LEHE0380-03 Page 1 of 2 C18 Sound Attenuated Enclosures 50 Hz / 60 Hz These sound attenuated, factory installed enclosures incorporate internally mounted super critical level silencers, designed for safety and aesthetic value on integral fuel tank base or optional dual wall integral fuel tank base for total fluid containment. These enclosures are of extremely rugged construction to withstand exposure to the elements and provide weather protection. Image shown may not reflect actual configuration. Enclosures Robust/Highly Corrosion Resistant Construction • Factory installed on integral fuel tank base • Environmentally friendly, polyester powder baked paint • 1.6 mm (0.063 in) galvanized steel • All round overhanging base to protect enclosure • High-grade engineering thermoplastic corner posts for protection • Compression door latches giving solid door seal • Zinc plated or black coated stainless steel fasteners • Internally mounted super critical exhaust silencing system Excellent Access • Large cable entry area for installation ease • Accommodates rear mounted breaker and control panel • Double doors on both sides • Vertically hinged doors with solid bar door stays to hold doors open at 135° rotation • Lube oil and coolant drains pipes to exterior of enclosure and terminated drain valves • Radiator fill cover Security and Safety • Lockable access doors which give full access to control panel and breaker • Cooling fan and battery charging alternator fully guarded • Fuel fill, oil fill and battery can only be reached via lockable access • Externally mounted emergency stop button • Designed for spreader-bar lifting to ensure safety • Control panel viewing window • Stub-up area is rodent proof Options • Caterpillar yellow or white paint • Integral dual wall fuel tank base for total fluid containment (fuel, oil and coolant) Features
13
Embed
0&1'2,1 - Myrak Generators & Plant Sales · Rating Type: STANDBY Fuel Strategy: LOW FUEL CONSUMPTION STANDARD C18. DEFINITIONS AND CONDITIONS 1. For ambient and altitude capabilities
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
LEHE0380-03 Page 1 of 2
C18 Sound Attenuated Enclosures50 Hz / 60 HzThese sound attenuated, factory installed enclosures incorporate internally mounted super critical level silencers, designed for safety and aesthetic value on integral fuel tank base or optional dual wall integral fuel tank base for total fluid containment. These enclosures are of extremely rugged construction to withstand exposure to the elements and provide weather protection.
Image shown may not reflect actual configuration.
Enclosures
Robust/Highly Corrosion Resistant Construction• Factory installed on integral fuel tank base• Environmentally friendly, polyester powder baked paint• 1.6 mm (0.063 in) galvanized steel • All round overhanging base to protect enclosure• High-grade engineering thermoplastic corner posts for protection• Compression door latches giving solid door seal• Zinc plated or black coated stainless steel fasteners• Internally mounted super critical exhaust silencing system
Excellent Access• Large cable entry area for installation ease• Accommodates rear mounted breaker and control panel• Double doors on both sides• Vertically hinged doors with solid bar door stays to hold doors open at 135° rotation• Lube oil and coolant drains pipes to exterior of enclosure and terminated drain valves• Radiator fill cover
Security and Safety• Lockable access doors which give full access to control panel and breaker• Cooling fan and battery charging alternator fully guarded• Fuel fill, oil fill and battery can only be reached via lockable access• Externally mounted emergency stop button• Designed for spreader-bar lifting to ensure safety• Control panel viewing window• Stub-up area is rodent proof
Options• Caterpillar yellow or white paint• Integral dual wall fuel tank base for total fluid containment (fuel, oil and coolant)
*Ambient capability measured with the Cat extended life coolant at sea level.
Enclosure Package Operating Characteristics
5320 (209.4”)1920 (75.6’’)
2289 (”9
0.1”)
2289 (90.1”)
Approximate weight of enclosure package: 5952 kg (13122 lb). Exact weight is dependent on options. Enclosure weight includes: sound attenuated enclosure, exhaust system, base and generator set.
LEHE0380-03 (10/16)
Materials and specifications are subject to change without notice.CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
1. For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.
2. UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
3. Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
Heat Rejection
Heat Rejection to Jacket Water 181 kW 10278 Btu/min
Heat Rejection to Exhaust (Total) 548 kW 31158 Btu/min
Heat Rejection to Aftercooler 109 kW 6196 Btu/min
Heat Rejection to Atmosphere from Engine 90 kW 5120 Btu/min
Heat Rejection to Atmosphere from Generator 31 kW 1769 Btu/min
Alternator²
Motor Starting Capability @ 30% Voltage Dip 2055 skVA
Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for availability.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions
Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29º C (85º F) and weighing 838.9 g/liter (7.001 lbs/U.S. gal.). Additional ratings may be available for specific customer requirements, contact your Cat representative for details. For information regarding Low Sulfur fuel and Biodiesel capability, please consult your Cat dealer.
www.Cat-ElectricPower.com
STANDBY:Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, ADEM, EUI, S•O•S, "Caterpillar Yellow" and the "Power Edge" trade dress, as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Click here to view the Schematic Symbols and Definitions page
INTERACTIVE SCHEMATIC
The Bookmarks panel will allow you to quickly navigate to points of interest.
Click on any text that is BLUE and underlined. These are hyperlinks that can be used to navigate the schematic and machine views.
When only one callout is showing on a machine view, clicking on this button will make all of the callouts visible. This button is located in the top right corner of every machine view page.
VIEW ALL CALLOUTS
Cover PageTables
SchematicMachine Views
ComponentConnector
Chassis View
Cab View
Engine View
Features
Options
Bookmarks X
EC-C3EC-C2 E-C60
EC-C1
E-C61
To set your screen resolution do the following:RIGHT CLICK on the DESKTOP. Select PROPERTIES. CLICK the SETTINGS TAB. MOVE THE SLIDER under SCREEN RESOLUTION until it shows 1024 X 768. CLICK OK to apply the resolution.
*This document is best viewed at a screen resolution of 1024 X 768.
*Due to different monitor sizes and PDF reader preferencesthere may be some variance in linked schematic locations
Fuse: A component in an electrical circuit that will open the circuit if too much current flows through it.
Switch (Normally Open): A switch that will close at a specified point (temp, press, etc.). The circle indicatesthat the component has screw terminals and a wire can be disconnected from it.
Switch (Normally Closed): A switch that will open at a specified point (temp, press, etc.). No circle indicates that the wire cannot be disconnected from the component.
Ground (Wired): This indicates that the component is connected to a grounded wire.The grounded wire is fastened to the machine.
Ground (Case): This indicates that the component does not have a wire connected to ground. It is grounded by being fastened to the machine.
Reed Switch: A switch whose contacts are controlled by a magnet. A magnet closes the contacts ofa normally open reed switch; it opens the contacts of a normally closed reed switch.
Sender:
A component that is used with a temperature or pressure gauge. The sender measures the temperature or pressure.Its resistance changes to give an indication to the gauge of the temperature or pressure.
Relay (Magnetic Switch): A relay is an electrical component that is activated by electricity.It has a coil that makes an electromagnet when current flows through it.The electromagnet can open or close the switch part of the relay.
Solenoid: A solenoid is an electrical component that is activated by electricity. It has a coil that makes an electromagnet when current flows through it.The electromagnet can open or close a valve or move a piece of metal that can do work.
Magnetic Latch Solenoid: An electrical component that is activated by electricity and held latched by a permanent magnet. It has two coils (latch and unlatch) that make electromagnet when current flows through them. It also has an internal switch that places the latch coil circuit open at the time the coil latches.
BASIC ELECTRICAL COMPONENT SYMBOLS
Push-pull Lever PedalGeneral Manual Push Button SpringManual Shutoff