Top Banner
BRS2111(1.6 M) Outdoor Power System 1 Telecom Power RBS2111 (1.6M) Outdoor System NTBU
23
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

1

Telecom Power RBS2111 (1.6M)

Outdoor System

NTBU

Page 2: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

21

Telecom Power System

Telecom Power SystemTelecom Power System

AC

Distribution U

nit

Rectifier # 1

Control Supervisory Unit (CSU)

LOA

D (Sw

itch ,AD

SL…E.T.C

.)

Output D

C D

istribution Unit

LVDS

Rectifier # 3

Rectifier # 2

Rectifier # N

Battery

AC Input

Generator

U.P.S

Page 3: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

3

ContentsSystem Overview

Main Features /Configuration

Outdoor Cabinet type (1.6 M)

Power Distribution configuration (AC,Surge , DC Load , Battery.

Rectifier Power shelf configuration

Rectifier module specification (DP2700)

New Smart CSU controller with LCD Display

System Function Introduction

Delta Remote/Monitor function

-- NRMS monitor software (RS-232 port)

-- Web Server/ SNMP function (Optional)

Q&A

Page 4: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

4

Delta DPS 2700 Series Power System

Main Features:AC Input: Optional for three conditions

1. 220Vac, Single phase (Already) 2. 380Vac, Three phases / Five Wire ( Y Connection)

System Capacity: -54Vdc / 150A Max. IP Protect:Power Battery Space: IP54, Equipment Space: IP55DC Distribution: Load Breaker Configurations: Breaker (DIN rail ), Battery Breaker: ~125A Breaker, 2 Positions Max.LVDB *1 (Standard): 150A on Battery SideLVDL *1: 150A on Load SideRectifier: -54Vdc/50A (DPR2700) *3Controller: New Smart CSU with LCD Relay Output: Total 8 Positions, Customer DefinableLocal/Remote Monitoring and Control – NRMS software

− Local Access: By NRMS via RS232 Interface− Internet Web Server Function: By Web Server Software/SNMP via RJ45 Interface

(Optional)System Dimension (W*D*H): 55.1” x 29.6” x 29.6” inch / 1600 x 750 x 750mmOperating Temperature: 0℃~+55℃(32℉~131℉)

Page 5: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

5PDU (Several Configurations)

Rectifier ESR-48/56A

Battery & Base

New Smart CSU (Main Board))

New Smart CSU (Relay Board))

19” Rectifier Shelf (SB-05N/HG A )

CCU (Climate Control Unit )

Fan Tray

Page 6: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

6

RBS2111 Outdoor System Drawing

Page 7: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

7

Delta Power System Drawing

Page 8: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

8

Dimension: W750mm * D750mm * H1600mmIP54, two-walled aluminum alloy (5052-H32) constructions (Cabinets)Enclosure/Plinth’s color: Ericsson LMY 904, (NCS2502)Plinth: Steel with powder coating Eyebolts inside removable roof

W

H

D

Delta P/N: ESOA150-ABC01

Estimated Weight: 113 Kg (with Power system)

RBS2111 (1.6M) Outdoor System Overviews

Page 9: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

9

Air filter

Fan Tray mounted on inside of Roof

Power system

Changeover SwitchClimate Control Unit

(Battery excluded in cabinets)

2nd Battery ShelfMax. Space suitable forCSB TPX122200 * 4pcs

(Battery excluded in cabinets)

1st Battery ShelfMax. Space suitable forCSB TPX122200 * 4pcs

DC Light mounted on inside of Frame

Smoke Sensor

Humidity Sensor

Genset Socket, 32A 3N~(R,S,T,N ,PE)

RBS2111 (1.6 M) Configurations

Page 10: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

10

3pcs MG32A 3-holeFor cable range (OD): 5~10mm

1pce MG25A 1-holeFor cable range (OD): 10~16mm

1pce MG32A 1-hole Cable Gland For cable range (OD): 15~22mm

4pcs of bottom cable entries reserved

3pcs MG32A 3-hole Cable Gland For cable range (OD): 5~10mmFor AC Terminations

1pce MG25A 1-hole Cable Gland For cable range (OD): 12~16mmFor DC grounding cable

5pcs of Side cable entries reservedRBS2111 (1.6M) Cable Entries

Page 11: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

11

Grounding BUS Bar4pcs M6 insert nuts pre-installed fixed on plinth

Loosen screws opening plinth cover

Grounding bus bar Location and Grounding cable path

Page 12: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

12

Plate (1pcs):Pre-install on right sideDesign to block unused side

RBS2111 (1.6M) AC Cable Entry on Both Sides

AC cables pass through left side of plinth.

New requirement:AC cables can pass through right side of plinth.

Page 13: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

13

Cabinet Mountings

600

83

705

Anchor Pattern and Footprint 15mm X 4

: Footprint Area

35

550

71283

35

Installation template (1pcs) for RBS2111 system along with first shipment

(2.1M and 1.6M systems are the same template.)

Page 14: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

14

Recommended Spare Parts & Part Numbers

 

RBS 2111 1.6MESOA150-ABC01

Remark

CU-18A A-SClimate Control Unit V

3790335100-SController(NCSU)-LCD Display V

5505602118-SController(NCSU)-Main Board V

ESR-48/56A A-SRectifier 2700W (DPR2700) V

3790335000Temperature Sensor Cable 3M V

EX-F01 B-SFan Tray V

EX-H01 A-SHeat Exchanger 22W/K

(Delta HEX)NA

Air Filter G33243139500 V

Heat Exchanger160W/K

50400000196NA

Model NameSpare parts(Delta P/N)

Page 15: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

15

SMR Shelf 19” H type

SB-05N/HG A DPS 2700 shelf 54V/150A

W x H x D=19 x 1.7 x 11.7 inch =483 x 44 x 297.8 mm

Page 16: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

16

Features and Benefits-48V/41.7A, Output; Max. Power 2000W

Wide Input Voltage Range (90V~300V)

Power Factor Correction (>0.99)

Hot-pluggable, All Connectors are at the rear

Compact Size

≅ 24W/in3 (48V) Power Density

Dimension:42mm/1U(H)*125.5mm/2.8U(W)*268mm(D)

Light weight:1.64 Kg (4.4lb)

Horizontal(1U)/Vertical(2.8U) Models Available

High Efficiency: >91% (48V)

Fan cooling and Easy replaceable fan design

Operation temp.:-5oC~+65oC

UL/CUL,TUV/CE Certificated

DP 2000 Series Rectifier

Page 17: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

17

Rectifier - Interface

I/O ConnectorOutputSignalInput

Load Sharing Bus IBUSD2

ID digitalIDDD1

ID analogIDAC2

Short pin for well connectionINHC1

Communication groundCGNDB1

RS 485 + communicationRS485+A2

RS 485 – communicationRS485-B2

Signal ground SGNDOA1

DC Output “+”VO+P8-P10

DC Output “-”VO-P5-P7

Precharge VOPP4

DescriptionSignal Pin Number

AC main, frame groundFGP3

AC main, N terminalAC_NP2

AC main, L terminal AC_LP1

DescriptionSignal Pin Number

Page 18: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

18

RS-485

New Smart CSU: DPS 2700 Series

Configuration,Supervision Terminal Interface

Web/SNMP Card

Ethernet

Configuration,Supervision

(web browser)

54Vdc/50A With SMR

AnalogSignal Detection

LCD Display

RS-485 X 3 With SMR

RS-485 With SMR

AnalogI.D address

Page 19: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

19

Easy integration with most Delta power systemsModular system controllerUser friendly operating interface

Large 128 x 64 pixel LCD Display Entry of alarm and system parameters from keypad

High reliable RS-485 communication with RectifierEasy system expansion

Easy extendable custom-design I/O boardComplete function support

More then 100 system events logTemperature & Voltage compensation chargingSmart Battery managementGreen Function

Different possibilities for remote monitoring1 outside communication port (RS-232) DB9Local Access monitoring & ControlWeb Server Function (RJ-45)

Power System Controller – New Smart CSU

User Interface

Page 20: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

20

Delta Power System Monitoring & Control

Build in HTTP Web Server

AC Distribution Rectifiers

DC Distribution Battery Management

Environment Data

Acquisition

Control &Supervisory

Unit

Client User Client User

Internet

Telecom Power Manage Program

Local

Client User

Mini USB

Page 21: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

21

Local Access

Mini USB

NRMS Monitor software

Page 22: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

22

Web Server Function and Feature (Optional)Features:

Applied in TCP/IP Internet/Intranet Environment

Complete Supervising to Power System

User-friendly Graphic Interface

Dynamic information presentation

Password function

Multi Language Support

Microsoft Explorer and Netscape SupportMain Screen

StatusParameter Setting

Alarm Configuration

Page 23: 01 3 rbs2111 1-6 m od system

BRS2111(1.6 M) Outdoor Power System

23