8830005 - REV D 7/14 PAGE 1 OF 2 Potter Electric Signal Company, LLC St. Louis, MO Tech Support: 866-956-0988 / Customer Service: 866-572-3005 www.pottersignal.com TRM-4 Twin Relay Module Features Stock Number: 1430824 S2930 Application The TRM-4 is compatible with Potter’s PFC-6000 series and PFC- 8500 addressable fire alarm control panels. The TRM-4 is a relay module that is programmed to activate in correlation with initiating devices, such as detectors and pull stations. The TRM-4 can be used for applications such as elevator recall, AHU shutdown, or where general purpose relays are needed. Description The TRM-4 module uses one (1) address on an SLC Loop. The module has two (2), Isolated Form C relay contacts that transfer simultaneously when the device is activated. The TRM-4 module includes one red LED that flashes when the device is being polled by the control panel. Technical Specifications Operating Voltage 22.0-24.0V Max SLC Standby Current 325 µA Max SLC Alarm Current 1mA Contact Output Style Two (2) Form C Contact Rating (Resistive) 2A @ 24 VDC / 0.5A @ 125VAC Operating Tempurature Range 32 to 120ºF (0 to 49ºC) Operating Humidity Range 0 to 93% (non-condensing) Max no. of Modules per Loop 127 units Dimensions 4.17” (106mm)L × 4.17” (106mm)W × 1.14” (29mm) Mounting Options Standard 4” Square or Double Gang Box Shipping Weight 0.6 lbs Two (2) Isolated Sets of Form C Contacts • Powered directly from 2-wire SLC loop. • No additional power required. SLC Class A (Style 6,7) & Class B (Style4) Mounts on a standard 4” or double gang box Wiring terminals accessible when mounted in box Wiring terminals accept 22 to 14 AWG • Product includes a 5 year warranty 7165-0328:0196
2

8830005-D-TRM-4Title: 8830005-D-TRM-4.indd Created Date: 8/21/2014 11:02:27 AM

Jan 29, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8830005 - REV D • 7/14 PAGE 1 OF 2

    Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com

    TRM-4 Twin Relay Module

    Features

    Stock Number: 1430824

    S2930

    ApplicationThe TRM-4 is compatible with Potter’s PFC-6000 series and PFC-8500 addressable fi re alarm control panels. The TRM-4 is a relay module that is programmed to activate in correlation with initiating devices, such as detectors and pull stations. The TRM-4 can be used for applications such as elevator recall, AHU shutdown, or where general purpose relays are needed.

    Description The TRM-4 module uses one (1) address on an SLC Loop. The module has two (2), Isolated Form C relay contacts that transfer simultaneously when the device is activated. The TRM-4 module includes one red LED that fl ashes when the device is being polled by the control panel.

    Technical Specifi cations Operating Voltage 22.0-24.0VMax SLC Standby Current 325 µAMax SLC Alarm Current 1mAContact Output Style Two (2) Form CContact Rating (Resistive) 2A @ 24 VDC / 0.5A @ 125VACOperating Tempurature Range 32 to 120ºF (0 to 49ºC)Operating Humidity Range 0 to 93% (non-condensing)Max no. of Modules per Loop 127 units

    Dimensions 4.17” (106mm)L × 4.17” (106mm)W × 1.14” (29mm)

    Mounting Options Standard 4” Square orDouble Gang BoxShipping Weight 0.6 lbs

    • Two (2) Isolated Sets of Form C Contacts• Powered directly from 2-wire SLC loop. • No additional power required.• SLC Class A (Style 6,7) & Class B (Style4)• Mounts on a standard 4” or double gang box• Wiring terminals accessible when mounted in box• Wiring terminals accept 22 to 14 AWG• Product includes a 5 year warranty

    7165-0328:0196

  • 8830005 - REV D • 7/14 PAGE 2 OF 2

    Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com

    TRM-4Twin Relay Module

    Installation Using Compatible Electrical Box

    Wiring Diagram

    Setting the Address

    Each SLC device must be assigned an address prior to installation. The address is set using either the hand held device programmer or the addressing feature on the PFC-6000 /PFC-8500 Series control panels.

    Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:1. Power to the device is removed2. Field wiring is correctly installed.3. Field wiring has no open or short circuits.

    S-

    S+

    SLC Loop

    To Next Module

    From FACP or Previous Module

    Twin Relay ModuleModel No. TRM-4 LED

    NO1

    C1

    NC1

    NO2

    C2

    NC2

    Contact Rating:24VDC / 2.0A125VAC / .5A Normally Open 1

    Common 1

    Normally Closed 1

    Normally Open 2

    Common 2

    Normally Closed 2

    DWG. #593-17

    It is possible that the relay contacts on the TRM-4 may be shipped in the non-normal / activated state. To ensure that the internal relays are set to the normal state, connect the module to the SLC loop and reset the control panel before terminating the wiring to the dry relay contacts.

    Normally Open Normally ClosedContact 1 C1 & NO1 C1 & NC1Contact 2 C2 & NO2 C2 & NC2