Top Banner

of 42

02-4 AC Transmission

Jun 02, 2018

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/10/2019 02-4 AC Transmission

    1/421539pk

    AC TRANSMISSION

    Copyright P. Kundur

    This material should not be used without the author's consent

  • 8/10/2019 02-4 AC Transmission

    2/42

    1539pkACT - 1

    Performance Equations and Parameters

    of Transmission Lines

    A transmission line is characterized by four

    parameters:

    series resistance (R) due to conductor resistivity

    shunt conductance (G) due to currents along

    insulator strings and corona; effect is small andusually neglected

    series inductance (L) due to magnetic field

    surrounding the conductor

    shunt capacitance (C) due to the electric field

    between the conductors

    These are distributed parameters.

    The parameters and hence the characteristics of

    cables differ significantly from those of overhead

    lines because the conductors in a cable are

    much closer to each other surrounded by metallic bodies such as shields,

    lead or aluminum sheets, and steel pipes

    separated by insulating material such as

    impregnated paper, oil, or inert gas

  • 8/10/2019 02-4 AC Transmission

    3/42

  • 8/10/2019 02-4 AC Transmission

    4/42

    1539pkACT - 3

    The constant ZCis called the character is t icimpedanceand is called the propagat ion constant.

    The constants and ZCare complex quantities. The

    real part of the propagation constant is called the

    attenuation constant , and the imaginary part the

    phase constant .

    If losses are completely neglected,

    )resistance(pure

    NumberReal

    C

    LZC

    numberImaginary j

  • 8/10/2019 02-4 AC Transmission

    5/42

    1539pkACT - 4

    For a lossless line, Equations 6.8 and 6.9 simplify to

    When dealing with lightening/switching surges, HV

    lines are assumed to be lossless. Hence, ZCwithlosses neglected is commonly referred to as the surge

    impedance.

    The power delivered by a line when terminated by its

    surge impedance is known as the natural load or su rge

    impedance load.

    where V0 is the rated voltage

    At SIL, Equations 6.17 and 6.18 further simplify to

    (6.17)

    (6.18)

    xIjZxVVRCR

    sincos~~

    xZ

    VjxII

    C

    RR sin

    ~cos

    ~~

    wattsZ

    VSIL

    C

    2

    0

    x

    R

    x

    R

    eII

    eVV

    ~

    ~~

    (6.20)

    (6.21)

  • 8/10/2019 02-4 AC Transmission

    6/42

    1539pkACT - 5

    Hence, for a lossless line at SIL,

    V and I have constant amplitude along the line

    V and I are in phase throughout the length of the line

    The line neither generates nor absorbs VARS

    As we will see later, the SIL serves as a convenient

    reference q uant i tyfor evaluating and expressing line

    performance

    Typical values of SIL for overhead lines:

    nominal (kV): 230 345 500 765

    SIL (MW): 140 420 1000 2300

    Underground cables have higher shunt capacitance;

    hence, ZCis much smaller and SIL is much higher than

    those for overhead lines.

    for example, the SIL of a 230 kV cable is about

    1400 MW

    generate VARs at all loads

  • 8/10/2019 02-4 AC Transmission

    7/42

    1539pkACT - 6

    Typical Parameters

    Table 6.1 Typical overhead transmission line parameters

    Table 6.2 Typical cable parameters

    Note: 1. Rated frequency is assumed to be 60 Hz

    2. Bundled conductors used for all lines listed, except for the 230 kV line.

    3. R, xL, and bCare per-phase values.

    4. SIL and charging MVA are three-phase values.

    * direct buried paper insulated lead covered (PILC) and high pressure pipe

    type (PIPE)

  • 8/10/2019 02-4 AC Transmission

    8/42

    1539pkACT - 7

    Voltage Profile of a Radial Line at No-Load

    With receiving end open, IR= 0. Assuming a

    lossless line from Equations 6.17 and 6.18, we have

    At the sending end (x = l),

    where = l. The angle is referred to as the

    electr ic al lengthor the l ine angle, and is expressed

    in radians.

    From Equations 6.31, 6.32, and 6.33

    xsinZV~jI~xcosV

    ~V~

    CR

    R

    cosV~

    lcosV~

    E~

    R

    RS

    (6.31)

    (6.32)

    (6.33)

    (6.35)

    (6.36)

    cos

    xsin

    Z

    EjI

    cos

    xcosE~

    V~

    C

    S

    S

  • 8/10/2019 02-4 AC Transmission

    9/42

    1539pkACT - 8

    As an example, consider a 300 km, 500 kV line with = 0.0013 rads/km, ZC= 250 ohms, and ES= 1.0 pu:

    Base current is equal to that corresponding to SIL.

    Voltage and current profiles are shown in Figure 6.5.

    The only line parameter, other than line length, thataffects the results of Figure 6.5 is. Sinceispractically the same for overhead lines of all voltagelevels (see Table 6.1),the results are universallyapplicable, not just for a 500 kV line.

    The receiving end voltage for different line lengths:

    - for l= 300 km, VR= 1.081 pu- for l= 600 km, VR= 1.407 pu- for l= 1200 km, VR= infinity

    Rise in voltage at the receiving end is because ofcapacitive charging current flowing through line

    inductance.

    known as the "Ferranti effect".

    pu411.0I

    pu081.1V

    3.22

    rads39.00013.0x300

    S

    R

  • 8/10/2019 02-4 AC Transmission

    10/42

    1539pkACT - 9

    Figure 6.5 Voltage and current profiles for a 300 km lossless

    line with receiving end open-circuited

    (b) Voltage Profile

    (a) Schematic Diagram

    (c) Current Profile

  • 8/10/2019 02-4 AC Transmission

    11/42

    1539pkACT - 10

    Voltage - Power Characteristics

    of a Radial Line

    Corresponding to a load of PR+jQRat the receiving end, wehave

    Assuming the line to be lossless, from Equation 6.17with x = l

    Fig. 6.7 shows the relationship between VRand PRfor a300 km line with different loads and power factors.

    The load is normalized by dividing PRbyP0, the naturalload (SIL), so that the results are applicable to overhead

    lines of all voltage ratings.

    From Figure 6.7 the following fundamental properties of actransmission are evident:

    a) There is an inherent maximum limit of power that can betransmitted at any load power factor. Obviously, therehas to be such a limit, since, with ESconstant, the onlyway to increase power is by lowering the loadimpedance. This will result in increased current, butdecreased VRand large line losses. Up to a certain pointthe increase of current dominates the decrease of VR,thereby resulting in an increased PR. Finally, thedecrease in VR is such that the trend reverses.

    *~~

    R

    RRR

    V

    jQPI

    *~sincos~~

    R

    RRCRS

    V

    jQPjZVE

  • 8/10/2019 02-4 AC Transmission

    12/42

    1539pkACT - 11

    Figure 6.7 Voltage-power characteristics of a 300 km

    lossless radial line

  • 8/10/2019 02-4 AC Transmission

    13/42

    1539pkACT - 12

    Voltage - Power Characteristics

    of a Radial Line (cont'd)

    b) Any value of power below the maximum can be

    transmitted at two different values of VR. The

    normal operation is at the upper value, within

    narrow limits around 1.0 pu. At the lower voltage,

    the current is higher and may exceed thermal

    limits. The feasibility of operation at the lower

    voltage also depends on load characteristics, andmay lead to voltage instability.

    c) The load power factor has a significant influence

    on VRand the maximum power that can be

    transmitted. This means that the receiving end

    voltage can be regulated by the addition of shunt

    capacitive compensation.

    Fig. 6.8 depicts the effect of line length:

    For longer lines, VRis very sensitive to variations

    in PR.

    For lines longer than 600 km ( > 45),VRatnatural load is the lower of the two values which

    satisfies Equation 6.46. Such operation is likely

    to be unstable.

  • 8/10/2019 02-4 AC Transmission

    14/42

    1539pkACT - 13

    Figure 6.8 Relationship between receiving end voltage,

    line length, and load of a lossless radial line

  • 8/10/2019 02-4 AC Transmission

    15/42

    1539pkACT - 14

    Voltage-Power Characteristic of a Line

    Connected to Sources at Both Ends

    With ESand ERassumed to be equal, the following

    conditions exist:

    the midpoint voltage is midway in phase between

    ESand ER

    the power factor at midpoint is unity

    with PR>P0, both ends supply reactive power to theline; with PR

  • 8/10/2019 02-4 AC Transmission

    16/42

    1539pkACT - 15

    Power Transfer and Stability

    Considerations

    Assuming a lossless line, from Equation 6.17 with

    x = l,we can show that

    where = lis the electrical length of line and is the

    angle by which ESleads ER, i.e. the load angle.

    If ES= ER=rated voltage, then the natural load is

    and Equation 6.51 becomes

    The above is valid for synchronous as well as

    asynchronous load at the receiving end.

    Fig. 6.10(a) shows the PRrelationship for a 400 km

    line.

    For comparison, the Vm- PRcharacteristic of the line is

    shown in Fig. 6.10(b).

    (6.51)sin

    sinC

    RSR

    Z

    EEP

    C

    RSO

    Z

    EEP

    sin

    sinO

    R

    PP

  • 8/10/2019 02-4 AC Transmission

    17/42

    1539pkACT - 16

    Figure 6.10 PR- and Vm-PRcharacteristics of 400 km lossless

    line transmitting power between two large systems

  • 8/10/2019 02-4 AC Transmission

    18/42

    1539pkACT - 17

    Reactive Power Requirements

    From Equation 6.17, with x = land ES= ER=1.0, we canshow that

    Fig. 6.11 shows the terminal reactive powerrequirements of lines of different lengths as a functionof PR.

    Adequate VAR sources must be available at the twoends to operate with varying load and nearlyconstant voltage.

    General Comments

    Analysis of transmission line performancecharacteristics presented above represents a highlyidealized situation

    useful in developing a conceptual understanding ofthe phenomenon

    dynamics of the sending-end and receiving-endsystems need to be considered for accurateanalysis.

    sin

    coscos2

    C

    S

    SR

    Z

    E

    QQ

  • 8/10/2019 02-4 AC Transmission

    19/42

    1539pkACT - 18

    Figure 6.11 Terminal reactive power as a function of power

    transmitted for different line lengths

  • 8/10/2019 02-4 AC Transmission

    20/42

    1539pkACT - 19

    Loadability Characteristics

    The concept of "line loadability" was introduced by

    H.P. St. Clair in 1953

    Fig. 6.13 shows the universal loadability curve for

    overhead uncompensated lines applicable to all

    voltage ratings

    Three factors influence power transfer limits:

    thermal limit (annealing and increased sag)

    voltage drop limit (maximum 5% drop)

    steady-state stability limit (steady-state stability

    margin of 30% as shown in Fig. 6.14)

    The "St. Clair Curve" provides a simple means of

    visualizing power transfer capabilities of transmission

    lines.

    useful for developing conceptual guides to

    preliminary planning of transmission systems

    must be used with some caution

    Large complex systems require detailed assessment

    of their performance and consideration of additional

    factors

  • 8/10/2019 02-4 AC Transmission

    21/42

    1539pkACT - 20

    Figure 6.13 Transmission line loadability curve

    "St. Clair Curve"

  • 8/10/2019 02-4 AC Transmission

    22/42

    1539pkACT - 21

    Figure 6.14 Steady state stability margin calculation

    Stability Limit Calculation for Line

    Loadability

  • 8/10/2019 02-4 AC Transmission

    23/42

    1539pkACT - 22

    Factors Influencing Transfer of Active

    and Reactive Power

    Consider two sources connected by an inductive

    reactance as shown in Figure 6.21.

    representation of two sections of a power system

    interconnected by a transmission system

    a purely inductive reactance is considered

    because impedances of transmission elements

    are predominately inductive

    effects of shunt capacitances do not appear

    explicitly

    Figure 6.21 Power transfer between two sources

    (a) Equivalent system diagram

    (b) Phasor diagram

    = load angle

    = power factor angle

  • 8/10/2019 02-4 AC Transmission

    24/42

    1539pkACT - 23

    The complex power at the receiving end is

    Hence,

    Similarly,

    Equations 6.79 to 6.82 describe the way in which

    active and reactive power are transferred

    Let us examine the dependence of Pand Qtransfer

    on the source voltages, by considering separately

    the effects of differences in voltage magnitudes and

    angles

    jX

    EjEEE

    jX

    EEEIEjQPS

    RSSR

    RSRRRRR

    sincos

    ~~~~~~

    *

    X

    EEEQ

    X

    EEP

    RRSR

    RS

    R

    2cos

    sin

    (6.79)

    (6.80)

    X

    EEEQ

    XEEP

    RSSS

    RSS

    cos

    sin

    2

    (6.81)

    (6.82)

  • 8/10/2019 02-4 AC Transmission

    25/42

    1539pkACT - 24

    From Equations 6.79 to 6.82, we have

    With ES> ER, QSand QRare positive

    With ES< ER, QSand QRare negative

    As shown in Fig. 6.22,

    transmission of lagging current through an

    inductive reactance causes a drop in receiving

    end voltage

    transmission of leading current through an

    inductive reactance causes a rise in receiving

    end voltage

    Reactive power "consumed" in each case is

    Figure 6.22 Phasor diagrams with = 0

    (a) Condition with = 0:

    0 SR PP

    X

    EEEQ

    X

    EEEQ RSSS

    RSRR

    ,

    22

    XIX

    EEQQ RSRS

    (a) ES>ER (b) ER>ES

  • 8/10/2019 02-4 AC Transmission

    26/42

    1539pkACT - 25

    From Equations 6.79 to 6.82, we now have

    With positive, PSand PRare positive, i.e., active

    power flows from sending to receiving end

    In each case, there is no reactive power transferred

    from one end to the other; instead, each endsupplies half of Qconsumed by X.

    (b) Condition with ES= ERand 0

    Figure 6.23 Phasor diagram with ES= ER

    2

    2

    2

    2

    1

    cos1

    sin

    IX

    X

    EQQ

    X

    EPP

    RS

    SR

    (b) < 0(a) > 0

  • 8/10/2019 02-4 AC Transmission

    27/42

    1539pkACT - 26

    We now have

    If, in addition to X, we consider series resistance R

    of the network, then

    The reactive power "absorbed" by Xfor all

    conditions is XI 2. This leads to the concept of

    "reactive power loss", a companion term to active

    power loss.

    An increase in reactive power transmitted increases

    active as well as reactive power losses. This has an

    impact on efficiency and voltage regulation.

    (c) General case applicable to any condition:

    22

    22 cos2

    sincos

    XI

    X

    XI

    X

    EEEEQQ

    jX

    EjEEI

    RSRSRS

    RSS

    2

    22

    2

    2

    22

    2

    R

    RRloss

    R

    RRloss

    E

    QPRIRP

    E

    QPXIXQ

    (6.83)

    (6.84)

    (6.85)

    (6.86)

  • 8/10/2019 02-4 AC Transmission

    28/42

  • 8/10/2019 02-4 AC Transmission

    29/42

    1539pkACT - 28

    Appendix to Section on AC Transmission

    1. Copy of Section 6.4 from the book Power System

    Stability and Control

    provides background information related to

    power flow analysis techniques

  • 8/10/2019 02-4 AC Transmission

    30/42

    1539pkACT - 29

  • 8/10/2019 02-4 AC Transmission

    31/42

    1539pkACT - 30

  • 8/10/2019 02-4 AC Transmission

    32/42

    1539pkACT - 31

  • 8/10/2019 02-4 AC Transmission

    33/42

    1539pkACT - 32

  • 8/10/2019 02-4 AC Transmission

    34/42

    1539pkACT - 33

  • 8/10/2019 02-4 AC Transmission

    35/42

    1539pkACT - 34

  • 8/10/2019 02-4 AC Transmission

    36/42

    1539pkACT - 35

  • 8/10/2019 02-4 AC Transmission

    37/42

    1539pkACT - 36

  • 8/10/2019 02-4 AC Transmission

    38/42

    1539pkACT - 37

  • 8/10/2019 02-4 AC Transmission

    39/42

    1539pkACT - 38

  • 8/10/2019 02-4 AC Transmission

    40/42

    1539pkACT - 39

  • 8/10/2019 02-4 AC Transmission

    41/42

    1539pkACT - 40

  • 8/10/2019 02-4 AC Transmission

    42/42