Top Banner

of 5

01335150

Jun 02, 2018

Download

Documents

Foad Farahani
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/10/2019 01335150

    1/5

    Damning. Analvsis of Subsvnchronous

    Oscillation Caused

    by HVDC

    Abstract-The correct analysis of damping characteristics in

    subsynchronous frequency range is essential to evaluate the

    subsynchronous oscillation

    (SSO)

    caused by

    WDC

    but the

    damping calculation is handicapped by the modeling of HVDC in

    such a frequency range. The complex torque coefficient method

    realized by time domain simulation is adopted in this paper to

    estimate the

    SSO

    caused by HVDC. Frequency scanning in the

    subsynchronous frequency range is performed to calculate the

    subsynchronous damping

    of

    a

    unit. Impacts

    of

    unit interaction

    factor UDF),DC power level, firing angle and parameter settings

    of the HVDC controller on the electrical damping are studied.

    Research of the damping characteristics under inverter operation

    is

    also

    conducted and it shows that only the units adjacent to the

    rectifier have the potential for SSO, the units near the inverter

    have

    no such risk.

    Zndex

    Terms--complex torque coefficient method; SS0;HVDC

    I. INTRODUCTION

    ubsynchronous oscillation resulted from the interaction

    S etween the electrical power system and the turbine

    generator mechanical system can lead to turbine-generator

    shaft failure and electrical instability at oscillation frequency

    lower than the normal system frequency. The SSO mainly

    occurs in the system with series compensated lines, the first

    time that HVDC experienced

    SSO

    was in 1977 at Square

    Butte. Extensive research was conducted but till now few

    effective approaches were presented for SSO caused by

    HVDC except the Unit Interaction Factor---UIF method

    provided by EPRI [l]. The

    UIF

    establishes

    a

    relationship

    between the HVDC interaction with turbine-generator

    torsional vibration and the AC system strength, but there is no

    damping information given by the

    UIF.

    The detailed studies

    of

    SSO

    caused by HVDC were usually realized by HVDC

    simulator [2 31, which was based on the electrical damping

    characteristics of the units in the subsynchronous frequency

    range, and the

    SSO

    stability was also estimated on the basis of

    hangchunZhou, Zheng Xu Member,

    IEEE

    0-7803-8110-6/03/ 17.00

    02003

    IEEE 30

    Project 50277034 supported by National Natural Science Foundation

    of

    Project No. G1998020310 supported by National Key Basic Research Special

    Fund of China

    Changchun

    Zhou

    and Zheng

    Xu are

    with the Department

    of

    Electrical

    Engineering, Zhejiang University, Hangzhou, 310027 P. R. China

    e-mail:

    [email protected]).

    China.

    the damping characteristics, this is the so-called complex

    torque coefficient method.

    The term of complex torque coefficient is proposed by

    1.M.Canay in 1982

    [4].

    But before that time, the method

    based on the concepts of damping torque and synchronous

    torque for analysis of the SSO problem had been widely

    applied [2,3]. In complex torque coefficient method, the

    mechanical and electrical damping coefficient are calculated

    respectively and used to evaluate the SSO problem. Since it is

    a big challenge to establish an appropriate mathematical

    model for systems including HVDC or FACTS devices in the

    subsynchronous frequency range, it is difficult to obtain the

    analytical solutions of the complex torque coefficient for the

    study of the SSO problems caused by

    HVDC

    and FACTS.

    However, the complex torque coefficient method realized by

    time domain simulation has unique strong point to deal with

    such an issue

    [5].

    In this paper, a time domain simulation

    based on PSCADEMTDC is made to calculate the complex

    torque coefficients and a damping analysis of SSO caused by

    HVDC is also presented.

    II.

    MECHANISMS

    ESCRIPTION

    Investigations have revealed that the SSO problem of

    HVDC is due primarily to the effects of the controllers

    employed in HVDC systems [11. Turbine-generator rotor

    motion causes variations in both magnitude and phase angle

    of the commutating voltage. For an equidistant firing angle

    control, utilized in modem HVDC systems, a shift in voltage

    phase causes an equal shift in the firing angle. The change in

    firing angle, as well as variations in the voltage magnitude,

    will lead to changes in direct voltage and current, and thereby

    dc power transfer. A closed loop control on direct current,

    direct voltage, or firing angle applied in the HVDC would

    respond to correct for these changes, thereby impacting the

    magnitude and phase of variations in dc power transfer. The

    ultimate effect of the change in dc power is a change in the

    generator electrical torque. If the accumulated phase lags

    between the changes in the generator shaft speed and the

    ultimate resulting change in electrical torque on the generator

    rotor exceed 90, the electrical damping becomes negative

    [6]. Whether SSO occurs or not depends on the magnitudes of

    the positive mechanical damping and negative electrical

  • 8/10/2019 01335150

    2/5

    damping at the corresponding subsynchronous frequencies.

    Many factors may influence the characteristics of the

    electrical damping, such as the coupling between HVDC and

    turbine-generator, direct power level, magnitude of firing

    angle, characteristics of dc controller, parameters of the dc

    lines and so on.

    HI.

    REAJJZATION

    OF

    COMPLEX

    TORQUE

    OEFFICIENT METHOD

    IN HVDC

    In complex torque coefficient method, the increments of

    the electromagnetic torque and mechanical torque of a

    machine under a

    hHz h < f ,

    and f, is the base system

    frequency) disturbance can be represented as:

    A i' e = K , ( h )A ; + D e ( h ) A h

    (1)

    A T , =

    K, ( h )A S+ D ,(h)ACO (2)

    In (l),

    K,

    and De are called as the electrical spring

    coefficient and electrical damping coefficient respectively; In

    ( 2 ) , K , and D , are balled as the mechanical spring

    coefficient and mechanical damping coefficient respectively.

    When

    K , ( h ) + K e ( h ) z O

    and

    D , ( h ) + D , ( h ) < O ,

    the

    torsional mode of oscillation at hHz is regarded as unstable.

    For torsional modes of turbine-generator oscillation, the value

    ofK, s relatively small in comparison to that of

    K,

    Hence,

    the electrical spring coefficient has little effect on rotor

    torsional oscillations. However, the inherent damping of the

    turbine-generator torsional modes is extremely low, and the

    damping contribution of the electrical system can be a

    significant factor. Hence, the emphasis of this paper is to

    examine the damping contribution of the power system. From

    (1).

    the electrical damping coefficient can be represented as:

    D e

    =

    R e ( A i ' e / A & ( 3 )

    where

    A

    T e

    A h

    = the increment of the electrical torque

    = the increment of the electrical speed

    The prerequisite for the complex torque coefficient method

    is that the increment of the electromagnetic torque of a

    generator can be represented as a linear function of the

    generator's increment power angle and increment angular

    frequency

    [SI so

    the complex torque coefficient method is

    only valid for power system with only one generator and some

    fixed frequency sources but not valid for multi-machine

    power systems. In studying the

    SSO

    problem of a multi-

    machine power system, the generator interested can always be

    separated from the system and replace the rest of the units

    with an equivalent source. Then the complex torque

    coefficient for the unit interested can be calculated in the

    equivalent network. The complex torque coefficient of each

    unit in the system can be obtained after several times of

    equivalence and calculation. A simplified equivalent network

    for calculation of complex torque coefficient

    is

    shown in Fig.1

    For the

    SSO

    study of this kind of network shown in Figl, a

    relationship between the magnitude of the

    HVDC

    interaction

    with turbine-generator torsional vibration and the AC system

    strength has been established [13. This relationship, as

    represented in

    4),

    with no damping characteristics provided,

    Fig.1 E quivalentconfigurationof

    A C D C

    system

    has been a cursory index and often used as a quantitative

    screening tool.

    where

    UIFi

    MVAi

    sci

    sc

    =Unit Interaction Factor of the ith unit

    =HVDC rating

    =Rating of the ith unit

    =Short circuit capacity at

    HVDC

    commutation bus excluding the ith unit

    =Short circuit capacity at

    HVDC

    commutation bus including the ith unit

    MVA ,,

    According to the related guideline [l], the interaction

    between the HVDC and turbine-generator can be ignored in a

    network configuration with a UIF less than about 0.1, hence,

    there is no potential risk

    of

    SSO in such a system. Equation 4)

    can also be expressed in the form of impedance as shown in

    (5).Thereby, supposing that the rating of the generator is not

    changed, the

    UIF

    can be changed by varying the impedance.

    where

    zs =Equivalent AC system impedance

    as seen from the converter excluding

    the ith unit.

    =Equivalent AC system impedance as

    seen from the converter including the

    ith unit and

    Z ,

    =

    Zs

    /

    Z , .

    It is convenient to realize the complex torque coefficient

    method by time domain simulation. For a certain operating

    point, after the system enters steady state, add a series of

    small oscillating torques, whose frequencies are in the

    subsynchronous range, to the rotor of the turbine-generator

    under study, then the electrical damping coefficients can be

    calculated according to (3) after getting the resulting changes

    of the electromagnetic torque. Reference [SIhas provided the

    steps of the time domain simulation, and a noticeable question

    is how many small oscillating torques should be added in one

    time. Due to the strongly nonlinear characteristics of HVDC

    or

    FACTS,

    the different frequency quantities may interfere

    with each other if more than one frequency oscillating torques

    Ze q

    31

  • 8/10/2019 01335150

    3/5

    are added in one time. Thereby, only one frequency

    oscillating torque can be added in one time in the simulation

    for a system associated with HVDC or FACTS.

    IV SIMULATION

    ND

    ANALYSIS

    A. Studied System

    The studied system model is shown in Fig.2. Remain the

    turbine-generator G which is connected to the rectifier via a

    step-up transformer and reduce the rest of the machines to

    fixed frequency sources. Each reduced machine is represented

    by its sub-transient reactance in series with a voltage source.

    Further, combine the reduced machines and represent them

    with a fixed frequency source. In this way, the AC system is

    reduced to be a single unit in parallel with a single fix

    frequency source system, as the rectifier part shown in Fig.2.

    The impedance Z , consists of the sub-transient reactance and

    leak reactance of the step-up transformer, Z is only used in

    the calculation of UIF n the real simulation the generator

    G is modeled by the Park equations with a single mass. The

    rating

    of

    generator

    G

    is 892MVA. The dc power and voltage

    are rated at lOOOMW and 500kV respectively. The inverter

    side AC system is also represented with an infinite source

    behind an impedance.

    Fig.2 Studied system model

    The dc system is a mono-pole and

    12

    pulse system with a

    current controller at the rectifier and an extinction angle

    controller at the inverter. The block diagram of the current

    controller is described in Fig.3, the dc current error is

    processed through a PI regulator to produce the firing angle

    order abrd.

    r

    -

    Fig.3 Block diagram

    of

    current regulator

    B.

    Dam ping characteristics o the rectifier unit

    I Impact of UIF on electrical damping

    For the studied system in Fig.2, keep the rating of the

    generator

    G

    and the equivalent impedance Z as constants.

    Change the AC system strength by varying the impedance Z

    to obtain different UIF Corresponding to different UIF , he

    curves of electrical damping in the frequency range from

    5Hz to 50Hz are depicted in Fig.4. For the situation

    of

    UIF being 0.1,a positive damping exits almost over the entire

    ~

    32

    subsynchronous frequency range. Negative damping only

    occurs at some isolated frequency with small magnitude.

    Considering the positive contribution of the mechanical

    damping, it is deemed that the SSO will not occur in such a

    situation. As shown in Fig.4, the magnitudes of the negative

    damping are increased with the increase of

    UIF ,

    he damping

    coefficients equal - 0 . 8 ~ ~nd -2.Opu for UIF up to 0.36

    and 0.79 respectively. If these negative effects can not be

    counteracted by the mechanical damping of the shaft itself,

    SSO will definitely occur.

    0

    20

    4

    20

    4

    20 4

    Frequency Hz) Frequency

    Hz)

    Frequency Hz)

    Fig.4 Impacts ofUlF on electrica l damplng re ctifieroperation)

    The magnitude of

    UIF

    reflects the coupling between the

    HVDC and the unit. In principle, the impact of the

    disturbance of the generator terminal voltage on the

    commutating voltage is decreased by the parallel

    impedance Z s R and the resulting perturbation of dc current is

    also shunted by Z , . Thereby the ultimate change of A ; ~ is

    smaller than that in the situation without

    Z ,

    . Supposing that

    the ratings of unit and dc power transfer

    are

    not changed, it

    can be seen from (4) and (5) that the UIF is determined by

    SC, and SC , or Z sR and Z . UIF can be of small value

    only

    if

    Z,is very large or

    Z,is

    quite small,

    that is

    to say,

    only on the condition that the electrical distance between the

    unit and HVDC is very large, or the parallel equivalent AC

    system is fairly strong, the SSO can be avoided effectively.

    Another characteristic reflected by Fig.4 is that the

    damping for UIF being 0.36 and 0.79 is negative only in the

    frequency range about 5-2OHz This phenomenon is

    resulted from the effects of the current regulator employed in

    the rectifier. HVDC current regulators typically have

    bandwidth in the range of

    10

    to 20

    Hz

    [7], which include the

    first few torsional modes of vibration of turbine-generator

    units. Only the disturbances in the range of the bandwidth can

    be transferred through the closed loop control and produce

    negative damping. Thereby, in studying the

    SSO

    of HVDC,

    special attentions should be paid to the first few torsional

    modes which have the same frequency range as the controller

    bandwidth.

    2 ) Impact

    of

    dc po wer level

    on

    electrical damping

    From the analysis above, it can be seen that the

    perturbation of dc power is the direct cause of

    SSO

    in HVDC.

    For the same studied system shown in Fig.2 with UIF being

    0.79, Fig.5 gives the curves of damping characteristic versus

    different dc power level. For the dc power Pdc s

    1 .Opu

    , he

    damping is of large negative values in the frequency range

    from

    5

    to 20Hzand is the same as the one shown in Fig.3

  • 8/10/2019 01335150

    4/5

    with UIF =0.79 Less destabilization exits as the dc power is

    reduced, as illustrated by Fig.5. With the dc power dropping

    to

    0.2

    pu

    positive damping exits almost over the entire

    subsynchronous frequency range except the frequencies near

    5 Hz It is well known that the first natural torsional

    frequency of a turbine-generator shaft is generally larger than

    lOHz,

    hence the small negative damping is not capable of

    causing

    SSO

    at the frequency about

    5

    z

    -0

    10

    20 30 40 50

    Frequency

    Hz)

    Fig .5 Impact of dc power level on electrical damping

    Being a kind of oscillation of active power, the SSO caused

    by HVDC is heavily dependent on the dc power transfer and

    the output of generator. UIF is an index of interaction in the

    rated operation, which indicates the coupling of the HVDC

    and the unit in rated operation mode. From the view of

    coupling, the relationship between the unit and HVDC is

    weakened as the dc power transfer drops down. Hence the

    interaction between them and the destabilization are also

    decreased.

    3

    Impact offiring angle on electrical damping

    The disturbance of generator rotor can lead to the changes

    in dc voltage, dc current and hence dc power transfer. The dc

    control would respond to these changes. All the control

    actions at the rectifier are done by changing the firing angle.

    Changes in the fiing angle have a significant impact on the

    interaction of HVDC and unit. This influence arises from the

    inherent cosine relationship between firing angle and dc

    voltage. Fig.6 illustrates the different damping characteristics

    for varied firing angle. As shown in Fig.6, destabilization

    increases as the firing angle is increased. There will be more

    risk in the condition of high firing angle.

    I I

    10 20 30 40

    50

    Frequency Hz)

    Fig .6 Impactof firing angle on electrical damping

    To ensure the operation of valves, firing angle should be

    larger than its minimum limit, which is about

    3 -

    5 In real

    HVDC operation, the firng angle is usually set in the range of

    10'

    -

    15 .

    In general, high firing angle at the rectifier exist

    only for transient situation of at most a few hundred

    milliseconds, during which time torsional damping is not of

    primary concern. However, there may be situations where it is

    operated at reduced voltage in steady-state. Such a case will

    have more potential risk of SSO than HVDC system operating

    near 15 iring angle.

    4

    Impact

    of

    controller settings

    on

    electrical damping

    Since the negative electrical damping is produced by the

    HVDC closed loop current controller, the characteristics of

    damping

    are

    heavily dependent upon the parameter settings of

    them. The structure of current controller has been shown in

    Fig.3. A PI regulator is adopted to produce firing angle order

    for HVDC system. The curves of damping corresponding to

    different integral time constants

    i

    and to different

    proportional gains K , are depicted in Fig.7 and Fig.8

    respectively.

    2

    1 - - - r - - -

    =OiOlS I

    10 20 30 4

    50

    Frequency Hz)

    Fig.7 Impact

    of

    Ti on eiectrical damping

    0 10 20 30 40 50

    Frequency

    Hz)

    Fig .8 Impact ofKp on electrical damping

    The characteristics of damping have a similar tendency of

    change for the three different settings of

    T.

    ,

    which is negative

    in a low frequency range and becomes positive in a high

    frequency range. Define the frequency at which the damping

    turns from negative to positive as f,

    .

    It is clear that

    when Ti

    >Ti*

    T 3 , he relationship of

    f,

    can be expressed

    as f,,

  • 8/10/2019 01335150

    5/5

    shown in Fig.8, for different proportional gains

    K ,

    , he values

    of

    f,

    are almost the same, moreover, the characteristics of

    damping are almost the same in the f < f frequency range.

    When frequency

    f

    increases and is higher than f , the

    damping characteristics behave obviously different for

    different values of. K,

    Because of the complexity

    of

    the HVDC system, it is

    difficult to establish a mathematical model for the closed loop

    current control including the whole dc system. In normal

    operation, different parameters have different impacts on the

    dc controller bandwidth and comparing with the proportional

    gain

    K ,

    , the integral time constant is a more significant

    factor. The larger the c i s , the lower the bandwidth and f

    would be. The unit will benefit from higher time constant to

    avoid

    SSO,

    but the large time constant can surely slow down

    the respond speed of the dc controller. Proportional gain

    behaves as an amplifier to the dc disturbance, from Fig.8 we

    can see, high setting of K , will bring more risks of SSO.

    C.

    Dam ping characteristics

    of

    inverter unit

    Former researches have led to such a conclusion that

    turbine-generators in the vicinity of an inverter station have

    no potential risk of SSO

    [3].

    It is of interest to validate it by

    means of the complex torque coefficient method realized in

    time domain. Suppose that the unit in parallel with equivalent

    AC system is connected to the inverter, or reverse the power

    flow and make the rectifier work as an inverter, the studied

    system in Fig.2 can be used to examine the SSO

    characteristics of the units adjacent to inverter. Fig.9 gives the

    electrical damping of the inverter unit for different UZF .

    Unlike the damping of unit near rectifier, the negative

    damping with small magnitude is achieved only for range of

    high frequency. And the frequency range covered by negative

    damping is decreased as the

    UIF

    increase, as can be seen

    from Fig.9,

    the

    positive damping exists over the entire

    subsynchronous frequency range for UIF being 0.36. As no

    loads are included in the simulation, the results shown in Fig.9

    are very conservative.

    B

    0

    20

    40

    1.5

    1

    0.5

    0

    -0.5

    : :

    0

    2 4

    2.5

    2

    1.5

    1

    0.5

    0

    20

    4

    Frequency Hz) Fresuency (W Frequency Hz)

    Fig.9 Impact of UIF on electrical damping (inverter operation)

    Power system loads have positive frequency-dependent

    characteristic, which will contribute positive damping to

    power oscillations with any frequency, obviously including

    the oscillation in the subsynchronous frequency range. Being

    rigid load, the rectifier station is independent of network

    frequency and usually has negative contribution to power

    oscillations.

    If

    the rated power

    of

    HVDC and

    of

    the unit are at

    the same level, i.e. the UZF is high, there will be more

    possibility of SSO occurrence. Inverter is something like an

    AC source, and the adjacent units do not supply any power to

    the HVDC. Operating parallel with the inverter, the units

    supply conventional, frequency-dependent loads. In addition,

    an inverter, at least operating with dc voltage regulations, is

    similar to the conventional loads----each increase in voltage

    lead to an increased reactive power consumption and vice

    versa. Thereby, the turbine-generators adjacent to an inverter

    are not endangered by SSO problems.

    V

    CONCLUSION

    The complex torque coefficient method is adopted in this

    paper to study the SSO caused by HVDC. The method is

    realized by a time domain simulation. Frequency scanning in

    the subsynchronous range has been performed and the

    characteristics of electrical damping are calculated. This

    method adapts to not only the SSO caused by HVDC, but also

    the SSO problems caused by FACTS

    or

    other power

    electronic devices.

    Current control at rectifier would produce negative

    damping, and the frequency range of negative damping is

    determined by the controller bandwidth. Therefore, properly

    settings of the controller parameters will decrease the risk of

    SSO,

    but can not eliminate the potential danger. Reduce the

    coupling between the HVDC and unit, or reduce the dc power

    transfer and firing angle can mitigate the SSO stress caused by

    HVDC. Units adjacent to inverter have no SSO risk.

    W

    REFERENCES

    Electric Power Research Institute, HVDC System Control

    for

    Damping of

    Subsynchronous Oscillations, EPRl EL-2708,

    Final

    Report,Ocyober

    1982.

    SvenssonS, Mortensen K. Damping of subsynchronous oscillations by an

    HVDC link, an HVDC simulator study, IEEE Trans on Power Apparatus

    and System, vol. 3, pp.1431-1437, 1981.

    Ymg Jiang-Haher,Hugo Duchen, Kerstin Linden and Mats Hyttinen,

    Improvement of subsynchronous torsional damping using VSC HVDC,

    Proceedings of PowerCon2002, vol. 2, pp.998-1003,2002.

    Canay I.M.,

    A

    new approach to the torque inyrtaction and electrical

    damping of the synchronous machine, part I and part 11, I EEETrans on

    Power Apparatus and Systems, vol. 10, pp.3630-3647, 1982.

    Xu Zheng, Feng Zhouyan, A novel unified approach for analysis of

    small-

    signal stability

    of

    power system, Proceedings

    of

    IEEE/PES Winter

    Meeting, vol. 2, pp.963-967,2000.

    The Institute

    of

    Electrical and Electronics Engineers, IEEE guide for

    planning DC

    l i

    erminating at

    AC

    locations having low short-circuit

    capacities,I EEEStd 1204, 1997.

    P. Kundur, Power System Stability and Control, New YorkMcGraw-Hill ,

    1994, p.1026

    VIII.

    BIOGRAPHIES

    Changchun Zhou

    was

    bom

    in Shandong, China, in January 1976. He received

    B.S from SouthEast University, Nanjing, China in 1998. He received M.S from

    Shandong University, Jinan,

    China

    in 2000. He is now a Ph.D. student in the E.E.

    Department of Zhejiang University. His main field of interest includes power

    system stability and control of HVDC.

    Zheng Xu was bom in Zhejiang, China, in September 1962. He received the BS,

    MS and Ph.D. degrees from Zhejiang University, China in 1983,1986 and 1993

    respectively, all in Electrical Engineering. He has been with the Electrical

    Engineering Department of Zhejiang University since 1986. Since 1998 he is a

    professor of Zhejiang University.

    His

    research area includes

    HVDC, FACTS,

    power harmonics and power quality.

    34