    Based on Project Minerals Library, CoE Cement and Minerals

    Prep. ATBPA / P.Topfmeyer 10.07.2009Appr. ATBPA / M.Knabenhans 30.04.2010Doc. kind Reference Manual Doc. Item

    Title Basic Objects des. des.800xA Minerals Library version 5.1/4a Resp. dept. CHIND / ATBPA

    Document identityLang. Rev. ind. Sheet 1

    ABB Switzerland Ltd 3BHS 161556 en R No. of sh. 113Template: Design Description_1,1_A4h_en_standard.dot; Filename: 02 Minerals Library Basic Objects 5p1s4a.docx; Print: 9/15/2013 10:02:00 PM; Save: 9/14/2013 4:34:00 PM; CHIND No. 3BHS102547 ZAB E01 Rev A. -; I-Q

    Basic ObjectsReference Manual

    800xA AC800M Connect - Minerals Library

    Version 5.1/4a

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    2/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 2

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    CONTENT

    1 SUMMARY ................................................................................................................ 5

    2 COMMON DATA ....................................................................................................... 52.1 BASIC DESCRIPTION ..................................................................................... 52.2 CONTROL ....................................................................................................... 6

    2.2.1 Library location .................................................................................... 62.2.2 Control modes ..................................................................................... 6

    2.2.3 PCC, Interlock Bus (Process Control Connection) ............................... 62.2.3.1 PCC Bus concept ................................................................ 62.2.3.2 Basic Functions of PCC ....................................................... 62.2.3.3 PCC Interlock Parameter Description .................................. 7

    2.2.4 Simulation Mode ............................................................................... 112.3 OPERATION.................................................................................................. 11

    2.3.1 Properties .......................................................................................... 112.3.1.1 IndicationType ................................................................... 112.3.1.2 EnableLimitLabel ............................................................... 132.3.1.3 NumberOfDigits ................................................................. 132.3.1.4 EnableUnit ......................................................................... 132.3.1.5 TextIndAbnormalPos / TextIndNormalPos ......................... 132.3.1.6 Orientation ......................................................................... 142.3.1.7 SymbolSize ........................................................................ 142.3.1.8 EnableFitToBestSize ......................................................... 142.3.1.9 EnableLogicalColor ............................................................ 142.3.1.10 ValueColor ......................................................................... 14

    3 AI Analogue Input .................................................................................................. 163.1 BASIC DESCRIPTION ................................................................................... 163.2 CONTROL ..................................................................................................... 17

    3.2.1 Diagram Graphical Representation AIS ............................................. 173.2.2 Diagram Graphical Representation AIC............................................. 173.2.3 Parameter description ....................................................................... 17

    3.2.3.1 Parameter AIS ................................................................... 173.2.3.2 Parameter AIC ................................................................... 19

    3.2.4 Data Type description ....................................................................... 223.2.5 Project Constants .............................................................................. 243.2.6 PCC Interlock Limitations for AIS and AIC ......................................... 24

    3.3 OPERATION.................................................................................................. 253.3.1 Graphic elements .............................................................................. 25

    3.3.1.1 AISandUnit or AICandUnit ................................................. 263.3.1.2 AISTxt or AICTxt ................................................................ 283.3.1.3 AISBar or AICBar............................................................... 30

    3.3.2 Faceplate .......................................................................................... 333.3.2.1 Aspect Link Buttons ........................................................... 333.3.2.2 Default View ...................................................................... 333.3.2.3 Extended View ................................................................... 343.3.2.4 Faceplate Control Permission ............................................ 41

    3.3.3 Alarm & Event List ............................................................................. 423.3.3.1 Object Status and Modes ................................................... 423.3.3.2 Alarm Messages ................................................................ 42

    4 AO Analogue Output .............................................................................................. 444.1 BASIC DESCRIPTION ................................................................................... 444.2 CONTROL ..................................................................................................... 44

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    3/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 3

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    4.2.1 Diagram Graphical Representation AOS ........................................... 444.2.2 Diagram Graphical Representation AOC ........................................... 444.2.3 Parameter description ....................................................................... 45

    4.2.3.1 Parameter AOS ................................................................. 454.2.3.2 Parameter AOC ................................................................. 45

    4.2.4 Data Type description ....................................................................... 464.3 OPERATION.................................................................................................. 48

    4.3.1 Graphic elements .............................................................................. 48

    4.3.1.1 AOSandUnit or AOCandUnit .............................................. 494.3.1.2 AOCBar or AOSBar ........................................................... 514.3.1.3 AOCIncDecButton or AOSIncDecButton ............................ 53

    4.3.2 Faceplate .......................................................................................... 544.3.2.1 Aspect Link and Command Buttons ................................... 544.3.2.2 Default View ...................................................................... 544.3.2.3 Extended View ................................................................... 554.3.2.4 Faceplate Control Permission ............................................ 58

    4.3.3 Alarm & Event List ............................................................................. 594.3.3.1 Object Status and Modes ................................................... 594.3.3.2 Alarm Messages ................................................................ 59

    5 DI Digital Input ....................................................................................................... 605.1 BASIC DESCRIPTION ................................................................................... 605.2 CONTROL ..................................................................................................... 61

    5.2.1 Diagram Graphical Representation DIS............................................. 615.2.2 Diagram Graphical Representation DIC ............................................ 615.2.3 Parameter description ....................................................................... 61

    5.2.3.1 Parameter DIS ................................................................... 615.2.3.2 Parameter DIC ................................................................... 62

    5.2.4 Data Type description ....................................................................... 635.2.5 Project Constants .............................................................................. 645.2.6 PCC Interlock Limitations .................................................................. 64

    5.3 OPERATION.................................................................................................. 65

    5.3.1 Time Diagram.................................................................................... 655.3.2 Graphic elements .............................................................................. 65

    5.3.2.1 DIS or DIC ......................................................................... 665.3.2.2 DISTxt or DICTxt ............................................................... 68

    5.3.3 Faceplate .......................................................................................... 705.3.3.1 Aspect Link and Command Buttons ................................... 705.3.3.2 Default View ...................................................................... 705.3.3.3 Extended View ................................................................... 715.3.3.4 Faceplate Control Permission ............................................ 74

    5.3.4 Alarm & Event List ............................................................................. 755.3.4.1 Object Status and Modes ................................................... 755.3.4.2 Alarm Messages ................................................................ 75

    6 DO Digi tal Outpu t ................................................................................................... 766.1 BASIC DESCRIPTION ................................................................................... 766.2 CONTROL ..................................................................................................... 76

    6.2.1 Diagram Graphical Representation DOS ........................................... 766.2.2 Diagram Graphical Representation DOC........................................... 766.2.3 Parameter description ....................................................................... 77

    6.2.3.1 Parameter DOS ................................................................. 776.2.3.2 Parameter DOC ................................................................. 77

    6.2.4 Data Type description ....................................................................... 78

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    4/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 4

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    6.3 OPERATION.................................................................................................. 796.3.1 Graphic elements .............................................................................. 79

    6.3.1.1 DOS or DOC...................................................................... 806.3.1.2 DOSTxt or DOCTxt ............................................................ 826.3.1.3 DOSButton or DOCButton ................................................. 84

    6.3.2 Faceplate .......................................................................................... 866.3.2.1 Aspect Link and Command Buttons ................................... 866.3.2.2 Default View ...................................................................... 86

    6.3.2.3 Extended View ................................................................... 876.3.3 Faceplate Control Permission ........................................................... 896.3.4 Alarm & Event List ............................................................................. 90

    6.3.4.1 Object Status and Modes ................................................... 906.3.4.2 Alarm Messages ................................................................ 90

    7 PCC_Connect_2 ..................................................................................................... 917.1 BASIC DESCRIPTION ................................................................................... 917.2 CONTROL ..................................................................................................... 91

    7.2.1 Parameter description ....................................................................... 917.3 OPERATION.................................................................................................. 92

    7.3.1 PCC Parent Link ............................................................................... 92

    8 PCC_Connect ......................................................................................................... 938.1 BASIC DESCRIPTION ................................................................................... 938.2 CONTROL ..................................................................................................... 93

    8.2.1 Diagram Graphical Representation ................................................... 938.2.2 Parameter description ....................................................................... 938.2.3 Interlock Masks ................................................................................. 958.2.4 Application Example .......................................................................... 96

    8.3 OPERATION.................................................................................................. 988.3.1 PCC Parent Link ............................................................................... 98

    9 PCC_Threshold_AND3 .......................................................................................... 999.1 Basic Description ........................................................................................... 99

    9.2 CONTROL ................................................................................................... 1009.2.1 Diagram Graphical Representation ................................................. 1009.2.2 Parameter description ..................................................................... 1009.2.3 Application Example ........................................................................ 1029.2.4 PCC Viewer Presentation ................................................................ 103

    9.3 OPERATION................................................................................................ 1049.3.1 Faceplate ........................................................................................ 104

    9.3.1.1 Aspect Link Buttons ......................................................... 1049.3.1.2 Default View .................................................................... 1049.3.1.3 Application Example ........................................................ 108

    10 PCC_Intlk .............................................................................................................. 109

    10.1 BASIC DESCRIPTION ................................................................................. 10910.2 CONTROL ................................................................................................... 10910.2.1 CDE Graphical Representation ....................................................... 10910.2.2 Parameter description ..................................................................... 10910.2.3 Data Type Definition ........................................................................ 110

    10.2.3.1 OPERATION ................................................................... 11110.2.3.2 Extended View ................................................................. 112

    11 DOCUMENT REVISION HISTORY........................................................................ 113

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    5/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 5

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    1 SUMMARY

    This document contains a detailed description of the following Basic Objects:

    AI (Analog Input)

    AO (Analog Output)

    DI (Digital Input)

    DO (Digital Output)

    Additionally, four PCC specific Function Blocks and Control Modules are described

    PCC_Connect_2

    PCC_Connect

    PCC_Threshold_AND3

    PCC_Intlk

    2 COMMON DATA

    2.1 BASIC DESCRIPTION

    Basic Objects provide access and control for process IO-signals and calculated IO-signalsfrom the ABB System 800xA operator workplace.

    All basic objects have the following commonbasic functions:

    Tracking of control mode and status changes on the Operator station

    Operator Station Interface (graphic element and faceplate) including detailed alarmand interlock indications.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    6/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 6

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    2.2 CONTROL

    2.2.1 Library location

    The Control Module Types for basic objects and its corresponding Structured Data Typesare located in the library BMIStandardfor Control Builder M Professional.

    2.2.2 Control modes

    The basic objects AO and DO have 2 different control modes ManandAuto. All modesare selectable from the operator station or the superior application.

    Man:Object is controlled via On/Off commands for DOs and Set Value commands for AOs.These commands are issued from the faceplate.

    Auto :Object is controlled by On/Off commands for DOs and Set Value commands for AOs.These commands are issued from the superior application.

    2.2.3 PCC, Interlock Bus (Process Control Connection)

    2.2.3.1 PCC Bus concept

    Using the unique PCC (Process Control Connection) concept input signal objects(AIS/AIC and DIS/DIC) can propagate their state to the consumer object. Depending onthe configuration, signals may send interlock actions to the connected consumer withoutusing binary interlock code. In addition it is possible to link between faceplates of signalsand consumers as soon a PCC is available.

    2.2.3.2 Basic Functions of PCC

    Interlock configuration for connected consumers thru parameters on AIS/AIC andDIS/DIC.

    Connection of unlimited number of AIS and DIS to a Consumer Object or Group

    Local Start override and Start Inhibit

    Automatic first fault detection of signal causing an interlock. First fault is presented onthe Consumer Object and Group faceplates including a link button to the source signal

    Link between AIS, AIC / DIS, DIC faceplates and to the consumer / group faceplate

    Two direction Alarm Acknowledgement between AIS/DIS and Consumer / Group.Typical use is the auto alarm-acknowledge while a Consumer Object is controlled inLocal.

    Function Block PCC_Connect allows connecting two or more consumers or groups toone AIS / DIS. In addition, this Function Block allows overwriting of the PCC

    Alarm/Event enabling from the consumer for the connected AIS / DIS. For eachconnected consumer an individual Interlock forwarding mask defines which interlocksare blocked on a per limit basis if they are not desired.

    Function Block PCC_ThresholdAND3 to handle complex interlocks. It allows definingmultiple custom conditions to be used as interlocks on the PCC bus.

    PCC Status viewer for consumer and group objects

    Automatic disabling of AIS / DIS alarming with the following option:

    cBMI.Std_Type: 0

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    7/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 7

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    Motor is not running, NC Valve is closed, NO Valve is Open, for PCC connected toGroup: if Group is not started

    cBMI.Std_Type: 1Same as Std_Type 0 but always alarm on all Objects if Group is started andConsumer preselected. In case object is standby preselected alarm priority isautomatically reduced from Failure to Warning.

    PCCAEListFrcEn = trueAutomatic alarm disabling switched off. This option shall be used in cases a signalhas to alarm independent from the status of its parent.

    2.2.3.3 PCC Interlock Parameter Description

    The following configuration options are applicable for AIC, AIS, DIC, DIS, PIDCtrl,PCC_Intlk and PCC_Threshold_AND3.

    IntlkType and IntlkDir are limit based configurations where as IntlkStartInhibit andIntlkLocStartOverride are valid for all limits of the object.

    Parameter Name Description

    IntlkType - assigns the interlock to one of the interlock categories- ready for start (RFS) configuration option to keep consumer readyfor group start even when interlock is present

    - can be configured to start consumer in auto mode

    IntlkDir - direction of interlock for two direction consumers

    - Option to act only as start interlock

    IntlkStartInhibit the interlocks are bypassed for the set time after the start of thePCC parent (MOTx, VLVx)Application example: bypass of rush in for motor current

    IntlkLocStartOverride Bypass interlocks in Local mode if LCBStart is continuouslypushed. All PCC parents need to be in LOC.Application example: temporary bypass of drift switches for a beltconveyor in local mode to align the belt

    The possible configuration settings for Interlock Type are:

    IntrlkTypeConfiguration Option

    Description

    PCC_Disabled No alarm or interlock forwarding on PCC bus

    No_Interlock No interlock forwarding, only alarm forwarding

    PD_PrevDrive Previous drive interlock, group remains ready for start

    IA_Process Process interlockIf the consumer is in Auto mode the IA interlock is not reset againon the ok condition. It is only reset by an Auto_Start command fromanother PCC limit or signal.

    IA_Process_RFS Process interlock, group remains ready for startSame functionality in Auto as described above.

    IB_Equipment Equipment interlock

    IB_Equipment_RFS Equipment interlock, group remains ready for start

    IC_Safety Safety interlock

    IC_Safety_RFS Safety interlock, group remains ready for start

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    8/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 8

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    Auto_Start Only used if consumer is in Auto mode: removes retained IAinterlock if it is not active anymore and thus the drive will start(IO.In.IA also needs to be ok)

    The possible configuration settings for Interlock Direction are:

    IntlkDirConfiguration Option

    Description

    DirX Configured interlock is only valid for direction X

    DirXStart Same as DirX, but once the consumer is running in direction X (or has reached end position X) the interlock is disregarded.

    DirY Configured interlock is only valid for direction Y

    DirYStart Same as DirY, but once the consumer is running in direction Y (or has reached end position Y) the interlock is disregarded.

    DirXY Configured interlock is valid for direction X and Y

    DirXYStart Same as DirXY, but once the consumer is running in direction X/Y(or has reached end position X/Y) the interlock is disregarded.

    DirFBX Configured interlock is dynamic feedback (like FB1 in MOT1) fordirection X.

    IO.Out.RunX or PosX will only become active if condition is fulfilled.It can be used for additional limit switches [MOTP], speed-,pressure, flow-switch with advantage of prewarning, alarm andready delay.

    DirFBY Configured interlock to handle as dynamic feedback (like FB1 inMOT2) for direction Y.IO.Out.RunY or PosY will only become active if condition is fulfilled.It can be used for additional limit switches [MOTP], speed-,pressure, flow-switch with advantage of prewarning, alarm andready delay.

    DirFBXY Configured interlock to handle as dynamic feedback for directionX/Y.

    IO.Out.RunX/Y or PosX/Y will only become active if condition isfulfilled.It can be used for additional limit switches [MOTP], speed-,pressure, flow-switch with advantage of prewarning, alarm andready delay.

    DirXFast Configured interlock to execute action in fast task for direction X.

    Applicable for stop at position for MOT2, middle position stop forMOTP and the other application where fast stop is required.

    DirYFast Configured interlock to execute action in fast task for direction Y.

    Applicable for stop at position for MOT2, middle position stop forMOTP and the other application where fast stop is required.

    DirXYFast Configured interlock to execute action in fast task for direction X/Y.

    Applicable for stop at position for MOT2, middle position stop forMOTP and the other application where fast stop is required.

    DirFBXFast Combination of FB and Fast for Direction X

    DirFBYFast Combination of FB and Fast for Direction Y

    DirFBXYFast Combination of FB and Fast for Direction X/Y

    DirXnoAck Configured interlock to use "Value" instead of "Normal". Useful forcases where operation will be possible even if the alarm was notacknowledged but the value returned to Normal Position.

    DirYnoAck Configured interlock to use "Value" instead of "Normal". Useful forcases where operation will be possible even if the alarm was not

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    9/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 9

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    IntlkDirConfiguration Option

    Description

    acknowledged but the value returned to Normal Position.

    DirXYnoAck Configured interlock to use "Value" instead of "Normal". Useful forcases where operation will be possible even if the alarm was notacknowledged but the value returned to Normal Position.

    DirXStartnoAck Same as DirXnoAck, but once the parent is running in direction X(or has reached end position X) the interlock is disabled.

    DirYStartnoAck Same as DirYnoAck, but once the parent is running in direction Y(or has reached end position Y) the interlock is disabled.

    DirXYStartnoAck Same as DirXYnoAck, but once the parent is running in directionX/Y (or has reached end position X/Y) the interlock is disabled.

    DirFBXnoAck Combination of FB and noAck for Direction X.

    DirFBYnoAck Combination of FB and noAck for Direction Y.

    DirFBXYnoAck Combination of FB and noAck for Direction X/Y.

    DirXFastnoAck Combination of Fast and noAck for Direction X.

    DirYFastnoAck Combination of Fast and noAck for Direction Y.

    DirXYFastnoAck Combination of Fast and noAck for Direction X/Y.

    DirFBXFastnoAck Combination of FB and Fast and noAck for Direction X.

    DirFBYFastnoAck Combination of FB and Fast and noAck for Direction Y.DirFBXYFastnoAck Combination of FB and Fast and noAck for Direction X/Y.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    10/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 10

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    The possible assignment for different control modules are:

    IntlkDirConfigurationOption

    AIS AIC DIS DICPCC_Com_

    Drive(ComError)

    PCC_Threshold_AND_3& PCC_Intlk

    PID

    DirX Yes Yes Yes Yes Yes Yes Yes

    DirXStart Yes Yes Yes Yes Yes Yes Yes

    DirY Yes Yes Yes Yes Yes Yes Yes

    DirYStart Yes Yes Yes Yes Yes Yes YesDirXY Yes Yes Yes Yes Yes Yes Yes

    DirXYStart Yes Yes Yes Yes Yes Yes Yes

    DirFBX Yes Yes Yes Yes - Yes Yes

    DirFBY Yes Yes Yes Yes - Yes Yes

    DirFBXY Yes Yes Yes Yes - Yes Yes

    DirXFast - - Yes - - - -

    DirYFast - - Yes - - - -

    DirXYFast - - Yes - - - -

    DirFBXFast - - Yes - - - -

    DirFBYFast - - Yes - - - -

    DirFBXYFast - - Yes - - - -

    DirXnoAck Yes Yes Yes Yes - - Yes

    DirYnoAck Yes Yes Yes Yes - - Yes

    DirXYnoAck Yes Yes Yes Yes - - Yes

    DirXStartnoAck Yes Yes Yes Yes - - Yes

    DirYStartnoAck Yes Yes Yes Yes - - Yes

    DirXYStartnoAck Yes Yes Yes Yes - - Yes

    DirFBXnoAck Yes Yes Yes Yes - - Yes

    DirFBYnoAck Yes Yes Yes Yes - - Yes

    DirFBXYnoAck Yes Yes Yes Yes - - Yes

    DirXFastnoAck - - Yes - - - -

    DirYFastnoAck - - Yes - - - -

    DirXYFastnoAck - - Yes - - - -

    DirFBXFastnoAck - - Yes - - - -

    DirFBYFastnoAck - - Yes - - - -

    DirFBXYFastnoAck - - Yes - - - -

    For more details about PID refer to the Loop Object Reference manual document ID:3BHS161562.

    http://europe.abb.com/ch/c04/01/Aut_Devel/03_OperateIT_BMI/Documentation%20-%20Original/AC800M/08%20System%20Version%205p1s4%20for%20Minerals/03%20Minerals%20Library%20Loop%20Objects%205p1s3.pdfhttp://europe.abb.com/ch/c04/01/Aut_Devel/03_OperateIT_BMI/Documentation%20-%20Original/AC800M/08%20System%20Version%205p1s4%20for%20Minerals/03%20Minerals%20Library%20Loop%20Objects%205p1s3.pdfhttp://europe.abb.com/ch/c04/01/Aut_Devel/03_OperateIT_BMI/Documentation%20-%20Original/AC800M/08%20System%20Version%205p1s4%20for%20Minerals/03%20Minerals%20Library%20Loop%20Objects%205p1s3.pdfhttp://europe.abb.com/ch/c04/01/Aut_Devel/03_OperateIT_BMI/Documentation%20-%20Original/AC800M/08%20System%20Version%205p1s4%20for%20Minerals/03%20Minerals%20Library%20Loop%20Objects%205p1s3.pdf
  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    11/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 11

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    2.2.4 Simulation Mode

    It is possible to simulate DIS, AIS, DOS and AOS objects. Under simulation mode thehardware error connection is not considered.

    When set the simulation mode, the following is set as initial behaviour after a warm start.Notice that it is the initial condition which can be changed afterwards.

    AIS hardware connection (error condition) is not considered and the value

    is set to 50% of the total range. Input is blocked. Notice that the input willbe blocked and the value will be set to 50% only in case of warm start.

    DIS hardware connection is not considered and the value is set to thenormal position. Input is blocked. Notice that the value is simulated only incase of warm start.

    DOS and AOS hardware connections are not considered.

    In case any of output objects (DOS and AOS) are connected to thehardware all the changes to them will be written to the hardware.

    For safety reason we advise to disconnect the Profibus, modulebus or anyother hardware interface.

    2.3 OPERATION

    Details on all available graphic elements for the basic objects are available in theoperation chapter of the individual object type e.g. Analog Input.

    2.3.1 Properties

    Below is an overview of the properties that are applicable for the graphic elements thatrepresent basic objects.

    2.3.1.1 IndicationType

    Name DataType Default Value Description

    IndicationType IndicationTypeEnum A03_MotorM Symbol type selection

    Name Values

    IndicationTypeEnum A00_Rectangle.A01_Motor.A03_MotorM.A04_Pump.A05_Fan.A06_RotaryFeeder.E77_BeltCleaner.A02_Valve.B11_Damper.B14_LouvreDamper.B16_PropRoller.B15_AirslideDiverter.B12_Shut.B13_Diverter.E21_GearwheelPump.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    12/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 12

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    C31_Valve3way.C32_ValveMan.C33_ValveAuto.E41_Generator.E42_Switch.E07_Triangle.E08_Lollipop.E09_Diamond.

    E99_TagName.F00_None.

    With this property the type of graphic symbol that shall represent a DI or DO object canbe selected.

    Not applicable for AI / AO objects.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    13/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 13

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    2.3.1.2 EnableLimitLabel

    Name DataType Default Value Description

    EnableLimitLabel Boolean True Show limit labels

    When set to True, the alarm limits are visible next to the graphic element.

    Only applicable for AI objects.

    2.3.1.3 NumberOfDigits

    Aspect: AISandUnit, AICandUnit, AOSandUnit, AOCandUnit

    Name DataType Default Value Description

    NumberOfDigits Integer 4 Number of presented digits

    Used for setting how many digits need to be shown.

    This is only applicable for AI / AO objects.

    Not applicable for the bar graph.

    2.3.1.4 EnableUnitAspect: AISandUnit, AICandUnit, AOSandUnit, AOCandUnit, PIDCtrl

    Name DataType Default Value Description

    EnableUnit Boolean True Show units

    When set to true, the engineering units are visible next to the graphic element.

    This is only applicable for AI / AO / PID objects.

    2.3.1.5 TextIndAbnormalPos / TextIndNormalPos

    Aspect: DISTxt, DICTxt, DOSTxt, DOCTxt

    Name DataType Default Value DescriptionTextIndAbnormalPos String "On" Text for abnormal positionTextIndNormalPos String "Off" Text for normal position

    With these properties a text can be added for abnormal position and normal position.This text will be represented on the graphic symbol for DI / DO objects.

    Aspect: AISTxt, AICTxt

    Name DataType Default Value Description

    TextIndTrH1AbnormalPos String "H1" TextIndTrH1AbnormalPosTextIndTrH1NormalPos String "Off" TextIndTrH1NormalPos

    With these properties a text can be added for abnormal position and normal position.This text will be represented on the graphic symbol for AI.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    14/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 14

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    2.3.1.6 Orientation

    Name DataType Default Value Description

    Orientation Integer 0 Obsolete property used for migrationonly, Orientation in degrees, clockwise.

    Obsolete property used for migration only, Orientation in degrees, clockwise.

    Orientation is still used (to rotate the symbol indication) in the following Generic

    Elements core: DigitalCmdButtonCore

    DigitalCore

    DriveCmdButtonCore

    DriveCore

    SymbolCore

    2.3.1.7 SymbolSize

    Name DataType Default Value Description

    SymbolSize Integer 12 Defined the square size in case of IndicationType = 10

    Size of the symbol in the graphic display.

    E.g. Symbol size in pixel: 8 = Little

    12 = Small

    16 = Standard

    20 = Large

    24 = XXL

    2.3.1.8 EnableFitToBestSize

    Name DataType Default Value Description

    EnableFitToBestSize Boolean True Set best unit size

    When set to True, the unit size is calculated to best size according to the string.

    Not applicable for the bar graph.

    2.3.1.9 EnableLogicalColor

    Name DataType Default Value Description

    EnableLogicalColor Boolean True If EnableLogicalColor is true, then allused colors are logical colors. The

    logical color reference is equal to thedefault logical color used in the colorproperties. To use an individual colorset it to false.

    When set to True, the colors are based on logical colors.

    Not applicable for the PID object.

    2.3.1.10 ValueColor

    Name DataType Default Value Description

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    15/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 15

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    ValueColor Color BMIvalueMV(AI)

    BMIvalueOUT(AO)

    Value color. Only applied ifEnableLogicalColor is set to false.

    When EnableLogicalColorset to False, the ValueColor is used to show the value color orBar color with the defined ValueColor.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    16/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 16

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3 AI Analogue Input

    3.1 BASIC DESCRIPTION

    The Control Module Types AIS and AIC are used to access and control an analog input.

    AIS module is used to read one analog input signal, coming from the process

    AIC module is used to write a calculated signal from the application, that is to be

    indicated on the operator station and that will have alarm limit control.

    The analog input module provides the following features:

    Blocking and forcing of input value

    Threshold detection and alarming on 4 alarm limit levels (L2,L1,H1,H2)

    Threshold detection and eventing on 2 Process Limit levels (PLo, PHi)

    Adjustable Low Pass Filter to create the FilteredSignal output.

    FilteredSignal Rate of change calculation and alarm. The ROC is presented in % ofTotal Range per second.

    All Substatus for DP, PA and FF Field Devices will generate error control when qualityis Bad or Uncertain for AIS Control Module.

    Common or Individual alarm delay for all 6 limits.

    Alarm blocking (from faceplate). All alarm limit levels will be blocked.

    Alarm disabling/enabling of each alarm limit individually (from application program /Faceplate); generating events when blocked.

    Single and Triple trend and automatic log configuration for:

    FilteredSignal

    IOSignal

    RateofChange

    Minerals Library Process Control Connection (PCC)

    Parameterized interlocks towards parent objects

    Advanced alarm disabling from parent objects

    Interface to Process Panel

    Additionally, the AIS Control Module has the following feature:

    Signal Error pre-warning with adjustable alarm delay.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    17/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 17

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.2 CONTROL

    3.2.1 Diagram Graphical Representation AIS

    The default view is shown, its possible to modify the visible ports in CBM.

    3.2.2 Diagram Graphical Representation AIC

    The default view is shown, its possible to modify the visible ports in CBM.

    3.2.3 Parameter description

    3.2.3.1 Parameter AIS

    No Name Data Type Initial Value Port Direction Description

    1 Name string 'Name' 1 in INIT: Tag name of the AIS (allowed deliminatorsare "_" or "." or "-", no blanks,":" or ";" allowed)

    2 Description string 'Description' 1 in IN: Description text of the AIS

    3 IO AISData 1 in_out IN/OUT: Connection to AISData variable

    4PCC PCCComDat

    aDefault 1 out IN/OUT: Interlock Bus, Priority

    Command/Interlock to motors, valves or groups

    5 PCCAEListFrcEn

    bool false 0 in IN: PCC AE List handling forced to be always onand not controlled by PCC parent

    6 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)

    7 Lim2Tr dint 3 0 in INIT: Alarm L2/H2 limit treatment: -1 no AE; 0 =Event ; 1,2,3 = ALPrio# (1=lowest)

    8 Lim1Tr dint 2 0 in INIT: Alarm L1/H1 limit treatment: -1 no AE; 0 =Event ; 1,2,3 = ALPrio# (1=lowest)

    9 ROCLimTr dint -1 0 in INIT: ROC limit treatment: -1 no AE; 0 = Event ;1,2,3 = ALPrio# (1=lowest)

    10 PLimTr dint 0 0 in INIT: Process limit treatment: -1 no AE; 0 =Event

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    18/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 18

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    No Name Data Type Initial Value Port Direction Description

    11 StatusTr bool true 0 in IN: True enables events on Forced valuechanges

    12 LogTr bool true 0 in INIT: Limit change treatment: true = Event onlimit value change, false = Events on limit valuechange are disabled.

    13 ErrCtrl bool true 0 in IN: Action in case of Signal Error: false = noaction; true = IO.Signal.Value is forced to Err_Val

    14 ErrVal real 99999 0 in IN: Error Value used in case of Err_Ctrl = true

    15 ErrTr dint cBMI.AE.Sig

    Err_Sev

    0 in IN: Severity for the Signal Error AlarmCond

    16 EnExtLimits bool false 0 in IN: false = limit settings from Operate IT, true =COLD INIT can be used as external limits

    17 HiLim2 real 100 0 in COLD INIT: Initial limit for High2 alarm.

    18 BlkHiLim2 bool false 0 in COLD INIT: Initial value for blocking of the limithigh 2 handling

    19 IntlkTypeHiLim2

    dint No_Interlock 1 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    20 IntlkDirHiLim2 dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;2:DirFBX/Y/XY+noAck;3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,noAck=Acknowledge not need if value back toNormPos

    21 HiLim1 real 100 0 in COLD INIT: Initial limit for High1 alarm.

    22 BlkHiLim1 bool false 0 in COLD INIT: Initial value for blocking of the limithigh 1 handling

    23 IntlkTypeHiLim1

    dint No_Interlock 1 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    24 IntlkDirHiLim1 dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;2:DirFBX/Y/XY+noAck;3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,noAck=Acknowledge not need if value back toNormPos

    25 PHiLim real 90 0 in COLD INIT: Initial limit for Process High alarm.

    26 BlkPHiLim bool true 0 in COLD INIT: Initial value for blocking of the limitProcess High handling

    27 IntlkTypePHiLi

    m

    dint No_Interlock 0 in INIT:

    PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    28 IntlkDirPHiLim dint DirXY 0 in INIT: DirX; DirFBX; DirXStart; DirY; DirFBY;DirYStart; DirXY; DirFBXY; DirXYStart;

    29 PLoLim real 10 0 in COLD INIT: Initial limit for Process Low alarm.

    30 BlkPLoLim bool true 0 in COLD INIT: Initial value for blocking of the limitProcess Low handling

    31 IntlkTypePLoLim

    dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    32 IntlkDirPLoLim dint DirXY 0 in INIT: DirX; DirFBX; DirXStart; DirY; DirFBY;DirYStart; DirXY; DirFBXY; DirXYStart;

    33 LoLim1 real 0 0 in COLD INIT: Initial limit for Low1 alarm.

    34 BlkLoLim1 bool false 0 in COLD INIT: Initial value for blocking of the limitlow 1 handling

    35 IntlkTypeLoLim1

    dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    36 IntlkDirLoLim1 dint DirXY 0 in INIT: 1:DirX/Y/XY+noAck;2:DirFBX/Y/XY+noAck;3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,noAck=Acknowledge not need if value back toNormPos

    37 LoLim2 real 0 0 in COLD INIT: Initial limit for Low2 alarm.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    19/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 19

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    No Name Data Type Initial Value Port Direction Description

    38 BlkLoLim2 bool false 0 in COLD INIT: Initial value for blocking of the limitlow 2 handling

    39 IntlkTypeLoLim2

    dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    40 IntlkDirLoLim2 dint DirXY 0 in INIT: 1:DirX/Y/XY+noAck;2:DirFBX/Y/XY+noAck;3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,noAck=Acknowledge not need if value back toNormPos

    41 IntlkTypeROC dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    42 IntlkDirROC dint DirXY 0 in INIT: DirX; DirXStart; DirY; DirYStart; DirXY;DirXYStart

    43 IntlkStartInhibit time 0s 0 in INIT: Bypass Interlock for a certain time after start of PCC parent (MOTx, VLVx), Time will startwith Ord# instead of Run# where the IntlkD

    44 IntlkLocStartOverride

    bool false 0 in INIT: Bypass Interlock in LOC mode if LCBStartis continuously pushed. All PCC parents need tobe in LOC.

    45 Hyst real 1.0 0 in COLD INIT: Initial Hysteresis in %

    46 AlarmDelay time 0s 0 in COLD INIT: Initial time delay for the limit level

    supervision47 EnIndividualAl

    armDelaysbool cBMI.AIS.En

    IndividualAlarmDelays

    0 in IN: Enables the individual alarm delay setting for all the 6 limits in the faceplate. If True,

    AlarmDelay has only effect for upgrade.

    48 AlarmAck bool false 0 in IN pulse: Acknowledge the alarms

    49 Simulation bool false 0 in IN: TRUE = override signal error indication inOperate IT, used for simulations only

    For more information on how to use Interlock Parameters, see chapterPCC Interlock Parameter Description.

    3.2.3.2 Parameter AIC

    No Name Data Type Initial Value Port Direction Description

    1 Name string 'Name' 1 in INIT: Tag name of the AIC (allowed deliminatorsare "." and "-", no blanks ":" or ";" allowed)

    2 Description string 'Description' 1 in IN: Description text of the AIC

    3 IO AISData Default 1 in_out IN/OUT: Connection to AISData variable

    4 PCC PCCComData

    Default 1 out IN/OUT: Interlock Bus,PriorityCommand/Interlock to motors, valves orgroups

    5 PCCAEListFrcEn

    bool false 0 in IN: PCC AE List handling forced to be always onand not controlled by PCC parent

    6 Min real 0 1 in INIT: Scaling Parameter Range.

    7 Max real 100 1 in INIT: Scaling Parameter Range Max.

    8 Unit string '%' 1 in INIT: Scaling Parameter Unit.

    9 Fraction dint 1 1 in INIT: Fraction (Number of Decimals).

    10 SignalError bool false 1 in IN false: Input for calculated signal error indication

    11 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)12 Lim2Tr dint 3 0 in INIT: Alarm L2/H2 limit treatment: -1 no AE; 0 =

    Event ; 1,2,3 = ALPrio# (1=lowest)

    13 Lim1Tr dint 2 0 in INIT: Alarm L1/H1 limit treatment: -1 no AE; 0 =Event ; 1,2,3 = ALPrio# (1=lowest)

    14 ROCLimTr dint -1 0 in INIT: ROC limit treatment: -1 no AE; 0 = Event ;1,2,3 = ALPrio# (1=lowest)

    15 PLimTr dint 0 0 in INIT: Process limit treatment: -1 no AE; 0 =Event

    16 LogTr bool true 0 in INIT: Limit change treatment: true = Event onlimit value change, false = Events on limit valuechange are disabled.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    20/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 20

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    No Name Data Type Initial Value Port Direction Description

    17 ErrCtrl bool true 0 in IN: Action in case of Signal Error: false = noaction; true = IO.Signal.Value is forced to Err_Val

    18 ErrVal real 0.0 0 in IN: Error Value used in case of Err_Ctrl = true

    19 EnExtLimits bool false 0 in IN: false = limit settings from Operate IT, true =COLD INIT can be used as external limits

    20 EnExtAlarm dint in no cBMI.AIC.EnExtAlarm.None

    IN: Limit checks are external and Events aregenerated by writing to IO.H1.Value etc. for H2/1,PLo/Hi and L1/2. AlarmDelays are disabled.

    21 HiLim2 real 100 0 in COLD INIT: Initial limit for High2 alarm.

    22 BlkHiLim2 bool false 0 in COLD INIT: Initial value for blocking of the limithigh 2 handling

    23 IntlkTypeHiLim2

    dint No_Interlock 1 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    24 IntlkDirHiLim2 dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;2:DirFBX/Y/XY+noAck;3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,noAck=Acknowledge not need if value back toNormPos

    25 HiLim1 real 100 0 in COLD INIT: Initial limit for High1 alarm.

    26 BlkHiLim1 bool false 0 in COLD INIT: Initial value for blocking of the limithigh 1 handling

    27 IntlkTypeHiLim1

    dint No_Interlock 1 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    28 IntlkDirHiLim1 dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;2:DirFBX/Y/XY+noAck;3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,noAck=Acknowledge not need if value back toNormPos

    29 PHiLim real 90 0 in COLD INIT: Initial limit for Process High alarm.

    30 BlkPHiLim bool true 0 in COLD INIT: Initial value for blocking of the limitProcess High handling

    31 IntlkTypePHiLim

    dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    32 IntlkDirPHiLim dint DirXY 0 in INIT: DirX; DirFBX; DirXStart; DirY; DirFBY;

    DirYStart; DirXY; DirFBXY; DirXYStart;33 PLoLim real 10 0 in COLD INIT: Initial limit for Process Low alarm.

    34 BlkPLoLim bool true 0 in COLD INIT: Initial value for blocking of the limitProcess Low handling

    35 IntlkTypePLoLim

    dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    36 IntlkDirPLoLim dint DirXY 0 in INIT: DirX; DirFBX; DirXStart; DirY; DirFBY;DirYStart; DirXY; DirFBXY; DirXYStart;

    37 LoLim1 real 0 0 in COLD INIT: Initial limit for Low1 alarm.

    38 BlkLoLim1 bool false 0 in COLD INIT: Initial value for blocking of the limitlow 1 handling

    39 IntlkTypeLoLim1

    dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr

    ocess;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    40 IntlkDirLoLim1 dint DirXY 0 in INIT: 1:DirX/Y/XY+noAck;2:DirFBX/Y/XY+noAck;3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,noAck=Acknowledge not need if value back toNormPos

    41 LoLim2 real 0 0 in COLD INIT: Initial limit for Low2 alarm.

    42 BlkLoLim2 bool false 0 in COLD INIT: Initial value for blocking of the limitlow 2 handling

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    21/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 21

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    No Name Data Type Initial Value Port Direction Description

    43 IntlkTypeLoLim2

    dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    44 IntlkDirLoLim2 dint DirXY 0 in INIT: 1:DirX/Y/XY+noAck;2:DirFBX/Y/XY+noAck;3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,noAck=Acknowledge not need if value back toNormPos

    45 IntlkTypeROC dint No_Interlock 0 in INIT:PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Process;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

    46 IntlkDirROC dint DirXY 0 in INIT: DirX; DirXStart; DirY; DirYStart; DirXY;DirXYStart

    47 IntlkStartInhibit time 0s 0 in INIT: Bypass Interlock for a certain time after start of PCC parent (MOTx, VLVx), Start by Ordinstead of Run where the IntlkDir is DirFB

    48 IntlkLocStartOverride

    bool false 0 in INIT: Bypass Interlock in LOC mode if LCBStartis continuously pushed. All PCC parents need tobe in LOC.

    49 Hyst real 1.0 0 in COLD INIT: Initial Hysteresis in %

    50 AlarmDelay time 0s 0 in COLD INIT: Initial time delay for the limit levelsupervision

    51 EnIndividualAl

    armDelays

    bool cBMI.AIS.En

    IndividualAlarmDelays

    0 in IN: Enables the individual alarm delay setting for

    all the 6 limits in the faceplate. If True,AlarmDelay has only effect for upgrade.

    52 ExtendedInfo dint in no 0 IN: Extended Info on Faceplace - setting onlyuseful if Faceplate is including the Extended Info

    53 AlarmAck bool false 0 in IN pulse: Acknowledge the alarms

    For more information on how to use Interlock Parameters, see chapterPCC Interlock Parameter Description.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    22/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 22

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.2.4 Data Type description

    Together with the AIS and AIC Control Module Type a Structured Data Type AISData isavailable. This makes it possible to create one Global Variable in the application for eachAI instance.

    AISData; componentsName Data Type Attributes Initial

    ValueDescription

    1 LimEn bool retainnosort

    true IN true: External Enabling of AIS LimitSupervision, used to temporary block thealarming

    2 EnHiLim2 bool retainnosort

    true IN true: Enables High Limit 2

    3 EnHiLim1 bool retainnosort

    true IN true: Enables High Limit 1

    4 EnPHiLim bool retainnosort

    true IN true: Enables Process High Limit

    5 EnPLoLim bool retainnosort

    true IN true: Enables Process Low Limit

    6 EnLoLim1 bool retainnosort

    true IN true: Enables Low Limit 1

    7 EnLoLim2 bool retainnosort

    true IN true: Enables Low Limit 2

    8 AEListEn bool retainnosort true IN true: External Alarm List Enabling of AIS,temporary disabling of unack alarming andentries in alarmlist, NOTE: Overwritten byPCC

    9 H2 BoolAL retain OUT: Alarm Status of limit H2. Use the.Normal value for interlocking

    10 H1 BoolAL retain OUT: Alarm Status of limit H1. Use the.Normal value for interlocking

    11 PHi bool retain OUT: Indication of limit Process Limit High

    12 PLo bool retain OUT: Indication of limit Process Limit Low

    13 L1 BoolAL retain OUT: Alarm Status of limit L1. Use the.Normal value for interlocking

    14 L2 BoolAL retain OUT: Alarm Status of limit L2. Use the.Normal value for interlocking

    15 SigErr BoolAL retain OUT: Alarm Status of Signal Error (e.g.electrical signal less than 4 mA)

    16 SigErrWarn bool retain OUT: Signal Error Warning Normal

    17 ROCLim BoolAL retain OUT: Alarm Status of Rate of Change limit.Use the .Normal value for interlocking

    18 Signal RealIO retaindisplayvalue

    IN/OUT: Signal to be connected to the S800HW I/O

    19 FilteredSignal RealIO retain IN/OUT: Filter to Signal.Value

    20 RateofChange RealIO retain IN/OUT: Signal rate of change

    21 FieldDeviceStatus

    dword retainnosort

    cBMI.AIS.FDStatusNC

    IN: 2nd DWORD for Field Device StatusSupervision e.g. Profibus PA Devices etc. Ifvalue equals 16#80C0 the faceplateindication is hidden

    22 FieldDeviceStatusDINT

    dint retainnosort

    cBMI.AIS.FDStat

    usNCDINT

    IN: 2nd DINT for Field Device StatusSupervision e.g. Profibus PA Devices etc. If

    value equals 16#80C0 FieldDeviceStatusdword is used inste

    23 ProcessPanel PanelLinkAIS

    retain Interface from / to ProcessPanel

    24 Name string[24] retain Name of AIS/AIC

    For AIS, use the Data type structure as follows:Write: no supported (directly connected to IO Channel)Read: IO.. FilteredSignal.ValueInterlock: IO...Normal

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    23/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 23

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    For AIC, use the Data type structure:Write: IO..Signal.IOValueRead: IO.. FilteredSignal.ValueInterlock: IO...Normal

    FilteredSignal is related to the Signal as follows:

    187.0

    1

    );1(1+

    D

    =-+= -

    T

    FilterTimeyxy kkk aaa

    Which is equivalent to a 1storder low pass with15.1

    FilterTime=t

    Note that the IO.FilteredSignal.Parameter Values are copied from theIO.Signal.Parameter on Application Start only. In case of changes in theHardware Structure for the Channel where IO.Signal is connected, theParameter Value can be different between these two Variables after the

    download to the Controller.

    PanelLinkAIS; componentsName Data

    TypeAtt ributes Ini tial

    ValueDescription

    1 Status dint Retainnosorthidden

    Object Status (Ready, H,HH,Phi,Plo etc.)

    2 Cmd dint Retainnosorthidden

    Object Commands from Panel to Basic Object

    3 SignalValue real Retain

    nosorthidden

    Signal Value to Process Panel

    4 Blink bool Retainnosorthidden

    Enabling of Basic Object Blinking

    Cmd ; Bits

    Name BitPosition

    1 AlarmAck 0

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    24/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 24

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.2.5 Project Constants

    Name Data Type Default Value

    1 cBMI.AIS.DisabledIntMaxIndTr dint (dint): 132 cBMI.AIS.EnIndividualAlarmDelays bool (bool): false3 cBMI.AIS.FDStatusNC dword (dword): 16#80c04 cBMI.AIS.FDStatusNCDINT dint (dint): 16#80c05 cBMI.AIS.H1_txt string (string): 'H1'6 cBMI.AIS.H2_txt string (string): 'H2'

    7 cBMI.AIS.L1_txt string (string): 'L1'8 cBMI.AIS.L2_txt string (string): 'L2'9 cBMI.AIS.PHi_txt string (string): 'PHi'10 cBMI.AIS.PLo_txt string (string): 'PLo'11 cBMI.AIS.PropagateSigErrToPCC bool (bool): true12 cBMI.AIS.ROC_Txt string (string): 'ROC'13 cBMI.AIS.SigErr_txt string (string): 'SigError'14 cBMI.AIS.SigErrDelay time (time): 0s15 cBMI.AIS.SigErrWarn_txt string (string): 'SigError'16 cBMI.AIS.UncertainAsGood bool (bool): false

    FDStatusNC defines the Value that is used to detect that no Status is connected to theModule. Note that this Value should be impossible to be sent at any time by a Field

    Device.

    3.2.6 PCC Interlock Limitations for AIS and AIC

    The Fast interlock direction (e.g. DirXFast, DirFBXFast) is not supported for AIS andAIC.

    shown in FPL asParam Error

    With Fast

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    25/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 25

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3 OPERATION

    3.3.1 Graphic elements

    Graphic Element Description Example

    AISandUnit or AICandUnit Value indication and unit.

    AISBar or AICBar Bar graph indication

    AISTxt or AICTxt Limit status text indication

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    26/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 26

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.1.1 AISandUnit or AICandUnit

    The value and unit presents the measured value, alarm limits and status information.

    3.3.1.1.1 Presentation

    Indication Type Description Example

    Value and Unit Value and unit indication

    3.3.1.1.2 Status

    Object status Symbol color

    Value in normal range Value green

    H2 Limit and signal blocked Red thick frame / Value green

    Signal Quality Bad Yellow background color

    3.3.1.1.3 Labels

    Description Indication

    Signal blocked

    Limit High 2

    Limit High 1

    Limit Process High 1

    Limit Process Low 1

    Limit Low 1

    Limit Low 2

    Rate of Change

    Example:

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    27/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 27

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.1.1.4 Properties

    Name DataType Default Value Description

    EnableDisplayBackgroundColor Boolean False Show display background color assymbol background

    EnableFitToBestSize Boolean True Set best unit sizeEnableLimitLabel Boolean True Show limit labelsEnableLogicalColor Boolean True If EnableLogicalColor is true, then all

    used colors are logical colors. Thelogical color reference is equal to thedefault logical color used in the colorproperties. To use an individual colorset it to false.

    EnableUnit Boolean True Show unitsNumberOfDigits Integer 4 Number of presented digitsUnitSize Integer 8 Unit size in pixel: 7 = Small, 8 =

    Standard, 10 = Large, 12= XXLValueColor Color BMIvalueMV Value color. Only applied if

    EnableLogicalColor is set to false.ValueSize Integer 12 Value size in pixel: 8 = Small, 10

    Medium, 12 = Standard, 14 = Large,

    16 = XXLFor common settings please refer to [1] Minerals Library Overview (3BHS 161555).

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    28/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 28

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.1.2 AISTxt or AICTxt

    AIS and AIC text can be used to show alarm limits of analogue inputs as labels. The labeltext can be customized. The text appearance can be configured to show the text only onalarm, depending on the value, always but with different colours depending on value oralarm condition.

    3.3.1.2.1 PresentationIndication Type Description Example

    Text with background color Text with background color

    Square in front of text Square in front of text

    Text colored Text colored

    3.3.1.2.2 StatusObject status Symbol color

    Normal Position forAppearance Types, 0 = Alarm, 2= value

    Gray dimmed (semitransparent)

    Normal Position forAppearance Types, 10 = Alarm,12 = Value interlock

    Green

    Normal Position forAppearance Types, 0 = Alarm, 2= value

    Red

    3.3.1.2.3 Labels

    Description Indication

    Status blocked

    Example:

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    29/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 29

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.1.2.4 Properties

    Name DataType Default Value Description

    AppearanceType Integer 0 0 = Alarm, 2 = Value, 3 = Value customcolor, 10 = Alarm interlock, 12 Valueinterlock

    ColorAbnormalPos Color Lime Used for AppearanceType 3 = Valuecustom color

    ColorNormalPos Color RGB(159,159,159) Used for AppearanceType 3 = Valuecustom colorEnableFont Boolean False Enable the Font propertyEnableLogicalColor Boolean True To use an individual color set it to falseEnableNormalPos Boolean True Hide symbol in normal positionFont Font Font( "Arial" ,10

    ,Regular, Bold)Text font wehn EnableFont is true

    IndicationType Integer 0 0 = Text with background color, 10 =Square in front of text, 20 = Text colored

    IndicationValue Integer 1 0 = All, 1 = H2, 2 = H1, 3 = PH2, 4 = PH1,5 = PL1, 6 = PL2, 7 = L1, 8 = PL2

    NormalPos Boolean False Used for AppearanceType 2 = Value, 3 =Value custom color

    SymbolSize Integer 12 Symbol size in pixel: Little = 8, Small = 12,Standard = 14, Large = 18, XXL = 22

    TextBold Boolean True Text style is boldTextColor Color BMIstaticTextOff Text color TextIndTrH1AbnormalPos String "H1" TextIndTrH1AbnormalPosTextIndTrH1NormalPos String "H1" TextIndTrH1NormalPosTextIndTrH2AbnormalPos String "H2" TextIndTrH2AbnormalPosTextIndTrH2NormalPos String "H2" TextIndTrH2NormalPosTextIndTrL1AbnormalPos String "L1" TextIndTrL1AbnormalPosTextIndTrL1NormalPos String "L1" TextIndTrL1NormalPosTextIndTrL2AbnormalPos String "L2" TextIndTrL2AbnormalPosTextIndTrL2NormalPos String "L2" TextIndTrL2NormalPos

    TextIndTrPH1AbnormalPos String "PH1" TextIndTrPH1AbnormalPosTextIndTrPH1NormalPos String "PH1" TextIndTrPH1NormalPosTextIndTrPH2AbnormalPos String "PH2" TextIndTrPH2AbnormalPosTextIndTrPH2NormalPos String "PH2" TextIndTrPH2NormalPosTextIndTrPL1AbnormalPos String "PL1" TextIndTrPL1AbnormalPosTextIndTrPL1NormalPos String "PL1" TextIndTrPL1NormalPosTextIndTrPL2AbnormalPos String "PL2" TextIndTrPL2AbnormalPosTextIndTrPL2NormalPos String "PL2" TextIndTrPL2NormalPosTextSize Integer 10 Text size in pixel: 8 = Small, 10 =

    Standard, 12 = Large, 16 = XXLTextSource Integer 1 0 = None, 1 = TextIndAbnormalPos /

    TextIndNormalPos, 2 = OPC Text, 3 =NLS Text

    For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    30/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 30

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.1.3 AISBar or AICBar

    AIS and AIC bar presents the analogue value as bar. Alarm or process limits are graphicalshown and different bar graph appearances are possible.

    3.3.1.3.1 Presentation

    Appearance Descript ion Example

    0

    StandardThis is the standard appearance of the bar graph. The value willbe indicated in relation to the maximum and minimum range. Thegreen bar will always start from the minimum range.

    1Start from PivotUse this appearance to start the bar graph from another value

    than the minimum range. The related property is Pivot.

    2InverseThe bar will be inverse to the standard appearance.

    3LineThe value will be indicated as a small line instead of a bar.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    31/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 31

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.1.3.2 Status

    Example Object status Symbol color

    Limit Alarm or process limitexceeded.

    Colored Alarm band on one side.

    Alarm Blocked Yellow thin frame

    3.3.1.3.3 Labels

    Description Indication

    Signal blocked

    Signal Quality Bad

    Limit High 2

    Limit High 1

    Limit Process High 1

    Limit Process Low 1

    Limit Low 1

    Limit Low 2

    Example:

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    32/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 32

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.1.3.4 Properties

    Name DataType Default Value Description

    Appearance Integer 0 0 = Standard, 1 = Start from Pivot, 2 = Inverse,3 = Line

    BarColorCustom Color BMIbarMV Bar color. Only applied if EnableLogicalColor isset to false.

    EnableLimitLabel Boolean True Show limit labelsEnableLogicalColor Boolean True If EnableLogicalColor is true, then all used

    colors are logical colors. The logical colorreference is equal to the default logical colorused in the color properties. To use anindividual color set it to false.

    EnableManualRange Boolean False If set to true, the bar's range can be setmanually

    Pivot Real 0. Used together with Appearance = 1 (Start fromPivot). The bar will start from the value set asPivot.

    RangeMax Real 100. Maximum range if EnableManualRange is trueRangeMin Real 0. Minimum range if EnableManualRange is trueSubscriptionRate Integer 0 The update rate for all aspect object properties

    subscribed forSymbolSize Integer 14 Symbol size in pixel: Little = 8, Small = 12,

    Standard = 14, Large = 18, XXL = 22VerticalBar Boolean True VerticalBar: True = vertical appearance, false =

    horizontal appearance.

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    33/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 33

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.2 Faceplate

    3.3.2.1 Aspect Link Buttons

    The following aspect view buttons are available on AIS and AIC Faceplates

    Icon Aspect View

    Alarm List

    Event List

    Single Trend (Filtered Value)

    Multi Trend (Filtered Value / IO Value / Rate of Change)

    Operators Note

    Faceplate Documentation, reference to this document

    3.3.2.2 Default View

    Measured Value

    &

    alarm indication

    Graphical BarMeasured Value

    &alarm limits

    Mini Trend

    Measure Value

    Tagname&

    Description

    Extended Viewfor detailed

    information andsettings

    Appl y But ton

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    34/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 34

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.2.3 Extended View

    The faceplate extended view gives more detailed information about the Analogue Input.

    Additional information for the AIS is structured in tabs. The available tabs and a shortdescription of the contained information are shown below.

    Tab Description

    Trend Mini trend of filtered measured value, IO value and rate of changeLimit Limits and alarm delay settings for the measured valueROC Rate of change settingsBlock - Input Blocking

    - Alarm BlockingMVStatus Sub status for DP, PA and FF Field DevicesPCC - PCC interlock configuration summery

    - Link to connected consumer or consumer overview list

    Reduced View

    default

    Tabbedinformation

    Browse forward /backwards to show hidden

    tabs

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    35/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 35

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.2.3.1 Trend

    On-Line single Triple trend and log Configuration aspect with the actual values: Signal,FilterdSignal and RateofChange.

    Move over the trend area a curser will appear, showing enabled traces value and recordtime.

    3.3.2.3.2 Limit

    Limit settings for measured value are done here.

    Show / Hide Grid

    Show / Hide TracesMV: Filtered Signal

    IO: SignalROC: Rate of Change

    Record Time

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    36/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 36

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    Reference Table

    Description

    B Indication that the corresponding alarm limit has been blocked. Yellowmeans that the alarm limit is blocked (disabled)

    H2 2n

    High limit (H2) - FailureH1 1

    stHigh limit (H1) - Warning

    PHigh Process High LimitPLow Process Low LimitL1 1stLow limit (L1) - WarningL2 2n Low limit (L2) - FailureAlarm Delay Time delay before alarm message will be send to the operator station.

    Check below the special mode for 6 alarm limits.Hysteresis Alarm Hysteresis in %

    F When limits are changed from the faceplate, you must take into consideration thatthese values will be overwritten again with the initial values when a cold restart /resetis performed and the coldretain files are not available for the correspondingcontroller.

    To avoid this, you need to update the initial valuesfor the corresponding AIS/AIC

    control module instance with Control Builder, after changing the Values from theFaceplate.

    3.3.2.3.2.1 Six limits alarm delay special mode

    There is a possibility to enable individual alarm delays for each AIS/AIC element. Theway to do that is setting EnIndividualAlarmDelays parameter to true in each AIS/AICelement.

    After a download, you will be able to notice the following appearance of the AISfaceplate

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    37/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 37

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    3.3.2.3.3 ROC

    Description

    ROC High Limit Rate Of Change in % of Total Range per seconds High LimitROC Hysteresis ROC Alarm Hysteresis in %Filter Time Filter time to be applied to the IO..FilteredValue

    F When limits are changed from the faceplate, you must take into consideration thatthese values will be overwritten again with the initial values when a cold restart /resetis performed and the coldretain files are not available for the correspondingcontroller.

    To avoid this, you need to update the initial valuesfor the corresponding AIS/AICcontrol module instance with Control Builder, after changing the Values from theFaceplate.

    3.3.2.3.4 Block / Override

    Block / Force Input

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    38/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 38

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    Block Alarm

    Reference Table, Block

    Description

    Block Input The analog input will be forced on controller hardware input level.The IO Value shows the actual value in the process. Alarm limits remain

    active.Block Alarm All 4 alarm limits will be blocked as well as Signal Error and ROC Alarms.They are not taken into account anymore.

    3.3.2.3.5 MVStatus

    Substatus for Foundation Fieldbus and S800 Field Devices

  • 7/25/2019 02 Minerals Library Basic Objects 5p1s4a

    39/113

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.Copyright 2013 ABB. All rights reserved.

    Doc. kind Reference Manual Project Minerals Library, CoE Cement andMinerals

    Title Basic Objects800xA Minerals Library version 5.1/4a

    Document numberLang. Rev. ind. Pages 39

    ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113

    All Substatus for DP, PA and FF Field Devices will generate error control when quality isBad or Uncertain for AIS Control Module.An Aspect Link giving access to the Device Management Object can be configured viathe BMI DTM Link General Properties Aspect.

    General PropertiesAspect

    Property Description

    BMI DTM Link FPLAspectLink.DTM.ObjectName Name of the DTM ObjectBMI DTM Link FPLAspectLink.DTM.AspectName Name of the DTM Aspect

    BMI Overlap Link FPLAspectLink.DTM.DefaultAspectName Default Name of the DTMAspect

    The Device Management Button will be shown only if the Properties are not emptyStrings.

    Description

    Signal ErrorDelay

    Time between the Signal Error occurs until the Value is forced toErrValue. Only available for AIS Module.