.23/26 control valve DN 25 up to DN 100, stroke 10...35 mm 18391-7959108 84,00 1 wk.

    DN 125 up to DN 162, stroke 25...65 mm 18391-7959109 84,00 1 wk.

    Attachment kit for rotary actuators (mounting to VDI/VDE 3845), consisting ofa) Adapter (shaft coupler) 18391-7959110 37,00 1 wk.b) Mounting bracket, dimensions A/B = 80/20 mm 18391-0319603 63,00 1 wk.

    A/B = 80/30 mm 18391-0319604 63,00 1 wk.A/B = 130/30 mm 18391-0319605 63,00 1 wk.A/B = 130/50 mm 18391-0319606 63,00 2 wks.

    Mounting cost, material and adjustmentfor mounting to linear actuators to DIN/IEC 534or to rotary actuators to VDI/VDE 3845

    External tubing with Plastic tube 18391-0319628 58,00 2 wks.Copper pipe 18391-0319629 79,00 2 wks.Stainless steel pipe 18391-0319630 147,00 2 wks.

    for integral mounting to 23/24, 23/25 or 23/26 control valvesInternal tubing 18391-0319627 48,00 2 wks.External tubing1) with Copper pipe 18391-7959015 79,00 2 wks.

    Stainless steel pipe 18391-7959016 147,00 2 wks.

    1) External tubing only for 23/24 and 23/25 control valves with

    "air to close/spring to open" action, otherwise internal tubing only.

  • TZID-CIntelligent Positioner 10/18-0.22 EN

    AccessoriesPage 12 of 16 08.01

    Catalog No EUR Deliv. timePressure gage blockPressure gage block, including attachment material

    for single acting TZID-C, with 2 pressure gages 28 mm(1 x for air supply and 1 x for output pressure)G 1/4 connections Supply pressure range 0...10 bar/ 0...140 psi

    Output pressure range 0...4 bar/ 0...60 psi 18381-7959111 74,00 1 wk.Output pressure range 0...10 bar/ 0...140 psi 18381-7959112 74,00 1 wk.

    1/4-18 NPT connections Supply pressure range 0...10 bar/ 0...140 psiOutput pressure range 0...4 bar/ 0...60 psi 18381-7959113 74,00 1 wk.Output pressure range 0...10 bar/ 0...140 psi 18381-7959114 74,00 1 wk.

    for double acting TZID-C, with 3 pressure gages 28 mm(1 x for air supply and 2 x for output pressure)G 1/4 connections Supply pressure range 0...10 bar/ 0...140 psi

    Output pressure range 0...4 bar/ 0...60 psi 18381-7959115 84,00 1 wk.Output pressure range 0...10 bar/ 0...140 psi 18381-7959116 84,00 1 wk.

    1/4-18 NPT connections Supply pressure range 0...10 bar/ 0...140 psiOutput pressure range 0...4 bar/ 0...60 psi 18381-7959117 84,00 1 wk.Output pressure range 0...10 bar/ 0...140 psi 18381-7959118 84,00 1 wk.

    (Pressure gage blocks are delivered as separate units for mounting by the customer)Filter regulator

    Brass filter regulator, incl. material for mounting to pressure gage blockConnections Thread G 1/4 18381-7959119 152,00 1 wk.

    Thread 1/4-18 NPT 18381-7959120 152,00 1 wk.(Filter regulators are delivered as separate units for mounting by the customer)PC adapter for communicationLKS adapter See Data Sheet 63-6.71FSK modem See Data Sheet 63-6.71SMART VISION as CD-ROM See Data Sheet 63-1.20Option Modules (can be added later)Plug-in module for analog position feedback, signal range 4...20 mA, 2-wire 18391-7959128 170,00 1 wk.Plug-in module for analog position feedback, 48V ,without Ex protection 18391-7959194 207,00Plug-in module for digital feedback of minimum and maximum position 18391-7959129 160,00 1 wk.Plug-in module for shutdown function 18391-7959199 113,00

    Kit for Mechanical position indicator 18391-7959130 82,40 1 wk.(including front cover with glass)

    Kit for Digital feedback of minmum and maximum position(including front cover with mechanical position indicator)

    with 24 V DC/AC microswitches (change-over contacts) 18391-7959191 211,00with slot-type initiators SJ2 - SN (NC or logical 1) 18391-7959131 324,00

    SJ2 - S1N (NO or logical 0) 18391-7959132 324,00

    Kit for digital feedback of minimum and maximum position1)with 24 V DC/AC microswitches (change-over contacts) 18391-7959190 129,00with slot-type initiators SJ2 - SN (NC or logical 1) 18391-7959133 247,00

    SJ2 - S1N (NO or logical 0) 18391-7959134 247,00Spare partsSpare parts kit 18391-7959198 170,00

    I/P-Module (single acting, fail safe) (explosion-proof model, only) 18391-7958510 370,00I/P-Module (single acting, fail freeze) (explosion-proof model, only) 18391-7958511 370,00I/P-Module (double acting, fail safe) (explosion-proof model, only) 18391-7958512 440,00I/P-Module (double acting, fail freeze) (explosion-proof model, only) 18391-7958513 440,001) Only fits for basic model with mechanical position indicator

  • 08.01 Page 13 of 16

    TZID-CIntelligent Positioner 10/18-0.22 EN

    Wiring diagrams

    +31 -

    32

    +41 -

    42Li

    mit

    2Li

    mit

    1

    +51

    -52

    +51

    -52

    +11

    -12

    +83

    -84

    +81

    - 82

    1

    +41 -

    422

    4

    6

    8

    7

    9

    5

    3

    1. Plug-in module for analog position feedback2. Plug-in module for digital position feedback (first connector)

    or plug-in module for shutdown function

    3. Plug-in module for digital position feedback (second connector)4. Kit for digital position feedback, either proximity switches or

    24 V microswitch (first connector) 5. Kit for digital position feedback, either proximity switches or

    24 V microswitch (second connector)6. Digital input DI7. Digital output DO8. Signal 4...20 mA9. Enclosure ground

    Electrical connections

    +31 -

    32

    Plug-in module for analog position feedback

    24 V

    Basic model

    +11

    -12

    +83

    -84

    +81

    - 82

    4 20 mA

    Digital input DI(12 V)

    Digital output DO(NAMUR)

    +41 -

    42Li

    mit

    2Li

    mit

    1+

    51 -5

    2

    Limit 1

    Limit 2

    Kit for digital position feedbackPepperl & Fuchs proximity switches

    Kit for digital position feedback24 V Microswitch

    41 4

    2 43

    Lim

    it 2

    51 5

    2 53

    Lim

    it 1

    Enclosure ground

    Plug-in module for digital position feedback

    +41 -

    42SW 1

    Plug-in module for shutdown function

    +41 -

    4224 V

    +51 -

    52SW 2

    NC contactNO contact

    Input

    NC contactNO contact

    Input

    Terminal assignment

  • Page 14 of 16 08.01

    TZID-CIntelligent Positioner 10/18-0.22 EN

    168.5

    89.5

    110.752323

    25

    50

    58

    104.5

    65

    5 0

    33.560

    2

    7

    4545

    M5x0,5

    1414

    2929

    18

    92

    9

    28.5

    28

    14

    142

    10

    M5

    10

    14.5

    1 PositionerTZID-C

    Document 901047

    II 2G EEx ib IIC T6TVTV 98 ATEX 1370 X

    Ui, Ii, Pi, Ci, Li, Tambsee certificate

    CE 0032

    Made in GermanyMade in Germany

    TZID-C CETyp 18345-Softw.-Rev.Serial no.Serien Nr.Supply press.: 1.4...6barZuluftdruck: 20...90psiInput: analog 4-20mAEingang:

    Output:Ausgang:

    single einfachwirkenddouble doppeltwirkend

    Loss of electr. supply:Stromlos: fail entlftendentlftend

    fail blockierendblockierendOptions: analog feedbackanalog feedback

    electr. limit switchmech. limit switch

    FSKposition indicator

    Top view

    Front view Rear view

    Side view (from right)Side view (from left)

    Dimensional drawings

  • 08.01 Page 15 of 16

    TZID-CIntelligent Positioner 10/18-0.22 EN

    75

    30 / 53

    45 -

    75

    25

    A*

    B*

    *) Dimensions A and B depend on rotary actuator size

    141

    172

    70

    173

    172

    70

    Mounting to linear actuators to DIN/IEC 534 Mounting to rotary actuators to VDI/VDE 3845

    Mounting to 23/24 and 23/25 control valves Mounting to 23/26 control valves

    Dimensional drawings

  • ABB Automation Products GmbHSchillerstrae 72D-32425 MindenPhone +49(0) 57 18 30 - 0Fax +49(0) 57 18 30 - 18 60http://www.abb.com

    Page 16 of 16 08.01

    40120

    97

    TZID-C

    TZID-C with mounted pressure gage block and filter regulator

    Dimensional drawings

  • SpecificationPV-1100 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1101 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1102 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1103 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1200 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1201 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1202 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1203 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1300 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1301 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1302 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1030 - Case 1Case 2Case 3Case 4Case 5Case 6

    PV-1400 - Case 1Case 2Case 3Case 4Case 5

    PV-1401 - Case 1Case 2Case 3Case 4Case 5

    PV-1402 - Case 1Case 2Case 3Case 4Case 5

    PV-1403 - Case 1Case 2Case 3Case 4Case 5

    PV-1500 - Case 1Case 2Case 3Case 4

    PV-1501 - Case 1Case 2Case 3Case 4

    PV-1502 - Case 1Case 2Case 3Case 4

    PV-1503 - Case 1Case 2Case 3Case 4

    PV-1660 - Case 1Case 2Case 3

    PV-1661 - Case 1Case 2Case 3

    PV-1662 - Case 1Case 2Case 3

    PV-1663 - Case 1Case 2Case 3

    PV-1700 - Case 1Case 2Case 3

    PV-1701 - Case 1Case 2Case 3

    PV-1702 - Case 1Case 2Case 3

    PV-1703 - Case 1Case 2Case 3

    LV-1603LV-1605PV-1008APV-1008B

    DrawingsPV-1100PV-1101PV-1102PV-1103PV-1200PV-1201PV-1202PV-1203PV-1300PV-1301PV-1302PV-1303PV-1400PV-1401PV-1402PV-1403PV-1500PV-1501PV-1502PV-1503PV-1660PV-1661PV-1662PV-1663LV-1603LV-1605PV-1700PV-1701PV-1702PV-1703PV-1008APV-1008BPV-1834 (old PV-1034)

    Noise predictionPV-1100 - case 5cPV-1100 - case 5aPV-1100 - case 5bPV-1100 - case 2cPV-1200 - case 2cPV-1300 - case 2cPV-1500 case 1cPV-1660 - case 3cPV-1700 - case 1c

    CertificatesPV-1100PV-1101PV-1102PV-1103PV-1200PV-1201PV-1202PV-1203PV-1300PV-1301PV-1302PV-1303PV-1400PV-1401PV-1402PV-1403PV-1500PV-1501PV-1502PV-1503LV-1603LV-1605PV-1660PV-1661PV-1662PV-1663PV-1700PV-1701PV-1702PV-1703PV-1008APV-1008BESME valves (pilot controller of PV-1008A/B)

    Instruction & maintenance leafletsClassic 10 and 11 globe bodyPneumatic actuators'Alpha' series 12/19 single seated bodyP3300 series pneumatic valve positionerAssembly instructions for envirograph 2TZID-C intelligent positionerConstruction and mode of operationOperating systemOperationCommunication and special software for remote control and configurationTechnical dataOptionsAccessoriesWiring diagramsDimensional drawings

    Bifold operating and maintenance instructionsESME valve installation operating & maintenance instructions for tye R1140 (PV-1834)ESME installation operating & maintenance instructions for type R88 MP, pilot (for PV-1008A/B)

    menu: