-
(d. p. &) ctcl4yl " u zrfi KUWAIT OIL COMPANY (K.S.C.)
Engineering Group
Specification Number 0 75-pH- 19 1 I
Variable Speed Drive Con troller
1 17 JUN 94 ISSUED AS KOC ENG GROUP SPEC
0 7 MAR 93 ISSUED FOR INVITATION TO BID
Rev Date Revision BY Chkd Section PE Client
-
Specification Number Rev Date Sheet Engineering Group
Spedtkation O I ~ - P H - I ~ I I I 17-6-94 2 of 20
CONTENTS
1 1.0 SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 3 2.0 STANDARD
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 1 3.0 SERVICE CONDITIONS 5 1 4.0 BASIC ENGINEERING
INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
5.0 CONSTRUCTION REQUIREMENTS . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 6
6.0 PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 7
7.0 VARIABLE SPEED DRIVE CONTROLLER . . . . . . . . . . . . . .
. . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 8.0 EARTHING 11
9.0 WIRING AND TERMINALS . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 12
10.0 CABLE TERMINATIONS . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 13
. . . . . . . . . . . . . . . . . . . 11.0 CONTROL AND
PROTECTION EQUIPMENT 13
12.0 ELECTRONIC EQUIPMENT . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 17
13.0 ANTI-CONDENSATION HEATERS . . . . . . . . . . . . . . . . .
. . . . . . . . 18
14.0 NAMEPLATES AND LABELS . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 18
15.0 PAINTING . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 18
16.0 TESTING . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 19 . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 16.1 General 19
. . . . . . . . . . . . . . . . . . . . . . . 16.2 Electronic
Component Tests 19 16.3 Printed Circuit Boards . . . . . . . . . .
. . . . . . . . . . . . . . . . . 19 16.4 Wiring . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 16.5
Functional Test . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 19 16.6 Motor Tests . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 20 16.7 String Test . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 20
17.0 PACKING. MARKING AND DOCUMENTATION . . . . . . . . . . . .
. . . . 20
18.0 SPARE PARTS AND MAINTENANCE REQUIREMENTS . . . . . . . . .
. . 20
-
1.0 SCOPE
1 .I This specification covers the design, manufacture,
inspection, testing and supply of variable speed drive controllers
for installation at the Facility in Kuwait.
1.2 The variable speed drive controllers shall fully comply with
all relevant contractual requirements specified in the Scope of
Work and Technical Specification of the Contract.
2.0 STANDARD SPECIFICATIONS
2.1 The variable speed drive controllers shall conform in
design, materials and performance, except where otherwise
specified, with the current issue and amendments of the following
prevailing on the effective date of the Contract:
2.1 .I International Standards
IEC 51
IEC 70
IEC 76
IEC 146
IEC 185
IEC 186
IEC 255
IEC 269
IEC 282
IEC 439
IEC 664
IEC 947
Recommendations for Direct-Acting Indicating Analogue Measuring
Instruments and Their Accessories
Power Capacitors
Power Transformers
Semiconductor Convertors
Current Transformers
Voltage Transformers
Electrical Relays
Low-Voltage Fuse
High-Voltage Fuses
Low-Voltage Switchgear and Controlgear Assemblies
Insulation Co-ordination Within Low-Voltage Systems Including
Clearances and Creepage Distances for Equipment
Low-Voltage Switchgear and Controlgear
-
2.1.2 British Standards
Engineering Group Specification
BS 800 Limits and Methods of Measurement of Radio Interference
Characteristics
2.1.3 Other Standards
Specification Number
01 5-PH-1911
Engineering Recommendation G5/3 - Limit for Harmonics in the
United Kingdom Electricity Supply System (Electricity Council, Sept
1976).
2.1.4 Engineering Group Specifications
Rev
1
The variable speed drive controllers shall conform to all
relevant Engineering Group specifications of which the following
are specifically referred to in this specification:
01 5-AH-1001 Basic Design Criteria
Date
17-6-94
01 5-AH-1 002 International Codes and Standards
Sheet
4 of 20
01 5-KH-1902 Spare Parts and Maintenance Requirements
01 5-NH-1104 PlantIEquipment Noise Control
01 5-PH-1902 High-Voltage Switchgear
01 5-PH-1903 Power Transformers
01 5-PH-1905 Low-Voltage Switchgear and Motor Control
Centres
01 5-PH-1908 Induction Motors
01 5-UH-1001 Packing, Marking and Documentation
01 5-XH-1005 Shop and Field Painting
2.2 Compliance with this specification shall not relieve the
Contractor of its responsibility to supply equipment suited to meet
the specified service conditions and applicable regulations.
2.3 Where conflicts exist between this specification and other
Drawings, standards, codes and specifications, the most stringent
shall be applied.
2.4 Equipment may comply with other National Standards subject
to receipt of prior written approval from Company.
-
Specification Number Rev Date Sheet Engineering Group
Specification 01 5-PH-1911 1 17-6-94 5 of 20
3.0 SERVICE CONDITIONS
The equipment shall be suitable for continuous operation at a
desert location under high ambient temperatures and humidity. The
atmosphere at the Facility is generally dusty and corrosive and may
contain traces of hydrogen sulphide.
The variable speed drive controller units shall be new and in
all respects suitable for continuous operation in the service
conditions stated in the Engineering Group Specification entitled
"Basic Design Criteria" (Number 01 5- AH-1001).
The minimum degree of protection for enclosures in accordance
with IEC 947 shall be as follows:
3.3.1 Indoor equipment assemblies: IP4X.
3.3.2 Outdoor equipment assemblies: IP55.
Reliability of all equipment to perform continuously in the
service conditions specified is essential. Equipment typical of
that being supplied shall have been in operational use elsewhere
for a minimum of two years. Prototype or unproven equipment not
having a well-established record shall not be considered.
All equipment, including contactors, transformers, fuses,
relays, all other current-carrying parts, all auxiliary devices,
etc. shall have the specified ratings, which shall be their
continuous rating as installed in the equipment after being
suitably derated for the specified service conditions.
The variable speed drive controller shall be designed to provide
a minimum mean time between failure (MTBF) of 30,000 hours. The
variable speed drive controller shall be designed to provide a mean
time to repair (MTTR), with service personnel on-site, not
exceeding 4 hours.
4.0 BASIC ENGINEERING INFORMATION
4.1 The variable speed drive controller shall be suitable in all
respects for operation on a 3-phase, 50-Hz supply.
4.2 The variable speed drive controller shall be suitable for
continuous operation, without deleterious effect, with variations
of supply voltage and frequency as follows:
4.2.1 Voltage * 6%.
4.2.2 Frequency k 2.5%.
-
Variable speed drives rated at 120 kW or less may be connected
to the 440-V supply. For drives of greater than 120 kW, each
variable speed drive controller shall be fed from a high-voltage
system unit transformer, unless otherwise specified on the
single-line diagram.
The unit transformer and oil-cooled reactors or inductors shall
comply generally with the Engineering Group Specification entitled
"Power Transformers" (Number 01 5-PH-1903) and shall be suitable
for operation with non-sinusoidal current wave shapes and DC
components under normal and abnormal conditions of the variable
speed drive system without exceeding the specified maximum
operating temperature. Additional windings shall be included as
necessary for the design requirements.
Motors shall be 3-phase, squirrel-cage induction motors and
shall comply generally with the Engineering Group Specification
entitled "Induction Motors" (Number 01 5-PH-1908) and shall be
suitable for use with the variable speed drive system without
exceeding the maximum design temperature. Motors for use in
hazardous areas shall be certified for use within the area
classification applicable as specified in the above Engineering
Group specification and shall be certified for use in conjunction
with the particular variable speed controller from which it is
supplied.
Electrical components for incorporation into the variable speed
drive controller shall comply with the relevant IEC standards.
These shall be selected to exclude readily combustible insulating
and constructional material and excessive heat generation.
Electrical and mechanical reliability is of the utmost importance.
The components shall have been type tested to the relevant IEC
standard.
5.0 CONSTRUCTION REQUIREMENTS
5.1 The variable speed drive controller shall be housed in a
free-standing, floor- mounting, dust - and vermin-proof,
metal-enclosed enclosure permitting front access only. It shall be
complete with all necessary instruments, controls, indicators,
connections, circuit breakers, isolators, fuses and ventilation.
The rectifier and inverter equipment shall be assembled together.
The bypass facility components shall be located in a separate
compartment.
5.2 The equipment shall be designed to minimise risk of an
internal short circuit. It shall also provide for personnel and
operating safety during all operating conditions, inspections and
maintenance. Under extreme conditions of major short circuits or
mal-operation, there shall be no danger to persons in the vicinity
of the equipment. Interlocks and covers shall be provided to
prevent incorrect or unsafe operation and to prevent access to live
parts.
5.3 The enclosure shall be constructed from folded and welded
mild sheet steel not less than 2 mm thick.
-
Specification Number Rev Date Sheet Group , specification
015-PH-1911 1 17-6-94 7 of 20
Cable entry shall be via 3-mm thick removable gland plate(s).
Gland plate(s) shall be of adequate size to accommodate the cables
required.
Front access door(s) shall be sufficiently rigid and close
fitting to exclude dust. Gaskets of neoprene or other approved
material shall be used to provide a seal. Hinged doors shall not
exceed 900 mm wide and shall be fastened by means of a T-type key
lockable handle. Doors shall have facilities to restrain them in
the open position.
Door-mounted equipment shall be arranged in a logical manner for
ease of operation, inspection and maintenance.
All live terminals and door-mounted equipment shall be shrouded
or otherwise protected by barriers providing a degree of protection
IP2X with the enclosure door(s) open. This shall apply to all doors
or frames giving access to internal components.
The enclosure and equipment within shall be cooled in order of
preference by natural air cooling, forced air cooling or water
cooling. It is not expected that water cooling would be used for
controllers rated below 2000 kW. Redundancy shall be provided in
the forced cooling system such that any one cooling fan, pump or
heat exchanger failing on any thyristor stack shall not impair the
unit performance. Particular attention shall be paid to the
location of ventilation louvres and their arrangement. Dust filters
shall be provided on all louvres and shall be easily replaceable
during operation.
Controller noise level shall not exceed 65dB(A) measured 1 m
from the equipment, at any position and at any load between zero
and 100%. Reference shall be made to the Engineering Group
Specification entitled "Plant/Equipment Noise Control" (Number 01
5-NH-1104).
5.10 The enclosure design shall allow work to be carried out
safely on the variable speed drive controller, when isolated,
without contact with live parts, with the motor operating on fixed
speed bypass.
6.0 PERFORMANCE
6.1 The variable speed drive system shall comprise:
6.1.1 Transformer/incoming supply.
6.1.2 Controller.
6.1.3 Motor.
6.1.4 Driven plant.
-
Q KM: Engineering Group Spew'fication 6.2 The system shall be
designed as a coherent whole to give the required
performance characteristics. The characteristics shall be suited
to those of the driven equipment with due regard to the operating
and transient conditions, including torsional analysis and critical
speed avoidance.
I I
-
6.3 The variable speed drive controller shall be capable of
withstanding the thermal and dynamic stresses and the transient
mechanical torques such as those resulting from a short circuit.
Any damage resulting from such a short circuit or internal fault
shall be confined to the component concerned.
Specification Number
01 5-PH-1911
6.4 The variable speed control system shall be designed so that
in the event of a component(s) failure or power supply loss, the
system shall fail in a safe condition.
N12-0110
Date
17-6-94
Rev
1
6.5 The controller shall be fault tolerant so that no single
processor or component failure causes shutdown.
Sheet
8 of 20
6.6 The variable speed drive controller shall comprise the
following major components arranged in a modular construction:
Disconnection device.
Rectifier.
DC Link.
Inverter.
Commutation circuits.
Filter.
Controller bypass circuit including motor starter.
Controls and display panel.
6.7 The motor starter shall be either direct on-line,
reduced-voltage Korndorfer type or static soft-start as required to
meet the specified voltage dip limitations.
6.8 For motors of 120 kW or less rating (440 V), the variable
speed drive controller shall be of a 6-pulse configuration, with a
torque characteristic to match the requirements of the driven
equipment. The controller for drives larger than 120 kW shall be of
a 12- or 24-pulse configuration, depending on the design and size
of the drive. The configuration shall be selected to meet the
specified limitations on harmonic currents and voltages.
-
Specification Number Rev Date Sheet Engineering Group
Spewfication 015-PH-1911 1 17-6-94 9 of 20
6.9 The variable speed drive controller shall be rated for 100%
full-load current, duty class II in accordance with IEC 146, and
meet all torque requirements for the supply voltage and frequency
variation stated herein.
Acceleration and de-acceleration times shall be independently
programmable as a minimum for 1 to 250 seconds.
The variable speed drive controller shall incorporate inherent
voltage dip protection. The protection shall ensure continuous
operation for voltage transients down to 70% system voltage for a
duration less than or equal to 3 seconds. For voltage transients
greater than the criteria stated, the variable speed controller
shall be locked out.
The set frequency of the drive shall be maintained within rt 1 %
irrespective of variation in load. Speed regulation shall be
uniform and bump free.
Normal rated speed shall be 5% less than the maximum speed. The
speed control shall be calibrated for a range of 0 % to 105%.
The harmonic currents and voltages introduced to the electrical
system at all voltage levels shall not exceed the limits of
Engineering Recommendation G513, either individually or in total,
for the Facility. Any necessary calculations and measurements shall
be performed by the Contractor.
Provision shall be made for future addition of harmonic
reduction equipment as it is anticipated that similar equipment
shall be installed at other facilities.
The radio frequency interference from the equipment shall not
exceed the limits specified in BS 800.
The equipment performance shall not be affected by externally
produced electromagnetic fields.
7.0 VARIABLE SPEED DRIVE CONTROLLER
7.1 The variable speed drive controller shall provide the
following speed control modes:
7.1.1 lnput for auto speed control in the form of a 4 - 20mA
signal, powered from the Distributed Control System (DCS) 24-VDC
power supply.
7.1.2 lnput for remote manual speed control in the form of raise
and lower pushbuttons.
-
7.1.3 In-panel speed control for maintenance and commissioning
purposes only. This control shall be so arranged so that access is
limited to authorized personnel only.
7.2 The variable speed drive controller shall be microprocessor
controlled providing on-line monitoring and self-diagnostics. The
following minimum controls shall be provided:
7.2.1 Onloff control switch.
7.2.2 Emergency stay-put stop pushbutton.
7.2.3 Programmable control unit incorporating keypad and
alpha-numeric LCD display. The display shall include:
a. Operating parameters with set points and actual values.
b. Selection of parameters from programmes for adjustment and
monitoring.
c. Faults, alarms and diagnostic messages.
I 7.2.4 Startlstop inverter. 7.2.5 Electrical bypass transfer
switch.
7.3 The minimum following programmable set points shall be
provided:
7.3.1 Maximum and minimum speeds.
7.3.2 Calibration of 4 to 20mA input signal.
7.3.3 Maximum and minimum torque settings.
7.3.4 Motor ramp times.
7.3.5 Controller current limit.
7.4 Thyristor banks shall be provided with redundancy so that a
failure of one or two thyristors shall not cause system failure.
Thyristors shall be monitored such that any failure shall initiate
an alarm.
7.5 110-VAC control supplies for variable speed drive
controllers shall be derived internally within the controllers from
transformers.
7.6 Where the variable speed drive system is subject to
automatic control, it shall be designed so that start signals are
only acknowledged following initial operation of a pushbutton,
soft-key or sequence initiate. Under no circumstances shall the
drive start on reset of a stop switch or trip device.
-
Where sequence interlocks and control functions are carried out
via electronic control systems, safety interlocks, especially those
for personnel protection, shall be designed to act directly into
the main power supply disconnection device feeding the controller.
The disconnection device shall be an integral part of the
controller. lntertrip signals in the form of two volt-free change-
over contacts from the controller shall be provided.
An emergency stop stay-put pushbutton shall be provided on the
controller and local to the motor. These pushbuttons shall be hard
wired, configured in series with the controller Emergency Shutdown
(ESD) input and defined as a safety interlock in accordance with
the preceding clause.
Volt-free auxiliary contacts shall be provided to interface with
the DCS and indicate Drive Stopped, Drive Running and Drive
Available.
7.10 Variable speed drive systems shall include a testlnormal
selection facility operable from the controller by a key switch.
When test is selected, the controller shall be controlled from the
in-panel speed control. When normal is selected, the controller
shall be controlled from either the control station local to the
motor or via the 4-20mA input (selectable by a local/off/remote
facility on the local control station). All stop pushbuttons shall
operate regardless of switch positions.
Control facilities local to the motor shall be combined in a
common control station incorporating local/off/remote selector
switch, startlstop pushbuttons, raisellower speed pushbuttons,
emergency stay-put stop pushbutton, speed indication and current
indication. When located in a hazardous area the control station
shall be certified for hazardous area use.
7.12 Essential interlocks and safety trip devices shall remain
operable in all circuit configurations.
8.0 EARTHING
8.1 An earth bar shall be provided along the full length of each
enclosure. All metallic non-current-carrying parts shall be bonded
together and connected to the earth bar. External M I 0 earthing
terminals shall be provided to facilitate connection of the
enclosures to the earthing system.
8.2 Panel-mounted equipment with exposed metal parts such as
indicating lights, pushbuttons, and relays shall be separately
earthed.
8.3 Provision shall be made for connecting the earth continuity
conductors and cable armoring of all outgoing circuits.
-
Specification Number - eng~neering Group
01 5-PH-19' a I Y LID? I Shen n .I nrr I 8.4 Doors and hinged
parts shall be bonded to the switchgear structure by means
of a flexible copper connection having a minimum cross-sectional
area of 6 mm2 arranged so that it cannot be trapped as the door is
opened or closed.
8.5 Connections from the main earth bar to components shall
consist of copper strips or greenlyellow PVC-sheathed stranded
copper conductors. Termination lugs shall be of the compression
type.
9.0 WIRING AND TERMINALS
9.1 The internal wiring shall be carried out in a minimum of 1.5
mm2 stranded copper conductor 60011 000-V grade PVC-insulated
wires. A minimum of 2.5 mm2 shall be used for current transformer
wiring; solid conductors shall not be used. Wiring shall be
configured so that its insulation shall not be subject to injurious
temperature.
9.2 Internal wiring shall be adequately supported by clamping of
loomed runs or installed in plastic trunking. Self-adhesive fixings
are not acceptable. The supporting arrangements for wiring shall be
such that they are not liable to cause permanent physical damage or
deformation to the conductor or insulation. Wiring shall not be
bent to a radius less than the permissible value given by the
Approved Manufacturers. Trunking fill shall not exceed 75% of its
capacity.
9.3 Internal panel wiring shall be identified by proprietary
heat-shrinkable ferrules at each end, with numbers allocated by the
Contractor. All wiring Drawings produced by the Contractor shall
clearly identify the appropriate reference numbers. All wiring
shall be terminated with pin-crimped terminations.
9.4 Terminal blocks shall be arranged to facilitate
accessibility for cable-core termination and inspection of terminal
identification numbers. Terminals shall be of the pinch-plate type,
Klippon manufacture or Company-approved equivalent, suitable for a
minimum conductor size of 1.5 mm2.
9.5 Terminal blocks shall be logically grouped, indelibly marked
and provided with removable plastic shrouds. Segregation of
different voltage level within terminal blocks shall be achieved by
barriers. Voltage levels shall be clearly identified by labels.
9.6 No more than one wire shall be inserted into any one
terminal. Looping between terminals, when required, shall be
carried out using the purpose- made top of block cross connection
or comb-type busbar.
9.7 Terminal blocks associated with external sources of supply
shall be fully shrouded and fitted with a danger warning label.
9.8 Terminals associated with external current monitoring signal
shall be provided with, easily removable shorting plugs.
-
9.9 At least 300-mm clearance shall be allowed between the gland
plate and any internal equipment to permit easy cable installation
and connection.
Back of panel wiring shall be so arranged that access to the
connecting stems of relays and other apparatus and to contacts of
control and other switches is not impeded.
9.1 1 Wiring looms crossing from fixed to hinged panels shall be
mechanically supported on both panels, adjacent to the hinged side,
by means of saddles or compression-type supports.
9.12 Wiring colours shall comply with the following:
I Neutral Conductor I Black I 440-VAC Phases
I G h i n a Conductor I GreenNellow I
Red, Yellow, Blue
AC Control Wiring I Black
I
I DC Supply Positive Red or with Red I Markers DC Control
Wiring
9.13 Spare terminals equal to at least 25% of the total used
shall be provided to enable any spare multicore cable conductors to
be terminated.
Grey
I I 0 * O CABLE TERMINATIONS 10.1 Undrilled removable gland
plates shall be provided on cable
termination compartments.
10.2 All cable entries shall be from bottom and, all connections
will be made from the front of the panel.
10.3 The terminals shall be so arranged that dressing and
connecting of cables can be done safely, and without exposure to
adjacent live functional units.
10.4 Inside the compartments separate terminals or bolts of
adequate dimensions, one for each cable, shall be fitted for cable
armoring earthing purposes.
I 11-O CONTROL AND PROTECTION EQUIPMENT 11.1 The variable speed
drive controller shall be fully protected to prevent
damage to the motor or to any internal components.
-
In by-pass operation the motor circuit protection specified
below shall be provided. This shall take the form of
electronic/static motor protection relays and shall be provide the
following as a minimum:
Short circuit.
Overload. This protection shall include a motor thermal image
with memory.
Locked rotor.
Unbalanced loading (negative sequence and current).
Motor winding temperature.
Motor earth fault.
Extended motor starting time.
Undervoltage release (time delayed). Controllers, transformers
and other equipment shall be provided with the following minimum
protection:
Undervoltage, overvoltage, over-frequency and over-fluxing.
DC link earth fault/overcurrent.
Internal components monitored for over-temperature and thyristor
failure.
Reactor oil temperature and pressure.
Malfunctioning of control equipment.
Unit transformer earth fault, overcurrent, oil and winding over-
temperature and oil level and oil pressure.
Alarm, diagnostic and fault messages shall be displayed on
liquid crystal displays. All alarms and fault messages shall have
data- logging facilities with battery-backed memory. A serial data
link (RS232C) shall be provided for transfer of data to the DCS or
a printer.
Where a motor is equipped with resistance temperature detectors
and thermocouples, a temperature-monitoring unit shall be provided.
It shall be of the flush-fronted, door-mounting type and provide a
selectable digital readout for each of the temperature detectors.
Alarm and trip contacts shall be provided
-
Specification Number Rev Date Sheet , . . --- - - 3ring
Group
Spm'fication 015-PH-1911 1 17-6-94 15 of 20
in the form of volt-free change-over contacts.
LED brightness shall be such that displays are clearly visible
in normal artificial lighting levels.
A lamp test pushbutton shall be incorporated on the front of the
cubicle.
All alarm indications shall be latched until reset by means of a
reset command.
Analogue-indicating instruments shall be the 72-mm square-flush
type and comply with IEC 51, Class 1 and have 240 scale movements.
The instruments shall be back connected and have external zero
adjustment. The minimum scale reading shall not be less than 20% of
the normal or full-load reading. All facias shall be white and
pointers black; scale shall be in actual values. A red line or
adjustable red pointer to indicate the normal operating point shall
be provided.
Digital displays shall be accurate to at least & 1 volt or f
1 amp. Metering and indication shall be corrected to read true rms
values of voltage and current.
The variable speed drive controller shall be fully protected to
prevent damage to any internal components. All circuits shall be
adequately protected by means of circuit breakers or fuses, double
pole for DC circuits. The protective devices shall be readily
accessible.
The following metering shall be provided on the controller as a
minimum:
Motor voltage, current and speed.
Frequency output to motor.
DC link voltage and current.
Hours run.
Provision shall be included for display of the following signals
remote from the controller:
Motor speed.
Motor current.
Motor power in kW.
-
The equipment shall conform with the appropriate requirements of
the Engineering Group Specifications entitled "High-Voltage
Switchgear" and "Low-Voltage Switchgear and Motor Control Centres"
(Numbers 01 5-PH-1902 and 01 5-PH-1905). Each variable speed drive
controller shall be provided with a means of isolation for the
incoming supply suitable for the voltage and current pertaining.
The means of isolation shall be mechanically interlocked with the
equipment doors such that access can only be obtained in the
isolated position. Onloff indication shall be provided and the
operating handle shall be padlockable in the off position.
Sufficient auxiliary contacts shall be provided for isolation of
other external voltage sources.
Circuit breakers shall be used instead of isolators and
contactors where the contactor and/or fuse ratings available are
not sufficient to handle the larger motors.
Contactors shall be 3-pole, self-aligning, double-break, with a
current rating suitable for its application at the maximum ambient
temperature.
Contactors shall be suitable for both uninterrupted and
intermittent class 3 duties, utilization category AC3, and shall be
provided with auxiliary contacts as listed below:
To energise the motor anti-condensation heater when the motor is
not running or isolated.
Two NO and 2 NC volt-free contacts wired out to terminals via
isolator auxiliary contacts.
Semi-conductors shall be protected by high-speed fuses.
Miniature circuit breakers shall be fitted with thermal and
magnetic trips according to IEC 947.
Fuses shall be of the HRC type and fitted in fully insulated
carriers and bases.
Voltage transformers within the controller shall comply with the
following:
Transformers shall be in accordance with IEC 186, double wound
with an earth screen between the primary and secondary windings.
The transformer rating shall be 120% of worst case burden.
-
11.23.2 The earth screen shall be brought out to a termination
point adjacent to the transformer and connected to the main earth
bar within the controller. The primary and secondary windings shall
be protected by suitably rated protective devices.
Current transformers shall comply with the requirements of IEC
185. The secondary winding of current transformers shall be earthed
at one point through a removable link, with provision for attaching
test links. Current transformers shall be rated to withstand the
thermal and magnetic stresses resulting from through fault
current.
All alarms shall be both visual and audible. Test, accept and
reset pushbuttons shall be provided. Alarms shall be provided to
assist maintenance personnel in identifying faults down to card
level.
Volt-free contacts shall be provided for remote alarm purposes.
A contact shall be provided for each individual alarm, and contacts
shall be wired to terminals, grouped as applicable to serve as
common alarms.
Alarms shall be arranged so that their operation may be checked
by simulation, which is as close as possible to the alarm
condition.
11.28 Cubicles shall be provided with internal illumination
suitable for connection to an external 250-VAC supply.
ELECTRONIC EQUIPMENT
12.1 All connections to sub-assemblies, e.g. transformers,
semi-conductor heat- sink assemblies, control modules, etc, shall
be made via centralised termination or connection blocks.
12.2 Printed circuit boards shall be replaceable without the use
of a soldering iron. (Indirect edge connectors are preferred).
12.3 Useful test points and adjustment points shall be placed
such that it is not necessary to reach past exposed live parts
during live measurements/testing.
12.4 All exposed live parts shall be shrouded and provided with
warning labels. Printed circuit boards shall be tropic proofed.
-
13.0 ANTI-CONDENSATION HEATERS
Space heaters, controlled by thermostats, shall be provided for
each compartment. Heaters with isolating switch fuse and neutral
link shall be suitable for 250-V, single-phase supply from an
external source. Surface temperature of all heaters shall not
exceed 1 60C. Power for motor anti-condensation heaters shall be
from the same source. Separate protection shall be provided for
each heater sub-circuit.
14.0 NAMEPLATES AND LABELS
Each unit and main sub-assembly shall have a nameplate clearly
and indelibly marked with the data specified in the appropriate IEC
standard. Nameplates shall be fixed with non-corrodible screws or
rivets.
The unit shall have a label on its front at high level showing
the unit designation number.
An engraved instruction notice shall be affixed to the equipment
in a prominent location. The notice shall list procedures to be
employed in switching for startup, shutdown, maintenance and test
operations.
Warning labels shall be provided in all locations where
necessary to warn personnel of potentially dangerous
situations.
All instruments, selector switches, indicators, etc. shall be
provided with descriptive labels.
All solid-state or other equipment which can be damaged when
subjected to high voltage shall be provided with a warning label
stating that they must not be subjected to high-voltage tests.
Labels shall have black characters on a white background, except
warning labels shall have white characters on a red background.
All labels shall be engraved on plastic-laminated material and
secured with non-corrodible screws; adhesive or self-tapping screws
are unacceptable.
All components incorporated within the unit shall be indelibly
marked with the component circuit reference. Handwritten stickers
or dyno-tape labels are unacceptable.
15.0 PAINTING
Painting shall be in accordance with the Engineering Group
Specification entitled "Shop and Field Painting" (Number 01
5-XH-7005).
-
I 16.0 TESTING Engineering Group Specification
16.1 General
The tests shall be performed at the Approved Manufacturer's
Works and shall include those listed below.
Specification Number
01 ~-PH- I~ I 1
1 16.2 Electronic Com~onent Tests 16.2.1 Circuit burn-in at 70C
dynamically at 85OC statically for 160
hours. Parametric tests are to be made before and after the
burn-in phase.
Rev
1
16.2.2 Memory bit check on EPROMs. After a soak of 1 OOC for 72
hours, repeat memory bit check.
16.2.3 Functional test of microprocessor.
Date
17-6-94
16.3 Printed Circuit Boards
Sheet
19 of 20
16.3.1 In-circuit tests: These tests shall check the correctness
of the assembly and verify the soundness of all active and passive
components.
16.3.2 Functional tests: To verify the operation of the
completely assembled printed circuit boards when energised and
exercised over the full operating range.
16.4 Wiring 16.4.1 All edge connector sockets, outgoing
terminals, and internal
connecting wiring shall be tested for electrical continuity and
correctness of circuit connections.
16.4.2 Insulation testing at the appropriate volta e shall be
performed at all possible terminal points. All tests sha 7 I be
performed before the insertion of the completed system module
assembly. The test shall be a 100% test on all sockets, terminals
and connections.
1 6.5 Functional Test
16.5.1 T pe tests shall be carried out in accordance with IEC
146 and 4 !I 9 and shall include the following:
a. The complete assembled controller shall be subjected to a
complete functional test when energised to verify its operation.
The test shall be performed in conjunction with computerised test
equipment providing all required input and output simulated
signals.
I c. Harmonic current content of input wave form. I b. Harmonic
current content of output wave form.
-
d. Verification of protective devices.
e. Verification of the properties of the trigger equipment. f.
Light load test.
g. Verification of transfer system from controller operation to
electrical bypass and vice versa.
h. Load test at rated current.
i. Determination of power losses. j. Measuring of audible noise.
k. All units shall be subjected to a full load burn-in for a
duration of 24 hours.
16.5.2 For standard range controllers where type test
certificates are available, routine tests in accordance with IEC
146 and 439 shall be performed.
16.6 Motor Tests
Complete tests shall be performed as stated in the Engineering
Group Specification entitled "Induction Motors" (Number 01
5-PH-1908).
16.7 Strina Test 16.7.1 All controllers and their associated
motors shall be connected
together for performance of the following tests: a. Eight-hour
full-load test at maximum speed.
b. Eight-hour full-load test a minimum speed. 16.7.2 The above
specified test shall be contiguous with the following
tests performed:
a. Harmonic current content of output wave form.
b. Harmonic current content of input wave form. c. Measurement
of power factor.
d. Temperature rise.
e. Measurement of vibration levels.
17.0 PACKING, MARKING AND DOCUMENTATION For all relevant
requirements, refer to the Engineering Group Specification entitled
"Packing, Marking and Documentation" (Number 01 5-UH-1001).
18.0 SPARE PARTS AND MAINTENANCE REQUIREMENTS For all relevant
requirements, refer to the Engineering Grou Specification entitled
g "Spare Parts and Maintenance Requirements" (Number 01
-KH-1902).