Top Banner
SR GR DR Running times (Control) Operating range Degree of protection 20 Nm 40 Nm < 90 Nm AC/DC 24 V 90 s open-close, 3-point IP54 SR24A-5 150 s open-close GR24A-5 DR24A-5 DR24A-7 AC 230 V 90 s open-close, 3-point SR230A-5 150 s open-close GR230A-5 DR230A-5 DR230A-7 Flange ISO 7005-2 EN 1092-2 PN 6, 10 and 16 T max =120°C Range of use closed and open circuits (pH > 7) 2-way, with wafer type PN DN [mm] k vmax [m 3 /h] ∆ps [kPa] ∆ps [kPa] ∆ps [kPa] D625N 6 / 10 / 16 25 50 1200 1200 D632N 6 / 10 / 16 32 55 D640N 6 / 10 / 16 40 65 D650N 6 / 10 / 16 50 100 D665N 6 / 10 / 16 65 170 1200 D680N 6 / 10 / 16 80 260 1200 1200 D6100N 6 / 10 / 16 100 520 D6125N 6 / 10 / 16 125 880 1200 Butterfly Valves. Open-close, Standard actuators – flange Subject to technical changes.
8

ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Aug 08, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Subject to technical modifications

Damper actuators

LM..A 2) NM..A 2) SM..A 2) GM..A 2)

5 Nm 10 Nm 20 Nm 40 Nm

For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2

Open-close actuators

AC/DC 24 V LM24A NM24A SM24A GM24A

with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S

AC 230 V LM230A NM230A SM230A GM230A

with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA

AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR

AC 230 V LM230ASR NM230ASR SM230ASR

Parameterisable actuators parameterisable 1)

AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF

Technical data

Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm

Running time 150 s / 90°

Manual override Gear disengagement with push button, can be locked

Connection Cable 1 m / Terminals

Direction of rotation Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s

Degree of protection IP 54

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection

Other versions on request.

Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..

Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V

U = DC 2...10 VY = Control signalU = Measuring voltage

Y = DC 0...10 VU = DC 2...10 V

Direction of rotation

1

0

1

2 3

1

0

T

~

N L

+

0...100%

S1 S2 S3

1

2 3

0

1

0

T

~

N

L

+

0...100%

S1 S2 S3

Y

U

1 32 5

T

~

+

Y

U

1 32 5

1

2

N L

T

SG..24

Technical data sheet SR24A-5

Rotary actuator for rotary valves and butterfly valves• Nominaltorque20Nm• NominalvoltageAC/DC24V• ControlOpen-close,3-point

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 2.5 W Power consumption in rest position 0.2 W Power consumption for wire sizing 5.5 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 20 Nm Manual override Gear disengagement with push-button, can be

locked Running time motor 90 s / 90° Sound power level motor max. 45 dB(A) Position indication Mechanically, integrated, two-section

Safety Protection class IEC/EN III Safety extra-low voltage Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2004/108/EC Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight approx. 1 kg

Safety notes

!• Thisdevicehasbeendesignedforuseinstationaryheating,ventilationandair

conditioning systems and is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Onlyauthorisedspecialistsmaycarryoutinstallation.Allapplicablelegalorinstitutional installation regulations must be complied during installation.

• Theswitchforchangingthedirectionofrotationmayonlybeoperatedbyauthorisedspecialists. The direction of rotation must not in particular be reversed in a frost protection circuit.

• Thedevicemayonlybeopenedatthemanufacturer‘ssite.Itdoesnotcontainanyparts that can be replaced or repaired by the user.

• Thecablesmustnotberemovedfromthedevice.• Thedevicecontainselectricalandelectroniccomponentsandisnotallowedtobe

disposed of as household refuse. All locally valid regulations and requirements must be observed.

www.belimo.eu SR24A-5•en-gb•2014-08-13•subjecttochanges 1

Technical data sheet GR24A-5

Rotary actuator for rotary valves and butterfly valves• Nominaltorque40Nm• NominalvoltageAC/DC24V• ControlOpen-close

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 4 W Power consumption in rest position 2 W Power consumption for wire sizing 6 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 40 Nm Manual override Gear disengagement with push-button, can be

locked Running time motor 150 s / 90° Sound power level motor max. 45 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety extra-low voltage Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2004/108/EC Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight approx. 1.85 kg

Safety notes

!• Thisdevicehasbeendesignedforuseinstationaryheating,ventilationandair

conditioning systems and is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Onlyauthorisedspecialistsmaycarryoutinstallation.Allapplicablelegalorinstitutional installation regulations must be complied during installation.

• Theswitchforchangingthedirectionofrotationmayonlybeoperatedbyauthorisedspecialists. The direction of rotation must not in particular be reversed in a frost protection circuit.

• Thedevicemayonlybeopenedatthemanufacturer‘ssite.Itdoesnotcontainanyparts that can be replaced or repaired by the user.

• Thecablesmustnotberemovedfromthedevice.

www.belimo.eu GR24A-5•en-gb•2014-08-13•subjecttochanges 1

Technical data sheet DR24A-5

Rotary actuator for butterfly valves• Nominal torque Max. 90 Nm (not

constant)• Nominal voltage AC/DC 24 V• Control Open-close

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 4 W Power consumption in rest position 2 W Power consumption for wire sizing 6 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Nominal torque Max. 90 Nm (not constant) Manual override with push-button, can be locked Running time motor 150 s / 90° Sound power level, motor 45 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity Max. 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight 4.2 kg

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Outdoor application: only possible in case that no (sea)water, snow, ice, insolation or aggressive gases interfere directly with the actuator and that is ensured that the ambient conditions remain at any time within the thresholds according to the data sheet.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.

• The switch for changing the direction of rotation may not be adjusted.• The angle of rotation is not permitted to be subjected to mechanical limitation. It is

forbidden to alter the mechanical end stops.• The device may only be opened at the manufacturer’s site. It does not contain any

parts that can be replaced or repaired by the user.

www.belimo.com DR24A-5 • en-gb • 2018-06-06 • subject to changes 1

SR GR DR

Running times

(Control)Operating range

Degree of protection

20 Nm 40 Nm < 90 Nm

AC/DC 24 V 90 s open-close, 3-point

IP54

SR24A-5

150 s open-close

GR24A-5

DR24A-5

DR24A-7

AC 230 V 90 s open-close, 3-point SR230A-5

150 s open-close

GR230A-5

DR230A-5

DR230A-7

Flange ISO 7005-2 EN 1092-2

PN 6, 10 and 16Tmax=120°C

Range of useclosed and open circuits (pH > 7)

2-way, with wafer type

PN DN[mm]

kvmax

[m3/h]∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

D625N 6 / 10 / 16 25 50 1200 1200

D632N 6 / 10 / 16 32 55

D640N 6 / 10 / 16 40 65

D650N 6 / 10 / 16 50 100

D665N 6 / 10 / 16 65 170 1200

D680N 6 / 10 / 16 80 260 1200 1200

D6100N 6 / 10 / 16 100 520

D6125N 6 / 10 / 16 125 880 1200

Technical data sheet D6..N

Butterfly valve with Wafer types• For open and closed cold and warm

water systems• For switching heat generators or

cooling machines on and off

Type overview

Type DN[ ]

PN[ ]

kvmax[ m³/h]

D625N 25 6 / 10 / 16 45D632N 32 6 / 10 / 16 55D640N 40 6 / 10 / 16 70D650N 50 6 / 10 / 16 90D665N 65 6 / 10 / 16 180D680N 80 6 / 10 / 16 300D6100N 100 6 / 10 / 16 580D6125N 125 6 / 10 / 16 820D6150N 150 6 / 10 / 16 1600D6350N 350 10 / 16 10900D6400N 400 16 14200D6450N 450 16 18800D6500N 500 16 24100D6600N 600 16 37300D6700N 700 16 42800

Technical data

Functional data Media Cold and warm water, water with glycol up to max. 50% vol.

Medium temperature -20...120°C Permissible pressure ps 1600 kPa Leakage rate Leakage rate A, tight (EN 12266-1) Pipe connector Flange PN 6/10/16 (according to ISO 7005-2)

(DN 25...150)Flange PN 10/16 (according to ISO 7005-2) (DN 350)Flange PN 16 (according to ISO 7005-2) (DN 400...700)

Angle of rotation 90° Installation position Upright to horizontal (in relation to the stem) Suitable connection flange In accordance with ISO 7005-2 and EN 1092-2 Maintenance Maintenance-free

Materials Housing EN-JS1030 (GGG 40), epoxy-powder coating Closing element 1.4301 (stainless steel) Stem 1.4005 (stainless steel) Stem seal O-ring EPDM Stem bearing RPTFE Seat EPDM

Safety notes

!• The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

www.belimo.eu D6..N • en-gb • 2017-02-15 • subject to changes 1

The types D6200N, D6250N and D6300N have been replaced by the types D6200W, D6250W and D6300W. For technical data please check the datasheet D6..W.

Butterfly Valves. Open-close, Standard actuators – flange

Subject to technical changes.

Page 2: ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Subject to technical modifications

Damper actuators

LM..A 2) NM..A 2) SM..A 2) GM..A 2)

5 Nm 10 Nm 20 Nm 40 Nm

For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2

Open-close actuators

AC/DC 24 V LM24A NM24A SM24A GM24A

with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S

AC 230 V LM230A NM230A SM230A GM230A

with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA

AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR

AC 230 V LM230ASR NM230ASR SM230ASR

Parameterisable actuators parameterisable 1)

AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF

Technical data

Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm

Running time 150 s / 90°

Manual override Gear disengagement with push button, can be locked

Connection Cable 1 m / Terminals

Direction of rotation Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s

Degree of protection IP 54

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection

Other versions on request.

Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..

Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V

U = DC 2...10 VY = Control signalU = Measuring voltage

Y = DC 0...10 VU = DC 2...10 V

Direction of rotation

1

0

1

2 3

1

0

T

~

N L

+

0...100%

S1 S2 S3

1

2 3

0

1

0

T

~

N

L

+

0...100%

S1 S2 S3

Y

U

1 32 5

T

~

+

Y

U

1 32 5

1

2

N L

T

SG..24

Technical data sheet GR24A-5

Rotary actuator for rotary valves and butterfly valves• Nominaltorque40Nm• NominalvoltageAC/DC24V• ControlOpen-close

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 4 W Power consumption in rest position 2 W Power consumption for wire sizing 6 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 40 Nm Manual override Gear disengagement with push-button, can be

locked Running time motor 150 s / 90° Sound power level motor max. 45 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety extra-low voltage Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2004/108/EC Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight approx. 1.85 kg

Safety notes

!• Thisdevicehasbeendesignedforuseinstationaryheating,ventilationandair

conditioning systems and is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Onlyauthorisedspecialistsmaycarryoutinstallation.Allapplicablelegalorinstitutional installation regulations must be complied during installation.

• Theswitchforchangingthedirectionofrotationmayonlybeoperatedbyauthorisedspecialists. The direction of rotation must not in particular be reversed in a frost protection circuit.

• Thedevicemayonlybeopenedatthemanufacturer‘ssite.Itdoesnotcontainanyparts that can be replaced or repaired by the user.

• Thecablesmustnotberemovedfromthedevice.

www.belimo.eu GR24A-5•en-gb•2014-08-13•subjecttochanges 1

Technical data sheet DRC24A-7

Rotary actuator for butterfly valves• Nominal torque Max. 90 Nm (not

constant)• Nominal voltage AC/DC 24 V• Control Open-close• Running time motor 35 s

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 9 W Power consumption in rest position 2 W Power consumption for wire sizing 12 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Nominal torque Max. 90 Nm (not constant) Manual override with push-button, can be locked Running time motor 35 s / 90° Sound power level, motor 45 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity Max. 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F07

Weight Weight 4.1 kg

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Outdoor application: only possible in case that no (sea)water, snow, ice, insolation or aggressive gases interfere directly with the actuator and that is ensured that the ambient conditions remain at any time within the thresholds according to the data sheet.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.

• The switch for changing the direction of rotation may not be adjusted.• The angle of rotation is not permitted to be subjected to mechanical limitation. It is

forbidden to alter the mechanical end stops.• The device may only be opened at the manufacturer’s site. It does not contain any

parts that can be replaced or repaired by the user.

www.belimo.com DRC24A-7 • en-gb • 2018-06-06 • subject to changes 1

Technical data sheet PRCA-S2-T

Rotary actuator for butterfly valves• Nominal torque 160 Nm• Nominal voltage AC 24...240 V / DC

24...125 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 24...240 V / DC 24...125 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...264 V / DC 19.2...137.5 V Power consumption in operation 20 W Power consumption in rest position 6 W Power consumption for wire sizing with 24 V 20 VA / with 230 V 52 VA Auxiliary switch 2 x SPDT, 1 x 10° / 1 x 0...90° (ex works 85°) Switching capacity auxiliary switch 1 mA...3 (0.5 inductive) A, AC 250 V Connection supply / control Terminals 2.5 mm² Connection auxiliary switch Terminals 2.5 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor 160 Nm Manual override with hand crank, can be fixed in any position Running time motor 35 s / 90° Motor running time variable 30...120 s Sound power level motor 68 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN II reinforced insulation Protection class UL II reinforced insulation Protection class auxiliary switch IEC/EN II reinforced insulation Degree of protection IEC/EN IP66 + IP67 Degree of protection NEMA/UL NEMA 4X, UL Enclosure Type 4X EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply 4 kV Rated impulse voltage auxiliary switch 2.5 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F07 (F05 only with accessory)

Weight Weight 5.8 kg

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.

www.belimo.eu PRCA-S2-T • en-gb • 2017-03-21 • subject to changes 1

GRC DRC PRC

Runningtimes

(Control)Operating range

Degree of protection

40 Nm < 90 Nm 160 Nm

AC/DC 24 V35 s open-close

IP54 / IP66

GRC24A-5

DRC24A-5

DRC24A-7

AC 230 V35 s open-close

GRC230A-5

DRC230A-5

DRC230A-7

AC 24...240 VDC 24...125 V

35 s1) open-close, 3-point, terminal connection IP66 / IP67

PRCA-S2-T

PRCA-S2-T-200

PRCA-S2-T-250

Flange ISO 7005-2EN 1092-2

PN 6, 10 and 16Tmax=120°C

Range of useclosed and open circuits (pH > 7)

2-way, with wafer type

PN DN[mm]

kvmax

[m3/h]∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

D625N 6 / 10 / 16 25 50 1200

D632N 6 / 10 / 16 32 55

D640N 6 / 10 / 16 40 65

D650N 6 / 10 / 16 50 100

D665N 6 / 10 / 16 65 170

D680N 6 / 10 / 16 80 260 1200 1200 1200

D6100N 6 / 10 / 16 100 520

D6125N 6 / 10 / 16 125 880 1200

D6150N 6 / 10 / 16 150 1400

D6200W 6 / 10 / 16 200 2200

D6250W 6 / 10 / 16 250 4200

D6300W 6 / 10 / 16 300 5700 1200

Auxi

liary

sw

itch

SPDT

2

Technical data sheet D6..N

Butterfly valve with Wafer types• For open and closed cold and warm

water systems• For switching heat generators or

cooling machines on and off

Type overview

Type DN[ ]

PN[ ]

kvmax[ m³/h]

D625N 25 6 / 10 / 16 45D632N 32 6 / 10 / 16 55D640N 40 6 / 10 / 16 70D650N 50 6 / 10 / 16 90D665N 65 6 / 10 / 16 180D680N 80 6 / 10 / 16 300D6100N 100 6 / 10 / 16 580D6125N 125 6 / 10 / 16 820D6150N 150 6 / 10 / 16 1600D6350N 350 10 / 16 10900D6400N 400 16 14200D6450N 450 16 18800D6500N 500 16 24100D6600N 600 16 37300D6700N 700 16 42800

Technical data

Functional data Media Cold and warm water, water with glycol up to max. 50% vol.

Medium temperature -20...120°C Permissible pressure ps 1600 kPa Leakage rate Leakage rate A, tight (EN 12266-1) Pipe connector Flange PN 6/10/16 (according to ISO 7005-2)

(DN 25...150)Flange PN 10/16 (according to ISO 7005-2) (DN 350)Flange PN 16 (according to ISO 7005-2) (DN 400...700)

Angle of rotation 90° Installation position Upright to horizontal (in relation to the stem) Suitable connection flange In accordance with ISO 7005-2 and EN 1092-2 Maintenance Maintenance-free

Materials Housing EN-JS1030 (GGG 40), epoxy-powder coating Closing element 1.4301 (stainless steel) Stem 1.4005 (stainless steel) Stem seal O-ring EPDM Stem bearing RPTFE Seat EPDM

Safety notes

!• The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

www.belimo.eu D6..N • en-gb • 2017-02-15 • subject to changes 1

The types D6200N, D6250N and D6300N have been replaced by the types D6200W, D6250W and D6300W. For technical data please check the datasheet D6..W.

1) 30...120 s variable.

Subject to technical changes.

Butterfly Valves. Open-close, Fast runners – flange

Page 3: ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Subject to technical modifications

Damper actuators

LM..A 2) NM..A 2) SM..A 2) GM..A 2)

5 Nm 10 Nm 20 Nm 40 Nm

For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2

Open-close actuators

AC/DC 24 V LM24A NM24A SM24A GM24A

with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S

AC 230 V LM230A NM230A SM230A GM230A

with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA

AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR

AC 230 V LM230ASR NM230ASR SM230ASR

Parameterisable actuators parameterisable 1)

AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF

Technical data

Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm

Running time 150 s / 90°

Manual override Gear disengagement with push button, can be locked

Connection Cable 1 m / Terminals

Direction of rotation Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s

Degree of protection IP 54

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection

Other versions on request.

Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..

Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V

U = DC 2...10 VY = Control signalU = Measuring voltage

Y = DC 0...10 VU = DC 2...10 V

Direction of rotation

1

0

1

2 3

1

0

T

~

N L

+

0...100%

S1 S2 S3

1

2 3

0

1

0

T

~

N

L

+

0...100%

S1 S2 S3

Y

U

1 32 5

T

~

+

Y

U

1 32 5

1

2

N L

T

SG..24

Technical data sheet SRF24A-5

Rotary actuator with emergency control function for ball valves and butterfly valves• Nominaltorque20Nm• NominalvoltageAC/DC24V• ControlOpen-close• Deenergisedclosed(NC)

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 5 W Power consumption in rest position 2.5 W Power consumption for wire sizing 7.5 VA Connection supply / control Cable 1 m, 2 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 20 Nm Torque spring return Min. 20 Nm Direction of rotation spring-return Deenergised NC, valve closed (A - AB = 0%) Manual override By means of hand crank and locking switch Angle of rotation 90° Running time motor 75 s / 90° Running time emergency setting position <20 s / 90° Sound power level motor max. 45 dB(A) Position indication Mechanical Service life Min. 60,000 emergency positions

Safety Protection class IEC/EN III Safety extra-low voltage Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2004/108/EC Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight approx. 2.3 kg

Safety notes

!• Thisdevicehasbeendesignedforuseinstationaryheating,ventilationandair

conditioning systems and is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Onlyauthorisedspecialistsmaycarryoutinstallation.Allapplicablelegalorinstitutional installation regulations must be complied during installation.

• Thedevicemayonlybeopenedatthemanufacturer‘ssite.Itdoesnotcontainanyparts that can be replaced or repaired by the user.

• Thecablesmustnotberemovedfromthedevice.

www.belimo.eu SRF24A-5•en-gb•2014-10-15•subjecttochanges 1

Technical data sheet GRK24A-5

SuperCap rotary actuator with emergeny control function and extended functionalities for rotary valves and butterfly valves• Nominal torque 40 Nm• Nominal voltage AC/DC 24 V• Control Open-close• Design life SuperCaps: 15 years

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 11 W Power consumption in rest position 3 W Power consumption for wire sizing 21 VA Power consumption for wire sizing note Imax 20 A @ 5 ms Connection supply / control Cable 1 m, 2 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 40 Nm Setting emergency setting position (POP) NC / NO, adjustable (POP rotary button) Manual override with push-button Running time motor 150 s / 90° Running time emergency control position 35 s / 90° Running time emergency setting position

note<35 s @ 0...50 °C

Sound power level motor 52 dB(A) Sound power level emergency control

position61 dB(A)

Position indication Mechanical

Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight 2.8 kg

Terms Abbreviations POP = Power off position / emergency setting positionCPO = Controlled power off / controlled emergency control functionPF = Power fail delay time / bridging time

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

www.belimo.eu GRK24A-5 • en-gb • 2017-03-09 • subject to changes 1

Technical data sheet DRK24A-5

SuperCap rotary actuator with emergeny control function and extended functionalities for butterfly valves• Nominal torque Max. 90 Nm (not

constant)• Nominal voltage AC/DC 24 V• Control Open-close• Design life SuperCaps: 15 years

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 11 W Power consumption in rest position 2 W Power consumption for wire sizing 20 VA Power consumption for wire sizing note Imax 20 A @ 5 ms Connection supply / control Cable 1 m, 2 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Nominal torque Max. 90 Nm (not constant) Setting emergency setting position (POP) NC / NO, adjustable (POP rotary button) Manual override with push-button Running time motor 150 s / 90° Running time emergency control position 35 s / 90° Running time emergency setting position

note<35 s @ 0...50 °C

Sound power level, motor 52 dB(A) Sound power level emergency control

position61 dB(A)

Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50 °C Non-operating temperature -40...80 °C Ambient humidity Max. 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight 4.1 kg

Terms Abbreviations POP = Power off position / emergency setting positionCPO = Controlled power off / controlled emergency control functionPF = Power fail delay time / bridging time

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

www.belimo.com DRK24A-5 • en-gb • 2018-08-30 • subject to changes 1

Technical data sheet PRKCA-BAC-S2-T

Rotary actuator for butterfly valves• Torque motor 160 Nm• Nominal voltage AC 24...240 V / DC

24...125 V• Control modulating, communicative,

hybrid mode• with 2 integrated auxiliary switches• Conversion of sensor signals• Communication via BACnet MS/TP,

Modbus RTU, Belimo-MP-Bus or conventional control

Technical data

Electrical data Nominal voltage AC 24...240 V / DC 24...125 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...264 V / DC 19.2...137.5 V Power consumption in operation 52 W Power consumption in rest position 7 W Power consumption for wire sizing with 24 V 54 VA / with 230 V 68 VA Power consumption for wire sizing note Imax 20 A @ 5 ms Auxiliary switch 2 x SPDT, 1 x 10° / 1 x 0...90° (ex works 85°) Switching capacity auxiliary switch 1 mA...3 (0.5 inductive) A, AC 250 V Connection supply Terminals 2.5 mm² Connection control Terminals 1.5 mm² Connection auxiliary switch Terminals 2.5 mm² Parallel operation Yes (note the performance data)

Functional data Nominal torque 160 Nm Communicative control BACnet MS/TP (ex works)

Modbus RTUMP-Bus

Operating range Y DC 2...10 V Input Impedance 100 kΩ Operating range Y variable DC 0.5...10 V

4...20 mA Position feedback U DC 2...10 V Position feedback U note Max. 0.5 mA Position feedback U variable DC 0.5...10 V Setting emergency setting position (POP) 0...100%, adjustable (ex works 0%) Bridging time (PF) variable 0...10 s (ex works 2s) Position accuracy ±5% Manual override with hand crank, can be fixed in any position Running time motor 35 s / 90° Running time motor variable 30...120 s Running time emergency control position 30 s / 90° Sound power level Motor 68 dB(A) Sound power level emergency control

position61 dB(A)

Position indication Mechanically (integrated)

Safety Protection class IEC/EN II reinforced insulation Protection class UL II reinforced insulation Protection class auxiliary switch IEC/EN II reinforced insulation Degree of protection IEC/EN IP66/67 Degree of protection NEMA/UL NEMA 4X, UL Enclosure Type 4X EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA Rated impulse voltage supply 4 kV Rated impulse voltage control 0.8 kV Rated impulse voltage auxiliary switch 2.5 kV

www.belimo.com PRKCA-BAC-S2-T • en-gb • 2018-05-07 • subject to changes 1

SRF GRK DRK PRK

Runningtimes

(Control)Operatingrange

Degree of protection

20 Nm 40 Nm < 90 Nm 160 Nm

AC/DC 24 V75 s open-close IP54

SRF24A-5

SRF24A- S2-5

150 s open-close IP54

GRK24A-5

DRK24A-5

DRK24A-7

AC 24...240 VDC 24...125 V

75 s open-close IP54SRFA-5

SRFA-S2-5

35 s1)open-close, 3-point, modulating, terminal connection

IP66/ IP67PRKCA- BAC-S2-T

Emer

genc

y co

ntro

l fun

ctio

n

Auxi

liary

sw

itch

SPDT

2

2

2

Subject to technical modifications

Spring return actuators

TF.. LF.. NF..A SF..A EF..A

2.5 Nm 4 Nm 10 Nm 20 Nm 30 Nm

For air damper sizes up to approx. 0.5 m2 0.8 m2 2 m2 4 m2 6 m2

Open-close actuators

AC/DC 24 V TF24 LF24 NF24A SF24A EF24A

with auxiliary switch, 1 x SPDT TF24-S LF24-S

with auxiliary switch, 2 x SPDT NF24A-S2 SF24A-S2 EF24A-S2

AC 230 V TF230 LF230 NF230A SF230A EF230A

with auxiliary switch, 1 x SPDT TF230-S LF230-S

with auxiliary switch, 2 x SPDT NF230A-S2 SF230A-S2 EF230A-S2

AC 24...240 V / DC 24...125 V NFA SFA

with auxiliary switch, 2 x SPDT NFA-S2 SFA-S2

3-point actuator

AC 24 V TF24-3 NF24A-3 SF24A-3

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, max. 1 mA

AC/DC 24 V Operating range DC 2...10 V TF24-SR LF24-SR NF24A-SR SF24A-SR EF24A-SR

with auxiliary switch, 2 x SPDT NF24A-SR-S2 SF24A-SR-S2 EF24A-SR-S2

Operating range DC 0...10 V NF24A-SZ SF24A-SZ

with auxiliary switch, 2 x SPDT NF24A-SZ-S2 SF24A-SZ-S2

AC 230 V Operating range DC 2...10 V TF230-SR

Parameterisable actuators parameterisable 1)

AC/DC 24 V TF24-MFT LF24-MFT NF24A-MF SF24A-MF EF24A-MF

Technical data

Damper spindle 6...12 mm 8...16 mm 10...25.4 mm 10...25.4 mm 12...26.7 mm

Running time Motor

Emergency control function

<75 s / 90°(SR: 150 s / 90° )

<25 s / 90°

40...75 s / 90°(SR: 150 s / 90° )

20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR: 150 s / 90° )

<20 s / 90°

Manual override Hand crank

Connection Cable 1 m, PVC Cable FRNC 1 m

Direction of rotation Can be selected by mounting L / R

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level MotorEmergency control function

≤50 dB(A) @ 75 s=62 dB(A) @ 25 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

≤45 dB(A) @ 75 s=62 dB(A) @ 20 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

Degree of protection IP 42 IP 54 IP 54 2)

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) EF..: IP 66 versions on request.

Other versions on request.

Subject to technical modifications

Spring return actuators

TF.. LF.. NF..A SF..A EF..A

2.5 Nm 4 Nm 10 Nm 20 Nm 30 Nm

For air damper sizes up to approx. 0.5 m2 0.8 m2 2 m2 4 m2 6 m2

Open-close actuators

AC/DC 24 V TF24 LF24 NF24A SF24A EF24A

with auxiliary switch, 1 x SPDT TF24-S LF24-S

with auxiliary switch, 2 x SPDT NF24A-S2 SF24A-S2 EF24A-S2

AC 230 V TF230 LF230 NF230A SF230A EF230A

with auxiliary switch, 1 x SPDT TF230-S LF230-S

with auxiliary switch, 2 x SPDT NF230A-S2 SF230A-S2 EF230A-S2

AC 24...240 V / DC 24...125 V NFA SFA

with auxiliary switch, 2 x SPDT NFA-S2 SFA-S2

3-point actuator

AC 24 V TF24-3 NF24A-3 SF24A-3

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, max. 1 mA

AC/DC 24 V Operating range DC 2...10 V TF24-SR LF24-SR NF24A-SR SF24A-SR EF24A-SR

with auxiliary switch, 2 x SPDT NF24A-SR-S2 SF24A-SR-S2 EF24A-SR-S2

Operating range DC 0...10 V NF24A-SZ SF24A-SZ

with auxiliary switch, 2 x SPDT NF24A-SZ-S2 SF24A-SZ-S2

AC 230 V Operating range DC 2...10 V TF230-SR

Parameterisable actuators parameterisable 1)

AC/DC 24 V TF24-MFT LF24-MFT NF24A-MF SF24A-MF EF24A-MF

Technical data

Damper spindle 6...12 mm 8...16 mm 10...25.4 mm 10...25.4 mm 12...26.7 mm

Running time Motor

Emergency control function

<75 s / 90°(SR: 150 s / 90° )

<25 s / 90°

40...75 s / 90°(SR: 150 s / 90° )

20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR: 150 s / 90° )

<20 s / 90°

Manual override Hand crank

Connection Cable 1 m, PVC Cable FRNC 1 m

Direction of rotation Can be selected by mounting L / R

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level MotorEmergency control function

≤50 dB(A) @ 75 s=62 dB(A) @ 25 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

≤45 dB(A) @ 75 s=62 dB(A) @ 20 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

Degree of protection IP 42 IP 54 IP 54 2)

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) EF..: IP 66 versions on request.

Other versions on request.

Subject to technical modifications

SuperCap actuators

SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A

2 Nm 40 Nm 6 Nm 150 N 450 N

For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2

Open-close actuators

AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA

AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100

Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100

Parameterisable actuators parameterisable 1)

AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100

External SuperCap module

AC 230 V SKM230-T-B12.1

Technical data

Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm

Running time MotorEmergency control function

75 s / 90°15 s / 90°

150 s / 90°35 s / 90°

4 s / 90°4 s / 90°

120 s / 100 mm35 s / 100 mm

Manual override Gear disengage-ment with magnet

Gear disengagement with push button

Connection Terminals Cable 1 mDirection of rotation Selectable with

actuator 2)Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor

Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s

≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s

≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s

≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s

≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s

Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right

Other versions on request.

Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF

SKM230.. CM24K.. Open-close control modulating parameterisable

2 1

3

+

2 13 1N2L

T~

OUT 1 OUT 2 IN

CM24K.. CM24K.. AC 198 ... 264 V

50/60 Hz

–+

SKM230-T-B12

1 2 3

– +

L

R

L

R

1 2 3

1

0

– +

T

~

..-SR: Y = DC 0...10 V U = DC 2...10 V

..-SZ: Y = DC 0...10 V U = DC 0...10 V

Y = Control signalU = Measuring voltage

Y

U

1 32 5

T

~

+

Subject to technical modifications

SuperCap actuators

SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A

2 Nm 40 Nm 6 Nm 150 N 450 N

For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2

Open-close actuators

AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA

AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100

Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100

Parameterisable actuators parameterisable 1)

AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100

External SuperCap module

AC 230 V SKM230-T-B12.1

Technical data

Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm

Running time MotorEmergency control function

75 s / 90°15 s / 90°

150 s / 90°35 s / 90°

4 s / 90°4 s / 90°

120 s / 100 mm35 s / 100 mm

Manual override Gear disengage-ment with magnet

Gear disengagement with push button

Connection Terminals Cable 1 mDirection of rotation Selectable with

actuator 2)Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor

Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s

≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s

≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s

≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s

≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s

Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right

Other versions on request.

Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF

SKM230.. CM24K.. Open-close control modulating parameterisable

2 1

3

+

2 13 1N2L

T~

OUT 1 OUT 2 IN

CM24K.. CM24K.. AC 198 ... 264 V

50/60 Hz

–+

SKM230-T-B12

1 2 3

– +

L

R

L

R

1 2 3

1

0

– +

T

~

..-SR: Y = DC 0...10 V U = DC 2...10 V

..-SZ: Y = DC 0...10 V U = DC 0...10 V

Y = Control signalU = Measuring voltage

Y

U

1 32 5

T

~

+

Subject to technical modifications

SuperCap actuators

SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A

2 Nm 40 Nm 6 Nm 150 N 450 N

For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2

Open-close actuators

AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA

AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100

Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100

Parameterisable actuators parameterisable 1)

AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100

External SuperCap module

AC 230 V SKM230-T-B12.1

Technical data

Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm

Running time MotorEmergency control function

75 s / 90°15 s / 90°

150 s / 90°35 s / 90°

4 s / 90°4 s / 90°

120 s / 100 mm35 s / 100 mm

Manual override Gear disengage-ment with magnet

Gear disengagement with push button

Connection Terminals Cable 1 mDirection of rotation Selectable with

actuator 2)Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor

Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s

≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s

≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s

≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s

≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s

Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right

Other versions on request.

Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF

SKM230.. CM24K.. Open-close control modulating parameterisable

2 1

3

+

2 13 1N2L

T~

OUT 1 OUT 2 IN

CM24K.. CM24K.. AC 198 ... 264 V

50/60 Hz

–+

SKM230-T-B12

1 2 3

– +

L

R

L

R

1 2 3

1

0

– +

T

~

..-SR: Y = DC 0...10 V U = DC 2...10 V

..-SZ: Y = DC 0...10 V U = DC 0...10 V

Y = Control signalU = Measuring voltage

Y

U

1 32 5

T

~

+

Flange ISO 7005-2EN 1092-2

PN 6, 10 and 16Tmax=120°C

Range of useclosed and open circuits (pH > 7)

2-way, with wafer type

PN DN[mm]

kvmax

[m3/h]∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

D625N 6 / 10 / 16 25 50 1200 1200

D632N 6 / 10 / 16 32 55

D640N 6 / 10 / 16 40 65

D650N 6 / 10 / 16 50 100

D665N 6 / 10 / 16 65 170 1200

D680N 6 / 10 / 16 80 260 1200 1200 1200

D6100N 6 / 10 / 16 100 520

D6125N 6 / 10 / 16 125 880 1200

D6150N 6 / 10 / 16 150 1400

D6200W 6 / 10 / 16 200 2200

D6250W 6 / 10 / 16 250 4200

D6300W 6 / 10 / 16 300 5700 1200

Technical data sheet D6..N

Butterfly valve with Wafer types• For open and closed cold and warm

water systems• For switching heat generators or

cooling machines on and off

Type overview

Type DN[ ]

PN[ ]

kvmax[ m³/h]

D625N 25 6 / 10 / 16 45D632N 32 6 / 10 / 16 55D640N 40 6 / 10 / 16 70D650N 50 6 / 10 / 16 90D665N 65 6 / 10 / 16 180D680N 80 6 / 10 / 16 300D6100N 100 6 / 10 / 16 580D6125N 125 6 / 10 / 16 820D6150N 150 6 / 10 / 16 1600D6350N 350 10 / 16 10900D6400N 400 16 14200D6450N 450 16 18800D6500N 500 16 24100D6600N 600 16 37300D6700N 700 16 42800

Technical data

Functional data Media Cold and warm water, water with glycol up to max. 50% vol.

Medium temperature -20...120°C Permissible pressure ps 1600 kPa Leakage rate Leakage rate A, tight (EN 12266-1) Pipe connector Flange PN 6/10/16 (according to ISO 7005-2)

(DN 25...150)Flange PN 10/16 (according to ISO 7005-2) (DN 350)Flange PN 16 (according to ISO 7005-2) (DN 400...700)

Angle of rotation 90° Installation position Upright to horizontal (in relation to the stem) Suitable connection flange In accordance with ISO 7005-2 and EN 1092-2 Maintenance Maintenance-free

Materials Housing EN-JS1030 (GGG 40), epoxy-powder coating Closing element 1.4301 (stainless steel) Stem 1.4005 (stainless steel) Stem seal O-ring EPDM Stem bearing RPTFE Seat EPDM

Safety notes

!• The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

www.belimo.eu D6..N • en-gb • 2017-02-15 • subject to changes 1

The types D6200N, D6250N and D6300N have been replaced by the types D6200W, D6250W and D6300W. For technical data please check the datasheet D6..W.

1) 30...120 s variable. Actuator with mechanical emergency control function. Actuator with electrical emergency control function.

Subject to technical modifications

Spring return actuators

TF.. LF.. NF..A SF..A EF..A

2.5 Nm 4 Nm 10 Nm 20 Nm 30 Nm

For air damper sizes up to approx. 0.5 m2 0.8 m2 2 m2 4 m2 6 m2

Open-close actuators

AC/DC 24 V TF24 LF24 NF24A SF24A EF24A

with auxiliary switch, 1 x SPDT TF24-S LF24-S

with auxiliary switch, 2 x SPDT NF24A-S2 SF24A-S2 EF24A-S2

AC 230 V TF230 LF230 NF230A SF230A EF230A

with auxiliary switch, 1 x SPDT TF230-S LF230-S

with auxiliary switch, 2 x SPDT NF230A-S2 SF230A-S2 EF230A-S2

AC 24...240 V / DC 24...125 V NFA SFA

with auxiliary switch, 2 x SPDT NFA-S2 SFA-S2

3-point actuator

AC 24 V TF24-3 NF24A-3 SF24A-3

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, max. 1 mA

AC/DC 24 V Operating range DC 2...10 V TF24-SR LF24-SR NF24A-SR SF24A-SR EF24A-SR

with auxiliary switch, 2 x SPDT NF24A-SR-S2 SF24A-SR-S2 EF24A-SR-S2

Operating range DC 0...10 V NF24A-SZ SF24A-SZ

with auxiliary switch, 2 x SPDT NF24A-SZ-S2 SF24A-SZ-S2

AC 230 V Operating range DC 2...10 V TF230-SR

Parameterisable actuators parameterisable 1)

AC/DC 24 V TF24-MFT LF24-MFT NF24A-MF SF24A-MF EF24A-MF

Technical data

Damper spindle 6...12 mm 8...16 mm 10...25.4 mm 10...25.4 mm 12...26.7 mm

Running time Motor

Emergency control function

<75 s / 90°(SR: 150 s / 90° )

<25 s / 90°

40...75 s / 90°(SR: 150 s / 90° )

20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR: 150 s / 90° )

<20 s / 90°

Manual override Hand crank

Connection Cable 1 m, PVC Cable FRNC 1 m

Direction of rotation Can be selected by mounting L / R

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level MotorEmergency control function

≤50 dB(A) @ 75 s=62 dB(A) @ 25 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

≤45 dB(A) @ 75 s=62 dB(A) @ 20 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

Degree of protection IP 42 IP 54 IP 54 2)

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) EF..: IP 66 versions on request.

Other versions on request.

Subject to technical modifications

SuperCap actuators

SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A

2 Nm 40 Nm 6 Nm 150 N 450 N

For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2

Open-close actuators

AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA

AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100

Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100

Parameterisable actuators parameterisable 1)

AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100

External SuperCap module

AC 230 V SKM230-T-B12.1

Technical data

Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm

Running time MotorEmergency control function

75 s / 90°15 s / 90°

150 s / 90°35 s / 90°

4 s / 90°4 s / 90°

120 s / 100 mm35 s / 100 mm

Manual override Gear disengage-ment with magnet

Gear disengagement with push button

Connection Terminals Cable 1 mDirection of rotation Selectable with

actuator 2)Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor

Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s

≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s

≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s

≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s

≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s

Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right

Other versions on request.

Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF

SKM230.. CM24K.. Open-close control modulating parameterisable

2 1

3

+

2 13 1N2L

T~

OUT 1 OUT 2 IN

CM24K.. CM24K.. AC 198 ... 264 V

50/60 Hz

–+

SKM230-T-B12

1 2 3

– +

L

R

L

R

1 2 3

1

0

– +

T

~

..-SR: Y = DC 0...10 V U = DC 2...10 V

..-SZ: Y = DC 0...10 V U = DC 0...10 V

Y = Control signalU = Measuring voltage

Y

U

1 32 5

T

~

+

Butterfly Valves. Open-close Actuators with Emergency Control Function – flange

Subject to technical changes.

Page 4: ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Subject to technical modifications

Damper actuators

LM..A 2) NM..A 2) SM..A 2) GM..A 2)

5 Nm 10 Nm 20 Nm 40 Nm

For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2

Open-close actuators

AC/DC 24 V LM24A NM24A SM24A GM24A

with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S

AC 230 V LM230A NM230A SM230A GM230A

with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA

AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR

AC 230 V LM230ASR NM230ASR SM230ASR

Parameterisable actuators parameterisable 1)

AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF

Technical data

Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm

Running time 150 s / 90°

Manual override Gear disengagement with push button, can be locked

Connection Cable 1 m / Terminals

Direction of rotation Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s

Degree of protection IP 54

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection

Other versions on request.

Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..

Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V

U = DC 2...10 VY = Control signalU = Measuring voltage

Y = DC 0...10 VU = DC 2...10 V

Direction of rotation

1

0

1

2 3

1

0

T

~

N L

+

0...100%

S1 S2 S3

1

2 3

0

1

0

T

~

N

L

+

0...100%

S1 S2 S3

Y

U

1 32 5

T

~

+

Y

U

1 32 5

1

2

N L

T

SG..24

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

SY

Actuatingtime

Degree of protection

650 Nm 1000 Nm 1500 Nm 2000 Nm 2500 Nm 3500 Nm

AC 230 V 31 s

IP67

SY6-230- 3-T

55 s

SY7-230A- 3-T

SY8-230A- 3-T

70 s

SY9-230A- 3-T

SY10-230A- 3-T

SY12-230A- 3-T

onpe

n-cl

ose,

3-p

oint

, ter

min

al c

onne

ctio

n

Auxi

liary

sw

itch

SPDT

2

Flange ISO 7005-2 EN 1092-2

PN 10 and 16Tmax=120°C

Range of useclosed and open circuits (pH > 7)

2-way, with wafer type

PN DN[mm]

kvmax

[m3/h]∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

D6350N 10 / 16 350 10300 600 1200

D6400N 16 400 14200 600 1000

D6450N 16 450 18800 600 1000

D6500N 16 500 24100 600 1000

D6600N 16 600 37300 600 1000

D6700N 16 700 42800 200

Technical data sheet D6..N

Butterfly valve with Wafer types• For open and closed cold and warm

water systems• For switching heat generators or

cooling machines on and off

Type overview

Type DN[ ]

PN[ ]

kvmax[ m³/h]

D625N 25 6 / 10 / 16 45D632N 32 6 / 10 / 16 55D640N 40 6 / 10 / 16 70D650N 50 6 / 10 / 16 90D665N 65 6 / 10 / 16 180D680N 80 6 / 10 / 16 300D6100N 100 6 / 10 / 16 580D6125N 125 6 / 10 / 16 820D6150N 150 6 / 10 / 16 1600D6350N 350 10 / 16 10900D6400N 400 16 14200D6450N 450 16 18800D6500N 500 16 24100D6600N 600 16 37300D6700N 700 16 42800

Technical data

Functional data Media Cold and warm water, water with glycol up to max. 50% vol.

Medium temperature -20...120°C Permissible pressure ps 1600 kPa Leakage rate Leakage rate A, tight (EN 12266-1) Pipe connector Flange PN 6/10/16 (according to ISO 7005-2)

(DN 25...150)Flange PN 10/16 (according to ISO 7005-2) (DN 350)Flange PN 16 (according to ISO 7005-2) (DN 400...700)

Angle of rotation 90° Installation position Upright to horizontal (in relation to the stem) Suitable connection flange In accordance with ISO 7005-2 and EN 1092-2 Maintenance Maintenance-free

Materials Housing EN-JS1030 (GGG 40), epoxy-powder coating Closing element 1.4301 (stainless steel) Stem 1.4005 (stainless steel) Stem seal O-ring EPDM Stem bearing RPTFE Seat EPDM

Safety notes

!• The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

www.belimo.eu D6..N • en-gb • 2017-02-15 • subject to changes 1

The types D6200N, D6250N and D6300N have been replaced by the types D6200W, D6250W and D6300W. For technical data please check the datasheet D6..W.

Butterfly Valves. Open-close, Fast runners – flange

Subject to technical changes.

Page 5: ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Subject to technical modifications

Damper actuators

LM..A 2) NM..A 2) SM..A 2) GM..A 2)

5 Nm 10 Nm 20 Nm 40 Nm

For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2

Open-close actuators

AC/DC 24 V LM24A NM24A SM24A GM24A

with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S

AC 230 V LM230A NM230A SM230A GM230A

with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA

AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR

AC 230 V LM230ASR NM230ASR SM230ASR

Parameterisable actuators parameterisable 1)

AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF

Technical data

Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm

Running time 150 s / 90°

Manual override Gear disengagement with push button, can be locked

Connection Cable 1 m / Terminals

Direction of rotation Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s

Degree of protection IP 54

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection

Other versions on request.

Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..

Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V

U = DC 2...10 VY = Control signalU = Measuring voltage

Y = DC 0...10 VU = DC 2...10 V

Direction of rotation

1

0

1

2 3

1

0

T

~

N L

+

0...100%

S1 S2 S3

1

2 3

0

1

0

T

~

N

L

+

0...100%

S1 S2 S3

Y

U

1 32 5

T

~

+

Y

U

1 32 5

1

2

N L

T

SG..24

Technical data sheet SR24A-5

Rotary actuator for rotary valves and butterfly valves• Nominaltorque20Nm• NominalvoltageAC/DC24V• ControlOpen-close,3-point

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 2.5 W Power consumption in rest position 0.2 W Power consumption for wire sizing 5.5 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 20 Nm Manual override Gear disengagement with push-button, can be

locked Running time motor 90 s / 90° Sound power level motor max. 45 dB(A) Position indication Mechanically, integrated, two-section

Safety Protection class IEC/EN III Safety extra-low voltage Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2004/108/EC Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight approx. 1 kg

Safety notes

!• Thisdevicehasbeendesignedforuseinstationaryheating,ventilationandair

conditioning systems and is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Onlyauthorisedspecialistsmaycarryoutinstallation.Allapplicablelegalorinstitutional installation regulations must be complied during installation.

• Theswitchforchangingthedirectionofrotationmayonlybeoperatedbyauthorisedspecialists. The direction of rotation must not in particular be reversed in a frost protection circuit.

• Thedevicemayonlybeopenedatthemanufacturer‘ssite.Itdoesnotcontainanyparts that can be replaced or repaired by the user.

• Thecablesmustnotberemovedfromthedevice.• Thedevicecontainselectricalandelectroniccomponentsandisnotallowedtobe

disposed of as household refuse. All locally valid regulations and requirements must be observed.

www.belimo.eu SR24A-5•en-gb•2014-08-13•subjecttochanges 1

Technical data sheet GR24A-5

Rotary actuator for rotary valves and butterfly valves• Nominaltorque40Nm• NominalvoltageAC/DC24V• ControlOpen-close

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 4 W Power consumption in rest position 2 W Power consumption for wire sizing 6 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 40 Nm Manual override Gear disengagement with push-button, can be

locked Running time motor 150 s / 90° Sound power level motor max. 45 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety extra-low voltage Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2004/108/EC Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight approx. 1.85 kg

Safety notes

!• Thisdevicehasbeendesignedforuseinstationaryheating,ventilationandair

conditioning systems and is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Onlyauthorisedspecialistsmaycarryoutinstallation.Allapplicablelegalorinstitutional installation regulations must be complied during installation.

• Theswitchforchangingthedirectionofrotationmayonlybeoperatedbyauthorisedspecialists. The direction of rotation must not in particular be reversed in a frost protection circuit.

• Thedevicemayonlybeopenedatthemanufacturer‘ssite.Itdoesnotcontainanyparts that can be replaced or repaired by the user.

• Thecablesmustnotberemovedfromthedevice.

www.belimo.eu GR24A-5•en-gb•2014-08-13•subjecttochanges 1

Technical data sheet DR24A-5

Rotary actuator for butterfly valves• Nominal torque Max. 90 Nm (not

constant)• Nominal voltage AC/DC 24 V• Control Open-close

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 4 W Power consumption in rest position 2 W Power consumption for wire sizing 6 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Nominal torque Max. 90 Nm (not constant) Manual override with push-button, can be locked Running time motor 150 s / 90° Sound power level, motor 45 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity Max. 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight 4.2 kg

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Outdoor application: only possible in case that no (sea)water, snow, ice, insolation or aggressive gases interfere directly with the actuator and that is ensured that the ambient conditions remain at any time within the thresholds according to the data sheet.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.

• The switch for changing the direction of rotation may not be adjusted.• The angle of rotation is not permitted to be subjected to mechanical limitation. It is

forbidden to alter the mechanical end stops.• The device may only be opened at the manufacturer’s site. It does not contain any

parts that can be replaced or repaired by the user.

www.belimo.com DR24A-5 • en-gb • 2018-06-06 • subject to changes 1

SR GR DR

Running times

(Control)Operating range

Degree of protection

20 Nm 40 Nm < 90 Nm

AC/DC 24 V 90 s open-close, 3-point

IP54

SR24A-5

150 s open-close

GR24A-5

DR24A-5

DR24A-7

AC 230 V 90 s open-close, 3-point SR230A-5

150 s open-close

GR230A-5

DR230A-5

DR230A-7

Butterfly Valves. Open-close, Standard actuators – flange

Subject to technical changes.

Flange ISO 7005-2EN 1092-2

PN 10 and 16Tmax=120°C

Range of useclosed and open circuits (pH > 7)

2-way, with lug type

PN DN[mm]

kvmax

[m3/h]∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

D625NL 10 / 16 25 50 1200 1200

D632NL 10 / 16 32 55

D640NL 10 / 16 40 65

D650NL 10 / 16 50 100

D665NL 10 / 16 65 170 1200

D680NL 10 / 16 80 260 1200 1200

D6100NL 10 / 16 100 520

D6125NL 10 / 16 125 880 1200

Technical data sheet D6..NL

Butterfly valve with Lug types• For open and closed cold and warm

water systems• For switching heat generators or

cooling machines on and off

Type overview

Type DN[ ]

kvmax[ m³/h]

kvs[ m³/h]

PN[ ]

D625NL 25 50 24 10 / 16D632NL 32 55 25 10 / 16D640NL 40 65 27 10 / 16D650NL 50 100 30 10 / 16D665NL 65 170 50 10 / 16D680NL 80 260 75 10 / 16D6100NL 100 520 150 10 / 16D6125NL 125 880 260 10 / 16D6150NL 150 1400 400 10 / 16D6350NL 350 10300 3010 16D6400NL 400 14200 4140 16D6450NL 450 18800 5490 16D6500NL 500 24100 7060 16D6600NL 600 37300 10900 16D6700NL 700 42800 11760 16

The types D6200NL, D6250NL and D6300NL have been replaced by the types D6200WL, D6250WL and D6300WL. For technical data please check the datasheet D6..WL.

Technical data

Functional data Media Cold and warm water, water with glycol up to max. 50% vol.

Medium temperature -20...120°C Permissible pressure ps 1600 kPa Leakage rate Leakage rate A, tight (EN 12266-1) Angle of rotation 90° Installation position Upright to horizontal (in relation to the stem) Suitable connection flange In accordance with ISO 7005-2 and EN 1092-2 Maintenance Maintenance-free

Materials Body EN-JS1030 (GGG 40), epoxy-powder coating Closing element 1.4301 (stainless steel) Stem 1.4005 (stainless steel) Stem seal O-ring EPDM Stem bearing RPTFE Seat EPDM

Safety notes

!• The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.

• The valve does not contain any parts that can be replaced or repaired by the user.• The valve may not be disposed of as household refuse. All locally valid regulations

and requirements must be observed.

www.belimo.com D6..NL • en-gb • 2018-05-30 • subject to changes 1

1) 30...120 s variable.

Page 6: ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Subject to technical modifications

Damper actuators

LM..A 2) NM..A 2) SM..A 2) GM..A 2)

5 Nm 10 Nm 20 Nm 40 Nm

For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2

Open-close actuators

AC/DC 24 V LM24A NM24A SM24A GM24A

with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S

AC 230 V LM230A NM230A SM230A GM230A

with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA

AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR

AC 230 V LM230ASR NM230ASR SM230ASR

Parameterisable actuators parameterisable 1)

AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF

Technical data

Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm

Running time 150 s / 90°

Manual override Gear disengagement with push button, can be locked

Connection Cable 1 m / Terminals

Direction of rotation Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s

Degree of protection IP 54

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection

Other versions on request.

Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..

Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V

U = DC 2...10 VY = Control signalU = Measuring voltage

Y = DC 0...10 VU = DC 2...10 V

Direction of rotation

1

0

1

2 3

1

0

T

~

N L

+

0...100%

S1 S2 S3

1

2 3

0

1

0

T

~

N

L

+

0...100%

S1 S2 S3

Y

U

1 32 5

T

~

+

Y

U

1 32 5

1

2

N L

T

SG..24

Technical data sheet GR24A-5

Rotary actuator for rotary valves and butterfly valves• Nominaltorque40Nm• NominalvoltageAC/DC24V• ControlOpen-close

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 4 W Power consumption in rest position 2 W Power consumption for wire sizing 6 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 40 Nm Manual override Gear disengagement with push-button, can be

locked Running time motor 150 s / 90° Sound power level motor max. 45 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety extra-low voltage Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2004/108/EC Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight approx. 1.85 kg

Safety notes

!• Thisdevicehasbeendesignedforuseinstationaryheating,ventilationandair

conditioning systems and is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Onlyauthorisedspecialistsmaycarryoutinstallation.Allapplicablelegalorinstitutional installation regulations must be complied during installation.

• Theswitchforchangingthedirectionofrotationmayonlybeoperatedbyauthorisedspecialists. The direction of rotation must not in particular be reversed in a frost protection circuit.

• Thedevicemayonlybeopenedatthemanufacturer‘ssite.Itdoesnotcontainanyparts that can be replaced or repaired by the user.

• Thecablesmustnotberemovedfromthedevice.

www.belimo.eu GR24A-5•en-gb•2014-08-13•subjecttochanges 1

Technical data sheet DRC24A-7

Rotary actuator for butterfly valves• Nominal torque Max. 90 Nm (not

constant)• Nominal voltage AC/DC 24 V• Control Open-close• Running time motor 35 s

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 9 W Power consumption in rest position 2 W Power consumption for wire sizing 12 VA Connection supply / control Cable 1 m, 3 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Nominal torque Max. 90 Nm (not constant) Manual override with push-button, can be locked Running time motor 35 s / 90° Sound power level, motor 45 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity Max. 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F07

Weight Weight 4.1 kg

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Outdoor application: only possible in case that no (sea)water, snow, ice, insolation or aggressive gases interfere directly with the actuator and that is ensured that the ambient conditions remain at any time within the thresholds according to the data sheet.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.

• The switch for changing the direction of rotation may not be adjusted.• The angle of rotation is not permitted to be subjected to mechanical limitation. It is

forbidden to alter the mechanical end stops.• The device may only be opened at the manufacturer’s site. It does not contain any

parts that can be replaced or repaired by the user.

www.belimo.com DRC24A-7 • en-gb • 2018-06-06 • subject to changes 1

Technical data sheet PRCA-S2-T

Rotary actuator for butterfly valves• Nominal torque 160 Nm• Nominal voltage AC 24...240 V / DC

24...125 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 24...240 V / DC 24...125 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...264 V / DC 19.2...137.5 V Power consumption in operation 20 W Power consumption in rest position 6 W Power consumption for wire sizing with 24 V 20 VA / with 230 V 52 VA Auxiliary switch 2 x SPDT, 1 x 10° / 1 x 0...90° (ex works 85°) Switching capacity auxiliary switch 1 mA...3 (0.5 inductive) A, AC 250 V Connection supply / control Terminals 2.5 mm² Connection auxiliary switch Terminals 2.5 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor 160 Nm Manual override with hand crank, can be fixed in any position Running time motor 35 s / 90° Motor running time variable 30...120 s Sound power level motor 68 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN II reinforced insulation Protection class UL II reinforced insulation Protection class auxiliary switch IEC/EN II reinforced insulation Degree of protection IEC/EN IP66 + IP67 Degree of protection NEMA/UL NEMA 4X, UL Enclosure Type 4X EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply 4 kV Rated impulse voltage auxiliary switch 2.5 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F07 (F05 only with accessory)

Weight Weight 5.8 kg

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.

www.belimo.eu PRCA-S2-T • en-gb • 2017-03-21 • subject to changes 1

GRC DRC PRC

Runningtimes

(Control)Operating range

Degree of protection

40 Nm < 90 Nm 160 Nm

AC/DC 24 V35 s open-close

IP54 / IP66

GRC24A-5

DRC24A-5

DRC24A-7

AC 230 V35 s open-close

GRC230A-5

DRC230A-5

DRC230A-7

AC 24...240 VDC 24...125 V 35 s1) open-close, 3-point,

terminal connection IP66 / IP67 PRCA-S2-T

Auxi

liary

sw

itch

SPDT

2

Flange ISO 7005-2EN 1092-2

PN 10 and 16Tmax=120°C

Range of useclosed and open circuits (pH > 7)

2-way, with lug type

PN DN[mm]

kvmax

[m3/h]∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

D625NL 10 / 16 25 50 1200

D632NL 10 / 16 32 55

D640NL 10 / 16 40 65

D650NL 10 / 16 50 100

D665NL 10 / 16 65 170

D680NL 10 / 16 80 260 1200 1200 1200

D6100NL 10 / 16 100 520

D6125NL 10 / 16 125 880 1200

D6150NL 10 / 16 150 1400 1200

D6200WL 16 200 2200 1400

D6250WL 16 250 4200

D6300WL 16 300 5700 1400

Technical data sheet D6..NL

Butterfly valve with Lug types• For open and closed cold and warm

water systems• For switching heat generators or

cooling machines on and off

Type overview

Type DN[ ]

kvmax[ m³/h]

kvs[ m³/h]

PN[ ]

D625NL 25 50 24 10 / 16D632NL 32 55 25 10 / 16D640NL 40 65 27 10 / 16D650NL 50 100 30 10 / 16D665NL 65 170 50 10 / 16D680NL 80 260 75 10 / 16D6100NL 100 520 150 10 / 16D6125NL 125 880 260 10 / 16D6150NL 150 1400 400 10 / 16D6350NL 350 10300 3010 16D6400NL 400 14200 4140 16D6450NL 450 18800 5490 16D6500NL 500 24100 7060 16D6600NL 600 37300 10900 16D6700NL 700 42800 11760 16

The types D6200NL, D6250NL and D6300NL have been replaced by the types D6200WL, D6250WL and D6300WL. For technical data please check the datasheet D6..WL.

Technical data

Functional data Media Cold and warm water, water with glycol up to max. 50% vol.

Medium temperature -20...120°C Permissible pressure ps 1600 kPa Leakage rate Leakage rate A, tight (EN 12266-1) Angle of rotation 90° Installation position Upright to horizontal (in relation to the stem) Suitable connection flange In accordance with ISO 7005-2 and EN 1092-2 Maintenance Maintenance-free

Materials Body EN-JS1030 (GGG 40), epoxy-powder coating Closing element 1.4301 (stainless steel) Stem 1.4005 (stainless steel) Stem seal O-ring EPDM Stem bearing RPTFE Seat EPDM

Safety notes

!• The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.

• The valve does not contain any parts that can be replaced or repaired by the user.• The valve may not be disposed of as household refuse. All locally valid regulations

and requirements must be observed.

www.belimo.com D6..NL • en-gb • 2018-05-30 • subject to changes 1

1) 30...120 s variable.

Butterfly Valves. Open-close, Fast runners – flange

Subject to technical changes.

Page 7: ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Subject to technical modifications

Damper actuators

LM..A 2) NM..A 2) SM..A 2) GM..A 2)

5 Nm 10 Nm 20 Nm 40 Nm

For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2

Open-close actuators

AC/DC 24 V LM24A NM24A SM24A GM24A

with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S

AC 230 V LM230A NM230A SM230A GM230A

with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA

AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR

AC 230 V LM230ASR NM230ASR SM230ASR

Parameterisable actuators parameterisable 1)

AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF

Technical data

Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm

Running time 150 s / 90°

Manual override Gear disengagement with push button, can be locked

Connection Cable 1 m / Terminals

Direction of rotation Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s

Degree of protection IP 54

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection

Other versions on request.

Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..

Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V

U = DC 2...10 VY = Control signalU = Measuring voltage

Y = DC 0...10 VU = DC 2...10 V

Direction of rotation

1

0

1

2 3

1

0

T

~

N L

+

0...100%

S1 S2 S3

1

2 3

0

1

0

T

~

N

L

+

0...100%

S1 S2 S3

Y

U

1 32 5

T

~

+

Y

U

1 32 5

1

2

N L

T

SG..24

Technical data sheet SRF24A-5

Rotary actuator with emergency control function for ball valves and butterfly valves• Nominaltorque20Nm• NominalvoltageAC/DC24V• ControlOpen-close• Deenergisedclosed(NC)

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 5 W Power consumption in rest position 2.5 W Power consumption for wire sizing 7.5 VA Connection supply / control Cable 1 m, 2 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 20 Nm Torque spring return Min. 20 Nm Direction of rotation spring-return Deenergised NC, valve closed (A - AB = 0%) Manual override By means of hand crank and locking switch Angle of rotation 90° Running time motor 75 s / 90° Running time emergency setting position <20 s / 90° Sound power level motor max. 45 dB(A) Position indication Mechanical Service life Min. 60,000 emergency positions

Safety Protection class IEC/EN III Safety extra-low voltage Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2004/108/EC Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight approx. 2.3 kg

Safety notes

!• Thisdevicehasbeendesignedforuseinstationaryheating,ventilationandair

conditioning systems and is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Onlyauthorisedspecialistsmaycarryoutinstallation.Allapplicablelegalorinstitutional installation regulations must be complied during installation.

• Thedevicemayonlybeopenedatthemanufacturer‘ssite.Itdoesnotcontainanyparts that can be replaced or repaired by the user.

• Thecablesmustnotberemovedfromthedevice.

www.belimo.eu SRF24A-5•en-gb•2014-10-15•subjecttochanges 1

Technical data sheet GRK24A-5

SuperCap rotary actuator with emergeny control function and extended functionalities for rotary valves and butterfly valves• Nominal torque 40 Nm• Nominal voltage AC/DC 24 V• Control Open-close• Design life SuperCaps: 15 years

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 11 W Power consumption in rest position 3 W Power consumption for wire sizing 21 VA Power consumption for wire sizing note Imax 20 A @ 5 ms Connection supply / control Cable 1 m, 2 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Torque motor Min. 40 Nm Setting emergency setting position (POP) NC / NO, adjustable (POP rotary button) Manual override with push-button Running time motor 150 s / 90° Running time emergency control position 35 s / 90° Running time emergency setting position

note<35 s @ 0...50 °C

Sound power level motor 52 dB(A) Sound power level emergency control

position61 dB(A)

Position indication Mechanical

Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight 2.8 kg

Terms Abbreviations POP = Power off position / emergency setting positionCPO = Controlled power off / controlled emergency control functionPF = Power fail delay time / bridging time

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

www.belimo.eu GRK24A-5 • en-gb • 2017-03-09 • subject to changes 1

Technical data sheet DRK24A-5

SuperCap rotary actuator with emergeny control function and extended functionalities for butterfly valves• Nominal torque Max. 90 Nm (not

constant)• Nominal voltage AC/DC 24 V• Control Open-close• Design life SuperCaps: 15 years

Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 11 W Power consumption in rest position 2 W Power consumption for wire sizing 20 VA Power consumption for wire sizing note Imax 20 A @ 5 ms Connection supply / control Cable 1 m, 2 x 0.75 mm² Parallel operation Yes (note the performance data)

Functional data Nominal torque Max. 90 Nm (not constant) Setting emergency setting position (POP) NC / NO, adjustable (POP rotary button) Manual override with push-button Running time motor 150 s / 90° Running time emergency control position 35 s / 90° Running time emergency setting position

note<35 s @ 0...50 °C

Sound power level, motor 52 dB(A) Sound power level emergency control

position61 dB(A)

Position indication Mechanically (integrated)

Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50 °C Non-operating temperature -40...80 °C Ambient humidity Max. 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F05

Weight Weight 4.1 kg

Terms Abbreviations POP = Power off position / emergency setting positionCPO = Controlled power off / controlled emergency control functionPF = Power fail delay time / bridging time

Safety notes

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

www.belimo.com DRK24A-5 • en-gb • 2018-08-30 • subject to changes 1

Technical data sheet PRKCA-BAC-S2-T

Rotary actuator for butterfly valves• Torque motor 160 Nm• Nominal voltage AC 24...240 V / DC

24...125 V• Control modulating, communicative,

hybrid mode• with 2 integrated auxiliary switches• Conversion of sensor signals• Communication via BACnet MS/TP,

Modbus RTU, Belimo-MP-Bus or conventional control

Technical data

Electrical data Nominal voltage AC 24...240 V / DC 24...125 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...264 V / DC 19.2...137.5 V Power consumption in operation 52 W Power consumption in rest position 7 W Power consumption for wire sizing with 24 V 54 VA / with 230 V 68 VA Power consumption for wire sizing note Imax 20 A @ 5 ms Auxiliary switch 2 x SPDT, 1 x 10° / 1 x 0...90° (ex works 85°) Switching capacity auxiliary switch 1 mA...3 (0.5 inductive) A, AC 250 V Connection supply Terminals 2.5 mm² Connection control Terminals 1.5 mm² Connection auxiliary switch Terminals 2.5 mm² Parallel operation Yes (note the performance data)

Functional data Nominal torque 160 Nm Communicative control BACnet MS/TP (ex works)

Modbus RTUMP-Bus

Operating range Y DC 2...10 V Input Impedance 100 kΩ Operating range Y variable DC 0.5...10 V

4...20 mA Position feedback U DC 2...10 V Position feedback U note Max. 0.5 mA Position feedback U variable DC 0.5...10 V Setting emergency setting position (POP) 0...100%, adjustable (ex works 0%) Bridging time (PF) variable 0...10 s (ex works 2s) Position accuracy ±5% Manual override with hand crank, can be fixed in any position Running time motor 35 s / 90° Running time motor variable 30...120 s Running time emergency control position 30 s / 90° Sound power level Motor 68 dB(A) Sound power level emergency control

position61 dB(A)

Position indication Mechanically (integrated)

Safety Protection class IEC/EN II reinforced insulation Protection class UL II reinforced insulation Protection class auxiliary switch IEC/EN II reinforced insulation Degree of protection IEC/EN IP66/67 Degree of protection NEMA/UL NEMA 4X, UL Enclosure Type 4X EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA Rated impulse voltage supply 4 kV Rated impulse voltage control 0.8 kV Rated impulse voltage auxiliary switch 2.5 kV

www.belimo.com PRKCA-BAC-S2-T • en-gb • 2018-05-07 • subject to changes 1

SRF GRK DRK PRK

Runningtimes

(Control)Operatingrange

Degree of protection

20 Nm 40 Nm < 90 Nm 160 Nm

AC/DC 24 V75 s open-close IP54

SRF24A-5

SRF24A- S2-5

150 s open-close IP54

GRK24A-5

DRK24A-5

DRK24A-7

AC 24...240 VDC 24...125 V

75 s open-close IP54SRFA-5

SRFA-S2-5

35 s1)open-close, 3-point, modulating, terminal connection

IP66/ IP67PRKCA- BAC-S2-T

Emer

genc

y co

ntro

l fun

ctio

n

Auxi

liary

sw

itch

SPDT

2

2

2

Subject to technical modifications

Spring return actuators

TF.. LF.. NF..A SF..A EF..A

2.5 Nm 4 Nm 10 Nm 20 Nm 30 Nm

For air damper sizes up to approx. 0.5 m2 0.8 m2 2 m2 4 m2 6 m2

Open-close actuators

AC/DC 24 V TF24 LF24 NF24A SF24A EF24A

with auxiliary switch, 1 x SPDT TF24-S LF24-S

with auxiliary switch, 2 x SPDT NF24A-S2 SF24A-S2 EF24A-S2

AC 230 V TF230 LF230 NF230A SF230A EF230A

with auxiliary switch, 1 x SPDT TF230-S LF230-S

with auxiliary switch, 2 x SPDT NF230A-S2 SF230A-S2 EF230A-S2

AC 24...240 V / DC 24...125 V NFA SFA

with auxiliary switch, 2 x SPDT NFA-S2 SFA-S2

3-point actuator

AC 24 V TF24-3 NF24A-3 SF24A-3

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, max. 1 mA

AC/DC 24 V Operating range DC 2...10 V TF24-SR LF24-SR NF24A-SR SF24A-SR EF24A-SR

with auxiliary switch, 2 x SPDT NF24A-SR-S2 SF24A-SR-S2 EF24A-SR-S2

Operating range DC 0...10 V NF24A-SZ SF24A-SZ

with auxiliary switch, 2 x SPDT NF24A-SZ-S2 SF24A-SZ-S2

AC 230 V Operating range DC 2...10 V TF230-SR

Parameterisable actuators parameterisable 1)

AC/DC 24 V TF24-MFT LF24-MFT NF24A-MF SF24A-MF EF24A-MF

Technical data

Damper spindle 6...12 mm 8...16 mm 10...25.4 mm 10...25.4 mm 12...26.7 mm

Running time Motor

Emergency control function

<75 s / 90°(SR: 150 s / 90° )

<25 s / 90°

40...75 s / 90°(SR: 150 s / 90° )

20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR: 150 s / 90° )

<20 s / 90°

Manual override Hand crank

Connection Cable 1 m, PVC Cable FRNC 1 m

Direction of rotation Can be selected by mounting L / R

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level MotorEmergency control function

≤50 dB(A) @ 75 s=62 dB(A) @ 25 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

≤45 dB(A) @ 75 s=62 dB(A) @ 20 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

Degree of protection IP 42 IP 54 IP 54 2)

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) EF..: IP 66 versions on request.

Other versions on request.

Subject to technical modifications

Spring return actuators

TF.. LF.. NF..A SF..A EF..A

2.5 Nm 4 Nm 10 Nm 20 Nm 30 Nm

For air damper sizes up to approx. 0.5 m2 0.8 m2 2 m2 4 m2 6 m2

Open-close actuators

AC/DC 24 V TF24 LF24 NF24A SF24A EF24A

with auxiliary switch, 1 x SPDT TF24-S LF24-S

with auxiliary switch, 2 x SPDT NF24A-S2 SF24A-S2 EF24A-S2

AC 230 V TF230 LF230 NF230A SF230A EF230A

with auxiliary switch, 1 x SPDT TF230-S LF230-S

with auxiliary switch, 2 x SPDT NF230A-S2 SF230A-S2 EF230A-S2

AC 24...240 V / DC 24...125 V NFA SFA

with auxiliary switch, 2 x SPDT NFA-S2 SFA-S2

3-point actuator

AC 24 V TF24-3 NF24A-3 SF24A-3

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, max. 1 mA

AC/DC 24 V Operating range DC 2...10 V TF24-SR LF24-SR NF24A-SR SF24A-SR EF24A-SR

with auxiliary switch, 2 x SPDT NF24A-SR-S2 SF24A-SR-S2 EF24A-SR-S2

Operating range DC 0...10 V NF24A-SZ SF24A-SZ

with auxiliary switch, 2 x SPDT NF24A-SZ-S2 SF24A-SZ-S2

AC 230 V Operating range DC 2...10 V TF230-SR

Parameterisable actuators parameterisable 1)

AC/DC 24 V TF24-MFT LF24-MFT NF24A-MF SF24A-MF EF24A-MF

Technical data

Damper spindle 6...12 mm 8...16 mm 10...25.4 mm 10...25.4 mm 12...26.7 mm

Running time Motor

Emergency control function

<75 s / 90°(SR: 150 s / 90° )

<25 s / 90°

40...75 s / 90°(SR: 150 s / 90° )

20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR: 150 s / 90° )

<20 s / 90°

Manual override Hand crank

Connection Cable 1 m, PVC Cable FRNC 1 m

Direction of rotation Can be selected by mounting L / R

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level MotorEmergency control function

≤50 dB(A) @ 75 s=62 dB(A) @ 25 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

≤45 dB(A) @ 75 s=62 dB(A) @ 20 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

Degree of protection IP 42 IP 54 IP 54 2)

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) EF..: IP 66 versions on request.

Other versions on request.

Subject to technical modifications

SuperCap actuators

SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A

2 Nm 40 Nm 6 Nm 150 N 450 N

For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2

Open-close actuators

AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA

AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100

Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100

Parameterisable actuators parameterisable 1)

AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100

External SuperCap module

AC 230 V SKM230-T-B12.1

Technical data

Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm

Running time MotorEmergency control function

75 s / 90°15 s / 90°

150 s / 90°35 s / 90°

4 s / 90°4 s / 90°

120 s / 100 mm35 s / 100 mm

Manual override Gear disengage-ment with magnet

Gear disengagement with push button

Connection Terminals Cable 1 mDirection of rotation Selectable with

actuator 2)Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor

Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s

≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s

≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s

≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s

≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s

Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right

Other versions on request.

Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF

SKM230.. CM24K.. Open-close control modulating parameterisable

2 1

3

+

2 13 1N2L

T~

OUT 1 OUT 2 IN

CM24K.. CM24K.. AC 198 ... 264 V

50/60 Hz

–+

SKM230-T-B12

1 2 3

– +

L

R

L

R

1 2 3

1

0

– +

T

~

..-SR: Y = DC 0...10 V U = DC 2...10 V

..-SZ: Y = DC 0...10 V U = DC 0...10 V

Y = Control signalU = Measuring voltage

Y

U

1 32 5

T

~

+

Subject to technical modifications

SuperCap actuators

SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A

2 Nm 40 Nm 6 Nm 150 N 450 N

For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2

Open-close actuators

AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA

AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100

Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100

Parameterisable actuators parameterisable 1)

AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100

External SuperCap module

AC 230 V SKM230-T-B12.1

Technical data

Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm

Running time MotorEmergency control function

75 s / 90°15 s / 90°

150 s / 90°35 s / 90°

4 s / 90°4 s / 90°

120 s / 100 mm35 s / 100 mm

Manual override Gear disengage-ment with magnet

Gear disengagement with push button

Connection Terminals Cable 1 mDirection of rotation Selectable with

actuator 2)Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor

Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s

≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s

≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s

≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s

≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s

Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right

Other versions on request.

Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF

SKM230.. CM24K.. Open-close control modulating parameterisable

2 1

3

+

2 13 1N2L

T~

OUT 1 OUT 2 IN

CM24K.. CM24K.. AC 198 ... 264 V

50/60 Hz

–+

SKM230-T-B12

1 2 3

– +

L

R

L

R

1 2 3

1

0

– +

T

~

..-SR: Y = DC 0...10 V U = DC 2...10 V

..-SZ: Y = DC 0...10 V U = DC 0...10 V

Y = Control signalU = Measuring voltage

Y

U

1 32 5

T

~

+

Subject to technical modifications

SuperCap actuators

SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A

2 Nm 40 Nm 6 Nm 150 N 450 N

For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2

Open-close actuators

AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA

AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100

Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100

Parameterisable actuators parameterisable 1)

AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100

External SuperCap module

AC 230 V SKM230-T-B12.1

Technical data

Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm

Running time MotorEmergency control function

75 s / 90°15 s / 90°

150 s / 90°35 s / 90°

4 s / 90°4 s / 90°

120 s / 100 mm35 s / 100 mm

Manual override Gear disengage-ment with magnet

Gear disengagement with push button

Connection Terminals Cable 1 mDirection of rotation Selectable with

actuator 2)Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor

Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s

≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s

≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s

≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s

≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s

Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right

Other versions on request.

Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF

SKM230.. CM24K.. Open-close control modulating parameterisable

2 1

3

+

2 13 1N2L

T~

OUT 1 OUT 2 IN

CM24K.. CM24K.. AC 198 ... 264 V

50/60 Hz

–+

SKM230-T-B12

1 2 3

– +

L

R

L

R

1 2 3

1

0

– +

T

~

..-SR: Y = DC 0...10 V U = DC 2...10 V

..-SZ: Y = DC 0...10 V U = DC 0...10 V

Y = Control signalU = Measuring voltage

Y

U

1 32 5

T

~

+

Flange ISO 7005-2EN 1092-2

PN 10 and 16Tmax=120°C

Range of useclosed and open circuits (pH > 7)

2-way, with lug type

PN DN[mm]

kvmax

[m3/h]∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

D625NL 10 / 16 25 50 1200 1200

D632NL 10 / 16 32 55

D640NL 10 / 16 40 65

D650NL 10 / 16 50 100

D665NL 10 / 16 65 170 1200

D680NL 10 / 16 80 260 1200 1200 1200

D6100NL 10 / 16 100 520

D6125NL 10 / 16 125 880 1200

D6150NL 10 / 16 150 1400 1200

D6200WL 16 200 2200 1400

D6250WL 16 250 4200

D6300WL 16 300 5700 1400

Technical data sheet D6..NL

Butterfly valve with Lug types• For open and closed cold and warm

water systems• For switching heat generators or

cooling machines on and off

Type overview

Type DN[ ]

kvmax[ m³/h]

kvs[ m³/h]

PN[ ]

D625NL 25 50 24 10 / 16D632NL 32 55 25 10 / 16D640NL 40 65 27 10 / 16D650NL 50 100 30 10 / 16D665NL 65 170 50 10 / 16D680NL 80 260 75 10 / 16D6100NL 100 520 150 10 / 16D6125NL 125 880 260 10 / 16D6150NL 150 1400 400 10 / 16D6350NL 350 10300 3010 16D6400NL 400 14200 4140 16D6450NL 450 18800 5490 16D6500NL 500 24100 7060 16D6600NL 600 37300 10900 16D6700NL 700 42800 11760 16

The types D6200NL, D6250NL and D6300NL have been replaced by the types D6200WL, D6250WL and D6300WL. For technical data please check the datasheet D6..WL.

Technical data

Functional data Media Cold and warm water, water with glycol up to max. 50% vol.

Medium temperature -20...120°C Permissible pressure ps 1600 kPa Leakage rate Leakage rate A, tight (EN 12266-1) Angle of rotation 90° Installation position Upright to horizontal (in relation to the stem) Suitable connection flange In accordance with ISO 7005-2 and EN 1092-2 Maintenance Maintenance-free

Materials Body EN-JS1030 (GGG 40), epoxy-powder coating Closing element 1.4301 (stainless steel) Stem 1.4005 (stainless steel) Stem seal O-ring EPDM Stem bearing RPTFE Seat EPDM

Safety notes

!• The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.

• The valve does not contain any parts that can be replaced or repaired by the user.• The valve may not be disposed of as household refuse. All locally valid regulations

and requirements must be observed.

www.belimo.com D6..NL • en-gb • 2018-05-30 • subject to changes 1

1) 30...120 s variable. Actuator with mechanical emergency control function. Actuator with electrical emergency control function.

Subject to technical modifications

Spring return actuators

TF.. LF.. NF..A SF..A EF..A

2.5 Nm 4 Nm 10 Nm 20 Nm 30 Nm

For air damper sizes up to approx. 0.5 m2 0.8 m2 2 m2 4 m2 6 m2

Open-close actuators

AC/DC 24 V TF24 LF24 NF24A SF24A EF24A

with auxiliary switch, 1 x SPDT TF24-S LF24-S

with auxiliary switch, 2 x SPDT NF24A-S2 SF24A-S2 EF24A-S2

AC 230 V TF230 LF230 NF230A SF230A EF230A

with auxiliary switch, 1 x SPDT TF230-S LF230-S

with auxiliary switch, 2 x SPDT NF230A-S2 SF230A-S2 EF230A-S2

AC 24...240 V / DC 24...125 V NFA SFA

with auxiliary switch, 2 x SPDT NFA-S2 SFA-S2

3-point actuator

AC 24 V TF24-3 NF24A-3 SF24A-3

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, max. 1 mA

AC/DC 24 V Operating range DC 2...10 V TF24-SR LF24-SR NF24A-SR SF24A-SR EF24A-SR

with auxiliary switch, 2 x SPDT NF24A-SR-S2 SF24A-SR-S2 EF24A-SR-S2

Operating range DC 0...10 V NF24A-SZ SF24A-SZ

with auxiliary switch, 2 x SPDT NF24A-SZ-S2 SF24A-SZ-S2

AC 230 V Operating range DC 2...10 V TF230-SR

Parameterisable actuators parameterisable 1)

AC/DC 24 V TF24-MFT LF24-MFT NF24A-MF SF24A-MF EF24A-MF

Technical data

Damper spindle 6...12 mm 8...16 mm 10...25.4 mm 10...25.4 mm 12...26.7 mm

Running time Motor

Emergency control function

<75 s / 90°(SR: 150 s / 90° )

<25 s / 90°

40...75 s / 90°(SR: 150 s / 90° )

20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR/SZ:

150 s / 90° )<20 s / 90°

<75 s / 90°(SR: 150 s / 90° )

<20 s / 90°

Manual override Hand crank

Connection Cable 1 m, PVC Cable FRNC 1 m

Direction of rotation Can be selected by mounting L / R

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level MotorEmergency control function

≤50 dB(A) @ 75 s=62 dB(A) @ 25 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

≤45 dB(A) @ 75 s=62 dB(A) @ 20 s

≤50 dB(A) @ 75 s=62 dB(A) @ 20 s

Degree of protection IP 42 IP 54 IP 54 2)

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) EF..: IP 66 versions on request.

Other versions on request.

Subject to technical modifications

SuperCap actuators

SKM230.. + CM24K.. GK..A NKQ..A LHK..A SHK..A

2 Nm 40 Nm 6 Nm 150 N 450 N

For air damper sizes up to approx. 0,4 m2 8 m2 1,2 m2 1 m2 3 m2

Open-close actuators

AC/DC 24 V CM24K-T-L, CM24K-T-R GK24A-1 NKQ24A-1 LHK24A-1-100 SHK24A-1-100

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ Position feedback DC 2...10 V or DC 0...10 V, 0.5 mA

AC/DC 24 V Operating range DC 2...10 V GK24A-SR NKQ24A-SR LHK24A-SR100 SHK24A-SR100

Operating range DC 0...10 V GK24A-SZ NKQ24A-SZ LHK24A-SZ100 SHK24A-SZ100

Parameterisable actuators parameterisable 1)

AC/DC 24 V GK24A-MF NKQ24A-MF LHK24A-MF100 SHK24A-MF100

External SuperCap module

AC 230 V SKM230-T-B12.1

Technical data

Damper spindle 6...12.7 mm 12...26.7 mm 8...26.7 mm

Running time MotorEmergency control function

75 s / 90°15 s / 90°

150 s / 90°35 s / 90°

4 s / 90°4 s / 90°

120 s / 100 mm35 s / 100 mm

Manual override Gear disengage-ment with magnet

Gear disengagement with push button

Connection Terminals Cable 1 mDirection of rotation Selectable with

actuator 2)Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Stroke range 0...100 mmPosition indication Mechanical, pluggableSound power level Motor

Emergency control function≤35 dB(A) @ 75 s≤55 dB(A) @ 15 s

≤52 dB(A) @ 150 s≤61 dB(A) @ 35 s

≤60 dB(A) @ 4 s≤60 dB(A) @ 4 s

≤45 dB(A) @ 120 s≤65 dB(A) @ 35 s

≤52 dB(A) @ 120 s≤61 dB(A) @ 35 s

Degree of protection IP 20 IP 54EMC CE according to 2004/108/ECAmbient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensating1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) CM..-L: Rotation to the left / CM..-R: Rotation to the right

Other versions on request.

Electrical installation GK24A-1, NKQ24A-1, ..HK24A-1-100 ..24A-SR, ..24A-SZ ..24A-MF

SKM230.. CM24K.. Open-close control modulating parameterisable

2 1

3

+

2 13 1N2L

T~

OUT 1 OUT 2 IN

CM24K.. CM24K.. AC 198 ... 264 V

50/60 Hz

–+

SKM230-T-B12

1 2 3

– +

L

R

L

R

1 2 3

1

0

– +

T

~

..-SR: Y = DC 0...10 V U = DC 2...10 V

..-SZ: Y = DC 0...10 V U = DC 0...10 V

Y = Control signalU = Measuring voltage

Y

U

1 32 5

T

~

+

Butterfly Valves. Actuators with Emergency Control Function – flange

Subject to technical changes.

Page 8: ˆˇ˚˘ ˚ ˆ Butterfly Valves. Open-close, Standard actuators – flange · 2018-12-03 · Butterfly valve with Wafer types • For open and closed cold and warm water systems •

Subject to technical modifications

Damper actuators

LM..A 2) NM..A 2) SM..A 2) GM..A 2)

5 Nm 10 Nm 20 Nm 40 Nm

For air damper sizes up to approx. 1 m2 2 m2 4 m2 8 m2

Open-close actuators

AC/DC 24 V LM24A NM24A SM24A GM24A

with auxiliary switch, 1 x SPDT LM24A-S NM24A-S SM24A-S

AC 230 V LM230A NM230A SM230A GM230A

with auxiliary switch, 1 x SPDT LM230A-S NM230A-S SM230A-S

Modulating actuators Control Signal Y: DC 0...10 V, 100 kΩ / Position feedback DC 2...10 V, max. 1 mA

AC/DC 24 V LM24A-SR NM24A-SR SM24A-SR GM24A-SR

AC 230 V LM230ASR NM230ASR SM230ASR

Parameterisable actuators parameterisable 1)

AC/DC 24 V LM24A-MF NM24A-MF SM24A-MF GM24A-MF

Technical data

Damper spindle 6...20 mm 8...26.7 mm 10...20 mm 12...26.7 mm

Running time 150 s / 90°

Manual override Gear disengagement with push button, can be locked

Connection Cable 1 m / Terminals

Direction of rotation Selectable with switch

Angle of rotation Max. 95° , can be limited at both ends with adjustable mechanical end stops

Position indication Mechanical, pluggable

Sound power level ≤35 dB(A) @ 150 s ≤45 dB(A) @ 150 s

Degree of protection IP 54

EMC CE according to 2004/108/EC

Ambient temperature –30...+50°C

Non-operating temperature –40...+80°C

Ambient humidity 95% r.h., non-condensating

1) Control, operating range, position feedback, running time and further functions are parameterisable with PC-Tool or with the parameterising device ZTH-GEN.2) Actuator types with extension «-TP» with terminal connection Actuator types without extension «-TP» with cable connection

Other versions on request.

Electrical installation ..M24A(-S), ..M230A(-S).. ..M24A-SR.. ..M24A-MF.. ..M230ASR..

Open-close control 3-point control modulating parameterisable modulating(not permitted for GM..A) Y = DC 0...10 V

U = DC 2...10 VY = Control signalU = Measuring voltage

Y = DC 0...10 VU = DC 2...10 V

Direction of rotation

1

0

1

2 3

1

0

T

~

N L

+

0...100%

S1 S2 S3

1

2 3

0

1

0

T

~

N

L

+

0...100%

S1 S2 S3

Y

U

1 32 5

T

~

+

Y

U

1 32 5

1

2

N L

T

SG..24

Technical data sheet SY6-230-3-T

Rotary actuator for butterfly valves• Nominal torque 650 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 193 W Power consumption in operation note incl. heating Power consumption for wire sizing 230 VA Current consumption 1 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 650 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 38 s Duty cycle 30 % (= active time 38 s / operating time 127 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F10

Weight Weight 22 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY6-230-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY7-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 1000 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 381 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 1000 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 58 s Duty cycle 30 % (= active time 58 s / operating time 193 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F14

Weight Weight 36 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY7-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY8-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 1500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 428 W Power consumption in operation note incl. heating Power consumption for wire sizing 437 VA Current consumption 1.9 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 1500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 59 s Duty cycle 30 % (= active time 59 s / operating time 197 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F14

Weight Weight 36 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY8-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

Technical data sheet SY12-230A-3-T

Rotary actuator for butterfly valves• Nominal torque 3500 Nm• Nominal voltage AC 230 V• Control Open-close, 3-point• with 2 integrated auxiliary switches

Technical data

Electrical data Nominal voltage AC 230 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 207...253 V Power consumption in operation 409 W Power consumption in operation note incl. heating Power consumption for wire sizing 414 VA Current consumption 1.8 A Auxiliary switch 2 x SPDT, 1 x 3° / 1 x 87° Switching capacity auxiliary switch 1 mA...5 (3 inductive) A, DC 5 V ... AC 250 V Connection supply / control Terminals 2.5 mm²

(Wire 2 x 1.5 mm² or 1 x 2.5 mm²) Parallel operation No

Functional data Torque motor 3500 Nm Manual override temporary with handwheel (non-rotating) Angle of rotation 90° Angle of rotation note Internal limit switch, not adjustable Running time motor 74 s Duty cycle 30 % (= active time 74 s / operating time 247 s) Sound power level motor 70 dB(A) Position indication Mechanically (integrated)

Safety Protection class IEC/EN I Protective earth Protection class auxiliary switch IEC/EN I Protective earth Degree of protection IEC/EN IP67 EMC CE according to 2014/30/EU Low voltage directive CE according to 2014/35/EU Mode of operation Type 1 Control pollution degree 4 Ambient temperature -30...65°C Non-operating temperature -30...80°C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free

Mechanical data Connection flange F16

Weight Weight 72 kg

Materials Housing material Aluminium pressure casting

www.belimo.eu SY12-230A-3-T • en-gb • 2016-05-30 • subject to changes 1

!• This device has been designed for use in stationary heating, ventilation and air

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Caution: Power supply voltage!• Only authorised specialists may carry out installation. All applicable legal or

institutional installation regulations must be complied during installation.• The device does not contain any parts that can be replaced or repaired by the user.• The device contains electrical and electronic components and must not be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Safety notes

SY

Actuatingtime

Degree of protection

650 Nm 1000 Nm 1500 Nm 2000 Nm 2500 Nm 3500 Nm

AC 230 V 31 s

IP67

SY6-230- 3-T

55 s

SY7-230A- 3-T

SY8-230A- 3-T

70 s

SY9-230A- 3-T

SY10-230A- 3-T

SY12-230A- 3-T

onpe

n-cl

ose,

3-p

oint

, ter

min

al c

onne

ctio

n

Auxi

liary

sw

itch

SPDT

2

Flange ISO 7005-2 EN 1092-2

PN 16Tmax=120°C

Range of useclosed and open circuits (pH > 7)

2-way, with lug type

PN DN[mm]

kvmax

[m3/h]∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

∆ps

[kPa]

D6350NL 16 350 10300 600 1200

D6400NL 16 400 14200 600 1000

D6450NL 16 450 18800 600 1000

D6500NL 16 500 24100 600 1000

D6600NL 16 600 37300 600 1000

D6700NL 16 700 42800 200

Technical data sheet D6..NL

Butterfly valve with Lug types• For open and closed cold and warm

water systems• For switching heat generators or

cooling machines on and off

Type overview

Type DN[ ]

kvmax[ m³/h]

kvs[ m³/h]

PN[ ]

D625NL 25 50 24 10 / 16D632NL 32 55 25 10 / 16D640NL 40 65 27 10 / 16D650NL 50 100 30 10 / 16D665NL 65 170 50 10 / 16D680NL 80 260 75 10 / 16D6100NL 100 520 150 10 / 16D6125NL 125 880 260 10 / 16D6150NL 150 1400 400 10 / 16D6350NL 350 10300 3010 16D6400NL 400 14200 4140 16D6450NL 450 18800 5490 16D6500NL 500 24100 7060 16D6600NL 600 37300 10900 16D6700NL 700 42800 11760 16

The types D6200NL, D6250NL and D6300NL have been replaced by the types D6200WL, D6250WL and D6300WL. For technical data please check the datasheet D6..WL.

Technical data

Functional data Media Cold and warm water, water with glycol up to max. 50% vol.

Medium temperature -20...120°C Permissible pressure ps 1600 kPa Leakage rate Leakage rate A, tight (EN 12266-1) Angle of rotation 90° Installation position Upright to horizontal (in relation to the stem) Suitable connection flange In accordance with ISO 7005-2 and EN 1092-2 Maintenance Maintenance-free

Materials Body EN-JS1030 (GGG 40), epoxy-powder coating Closing element 1.4301 (stainless steel) Stem 1.4005 (stainless steel) Stem seal O-ring EPDM Stem bearing RPTFE Seat EPDM

Safety notes

!• The valve has been designed for use in stationary heating, ventilation and air-

conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation.

• The valve does not contain any parts that can be replaced or repaired by the user.• The valve may not be disposed of as household refuse. All locally valid regulations

and requirements must be observed.

www.belimo.com D6..NL • en-gb • 2018-05-30 • subject to changes 1

Butterfly Valves. Open-close, Fast runners – flange