  • OMICRONPDSeminar2013

    OMICRON 1.1

    Introduction, History and Theory of Partial Discharge Measurement

    Rene Hummel, Stephan Krber

    Electric fields

    What is partial discharge ?

    > Partial discharge (PD) is a localized dielectric breakdown of a small portion of a solid or liquid electrical insulation system under high voltage stress.

    > Definition from IEC 60270 Specification: Localized electrical discharge that only partially bridges the insulation between conductors and which can or cannot occur adjacent to a conductor.

    Evidence of partial discharges

  • OMICRONPDSeminar2013

    OMICRON 1.2

    Evidence of partial discharges

    photo: VATech Hydro Austria

    Evidence of partial discharges

    photo: IPH Berlin

    Evidence of partial discharges

    photo: IPH Berlin

    Evidence of partial discharges

  • OMICRONPDSeminar2013

    OMICRON 1.3

    Evidence of partial discharges

    tracking structures

    Evidence of partial discharges

    Video ...

    video: IPH Berlin

    Partial discharge / total discharge

    photo: TU Berlin

  • OMICRONPDSeminar2013

    OMICRON 1.4

    Electricity around us Important units

    Charge Q [1Coulomb] = [1As]:

    Charge in movement = CURRENT!!!

    The more electrons per TIME interval, the higher is the current

    Current = Charge per Time[A] = [Coulomb] per [s][A] = [Coulomb] / [s]

    Charge = Current times TimeCharge = Current x Time

    +

    nucleus1st orbit

    2nd orbit

    electron-

    -

    -

    q =

    Charge How to measure?

    > Time Domain Integration q =

    q

    SI prefixes

    kilo Volts [kV]

    milli Ampere [mA]micro Farad [F]nano Coulomb [nC]pico Coulomb [pC]

    Most used prefixes:

  • OMICRONPDSeminar2013

    OMICRON 1.5

    Charge How it is measured

    > Frequency Domain Integration

    > More details in chapter FILTER

    PD

    C RpC

    Analog PD measurement systems

    PD

    C RpC

    Digital PD measurement systems

    Filter is analogue!

    PD

    V

    0- Detect

    AD

    MPD600 digital PD measurement system with digital filtering

    PD

    V

    AD

    AD

    Digital Filter + PD Processor

    Communications Processor

    Power Management

    Fiber Optic Cable

    USB 2.0

    +-

  • OMICRONPDSeminar2013

    OMICRON 1.6

    PD measurement with the OMICRON MPD software

    test voltage over time

    PD activity over time

    voltage reading

    disturbed voltage signal

    What are partial discharges?

    Partial discharge:

    > Local electrical stress in the insulation or on the surface of the insulation

    > Always generates electromagnetic signals

    > Often accompanied by an emission of sound, light, heat and chemical reactions

    Types of PD

    > Internal PD> Void discharges, electrical treeing

    > External PD> Corona> Surface discharges

    Solid insulation

    Outer semicon

    Solid insulation

    Inner semicon

    Image Source: Andreas Kchler Hochspannungstechnik

    External PD

    Surface discharge Corona discharge

  • OMICRONPDSeminar2013

    OMICRON 1.7

    Internal PD

    Internal discharge in laminated material

    Treeing

    Cavity / void discharge

    PD classification

    Semicon layer protrusion(stress concentration at the tip)

    Void (field strength doubling)

    Lines ofelectrical field

    En = 2